ORACLE DATA SHEET

SUN RACK II
KEY BENEFITS ThHWZRPRGHOVRI2UDFOH¶VQHZ6XQ5DFN,,RIIHU\RXUGDWDFHQWHU  ease  of  use,  
OPTIMIZE YOUR SPACE
flexibility,  and  optimal  application  of  your  limited  space  to  bring  better  ROI  
x Optimization for vertical density
and  utilization  to  your  IT  infrastructure.  Offering  42U  capacity,  these  
x Choice of 1,058 mm or 1,200 mm depth
innovative,  industry-­standard  19-­inch  racks  pack  a  maximum  number  of  
x Highest-capacity power in two of the
smallest footprints available
components,  cables,  and  accessories  into  two  flRRUWLOHV¶ZRUWKRIVSDFHZKLOH
x Easy-to-install, compact PDUs with
providing  the  power  infrastructure  you  need.  
phase-current metering capabilities
x Ease of use and maintenance in robust
and safe designs capable of shipping
fully loaded
x Consistency with the latest Oracle rack-
mount products for a uniform look in the
data center

Designed for vertical density, the Sun Rack II provides a minimized footprint for
optimization of data center space.

Sun Rack II Product Overview


The Sun Rack II product line is well suited to a variety of data center environments. This
robust and cost-effective family of racks is optimized for vertical density and provides a
uniform appearance in your data center when installed with the latest Oracle servers and
storage products. The racks can be purchased with a strong shipping pallet for transport when
fully integrated with components. They offer an assortment of zero-RU, easily installed,
metered power distribution units (PDUs) for maximal rack power capacity in a minimal
footprint. In addition, they have been optimized for cooling, and both the front and rear doors
have 80 percent perforations that provide a high level of airflow through the rack.

Sun Rack II Features


The Sun Rack II includes the following features:

x 42U height, choice of 1,058 mm or 1,200 mm depth, and 600 mm width, with
industry-standard 19-inch adjustable square-hole RETMA rails to accommodate most
Oracle and third party rack-mountable IT equipment

x Selection of zero-RU PDU options with various input and output connectors,
providing the highest density in the lowest profile
ORACLE DATA SHEET

x 80 percent door perforations, enabling a high level of airflow through the cabinet

x Extruded aluminum frame and reduced rack height, making the rack relatively light
and easy to handle and enabling it to be safely rolled through most standard doorways

x 2,215 lb. (1,005 kg) maximum load²a rugged platform users can populate with more
components; available with enterprise packaging for safe shipment

Sun Rack II Specifications


PDUs
x A selection of 8 PDUs, from 10 kVA to 37 kVA, is available in single- and three-phase,
low- and high-voltage versions, with 14 to 45 C13 and two to 9 C19 outlets available
on a single PDU.
x Designed for quick and easy installation, each easy-to-mount PDU takes up zero RU,
enabling high vertical density and providing unobstructed access to rear FRUs and
accessories.
x The flexibility to add or change PDUs based on new data center wiring means that the
rack can be upgraded with higher-density PDUs.
x Rack-level power metering capability* with an LCD PDU display screen and a remote
network connection²and the ability to set threshold and alarm levels² prevents
overloaded circuits by providing a visible warning when the current draw is close to
the maximum amperage draw of the PDU strip

Stabilization Features
x Two foldaway anti-tilt bars inside the rack to ensure balance and prevent tipping
during equipment service from the front
x Four leveling feet that can be lowered to the floor

x Four floor-mounting brackets for extra safety

Dimensions
Model 1242 Model 1042
Height: 199.8cm (78.7 in.) Height: 199.8cm (78.7 in.)
Width: 60cm (23.6 in.) Width: 60cm (23.6 in.)
Depth: 120cm (47.2 in.) Depth: 105.8cm (41.66 in.)
Weight: 150.6 kg (332 lbs.) empty Weight: 123.4 kg (272 lbs.)
Models 1242 and 1042
Usable rack units 42
685.8mm (27 in.) adjustable from
Depth between front and rear RETMA rails
61.5mm(24.2 in.) to 825.8mm (32.4 in.)
Maximum dynamic load** 1,005 kg (2,215 lbs.)
Maintenance access requirement from rear 91.4cm (36 in.)
Maintenance access requirement from top 91.4cm (36 in.)

** Racks can be shipped with maximum load if enterprise packaging is used (models 1242E and 1042E).

Relevant Standards Supported


EIA 310-D

2
ORACLE DATA SHEET

Sun Rack II Power Distribution Unit Specifications


Oracle offers a selection of 8 easy-to-install PDUs.

Specifications for Low-Voltage PDUs


10 kVA 15 kVA 15 kVA 37 kVA
1 ph 1 ph 3 ph 3 ph
Amps per 48 A 72 A 69 A 180 A
PDU (2 × 24 A) (3 × 24 A) (3 × 23 A) (9 × 20 A)
42 C13 42 C13 42 C13 45 C13
Outlets
and 6 C19 and 6 C19 and 6 C19 and 9 C19
Number of Two 30 A, Three 30 A, One 60 A, Three 60 A,
Inputs 1 ph 1 ph 3 ph 3 ph
24 A max. 24 A max. per 40 A max. per 34.6 A max.
Current
per input input phase per phase
IEC 309- IEC 309-
Data Center NEMA NEMA 3P4W-IP67 3P4W-IP67
Receptacle L6-30R L6-30R 60 A, 250 V 60 A, 250 V
AC, 3 ph AC, 3 ph
Rack Models 1242 Models 1242
Model 1242 Model 1242
Compatibility and 1042 and 1042

Specifications for High-Voltage PDUs


10 kVA 22 kVA 15 kVA 37 kVA
1 ph 1 ph 3 ph 3 ph
Amps per 48 A 96 A 62.7 A 163 A
PDU (2 × 24 A) (3 × 32 A) (3 × 20.9 A) (9 × 18.1 A)
42 C13 42 C13 42 C13 45 C13
Outlets
and 6 C19 and 6 C19 and 6 C19 and 9 C19
Number of Two 25 A, Three 32 A, One 25 A, Three 25 A,
Inputs 1 ph 1 ph 3 ph 3 ph
25 A max. 32 A max. per 25 A max. per 18 A max.
Current
per input input phase per phase
IEC 309- IEC 309- IEC 309- IEC 309-
Data Center 2P3W-IP44 2P3W-IP44 4P5W-IP44 4P5W-IP44
Receptacle 32 A, 250 V 32 A, 250 V 32 A, 400 V 32 A, 400 V
AC AC AC, 3 ph AC, 3 ph
Rack Models 1242 Models 1242
Model 1242 Model 1242
Compatibility and 1042 and 1042

Warranty
9LVLWRUDFOHFRPVXQZDUUDQW\IRU2UDFOH¶VJOREDOwarranty support information on Sun products.

Services
9LVLWRUDFOHFRPVXQVHUYLFHVIRULQIRUPDWLRQRQ2UDFOH¶VVHUYLFHSURJUDPRIIHULQJVIRU6XQSURGXFWV

3
ORACLE DATA SHEET

Contact Us
For more information about [insert product name], visit oracle.com or call +1.800.ORACLE1 to speak to an Oracle representative.

Copyright © 2012, Oracle and/or its affiliates. All rights reserved.

This document is provided for information purposes only and the contents hereof are subject to change without notice. This document is not warranted to be error-free, nor subject
to any other warranties or conditions, whether expressed orally or implied in law, including implied warranties and conditions of merchantability or fitness for a particular purpose.
We specifically disclaim any liability with respect to this document and no contractual obligations are formed either directly or indirectly by this document. This document may not
be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without our prior written permission.

Oracle and Java are registered trademarks of Oracle and/or its affiliates. Other names may be trademarks of their respective owners.

AMD, Opteron, the AMD logo, and the AMD Opteron logo are trademarks or registered trademarks of Advanced Micro Devices. Intel and Intel Xeon are trademarks or registered
trademarks of Intel Corporation. All SPARC trademarks are used under license and are trademarks or registered trademarks of SPARC International, Inc. UNIX is a registered
trademark licensed through X/Open Company, Ltd. 1010

You might also like