40RUM 60Hz PDC V6
40RUM 60Hz PDC V6
Quality Assurance
Certificate Reg. No:
04 100 950420
The 40RUM Series air-handling units are the best choice for packaged air handlers. Model 40RUM units have
direct-expansion coils. All models offer excellent fan performance, a unique combination of indoor air quality features,
easy installation, and affordable prices. Their versatility and state-of-the-art features will provide economical
performance now and in the future.
Contact your local Carrier representative for additional reference materials. www.carrier.com
Page 1
TABLE OF CONTENTS
Features / Benefits .......................................................................................................................................................... 2
Model No. Nomenclature ................................................................................................................................................ 4
AHRI Capacity Ratings ................................................................................................................................................... 5
Unit Physical Data........................................................................................................................................................... 6
Options and Accessories ................................................................................................................................................ 8
Base Unit Dimensions .................................................................................................................................................. 10
Dimensions Corner Weight ........................................................................................................................................... 13
Accessory Dimensions ................................................................................................................................................. 14
Selection Procedure/Controls ....................................................................................................................................... 18
Cooling Capacities ....................................................................................................................................................... 19
Fan Performance Data ................................................................................................................................................ 21
Performance Data ......................................................................................................................................................... 23
Electrical Data / Electric Heater Data .......................................................................................................................... 24
Typical Wiring Schematic ............................................................................................................................................. 28
Typical Piping and Wiring ............................................................................................................................................. 29
Application Data ............................................................................................................................................................ 32
Guide Specifications ..................................................................................................................................................... 34
FEATURES / BENEFITS
Every compact one-piece unit arrives fully assembled, charged, tested, and ready to run.
Efficient operation
These air cooled condensing units will provide EER’s up to 11.5 which meets ASHRAE 90.1 efficiency levels. The
38AUMD dual compressor models provide two (2) stages of cooling for remarkable partial load performance.
This high efficiency will help reduce overall operating cost and energy consumption.
Innovative Carrier 40RUM packaged air handlers are custom matched to 38AUMZ/D condensing units
Information on matching 40RUM DX packaged air handler follows for convenience. See separate product data for
more details. The 40RUM Series has excellent fan performance, efficient direct-expansion (DX) coils, a unique
combination of indoor-air quality features, and is easy to install. Its versatility and state-of-the-art features help to
ensure economical performance of the split system both now and in the future.
Rugged dependability
The 40RUM series units are made to last. The die-formed galvanized steel panels ensure structural integrity under
all operating conditions. Galvanized steel fan housings are securely mounted to a die-formed galvanized steel fan
deck. Rugged pillow-block bearings (40RUM14, 40RUM16 and 40RUM28) are securely fastened to the solid steel
fan shaft with split collets and clamp locking devices. Smaller unit sizes have spider-type bearings.
Page 2
Controls for performance dependability
The 38AUM condensing units offer operating controls and components designed for performance dependability. The
high efficiency hermetic scroll compressor is engineered for long life and durability. The compressors include
vibration isolation for quiet operation. The high-pressure switch protects the entire refrigeration system from
abnormally high operating pressures. A low-pressure switch protects the system from loss of charge. These units
also include anti-short-cycling protection, which helps to protect the units against compressor failure.
All units include a crankcase heater to eliminate liquid slugging at start-up. Each unit comes standard with the
Comfort Alert control system. This provides:
• System Go LED indicator
• Fault LED indicator
• Compressor fault LED indicator
• Phase loss protection
• Phase reversal protection
• Safety pressure indicator
• Anti-short cycle protection
Standard 1-in (25.4mm) aluminum filters remove dust and airborne particles from the occupied space for cleaner air.
The pitched, non-corroding drain pan can be adjusted for a right-hand or left-hand connection to suit many
applications and provide positive drainage and prevent standing condensate.
Economy
The 40RUM Series packaged air handlers provide reduced installation expense and energy-efficient performance.
Quick installation is ensured by the multi-poise design. Units can be installed in either the horizontal or vertical
configuration without modifications. Fan motors and contactors are pre-wired and thermostatic expansion valves
(TXVs) are factory-installed on all 40RUM models.
High efficiency, precision-balanced fans minimize air turbulence, surging, and unbalanced operation, cutting
operation expenses.
Coil flexibility
Model 40RUM direct-expansion coils have galvanized steel casings; inlet and outlet connections are on the same
end. The coils are designed for use with Puron (R-410A) refrigerant and have 3/8-in. diameter copper tubes
mechanically bonded to aluminum sine-wave fins. The coils include matched, factory-installed thermostatic
expansion valves (TXVs) with matching distributor nozzles and offers a removable power element and extended
connections.
Page 3
MODEL NUMBER NOMENCLATURE - 40RUM- R410A SERIES
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
4 0 R U M - 0 7 A 2 A 1 - 0 A 0 A 0
Brand/Packaging
0 = Standard
Electrical Options
A = None
Model Type
40RUM = Commercial
Packaged Air Handler
Service Options
0 = None
Type of Coil
A = Standard 4 Row
Panel Option
0 = Standard
Refig. System Options
— = Direct Expansion
Unit Size
07 - 6.0 Ton Design Review
08 - 7.5 Ton - = Factory Assigned
12 - 10 Ton
14 - 12.5 Ton
16 - 15.0 Ton
28 - 28.0 Ton
Page 4
AHRI CAPACITY RATING
Cooling Net Cooling Capacity
Unit Compressors Unit Size (Ton) Total Power (kW) EER
Stages (BTU/Hr)
38AUMZ07 / 40RUM07 1 1 6.0 69000 6.0 11.50
38AUMZ08 / 40RUM08 1 1 7.5 93000 8.3 11.20
38AUMD12 / 40RUM12 2 2 10.0 120000 10.4 11.50
38AUMD14 / 40RUM14 2 2 12.5 148000 13.5 11.00
38AUMD16 / 40RUM16 2 2 15.0 188000 16.9 11.10
38AUMD28 / 40RUM28 2 2 28.0 312000 29.2 10.70
Legend:
AHRI - Air Conditioning, Heating and Refrigeration Institute
EER - Energy Efficiency Ratio
Notes:
1. Rated in accordance with AHRI Standards 340/360 and SASO 2874/2016
2. Ratings are net values, reflecting the effects of circulating fan heat
3. Rating are based on: Cooling Standard: 80 F db, 67 wb indoor entering-air temperature and 95 F db air entering outdoor unit
Legend:
dB - Decibel
ASHRAE - American Society of Heating, Refrigerating and Air Conditioning, Inc.
Notes:
1. The above estimated sound power levels are based upon the ASHRAE calculation approach from the ASHRAE 1987 HVAC Systems and Applications
handbook, Chapter 52.
2. Since this data is calculated, these sound power levels may be different than the actual sound power levels.
3. The acoustic center of the unit is located at the geometric center of the unit.
Page 5
UNIT PHYSICAL DATA (ENGLISH UNITS)
Unit 40RUM 07 08 12 14 16 28
Unit Size (Ton) 6.0 7.5 10.0 12.5 15.0 28.0
Operating Weight (lb)
Base Unit with TXV (4 Rows) 399 404 425 695 713 1050
Plenum 175 225 325
Fans
Qty / Diameter (in) 1 / 15 2 / 15 2 / 18
Nominal Airflow (cfm) 2400 3000 4000 5000 6000 10,000
Airflow Range (cfm) 1800-3000 2250-3750 3000-5000 3750-6250 4500-7500 7,500-12,500
Nominal Motor HP (Std. Motor)
230V-3Ph-60Hz 2.4 2.9 3.7 7.5
400V-3Ph-60Hz 1.7 3.0 7.5
460V-3Ph-60Hz 2.4 2.9 3.7 -
Motor Speed (rpm)
230/400/460V-3Ph-60Hz 1725 1745
Refrigerant Puron® (R-410A)
Operating Charge (lb)
230V-3Ph-60Hz 13.7 16.1 9.5 / 10.6 14.0 / 15.0 19.3 / 22.0 13.40 / 12.10
400V-3Ph-60Hz 16.1 15.2 9.0 / 10.6 19.3 / 22.0 14.1 / 15.0 11.90 / 11.40
460V-3Ph-60Hz 14.7 15.1 9.9 / 10.6 14.0 / 14.9 19.3 / 21.9 -
Initial Charge (lb)
230V-3Ph-60Hz 8.2 9.65 5.7 / 6.36 8.4 / 9.0 11.6 / 13.2 8.04 / 7.26
400V-3Ph-60Hz 9.7 9.1 5.4 / 6.35 11.7 / 13.2 8.4 / 9.0 7.14 / 6.84
460V-3Ph-60Hz 8.82 9.06 5.9 / 6.3 8.4 / 8.9 11.6 / 13.1 -
Piping Connections
Coil Connection Type TXV
Suction line - Qty. / Size (in) 1 / 7/8 2 / 7/8 2 / 1 / 3/8
Liquid line - Qty. / Size (in) 1 / 3/8 1 / 1/2 2 / 3/8 2 / 1/2 2 / 1/2
Filters Washable - Aluminum
Qty. / Size (in) 4 / 16x24x1 8 / 16x24x1 4 / 20x25x2
Direct Expansion Coils Enhanced Copper Tubes, Aluminum Double Wavy Fins
Face Area (sq ft) 6.67 8.33 10.01 13.25 17.67 24.81
Max Working Pressure (psig) 650
Fins / Inch 15
No. of Rows 4
Page 6
UNIT PHYSICAL DATA (SI UNITS)
Unit 40RUM 07 08 12 14 16 28
Unit Size (Ton) 6.0 7.5 10.0 12.5 15.0 28.0
Operating Weight (kg)
Base Unit with TXV (4 Rows) 181 183 193 315 323 470
Plenum 80 102 148
Fans
Qty / Diameter (mm) 1 / 381 2 / 381 2 / 457
Nominal Airflow (L/s) 1133 1604 1888 2360 2831 4719
Airflow Range (L/s) 850-1416 1203-2006 1416-2360 1770-2949 2124-3539 3540-5900
Nominal Motor kW (Std. Motor)
230V-3Ph-60Hz 1.8 2.2 2.8 7.5
400V-3Ph-60Hz 1.3 1.8 2.2 7.5
460V-3Ph-60Hz 1.8 2.2 2.8 -
Motor Speed (r/s)
230/400/460V-3Ph-60Hz 28.75 29.08
Refrigerant Puron (R-410A)
Operating Charge (kg)
230V-3Ph-60Hz 6.2 7.29 4.32 / 4.83 6.39 / 6.79 8.76 / 10.0 6.0 / 5.5
400V-3Ph-60Hz 7.3 6.88 4.1 / 4.8 8.76 / 9.96 6.39 / 6.79 5.4 / 5.1
460V-3Ph-60Hz 6.7 6.88 4.5 / 4.8 6.39 / 6.79 8.76 / 9.96 -
Initial Charge (kg)
230V-3Ph-60Hz 3.72 4.4 2.6 / 2.9 3.8 / 4.1 5.25 / 6.0 3.8 / 3.3
400V-3Ph-60Hz 4.38 4.13 2.46 / 2.88 5.3 / 6.0 3.8 / 4.1 3.2 / 3.1
460V-3Ph-60Hz 4.02 4.13 2.7 / 2.88 3.84 / 4.08 5.26 / 5.96 -
Piping Connections
Coil Connection Type TXV
Suction line - Qty. / Size (mm) 1 / 22 2 / 22 2 / 25.4/9.5
Liquid line - Qty. / Size (mm) 1 / 9.5 1 / 12.7 2 / 9.5 2 / 12.7 2 / 12.7
Filters Washable - Aluminum
Qty. / Size (mm) 4 / 406x610x25.4 8 / 406x610x25.4 4 / 508x635x50.8
Direct Expansion Coil Enhanced Copper Tubes, Aluminum Double Wavy Fins
Face Area (sq m) 0.62 0.77 0.93 1.23 1.64 2.39
Max Working Pressure (kPag) 4481
Fins / Meter 591
No. of Rows 4
Page 7
OPTIONS AND ACCESSORIES
Item Option* Accessory♦
Alternate Fan Motors X
Alternate Drives X
Condensate Drain Trap X
Discharge Plenum X
Electric Heater X
Overhead Suspension Package X
Programmable Thermostats X
Return Air Grille X
Sub-base X
UV-C Germicidal Lamp** X
* Factory-installed option.
♦ Field-installed accessory.
** Contact application engineer
Environment
Coil Description Moderate Severe
Std Non-Corrosive
Coastal Coastal
Al Fins / Cu Tube X
Cu Fins / Cu Tube X X
Alternate fan motors and drives are available to provide the widest possible range of performance.
Discharge plenum directs the air discharge into the occupied space; integral horizontal and vertical louvers enable
redirection of airflow. This accessory is available unpainted or painted.
Return-air grille provides a protective barrier over the return-air opening and gives a finished appearance to units
installed in the occupied space. This accessory is available unpainted or painted.
Sub-base provides a stable, raised platform and room for condensate drain connection for floor-mounted units.
This accessory is available unpainted or painted.
Overhead suspension package includes necessary brackets to support units in horizontal installations.
Condensate drain trap includes an overflow shutoff switch that can be wired to turn off the unit if the trap becomes
plugged. The kit also includes a wire harness that can be connected to an alarm if desired. The transparent trap is
designed for easy service and maintenance.
Electric resistance heat coils have an open-wire design and are mounted in a rigid frame. Safety cutouts for high
temperature conditions are standard. Terminal block for single-point power connections is included.
Page 8
OPTIONS AND ACCESSORIES (cont.)
UV-C germicidal lamps inhibit the growth of mold and fungus , which may grow on evaporator coil and
condensate pan surfaces. The use of UV-C germicidal lamps reduces the foul odors that may result from this
growth of mold and fungus. It also provides a self-cleaning function for the evaporator coil and drain pan.
Carrier’s line of thermostat provides both programmable and non-programmable capability with the new
Debonair® line of commercial programmable thermostats. The TEMP System controls offer communication
capability with staged heating and cooling, and the Commercial Electronic thermostats provide 7-day
programmable capability for economical applications.
Page 9
BASE UNIT DIMENSIONS – 40RUM Series Size 07-12
Top
Front
Notes:
1. Dimensions are in millimeter (mm).
2. Direction of airflow.
3. Recommended clearance:
Rear: 3.0 in (76.2mm), (2.0ft 6.0in (762mm) with electric heat accessory)
Front: 2.0ft 6.0in (762mm)
Right Side: 2.0ft 6.0in (762mm)
Left Side: 2.0ft 6.0in (762mm)
Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory installed.
Page 10
BASE UNIT DIMENSIONS – 40RUM Series Size 14 - 16
Top
Front
Notes:
1. Dimensions are in millimeter (mm).
2. Direction of airflow.
3. Recommended clearance:
Rear: 3.0 in (76.2mm), (2.0ft 6.0in (762mm) with electric heat accessory)
Front: 2.0ft 6.0in (762mm)
Right Side: 2.0ft 6.0in (762mm)
Left Side: 2.0ft 6.0in (762mm)
Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory installed.
Page 11
BASE UNIT DIMENSIONS – 40RUM Series Size 28
Top
Left Side
Notes:
1. Dimensions are in millimeter (mm).
2. Direction of airflow.
3. Recommended clearance:
Rear: 3.0 in (76.2mm),
(2.0ft 6.0in (762mm) with electric heat accessory)
Front: 2.0ft 6.0in (762mm)
Right Side: 2.0ft 6.0in (762mm)
Left Side: 2.0ft 6.0in (762mm)
Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
Front 5. Duct flange is factory installed.
Right Side
Page 12
DIMENSIONS – CORNER WEIGHTS
4 3
1 2
CORNER WEIGHTS - HORIZONTAL POSITION
40RUM - SI
40RUM UNIT OR Corner Number (Weight In kg)
UNIT OR ACCESSORY
UNIT ACCESSORY
NAME 1 2 3 4
SIZE WEIGHT - (kg)
07 Fan Coil Base Unit 181 49.6 48.1 41.1 42.3
08 Fan Coil Base Unit 183 50.1 48.6 41.5 42.8
12 Fan Coil Base Unit 193 52.9 51.3 43.8 45.2
14 Fan Coil Base Unit 315 86.3 83.7 71.5 73.7
16 Fan Coil Base Unit 323 88.5 85.9 73.3 75.6
28 Fan Coil Base Unit 477 130.5 126.7 108.2 111.6
40RUM - English
40RUM UNIT OR Corner Number (Weight In lb)
UNIT OR ACCESSORY
UNIT ACCESSORY
NAME 1 2 3 4
SIZE WEIGHT - (lb)
07 Fan Coil Base Unit 399 109.3 106.1 90.6 93.4
08 Fan Coil Base Unit 404 110.7 107.5 91.7 94.5
12 Fan Coil Base Unit 425 116.4 113 96.5 99.4
14 Fan Coil Base Unit 695 224 177.7 129.8 163.7
16 Fan Coil Base Unit 713 229.8 182.3 133.2 167.9
28 Fan Coil Base Unit 1050 338.4 268.5 196.1 247.2
40RUM - SI
UNIT OR Corner Number (Weight In kg)
40RUM
UNIT OR ACCESSORY ACCESSORY
UNIT
NAME WEIGHT 1 2 3 4
SIZE
(kg)
07 Fan Coil Base Unit 181 45.5 52.3 44.4 38.8
08 Fan Coil Base Unit 183 46.0 52.7 44.9 39.4
12 Fan Coil Base Unit 193 48.5 55.6 47.4 41.5
07 -12 Plenum Add 80 23.3 16.8 16.8 23.3
14 Fan Coil Base Unit 315 86.6 95.5 69.8 63.3
16 Fan Coil Base Unit 323 88.9 97.9 71.6 64.9
14 - 16 Plenum Add 102 32.9 18.1 18.1 32.9
28 Fan Coil Base Unit 477 131.2 144.5 105.5 95.6
28 Plenum Add 148 43.1 31.1 31.1 43.1
Page 13
40RUM - English
UNIT OR Corner Number (Weight In lb)
40RUM
UNIT OR ACCESSORY ACCESSORY
UNIT
NAME WEIGHT 1 2 3 4
SIZE
(lb)
07 Fan Coil Base Unit 399 100.5 114.9 98 85.8
08 Fan Coil Base Unit 404 101.7 116.3 99.1 86.9
12 Fan Coil Base Unit 425 107.6 122.3 108 87.1
07 -12 Plenum Add 175 50.8 36.7 36.7 5.8
14 Fan Coil Base Unit 695 191.2 210.5 153.8 139.5
16 Fan Coil Base Unit 713 196.2 216 157.8 143.1
14 - 16 Plenum Add 225 72.5 40 40 72.5
28 Fan Coil Base Unit 1050 288.9 318.1 232.3 210.6
28 Plenum Add 325 94.5 68.3 68.3 94.5
ACCESSORY DIMENSIONS
Overhead Suspension Accessory
Page 14
ACCESSORY DIMENSIONS (cont.)
Page 15
ACCESSORY DIMENSIONS (cont.)
Unit Sizes 28
Page 16
ACCESSORY DIMENSIONS (cont.)
40RUM
A B C D E F G H J
UNIT SIZE
1’ - 3 1/4″ 4’ - 6 3/8″ 2 - 5/16″ 2’ - 1 1/4″ 10’ 5/8″ 1’- 4″ 1’- 4 5/16″ 1’- 6 3/4″ 1’ - 7/8″
14 - 16
[387.4] [1381.1] [58.7] [641.4] [269.9] [406.4] [414.3] [476.3] [327.0]
1’ - 3 3/8″ 5’ - 4 7/8″ 2’ - 1/16″ 2’ - 6 3/16″ 1’ 1/4″ 1’- 7″ 1’- 4 5/16″ 1’- 10″ 1’ – 4 7/16″
28
[390.5] [1636.8] [26.9] [766.8] [311.2] [482.6] [414.3] [558.8] [417.1]
Page 17
SELECTION PROCEDURE
Combination ratings for 38AUMZ/D units matched with 40RUM Series air handlers are in this book. If unit is used
with an air handler, use the Carrier Electronic Catalog selection program to obtain combined ratings.
For extended line lengths over 100 feet, contact your Carrier representative or application engineer.
CONTROLS
Operating sequences
When the wall thermostat calls for cooling, terminals G and Y1 are energized. As a result, the indoor fan contactor
(IFC) and the compressor contactor (C1) are energized, causing the indoor fan motor (IFM), compressor #1, and
outdoor fans (OFM) to start. The field-supplied and field-installed liquid line valve also opens, allowing the system
to function in cooling mode.
If the unit has 2 stages of cooling, the wall thermostat will additionally energize Y2. The Y2 signal will energize
compressor contactor #2 (C2), causing compressor #2 to start.
Regardless of the number of stages, the field-supplied liquid line valve shall open and the outdoor fan motors
(OFM) runs continuously while unit is cooling.
When cooling demand decrease, the thermostat will de-energize Y2. Y2 signal will de-energize compressor
contactor #2 (C2), causing compressor #2 to stop. When cooling demand has been satisfied, the thermostat will
de-energize Y1, and G terminals. Y1 and G signal will de-energize compressor contactor #1 (C1), causing
compressor #1 to stop. If the wall thermostat is set to continuous (CONT), the indoor fan motor will continue to
operate. Otherwise, the indoor fan motor will stop.
The outdoor fan motors (OFM) will turn off and field-supplied liquid line valve shall close, minimizing the potential
for refrigerant migration.
Page 18
COOLING CAPACITIES - English
Evaporator Air Coil Refrigerant Temp (°F)
Unit
Airflow (Cfm) 30 35 40 45 50
40RUM Ewb (°F)
BPF TC SHC TC SHC TC SHC TC SHC TC SHC
72 124 59 111 54 100 49 85 43 69 37
1,800
67 103 65 91 60 79 54 65 48 50 43
0.06 62 86 71 74 65 61 59 49 49 42 42
72 145 70 130 64 116 58 98 51 80 45
2,400
7 67 120 78 106 73 92 66 76 60 59 52
0.10 62 101 87 87 80 72 72 60 60 50 50
72 161 78 145 73 128 66 109 60 89 52
3,000
67 134 91 120 83 103 76 86 70 65 61
0.12 62 112 102 96 92 80 80 69 69 58 58
72 160 77 145 70 129 63 110 56 89 48
2,250
67 133 85 118 78 102 70 85 62 66 56
0.06 62 111 92 97 85 79 77 63 63 55 55
72 188 90 168 83 150 76 127 68 105 59
3,000
8 67 156 102 138 95 120 86 99 77 77 69
0.10 62 131 112 113 105 93 93 78 78 66 66
72 208 102 187 95 167 87 141 78 116 68
3,750
67 175 118 156 108 133 99 111 90 86 80
0.12 62 147 131 125 120 105 105 89 89 76 76
72 206 98 186 86 164 81 141 72 115 62
3,000
67 172 109 153 99 131 91 109 81 84 72
0.05 62 143 118 124 109 102 99 83 83 70 70
72 238 115 215 106 191 97 163 86 133 76
4,000
12 67 199 130 177 121 153 111 127 99 98 88
0.07 62 168 145 145 134 121 121 101 101 85 85
72 263 130 237 120 211 110 180 99 147 86
5,000
67 221 149 197 140 170 128 141 116 109 104
0.12 62 187 170 159 155 134 134 116 116 98 98
72 250 120 229 111 206 102 176 91 143 79
3,750
67 211 136 190 126 162 115 133 101 106 91
0.06 62 173 149 153 138 128 125 106 106 90 90
72 291 142 263 131 236 121 202 109 163 95
5,000
14 67 247 164 218 153 186 139 155 126 124 112
0.08 62 200 183 175 168 151 151 128 128 109 109
72 319 159 289 148 258 137 222 125 180 110
6,250
67 272 186 235 173 206 163 172 147 134 131
0.10 62 221 211 193 193 168 168 146 146 125 125
72 321 152 289 140 259 127 221 114 184 101
4,500
67 265 170 238 157 203 142 170 127 133 113
0.03 62 218 185 192 172 160 157 132 132 112 112
72 364 178 333 165 299 152 254 135 204 118
6,000
16 67 314 206 277 190 236 174 198 156 156 140
0.05 62 256 228 225 211 190 190 159 159 135 135
72 407 201 363 185 330 173 282 156 224 137
7,500
67 347 237 299 218 261 203 220 182 174 164
0.08 62 286 264 248 245 214 214 183 183 155 155
72 325 147 298 134 266 121 231 107 193 92
7,500
67 271 159 243 146 212 132 178 118 141 103
0.08 62 222 170 195 157 165 143 132 128 109 109
72 328 148 300 135 268 121 233 107 195 93
9,750
28 67 274 161 245 147 214 133 179 119 142 104
0.09 62 224 172 196 158 166 144 133 129 110 110
72 376 170 345 157 309 142 268 126 222 109
12,500
67 315 189 282 173 246 158 205 141 164 125
0.10 62 258 204 226 189 191 173 154 153 130 130
Legend:
BPF — Bypass Factor SHC — Sensible Heat Capacity (1000 Btuh) Gross
Ewb — Entering Wet-Bulb TC — Total Capacity (1000 Btuh) Gross
Notes:
1. Direct interpolation is permissible. Do not extrapolate. 3. The SHC is based on 80 F edb temprature of air entering evaporator coil.
2. The following formaulas may be used. - Below 80 F edb, subtract (corr factor x cfm) from SHC.
tldb = tedb — sensible capacity (Btuh) - Above 80 F edb, add (corr factor x cfm) to SHC.
1.10 x cfm ENTERING AIR DRY-BULB TEMP (F)
tlwb = Wet-bulb temprature corresponding to enthalphy of air 79 78 77 76 75 under 75
BF
leaving evaporater coil (hlwb). 81 82 83 84 85 over 85
Correction Factor
hlwb = hewb — total capacity (Btuh) 0.05 1.04 2.07 3.11 4.14 5.18
Use formula
4.5 x cfm 0.10 0.98 1.96 2.94 3.92 4.90
shown
Where: hewb = Enthaply of air entering evaporator coil. 0.20 0.87 1.74 2.62 3.49 4.36
below.*
0.30 0.76 1.53 2.29 3.05 3.82
4. Cooling capacities are gross and do not include deductions for - Interpolation is permissible.
indoor fan motor heat. *Correction Factor = 1.10 x (1 - BF) x (edb - 80).
5. Variable Air Volume units will operate down to 70 cfm/ton. Performance at 70 cfm/ton is limited to unloaded operation and may be additinally limited to edb and ewb
conditions.
Page 19
COOLING CAPACITIES - SI
Evaporator Air Coil Refrigerant Temp (°C)
Unit
Airflow (L/s) –1 2 4 7 10
40RUM Ewb (°C)
BPF TC SHC TC SHC TC SHC TC SHC TC SHC
22 36 17 33 16 29 14 25 13 20 11
850
19 30 19 27 18 23 16 19 14 15 13
0.06 17 25 21 22 19 18 17 14 14 12 12
22 42 21 38 19 34 17 29 15 24 13
1130
7 19 35 23 31 21 27 19 22 18 17 15
0.10 17 29 25 25 24 21 21 18 18 15 15
22 47 23 42 21 38 19 32 18 26 15
1420
19 39 27 35 24 30 22 25 20 19 18
0.12 17 33 30 28 27 24 24 20 20 17 17
22 47 22 42 21 38 19 32 16 26 14
1060
19 39 25 35 23 30 21 25 18 19 16
0.06 17 33 27 28 25 23 22 19 19 16 16
22 55 26 49 24 44 22 37 20 31 17
1420
8 19 46 30 40 28 35 25 29 22 22 20
0.10 17 38 33 33 31 27 27 23 23 19 19
22 61 30 55 28 49 25 41 23 34 20
1770
19 51 35 46 32 39 29 33 26 25 23
0.12 17 43 38 37 35 31 31 26 26 22 22
22 60 29 54 25 48 24 41 21 34 18
1420
19 50 32 45 29 38 27 32 24 25 21
0.05 17 42 35 36 32 30 29 24 24 21 21
22 70 34 63 31 56 28 48 25 39 22
1890
12 19 58 38 52 35 45 33 37 29 29 26
0.07 17 49 43 43 39 35 35 30 30 25 25
22 77 38 69 35 62 32 53 29 43 25
2360
19 65 44 58 41 50 38 41 34 32 30
0.12 17 55 50 47 45 39 39 34 34 29 29
22 73 35 67 33 60 30 52 27 42 23
1770
19 62 40 56 37 47 34 39 30 31 27
0.06 17 51 44 45 40 38 37 31 31 26 26
22 85 41 77 39 69 36 59 32 48 28
2360
14 19 72 48 64 45 55 41 45 37 36 33
0.08 17 59 54 51 49 44 44 38 38 32 32
22 93 47 85 43 76 40 65 37 53 32
2980
19 80 55 69 51 60 48 50 43 39 39
0.10 17 65 62 57 57 49 49 43 43 37 37
22 94 45 85 41 76 37 65 33 54 30
2120
19 78 50 70 46 59 42 50 37 39 33
0.03 17 64 54 56 50 47 46 39 39 33 33
22 107 52 98 48 88 45 74 40 60 35
2830
16 19 92 60 81 56 69 51 58 46 46 41
0.05 17 75 67 66 62 56 56 47 47 40 40
22 119 59 106 54 97 51 83 46 66 40
3540
19 102 69 88 64 76 59 64 53 51 48
0.08 17 84 77 73 72 63 63 54 54 45 45
22 162 63 147 134 56 49 43 41 89 33
7,500
19 132 70 117 63 100 55 81 47 60 39
0.08 17 105 76 90 69 73 61 55 53 42 42
22 73 64 148 135 57 49 43 41 90 33
9,750
28 19 134 71 118 63 101 53 81 48 61 40
0.09 17 106 77 91 70 74 62 56 53 43 43
22 88 76 173 69 153 61 131 52 105 42
12,500
19 157 87 138 78 118 158 96 60 73 51
0.10 17 125 95 107 87 88 78 67 67 54 54
Legend:
BPF — Bypass Factor SHC — Sensible Heat Capacity (1000 Btuh) Gross
Ewb — Entering Wet-Bulb TC — Total Capacity (1000 Btuh) Gross
Notes:
1. Direct interpolation is permissible. Do not extrapolate. 3. The SHC is based on 80 F edb temprature of air entering evaporator coil.
2. The following formaulas may be used. - Below 80 F edb, subtract (corr factor x cfm) from SHC.
tldb = tedb — sensible capacity (Btuh) - Above 80 F edb, add (corr factor x cfm) to SHC.
1.10 x cfm ENTERING AIR DRY-BULB TEMP (F)
tlwb = Wet-bulb temprature corresponding to enthalphy of air 79 78 77 76 75 under 75
BF
leaving evaporater coil (hlwb). 81 82 83 84 85 over 85
Correction Factor
hlwb = hewb — total capacity (Btuh) 0.05 1.04 2.07 3.11 4.14 5.18
Use formula
4.5 x cfm 0.10 0.98 1.96 2.94 3.92 4.90
shown
Where: hewb = Enthaply of air entering evaporator coil. 0.20 0.87 1.74 2.62 3.49 4.36
below.*
0.30 0.76 1.53 2.29 3.05 3.82
4. Cooling capacities are gross and do not include deductions for - Interpolation is permissible.
indoor fan motor heat. *Correction Factor = 1.10 x (1 - BF) x (edb - 80).
5. Variable Air Volume units will operate down to 70 cfm/ton. Performance at 70 cfm/ton is limited to unloaded operation and may be additinally limited to edb and ewb
conditions.
Page 20
FAN PERFORMANCE DATA - English
External Static Pressure (in. wg)
Unit Airflow
0.2 0.4 0.6 0.8 1.0 1.2
40RUM (Cfm)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1,800 471 0.26 564 0.37 649 0.49 727 0.63 797 0.77 862 0.92
2,100 519 0.37 602 0.49 679 0.62 751 0.77 819 0.92 882 1.09
7 2,400 568 0.51 645 0.64 715 0.79 781 0.94 844 1.11 905 1.28
2,700 619 0.69 690 0.84 755 0.99 816 1.15 875 1.33 932 1.51
3,000 671 0.90 738 1.07 799 1.24 856 1.41 910 1.60 963 1.79
2,250 510 0.39 594 0.51 669 0.65 739 0.79 806 0.95 870 1.12
2,600 561 0.55 640 0.70 709 0.84 773 1.00 834 1.16 893 1.34
8 3,000 621 0.79 695 0.96 759 1.12 818 1.30 874 1.47 928 1.66
3,400 683 1.09 752 1.29 813 1.48 869 1.67 920 1.86 970 2.06
3,750 739 1.42 804 1.63 862 1.85 915 2.05 964 2.26 1011 2.48
3,000 592 0.73 670 0.90 737 1.06 797 1.23 854 1.41 908 1.59
3,500 664 1.08 735 1.28 798 1.48 855 1.67 908 1.87 958 2.07
12 4,000 738 1.54 803 1.77 862 2.00 917 2.23 967 2.45 1014 2.67
4,500 815 2.12 873 2.39 929 2.65 980 2.90 1028 3.16 1073 3.41
5,000 893 2.84 946 3.14 997 3.43 1046 3.72 1092 4.00 1135 4.28
3,750 467 0.55 567 0.83 649 1.12 721 1.41 788 1.72 851 2.05
4,300 504 0.74 599 1.05 679 1.38 748 1.70 811 2.04 871 2.39
14 5,000 556 1.06 641 1.39 718 1.76 786 2.14 847 2.52 903 2.91
5,700 612 1.47 686 1.82 759 2.23 825 2.66 884 3.09 939 3.52
6,250 657 1.87 725 2.24 793 2.66 856 3.12 915 3.59 969 4.06
4,500 483 0.72 576 1.01 660 1.35 732 1.69 797 2.03 856 2.38
5,300 538 1.07 617 1.37 696 1.74 767 2.13 830 2.53 888 2.94
16 6,000 590 1.48 659 1.79 730 2.17 798 2.59 860 3.04 918 3.49
6,800 651 2.06 712 2.39 774 2.78 836 3.22 896 3.71 952 4.21
7,500 706 2.69 761 3.04 817 3.44 873 3.89 929 4.39 984 4.93
7,500 590 2.80 660 3.20 725 3.70 785 4.20 840 4.80 890 5.5
8,750 690 4.50 750 4.70 805 5.10 860 5.60 910 6.10 960 6.7
28 10,000 710 5.50 765 6.10 820 6.60 870 7.10 920 7.70 970 8.3
11,250 800 7.90 840 8.40 890 9.00 930 9.50 975 10.10 1020 10.6
12,500 890 10.60 930 11.40 — — — — — — — —
LEGEND
Bhp — Brake Horsepower Input to Fan
ESP — External Static Pressure
Bold indicates field-supplied drive or motor is required. Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than the standard motor and standard drive combination is required. Refer
to fan motor and drive tables to complete selection.
Maximum allowable fan speed is 1200 rpm for all sizes. Fan performance is based on deductions for wet coil, clean 1-in.filters, and unit
casing. See table below for factory-supplied filter pressure drop.
Page 21
FAN PERFORMANCE DATA (cont.) - SI
External Static Pressure (Pa)
Unit Airflow
50 100 150 200 250 300
40RUM (L/s)
r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW
850 7.86 0.19 9.40 0.27 10.81 0.37 12.11 0.47 13.29 0.57 14.36 0.69
990 8.64 0.27 10.03 0.36 11.31 0.46 12.52 0.57 13.65 0.69 14.71 0.81
7 1130 9.46 0.38 10.75 0.48 11.91 0.59 13.01 0.70 14.07 0.83 15.08 0.96
1270 10.31 0.51 11.51 0.62 12.58 0.74 13.60 0.86 14.58 0.99 15.53 1.13
1420 11.18 0.67 12.30 0.80 13.31 0.92 14.26 1.05 15.17 1.19 16.05 1.33
1060 8.50 0.29 9.91 0.38 11.15 0.48 12.32 0.59 13.44 0.71 14.50 0.83
1230 9.35 0.41 10.67 0.52 11.81 0.63 12.88 0.74 13.90 0.87 14.89 1.00
8 1420 10.35 0.59 11.59 0.71 12.66 0.84 13.64 0.97 14.57 1.10 15.47 1.24
1600 11.39 0.81 12.54 0.96 13.55 1.10 14.48 1.24 15.34 1.39 16.17 1.53
1770 12.32 1.06 13.40 1.22 14.37 1.38 15.25 1.53 16.07 1.69 16.86 1.85
1420 9.86 0.54 11.17 0.67 12.28 0.79 13.29 0.92 14.23 1.05 15.14 1.19
1650 11.06 0.80 12.25 0.96 13.31 1.10 14.25 1.25 15.13 1.39 15.96 1.54
12 1890 12.31 1.15 13.38 1.32 14.37 1.49 15.28 1.66 16.11 1.83 16.89 1.99
2120 13.59 1.58 14.55 1.78 15.48 1.97 16.34 2.17 17.14 2.35 17.89 2.54
2360 14.89 2.12 15.76 2.34 16.62 2.56 17.43 2.77 18.20 2.98 18.92 3.19
1770 7.78 0.41 9.46 0.62 10.82 0.83 12.02 1.05 13.13 1.28 14.19 1.53
2030 8.40 0.55 9.98 0.78 11.31 1.03 12.47 1.27 13.52 1.52 14.51 1.78
14 2360 9.27 0.79 10.68 1.04 11.96 1.31 13.09 1.60 14.11 1.88 15.05 2.17
2690 10.20 1.10 11.44 1.36 12.64 1.66 13.74 1.98 14.74 2.30 15.65 2.63
2950 10.96 1.39 12.09 1.67 13.21 1.98 14.27 2.33 15.25 2.68 16.15 3.03
2120 8.05 0.54 9.60 0.75 11.00 1.00 12.21 1.26 13.28 1.51 14.27 1.78
2500 8.97 0.80 10.29 1.02 11.59 1.30 12.78 1.59 13.84 1.89 14.80 2.19
16 2830 9.83 1.10 10.99 1.33 12.16 1.62 13.29 1.93 14.34 2.27 15.30 2.60
3210 10.85 1.54 11.87 1.78 12.90 2.07 13.93 2.40 14.93 2.76 15.87 3.14
3540 11.77 2.01 12.69 2.27 13.62 2.56 14.56 2.90 15.49 3.27 16.40 3.67
7,500 30.86 2.09 34.52 2.39 37.92 2.76 41.06 3.13 43.93 3.58 46.55 4.10
8,750 36.09 3.36 39.23 3.50 42.10 3.80 44.98 4.18 47.59 4.55 50.21 5.00
28 10,000 37.13 4.10 40.01 4.55 42.89 4.92 45.50 5.29 48.12 5.74 50.73 6.19
11,250 41.84 5.89 43.93 6.26 46.55 6.71 48.64 7.08 50.99 7.53 53.35 7.90
12,500 46.55 7.90 48.64 8.50 — — — — — — — —
LEGEND
Bhp — Brake Horsepower Input to Fan
ESP — External Static Pressure
Bold indicates field-supplied drive or motor is required. Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than the standard motor and standard drive combination is required. Refer
to fan motor and drive tables to complete selection.
Maximum allowable fan speed is 20 r/s for all sizes. Fan performance is based on deductions for wet coil, clean 25.4-mm filters, and unit
casing. See table below for factory-supplied filter pressure drop.
Page 22
PERFORMANCE DATA
Factory-Supplied Filter Pressure Drop — English Factory-Supplied Filter Pressure Drop — SI
Unit Unit
Airflow (Cfm) Pressure Drop (in. wg) Airflow (L/s) Pressure Drop (Pa)
40RUM 40RUM
1800 0.05 850 13
7 2400 0.08 7 1150 20
3000 0.11 1450 28
2250 0.07 1000 17
8 3000 0.11 8 1400 27
3750 0.15 1800 38
3000 0.11 1450 28
12 4000 0.17 12 1900 42
5000 0.23 2350 56
3750 0.06 1750 15
14 5000 0.10 14 2350 24
6250 0.13 2950 33
4500 0.08 2100 20
16 6000 0.12 16 2800 30
7500 0.17 3500 42
7500 0.15 3500 36
28 10000 0.22 28 4700 55
12500 0.30 5900 76
Accessory Pressure Drop — English (in. wg) Accessory Pressure Drop — SI (Pa)
Discharge Electric Return Air Discharge Electric Return Air
Unit Airflow (Cfm) Unit Airflow (L/s)
Plenum Heater Grille Plenum Heater Grille
1800 0.06 0.04 0.01 850 15 9 2
7 2400 0.10 0.06 0.01 7 1150 25 16 3
3000 0.14 0.10 0.02 1450 36 26 5
2250 0.09 0.06 0.01 1000 20 12 2
8 3000 0.14 0.10 0.02 8 1400 34 24 5
3750 0.21 0.15 0.03 1800 51 39 8
3000 0.14 0.10 0.02 1450 36 26 5
12 4000 0.22 0.17 0.04 12 1900 56 43 10
5000 0.32 0.26 0.06 2350 79 65 15
3750 0.07 0.04 0.01 1750 18 10 2
14 5000 0.12 0.07 0.02 14 2350 29 17 5
6250 0.17 0.11 0.02 2950 43 26 5
4500 0.10 0.06 0.01 2100 24 14 2
16 6000 0.16 0.10 0.02 16 2800 39 24 5
7500 0.23 0.15 0.03 3500 56 37 7
7500 0.15 0.09 0.02 3500 37 22 5
28 10000 0.24 0.16 0.03 28 4700 59 39 7
12500 0.34 0.24 0.05 5900 86 60 12
Page 23
ELECTRICAL DATA TABLE
Standard Motors
Fan Motor Power Supply
Unit Voltage Voltage Range
HP (kW) FLA MCA MOCP
230-3-60 207-253 2.4 (1.8) 5.2 6.5 15
40RUM-07 400-3-60 360-440 1.7 (1.3) 2.8 3.5 15
460-3-60 414-506 2.4 (1.8) 2.6 3.3 15
230-3-60 207-253 2.4 (1.8) 5.2 6.5 15
40RUM-08 400-3-60 360-440 1.7 (1.3) 2.8 3.5 15
460-3-60 414-506 2.4 (1.8) 2.6 3.3 15
230-3-60 207-253 2.4 (1.8) 5.2 6.5 15
40RUM-12 400-3-60 360-440 2.4 (1.8) 4.1 5.1 15
460-3-60 414-506 2.4 (1.8) 2.6 3.3 15
230-3-60 207-253 2.9 (2.2) 7.5 9.4 15
40RUM-14 400-3-60 360-440 2.4 (1.8) 4.1 5.1 15
460-3-60 414-506 2.9 (2.2) 3.8 4.8 15
230-3-60 207-253 3.7 (2.8) 10.2 12.8 20
40RUM-16 400-3-60 360-440 3.0 (2.2) 5.0 6.3 15
460-3-60 414-506 3.7 (2.8) 4.8 6.0 15
230-3-60 207-253 10 (7.45) 25.2 31.5 50
40RUM-28
400-3-60 360-440 10 (7.45) 16.2 20.3 35
Alternate Motors
Fan Motor Power Supply
Unit Voltage Voltage Range
HP (kW) FLA MCA MOCP
230-3-60 207-253 2.9 (2.2) 7.5 9.4 15
40RUM-07 400-3-60 360-440 2.4 (1.8) 4.1 5.1 15
460-3-60 414-506 2.9 (2.2) 3.8 4.8 15
230-3-60 207-253 2.9 (2.2) 7.5 9.4 15
40RUM-08 400-3-60 360-440 3.0 (2.2) 5.0 6.3 15
460-3-60 414-506 2.9 (2.2) 3.8 4.8 15
230-3-60 207-253 3.7 (2.8) 10.2 12.6 20
40RUM-12 400-3-60 360-440 4.7 (3.5) 7.5 9.4 15
460-3-60 414-506 3.7 (2.8) 4.8 6.0 15
230-3-60 207-253 3.7 (2.8) 10.2 12.6 20
40RUM-14 400-3-60 360-440 4.7 (3.5) 7.5 9.4 15
460-3-60 414-506 3.7 (2.8) 4.8 6.0 15
230-3-60 207-253 5.0 (3.7) 12.6 15.6 25
40RUM-16 400-3-60 360-440 4.7 (3.5) 7.5 9.4 15
460-3-60 414-506 5.0 (3.7) 6.3 7.9 15
230-3-60 207-253 10 (7.45) 25.2 31.5 50
40RUM-28
400-3-60 360-440 10 (7.45) 16.2 20.3 35
Page 24
ELECTRICAL HEATER DATA TABLE
Fan Motor Electric Heater(s)
Heater Part No. 40RUM
V-Ph-Hz Nominal Application Capacity (kW) MCA MOCP
CAELHEAT Size Hp kW FLA FLA
Capacity (kW) Stage 1 Stage 2 Total
2.4 1.80 5.2 5 4.6 — 4.6 11.6 21.0 25.0
001A00 230-3-60
2.9 2.16 7.5 5 4.6 — 4.6 11.6 23.9 25.0
1.7 1.30 2.8 5 3.5 — 3.5 5.1 9.9 15.0
002A00 400-3-60
2.4 1.80 4.1 5 3.5 — 3.5 5.1 11.5 15.0
2.4 1.80 2.6 5 4.6 — 4.6 5.8 10.5 15.0
002A00 460-3-60
2.9 2.16 3.8 5 4.6 — 4.6 5.8 12.0 15.0
2.4 1.80 5.2 10 9.2 — 9.2 23.1 35.4 40.0
004A00 230-3-60
2.9 2.16 7.5 10 9.2 — 9.2 23.1 38.3 40.0
1.7 1.30 2.8 10 6.9 — 6.9 10.1 16.1 20.0
005A00 400-3-60
2.4 1.80 4.1 10 6.9 — 6.9 10.1 17.8 20.0
2.4 1.80 2.6 10 9.2 — 9.2 11.6 17.8 20.0
005A00 460-3-60
2.9 2.16 3.8 10 9.2 — 9.2 11.6 19.3 20.0
07
2.4 1.80 5.2 15 13.8 — 13.8 34.6 49.8 50.0
007A00 230-3-60
2.9 2.16 7.5 15 13.8 — 13.8 34.6 52.6 60.0
1.7 1.30 2.8 15 10.4 — 10.4 15.0 22.3 25.0
008A00 400-3-60
2.4 1.80 4.1 15 10.4 — 10.4 15.0 23.9 25.0
2.4 1.80 2.6 15 13.8 — 13.8 17.3 24.9 25.0
008A00 460-3-60
2.9 2.16 3.8 15 13.8 — 13.8 17.3 26.4 30.0
2.4 1.80 5.2 25 13.8 9.2 23.0 57.7 78.6 80.0
010A00 230-3-60
2.9 2.16 7.5 25 13.8 9.2 23.0 57.7 81.5 90.0
1.7 1.30 2.8 25 10.4 6.9 17.3 25.0 34.8 40.0
011A00 400-3-60
2.4 1.80 4.1 25 10.4 6.9 17.3 25.0 36.4 40.0
2.4 1.80 2.6 25 13.8 9.2 23.0 28.9 39.4 40.0
011A00 460-3-60
2.9 2.16 3.8 25 13.8 9.2 23.0 28.9 40.9 50.0
2.4 1.80 5.2 5 4.6 — 4.6 11.6 21.0 25.0
001A00 230-3-60
2.9 2.16 7.5 5 4.6 — 4.6 11.6 23.9 25.0
1.7 1.30 2.8 5 3.5 — 3.5 5.1 9.9 15.0
002A00 400-3-60
3.0 2.20 5.0 5 3.5 — 3.5 5.1 12.6 15.0
2.4 1.80 2.6 5 4.6 — 4.6 5.8 10.5 15.0
002A00 460-3-60
2.9 2.16 3.8 5 4.6 — 4.6 5.8 12.0 15.0
2.4 1.80 5.2 10 9.2 — 9.2 23.1 35.4 40.0
004A00 230-3-60
2.9 2.16 7.5 10 9.2 — 9.2 23.1 38.3 40.0
1.7 1.30 2.8 10 6.9 — 6.9 10.1 16.1 20.0
005A00 400-3-60
3.0 2.20 5.0 10 6.9 — 6.9 10.1 18.9 20.0
2.4 1.80 2.6 10 9.2 — 9.2 11.6 17.8 20.0
005A00 460-3-60
2.9 2.16 3.8 10 9.2 — 9.2 11.6 19.3 20.0
2.4 1.80 5.2 15 13.8 — 13.8 34.6 49.8 50.0
007A00 230-3-60
2.9 2.16 7.5 15 13.8 — 13.8 34.6 52.6 60.0
08
1.7 1.30 2.8 15 10.4 — 10.4 15.0 22.3 25.0
008A00 400-3-60
3.0 2.20 5.0 15 10.4 — 10.4 15.0 25.0 25.0
2.4 1.80 2.6 15 13.8 — 13.8 17.3 24.9 25.0
008A00 460-3-60
2.9 2.16 3.8 15 13.8 — 13.8 17.3 26.4 30.0
2.4 1.80 5.2 25 13.8 9.2 23.0 57.7 78.6 80.0
010A00 230-3-60
2.9 2.16 7.5 25 13.8 9.2 23.0 57.7 81.5 80.0
1.7 1.30 2.8 25 10.4 6.9 17.3 25.0 34.8 40.0
011A00 400-3-60
3.0 2.20 5.0 25 10.4 6.9 17.3 25.0 37.5 40.0
2.4 1.80 2.6 25 13.8 9.2 23.0 28.9 39.4 40.0
011A00 460-3-60
2.9 2.16 3.8 25 13.8 9.2 23.0 28.9 40.9 45.0
2.4 1.80 5.2 35 18.4 13.8 32.2 80.8 107.5 110.0
013A00 230-3-60
2.9 2.16 7.5 35 18.4 13.8 32.2 80.8 110.4 120.0
1.7 1.30 2.8 35 13.9 10.4 24.3 35.1 47.4 50.0
014A00 400-3-60
3.0 2.20 5.0 35 13.9 10.4 24.3 35.1 50.1 60.0
Page 25
ELECTRICAL HEATER DATA TABLE (cont.)
Fan Motor Electric Heater(s)
Heater Part No. 40RUM
V-Ph-Hz Nominal Application Capacity (kW) MCA MOCP
CAELHEAT Size Hp kW FLA FLA
Capacity (kW) Stage 1 Stage 2 Total
2.4 1.80 5.2 5 4.6 — 4.6 11.6 21.0 25.0
001A00 230-3-60
3.7 2.80 10.2 5 4.6 — 4.6 11.6 27.3 30.0
2.4 1.80 4.1 5 3.5 — 3.5 5.1 11.5 15.0
002A00 400-3-60
4.7 3.50 7.5 5 3.5 — 3.5 5.1 15.8 20.0
2.4 1.80 2.6 5 4.6 — 4.6 5.8 10.5 15.0
002A00 460-3-60
3.7 2.80 4.8 5 4.6 — 4.6 5.8 13.3 15.0
2.4 1.80 5.2 10 9.2 — 9.2 23.1 35.4 40.0
004A00 230-3-60
3.7 2.20 10.2 10 9.2 — 9.2 23.1 41.6 45.0
2.4 1.80 4.1 10 6.9 — 6.9 10.1 17.8 20.0
005A00 400-3-60
4.7 3.50 7.5 10 6.9 — 6.9 10.1 22.0 25.0
2.4 1.80 2.6 10 9.2 — 9.2 11.6 17.8 20.0
005A00 460-3-60
3.7 2.80 4.8 10 9.2 — 9.2 11.6 20.5 25.0
2.4 1.80 5.2 15 13.8 — 13.8 34.6 49.8 50.0
007A00 230-3-60
3.7 2.80 10.2 15 13.8 — 13.8 34.6 56.0 60.0
12
2.4 1.80 4.1 15 10.4 — 10.4 15.0 23.9 25.0
008A00 400-3-60
4.7 3.50 7.5 15 10.4 — 10.4 15.0 28.1 30.0
2.4 1.80 2.6 15 13.8 — 13.8 17.3 24.9 25.0
008A00 460-3-60
3.7 2.80 4.8 15 13.8 — 13.8 17.3 27.6 30.0
2.4 1.80 5.2 25 13.8 9.2 23.0 57.7 78.6 80.0
010A00 230-3-60
3.7 2.80 10.2 25 13.8 9.2 23.0 57.7 84.9 90.0
2.4 1.80 4.1 25 10.4 6.9 17.3 25.0 36.4 40.0
011A00 400-3-60
4.7 3.50 7.5 25 10.4 6.9 17.3 25.0 40.6 45.0
2.4 1.80 2.6 25 13.8 9.2 23.0 28.9 39.4 40.0
011A00 460-3-60
3.7 2.80 4.8 25 13.8 9.2 23.0 28.9 42.1 45.0
2.4 1.80 5.2 35 18.4 13.8 32.2 80.8 107.5 110.0
013A00 230-3-60
3.7 2.80 10.2 35 18.4 13.8 32.2 80.8 113.8 115.0
2.4 1.80 4.1 35 13.9 10.4 24.3 35.1 49.0 50.0
014A00 400-3-60
4.7 3.50 7.5 35 13.9 10.4 24.3 35.1 53.3 60.0
2.9 2.20 7.5 10 9.2 — 9.2 23.1 38.3 40.0
016A00 230-3-60
3.7 2.80 10.2 10 9.2 — 9.2 23.1 41.6 45.0
2.4 1.80 4.1 10 6.9 — 6.9 10.0 17.6 20.0
017A00 400-3-60
4.7 3.50 7.5 10 6.9 — 6.9 10.0 21.9 25.0
2.9 2.16 3.8 10 9.2 — 9.2 11.6 19.3 20.0
017A00 460-3-60
3.7 2.80 4.8 10 9.2 — 9.2 11.6 20.5 25.0
2.9 2.20 7.5 20 18.4 — 18.4 46.2 67.1 70.0
019A00 230-3-60
3.7 2.80 10.2 20 18.4 — 18.4 46.2 70.5 80.0
2.4 1.80 4.1 20 13.9 — 13.9 20.1 30.3 35.0
020A00 14 400-3-60
4.7 3.50 7.5 20 13.9 — 13.9 20.1 34.5 35.0
2.9 2.16 3.8 20 18.4 — 18.4 23.1 33.6 35.0
020A00 460-3-60
3.7 2.80 4.8 20 18.4 — 18.4 23.1 34.9 35.0
2.9 2.20 7.5 30 18.4 9.2 27.6 69.3 96.0 100.0
022A00 230-3-60
3.7 2.80 10.2 30 18.4 9.2 27.6 69.3 99.4 100.0
2.4 1.80 4.1 30 13.9 6.9 20.8 30.0 42.6 45.0
023A00 400-3-60
4.7 3.50 7.5 30 13.9 6.9 20.8 30.0 46.9 50.0
2.9 2.16 3.8 30 18.4 9.2 27.6 34.6 48.0 50.0
023A00 460-3-60
3.7 2.80 4.8 30 18.4 9.2 27.6 34.6 49.3 50.0
Page 26
ELECTRICAL HEATER DATA TABLE (cont.)
Fan Motor Electric Heater(s)
Heater Part No. 40RUM
V-Ph-Hz Nominal Application Capacity (kW) MCA MOCP
CAELHEAT Size Hp kW FLA FLA
Capacity (kW) Stage 1 Stage 2 Total
3.7 2.80 10.2 10 9.2 — 9.2 23.1 41.6 45.0
016A00 230-3-60
5.0 3.70 12.6 10 9.2 — 9.2 23.1 44.6 50.0
3.0 2.20 5.0 10 6.9 — 6.9 10.0 18.8 20.0
017A00 400-3-60
4.7 3.50 7.5 10 6.9 — 6.9 10.0 21.9 25.0
3.7 2.80 4.8 10 9.2 — 9.2 11.6 20.5 25.0
017A00 460-3-60
5.0 3.70 6.3 10 9.2 — 9.2 11.6 22.4 25.0
3.7 2.80 10.2 20 18.4 — 18.4 46.2 70.5 80.0
019A00 230-3-60
5.0 3.70 12.6 20 18.4 — 18.4 46.2 73.5 80.0
3.0 2.20 5.0 20 13.9 — 13.9 20.1 31.4 35.0
020A00 400-3-60
4.7 3.50 7.5 20 13.9 — 13.9 20.1 34.5 35.0
3.7 2.80 4.8 20 18.4 — 18.4 23.1 34.9 35.0
020A00 460-3-60
5.0 3.70 6.3 20 18.4 — 18.4 23.1 36.8 40.0
16
3.7 2.80 10.2 30 18.4 9.2 27.6 69.3 99.4 100.0
022A00 230-3-60
5.0 3.70 12.6 30 18.4 9.2 27.6 69.3 102.4 110.0
3.0 2.20 5.0 30 13.9 6.9 20.8 30.0 43.8 45.0
023A00 400-3-60
4.7 3.50 7.5 30 13.9 6.9 20.8 30.0 46.9 50.0
3.7 2.80 4.8 30 18.4 9.2 27.6 34.6 49.3 50.0
023A00 460-3-60
5.0 3.70 6.3 30 18.4 9.2 27.6 34.6 51.1 60.0
3.7 2.80 10.2 50 27.5 18.4 45.9 115.2 156.8 160.0
025A00 230-3-60
5.0 3.70 12.6 50 27.5 18.4 45.9 115.2 159.8 160.0
3.0 2.20 5.0 50 20.8 13.9 34.7 50.1 68.9 70.0
026A00 400-3-60
4.7 3.50 7.5 50 20.8 13.9 34.7 50.1 72.0 80.0
3.7 2.80 4.8 50 27.5 18.4 45.9 57.6 78.0 80.0
026A00 460-3-60
5.0 3.70 6.3 50 27.5 18.4 45.9 57.6 79.9 80.0
10.0 7.45 25.2 20 18.2 — 18.2 45.7 88.6 100.0
028A00 230-3-60
10.0 7.45 25.2 20 18.2 — 18.2 45.7 88.6 100.0
10.0 7.45 16.2 20 13.9 — 13.9 20.1 45.4 50.0
029A00 400-3-60
10.0 7.45 16.2 20 13.9 — 13.9 20.1 45.4 50.0
28
10.0 7.45 25.2 40 18.4 18.4 36.8 92.4 147.0 150.0
031A00 230-3-60
10.0 7.45 25.2 40 18.4 18.4 36.8 92.4 147.0 150.0
10.0 7.45 16.2 40 13.9 13.9 27.8 40.1 70.4 80.0
032A00 400-3-60
10.0 7.45 16.2 40 13.9 13.9 27.8 40.1 70.4 80.0
Page 27
TYPICAL WIRING SCHEMATIC
Page 28
TYPICAL PIPING AND WIRING
Roof Installation and a Ceiling--Mounted Fan Coil
WEATHERPROOF
FUSED DISCONNECT*
PER NEC
OUTDOOR
UNIT
MOISTURE ELECTRIC
INDICATOR HEATER
FIELD- SIGHT GLASS* ACCESSORY
SUPPLIED
POWER
POWER WIRES
LLSV*
FILTER LIQUID
INSULATED DRIER* LINE
INDOOR
VAPOR UNIT
LINE
INDOOR
THERMOSTAT†
FUSED DISCONNECT
PER NEC
TO OPEN SIGHT
DRAIN
C09054
LEGEND:
NEC --- National Electrical Code
TXV --- Thermostatic Expansion Valve
* Field ---supplied
{ Double riser may be required. Consult condensing unit product data catalog for details.
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not intended for, or to include all details for,
a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.
Page 29
TYPICAL PIPING AND WIRING (CONT.)
Roof Installation and a Vertical Discharge Fan Coil
FUSED
DISCONNECT
SWITCH PER
NEC*
38AUMZ08
UNIT
INSULATED
VAPOR LINE
ELECTRIC
HEATER
ACCESSORY
24V
CONTROL LIQUID LINE
WIRE
DISCONNECT
PER NEC*
POWER WIRE
BULB CAPILLARY
TUBES
FILTER DRIER
SIGHT GLASS*
40RUM08
RETURN UNIT
AIR
LEGEND:
NEC - National Electrical Code
TXV - Thermostatic Expansion Valve
Piping
* Field supplied
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design Manual for details.
2. All wiring must comply with applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not intended for, or to include all
details for, a specific installation.
4. Filter driers must be bi-flow type suited for heat pump duty.
5. Internal factory-supplied TXVs and check valves not shown.
Page 30
TYPICAL PIPING AND WIRING (CONT.)
Dual Condensing Units and a Dual Circuit Fan
DISCONNECT
ELECTRIC PER NEC*
HEATER
ACCESSORY
24 V
CONTROL
WIRE
WEATHERPROOF
FUSED
DISCONNECT HEAT PUMP
PER NEC† UNIT B
BULB CAPILLARY
TUBES
RETURN 8 DIAMS FIELD
AIR MIN SUPPLIED
POWER
POWER WIRES
SUBBASE
ACCESSORY
SIGHT
40RMQ024 GLASS*
UNIT INSULATED
VAPOR LINE
15 DIAM 10 DIAM FILTER LIQUID
MIN MIN DRIER* LINE BIFLOW LIQUID
LINE SOLENOID
CONDENSATE WEATHERPROOF VALVE* HEAT PUMP
DRAIN FUSED UNIT A
DISCONNECT†
PER NEC
INSULATED
VAPOR LINE
POWER
WIRES
LEGEND FIELD
DIAM — Diameter SUPPLIED
NEC — National Electrical Code POWER
TXV — Thermostatic Expansion Valve
Piping LIQUID
*Field supplied. LINE
†Field supplied; not required if FIOP disconnect is supplied. BIFLOW LIQUID LINE
SOLENOID VALVE*
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System
Design Manual for details.
2. All wiring must comply with applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not
intended for, or to include all details for, a specific installation.
4. Filter driers must be bi-flow type suited for heat pump duty.
5. Heat Pump Unit A should be the first on, last off and be connected to the lower half of
the coil.
6. Internal factory-supplied TXVs and check valves not shown.
C101131
Page 31
APPLICATION DATA
Operating limits
Maximum fan speed
40RUM07-28 . . . . . . . . . . . . . . . . . . . 1200 RPM (20 R/S)
General
IMPORTANT: Do not bury refrigerant piping underground. Select equipment to match or to be slightly less than
peak load. This provides better humidity control, less unit cycling, and less part-load operation. Equipment should
be selected to perform at no less than 300 cfm/ton (40 L/s per kW).
The air handler fan must always be operating when the condensing unit is operating.
Ductwork should be sized according to unit size, not building load. For larger units with two fans, a split duct
transition is recommended at the fan outlets, but a plenum can be used with slight reduction in external static
pressure capability.
For variable air volume (VAV) systems with supply-to return air recycling, use the equipment room as a return air
plenum.
LEGEND
TXV - Thermostatic Expansion Valve
Page 32
APPLICATION DATA (cont.)
Medium-Static Drive Data - 60Hz - SI
Unit 40RUM07 40RUM08 40RUM12 40RUM14 40RUM16
Motor Drive
Motor Pulley Pitch
86.4-111.8 86.4 -111.8 86.4-111.8 86.4-111.8 94.0-119.4
Diameter (mm)
Pulley Factory Setting
2.5 2.5 2.5 2.5 3
Full Turns Open
Fan Drive
Pulley Pitch Diameter (mm) 224 203 203 208 218
Pulley Bore (mm) 25.4 25.4 25.4 36.5 36.5
Belt No. - Section 1-A 1-A 1-A 1-A 1-B
Belt Pitch (mm) 1074 1024 1024 1049 1062
Fan Speed (r/s)
Factory Setting 12.7 14 14 13.7 14
Range 11.1-14.4 12.2-15.8 12.2-15.8 11.9-15.4 12.4-15.7
Max Allowable Speed (r/s) 20 20 20 20 20
Change Per 1/2 Turn Of Moveable
0.328 0.36 0.36 0.352 0.278
Motor Pulley Flange
Max Full Turns From Closed Position 5 5 5 6 6
Shafts Center Distance (mm) 265-313 265-313 265-313 265-313 265-313
Page 33
GUIDE SPECIFICATIONS
Commercial Packaged Air-Handling Unit
40RUM – Packaged Air Handler
Size Range: 6.0 to 28.0 Tons
Part 1 — General
A. Indoor, packaged air-handling unit for use in commercial split systems. Unit shall have a multi--position
design and shall be capable of horizontal or vertical installation on a floor or in a ceiling, with or without
ductwork. (Only vertical units are to be applied without ductwork.)
B. Unit with direct-expansion coil shall be used in a refrigerant circuit with a matching air-cooled condensing
unit. Unit with chilled water coil shall be used in a chilled water circuit.
Part 2 — Products
2.01 EQUIPMENT
Indoor mounted, draw-thru, packaged air-handling unit that can be used in a suspended horizontal configuration or
a vertical configuration. Unit shall consist of forward-curved belt-driven centrifugal fan(s), motor and drive assembly,
pre-wired fan motor contactor, factory-installed refrigerant metering devices (direct-expansion coil units), cooling
coil, 1 –in (25.4-mm) aluminum air filter, and condensate drain pans for vertical or horizontal configurations.
A. Base Unit:
a. Cabinet shall be constructed of mill-galvanized steel.
b. Cabinet panels shall be fully insulated with 1/2-in. (12.7-mm) fire-retardant closed cell polyolefin
foam (ethylene) with density 32 ~ 40 kg/cu. meter reinforced with aluminum foil face. Insulation
shall conform to NFPA 90A.
c. Unit shall contain non-corroding condensate drain pans for both vertical and horizontal
applications. Drain pans shall have connections on right and left sides of unit to facilitate field
connection. Drain pans shall have the ability to be sloped toward the right or left side of the unit to
prevent standing water from accumulating in pans.
d. Unit shall have factory-supplied 1 –in (25.4-mm) aluminum air filter installed upstream from the
cooling coil. Filter access shall be from either the right or left side of the unit.
B. Coils:
DX coil is 4-row and consists of copper tubes with sine-wave aluminum fins bonded to the tubes by
mechanical expansion. Suction and liquid line connections or supply and discharge connections shall be
made on the same side of the coil.
Direct-expansion coils shall feature factory installed thermostatic expansion valves (TXVs) for refrigerant
control. The TXVs shall be Puron® R-410A compatible and capable of external adjustment. Direct-
expansion heat pump coils shall have a factory-installed bypass line and check valve assembly around the
TXVs to allow liquid flow from the coil to the outdoor unit during the heating mode. Coil tubing shall be
internally rifled to maximize heat transfer.
C. Operating Characteristics:
Unit shall be capable of providing____ cfm (L/s) airflow at an external static pressure of ____in. wg (kPag).
Page 34
D. Motor:
a. Fan motor of the size and electrical characteristics specified on the equipment schedule shall be
factory supplied and installed.
b. Motors rated at 2.4 through 2.9hp (1.79 through 2.16 hp) shall have internal thermal overload
protection. Motors rated at 5 hp (3.73 kW) shall be protected by a circuit breaker.
c. Evaporator-fan motor shall have permanently lubricated, sealed bearings and inherent automatic-
reset thermal overload protection or manual reset calibrated circuit breakers. Evaporator motors
are designed specifically for Carrier and do not have conventional horsepower (hp) ratings listed on
the motor nameplate. Motors are designed and qualified in the “air-over” location downstream of
the cooling coil and carry a maximum continuous bhp rating that is the maximum application bhp
rating for the motor; no “safety factors” above that rating may be applied.
E. Features:
a. Alternate Motor and Drive:
An alternate motor and/or medium-static or high-static drive shall be available to meet the airflow
and external static pressure requirements specified on the equipment schedule.
b. Electric Heaters:
Heaters shall be factory-supplied for field installation as shown on the equipment drawings. Electric
heat assembly shall be ETL (U.S.A.) and ETL, Canada, agency approved, and shall have single-
point power wiring. Heater assembly shall include contactors with 24-v coils, power wiring, 24-v
control wiring terminal blocks, and a hinged access panel. Electric heaters shall not be used with
air discharge plenum.
c. Air Discharge Plenum:
Plenum shall be factory-supplied to provide free-blow air distribution for vertical floor-mounted
units. A grille with moveable vanes for horizontal or vertical airflow adjustment shall be included.
Plenum shall be field-assembled and field-installed on the unit’s fan deck for blow-thru air
distribution. Plenum shall not be used with electric heaters.
d. Return-Air Grille:
Grille shall be factory-supplied for field installation on the unit’s return air opening.
e. Unit Subbase:
Subbase assembly shall be factory-supplied for field installation. Subbase shall elevate floor-
mounted vertical units to provide access for correct condensate drain connection.
f. Thermostat Controls:
i. TEMP System programmable communicating multi-stage thermostat with fan switch, time
clock, LCD display, °F/°C capability, and CCN (Carrier Comfort Network®) compatibility.
ii. Commercial Electronic Thermostat with 7-day time clock, auto-changeover, multi-stage
capability, and large LCD temperature display.
g. Overhead Suspension Package:
Package shall include necessary brackets to support units in a horizontal ceiling installation.
h. Condensate Drain Trap:
Trap shall have transparent, serviceable design for easy cleaning. Kit shall include overflow shutoff
switch and wiring harness for connection to an alarm if desired.
i.UV-C Germicidal Lamps:
i. UV-C emitters and fixtures shall be specifically designed for use inside an HVAC system.
An ASME nozzled test apparatus using a 45°F (7.2°C) airstream moving at not less than
400 fpm (189 liters/sec.) shall measure individual lamp output. Lamp output at 253.7 nm
shall not be less than 10μW/cm2 per inch of arc length measured at a distance of one
meter.
ii. UV-C power supplies shall be high efficiency, electric type which are matched to the
emitters and are capable of producing the specified output intensity with an input power no
more than 80 watts.
iii. Emitters and fixtures shall be installed in sufficient quantity and arranged so as to provide
an equal distribution of UV-C energy on the coil and drain pan.
iv. The minimum UV-C energy striking the leading edge of the coil fins shall be not less than
820 μW/cm2 at the closest point and through placement, not less than 60% of that value at
the farthest point. Equal amounts are to strike the drain pan, either directly or indirectly
through reflection.
Page 35
Manufacturer reserves the rights to discontinue or change at any time, specifications or designs without notice and without incurring any obligations.
Supersedes Version: 40RUM-PDCV5 Page 36 Catalog Number: 40RUM-PDCV6
Effective Date: 25-08-2019 Phase: 60Hz