LF - DPS 600B 48 4 19IN - en
LF - DPS 600B 48 4 19IN - en
LF - DPS 600B 48 4 19IN - en
General Mechanics
Efficiency > 92 % Construction Steel rack
Losses, max. EN 55 022, class B Cabinet standard 19 IN
Safety EN 60 950, class I Width, body 430 mm
Cooling Fan cooled Depth, overall 280 mm (including handles)
Protection IP 20 Height, overall 88.9 mm (2 U)
Weight, system 5 kg / 11 lb (excluding rectifier)
Input Weight, rectifiers 0.9 kg / 2.0 lb
AC connection 1 x L/N/PE
Nominal voltage 230 Vrms Environment
Voltage range 80 ... 300 Vrms Operation temperature -25 … +65 °C
Range, reduced power 80 … 130 V rms Relative humidity 95 % max, non condensing
Frequency range 50 / 60 Hz
Current nominal 11.6 Arms Control and monitoring
Current maximum 24 Arms Power system controller PSC 1
Line current Meets IEC 1000-3-2
Mains terminal common terminal Options
Transient OVP Option / external Number of rectifiers 1…3
LVD 60 A
Output AC selectivity fuse 4A (5x20mm) per module
Voltage, nominal 53.5 Vdc Transient OVP For external installation
Voltage range 42 …58 Vdc
Output current 44.8 Adc Accessories
Current limitation 56.0 Adc Rectifier front cover D0117507
Power, limitation 4 x 600 W
Power, nominal 2400 W All technical data is valid for a system with DPR 600B-48
Power, redundant 1800 W rectifier module.
Power, at 88Vrms 1600 W
*on request
Load distribution
Fuses (DIN 72581-3) 12 pcs / 1 … 30 A Subject to change due to technical progress.
PLD None
Battery connection
Fuses (DIN 72581-3) 2 pcs / 40 A
LVD Option