Module-6-EE 262
Module-6-EE 262
Module-6-EE 262
Electrical Machines 1
Module- 6
Yasser O. Assolami, Ph.D.
Assistant Professor
Department of Electrical Engineering
Taibah University, Yanbu Campus
Year 2023 G, 1444 H / Third Term
ysolami@taibahu.edu.sa
6/7/2023 Dr. Yasser O. Assolami 1
Module 6: Per Unit System
Content
57 MVA,
T3 110 kV TL2 T4 0.6 pf lag.
#1 #2 #2 #1
Vab1 Vab2
65.43 ohm Vab2 Vab1
#1 #2 #2 #1
40MVA 40MVA
22/110 kV Bus Bus 110/11 kV
6.4% 5 6 8%
3
6/7/2023 Dr. Yasser O. Assolami
Module 6: Per Unit System
Per Unit System Bus
Bus Bus Bus
2 3 4
1 T1 T2
220 kV TL1
#1 #2 #2 #1 Dr. A.M. Gaouda
Vab1 Vab2
X=48.4 ohm Vab2 Vab1 UAEU, ELEC472
57 MVA,
T3 T4
0.6 pf
lag.
110 kV TL2
#1 #2 65.43 ohm #2 #1
Vab1 Vab2 Vab2 Vab1
#1 #2 #2 #1
40MVA 40MVA
22/110 kV Bus Bus 110/11 kV
6.4% 8%
5 6
1 T1 4
2 3 T2
220 kV Transmission Line 1
X=48.4 ohm
Single-line diagram M
representation G T3
Dr. A.M. Gaouda
UAEU, ELEC472
T4
110 kV Transmission Line 2
X= 65.43 ohm
5 6
Dr. A.M. Gaouda Load
UAEU, ELEC472
NOTE:
Transformer equivalent circuit
G
as reflected into primary and
secondary sides.
6
- Z multiplied by square turns ratio
- I divided by the turns ratio
- V multiplied by the turns ratio - Z divided by square turns ratio
Dr. Yasser O. Assolami - I multiplied by the turns ratio
- V divided by the turns ratio
Module 6: Per Unit System
Per Unit System
Using Transformer ratio in analyzing this system requires large mathematical work.
Bus Bus Bus
1 2 4
50 MVA,
M 0.6 pf 100
lag. Bus MVA,
3 0.6 pf
T1 T2 lag.
220 kV TL1
#1 #2 #2 #1 Dr. A.M. Gaouda
Vab1 Vab2
X=48.4 ohm Vab2 Vab1 UAEU, ELEC472
57 MVA,
T3 T4 0.6 pf
110 kV TL2 lag.
#1 #2 65.43 ohm #2 #1
Vab1 Vab2 Vab2 Vab1
#1 #2 #2 #1
40MVA 40MVA
22/110 kV Bus Bus 110/11 kV
6.4% 8%
5 6
6/7/2023 Dr. Yasser O. Assolami 7
Module 6: Per Unit System
Per Unit System
• This large mathematical work can be avoided by utilizing the per unit
system. Various physical quantities such as power, voltage, current and
impedance are expressed as a decimal fraction of base quantities.
• The numerical per unit value of any quantity is its ratio to a chosen base
quantity of the same dimension. Thus, a per unit quantity is a normalized
quantity with respect to the chosen base value.
actual quantity
quantity in per unit =
base value of quantity
Four base quantities must be considered: power, voltage, current and impedance base
6/7/2023 Dr. Yasser O. Assolami 8
Module 6: Per Unit System
Per Unit System
• The per unit method of power system analysis offers distinct advantages
over the use of actual ampere, volts and ohms.
VB2, LL ( 3 VB , LN ) 2 VB2, LN
ZB = = =
S B3f 3S 1Bf S 1Bf
Solution: Z Z | S Base |
Z p .u. = = p.u.
Z Base 2
| V Base |
NOTE
The impedance could be
presented in
pu or %
6/7/2023 Dr. Yasser O. Assolami 0.2 pu → 20% 14
Module 6: Per Unit System
Example 2 – Per Unit
10 𝑘𝑉𝐴, 2200/220 𝑉, 60 𝐻𝑧 1 −phase transformer delivers rated power at rated voltage.
The transformer equivalent impedance is 10.4 + 𝑗 31.3 when referred to the high-voltage
side and its exciting current is 0.25 𝐴 when measured on the high-voltage side. Taking the
transformer rating as base,
a) Determine the base values of voltages, currents, and impedances for both high-voltage
and low-voltage sides.
b) Express the exciting current in per-unit form for both high-voltage and low-voltage
sides.
c) Obtain the equivalent circuit in per-unit form.
d) Find the full-load copper loss in per-unit form.
e) Determine the per-unit voltage regulation (using the per-unit equivalent circuit from
part c) when the transformer delivers 75% full load at 0.6 lagging power factor.
6/7/2023 Dr. Yasser O. Assolami 15
Module 6: Per Unit System
Example 2 - Solution – Per Unit
The per-unit values of the equivalent impedances referred to the high and low-
voltage sides are the same. The per-unit equivalent circuit is shown below
𝑉1 = 1.0486∠0.9°
Source
G
Dr. A.M. Gaouda
UAEU, ELEC472
40kVA
240/480V
X eq = 0 . 20 pu
G
referred to a new base set. Dr. A.M. Gaouda
Make sure that the base voltages in the system zones are related by the turns
ratios of the intervening transformers.
1 4
T1 2 3 T2
220 kV Transmission Line 1
X=48.4 ohm
How many
zones do we G M
T3 T4
have in this 110 kV Transmission Line 2
system? X= 65.43 ohm
5 6
Load
57 MVA, 0.6 pf lag.
MVA Voltage X
G 90 22 kV 18 %
T1 50 22/220 kV 10 %
T2 40 220/11 kV 06 %
T3 40 22/110 kV 6.4 %
T4 40 110/11 kV 08 %
6/7/2023 23
Module 6: Per Unit System
The base voltages in the system zones are related by
Solution: the turns ratios of the transformers.
100
X G = 0.18 = 0.20 pu
G M
T3 T4 Dr. A.M. Gaouda
110 kV Transmission Line 2
90
UAEU, ELEC472
5 6
VBase = 110kV 100
Load
X T 1 = 0.10 = 0.20 pu
57 MVA, 0.6 pf lag.
50
MVA Voltage X
100
G 90 22 kV 18 % X T 2 = 0.06 = 0.15 pu
40
T1 50 22/220 kV 10 %
100
T2 40 220/11 kV 06 % X T 3 = 0.064 = 0.16 pu
T3 40 22/110 kV 6.4 %
40
100
6/7/2023
T4 40 110/11 kV 08 %
Dr. Yasser O. Assolami
X T 4 = 0.08 = 0.20 pu 25
40
Module 6: Per Unit System
For the motor
VBase = 11kV
MVA Voltage X
M 66.5 10.45kV 18.5 %
T2
M
| ( S Base ) new | | (VBase )old |2
( Z p.u. ) new = ( Z p.u. )old . p.u. T4
| ( S Base )old | | (VBase ) new | 2
2
100 10.45
X M = 0.185 = 0.25 pu Load
66.5 11
57 MVA, 0.6 pf lag.
T3 T4
Z 110 kV Transmission Line 2
Z p .u. = X= 65.43 ohm
Z Base
2 5 VBase = 110kV 6
| VBase |
| Z Base |=
| Sbase | Z | MVA, S Base |
Z p .u. = p.u.
2
| kV , VBase |
48.4(100) 65.43(100)
X line1 = = 0.10 p.u. X line 2 =
2
= 0.54 p.u.
2 (110)
( 220)
6/7/2023 Dr. Yasser O. Assolami 27
Module 6: Per Unit System
For the Load
Load = 57 MVA, 0.6 pf lag.
VBase = 11kV
4
Vf T2
S 3f = 3 (V LL )( I L ) = 3 (V LL )(
* *
)
(Z L )
V LL | V LL |2
= 3 (V LL )( ) =*
M
( 3Z L ) ZL * T4
| V L− L |2
Z Load = *
ohm
S L( 3 f )
Load
S = 5753.13 MVA VL− L = 10.45 kV
L ( 3f ) 57 MVA, 0.6 pf lag.
(10.45) 2
Z Load = = 1.1495 + j1.53267ohm Z | MVA, S Base |
57 − 53.13 Z p .u. =
| kV , VBase |2
p.u.
5 6
Load
57 MVA, 0.6 pf lag.
j0.25
j0.16 j0.54 j0.20
j0.20
0.95
G M
j1.2667
6/7/2023 Dr. Yasser O. Assolami 29