Drafts - Concrete - 17 Jun 2021

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Hilti PROFIS Engineering 3.0.

70

www.hilti.co.uk
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - 17 Jun 2021 Date: 20/06/2021
Fastening Point:

Specifier's comments:

1 Input data
Anchor type and size: HST3 M16 hef2
Return period (service life in years): 50
Item number: 2105858 HST3 M16x135 35/15
Effective embedment depth: hef = 85.0 mm, hnom = 98.0 mm
Material:
Approval No.: ETA-98/0001
Issued I Valid: 13/07/2020 | -
Proof: Design Method EN 1992-4, Mechanical
Stand-off installation: eb = 0.0 mm (no stand-off); t = 15.0 mm

Baseplate :
R lx x ly x t = 500.0 mm x 500.0 mm x 15.0 mm; (Recommended plate thickness: not calculated)

Profile: Square hollow, 120 x 120 x 5,0; (L x W x T) = 120.0 mm x 120.0 mm x 5.0 mm


Base material: 2
cracked concrete, C20/25, fc,cyl = 20.00 N/mm ; h = 900.0 mm, User-defined partial material safety
factor gc = 1.500
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: No reinforcement or Reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement

R
- The anchor calculation is based on a rigid baseplate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Hilti PROFIS Engineering 3.0.70

www.hilti.co.uk
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - 17 Jun 2021 Date: 20/06/2021
Fastening Point:

1.1 Load combination


Case Description Forces [kN] / Moments [kNm] Seismic Fire Max. Util. Anchor [%]
1 Load case 1 N = 0.000; Vx = 0.000; Vy = 0.000; no no 93
Mx = 0.000; My = 14.480; Mz = 0.000;

2 Load case 2 N = 0.000; Vx = 0.000; Vy = 0.000; no no 93


Mx = 0.000; My = 14.480; Mz = 0.000;

3 Load case 3 N = 0.000; Vx = 0.000; Vy = 0.000; no no -


Mx = 0.000; My = 0.000; Mz = 0.000;

2 Load case/Resulting anchor forces y


3 4
Controlling load case: 2 Load case 2

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y x
1 16.682 0.000 0.000 0.000 Tension Compression
2 0.066 0.000 0.000 0.000
3 16.682 0.000 0.000 0.000
4 0.066 0.000 0.000 0.000

max. concrete compressive strain: 0.09 [‰] 1 2


max. concrete compressive stress: 2.77 [N/mm ]
2

resulting tension force in (x/y)=(-198.4/0.0): 33.496 [kN]


resulting compression force in (x/y)=(233.9/0.0): 33.496 [kN]

Anchor forces are calculated based on the assumption of a rigid baseplate.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Hilti PROFIS Engineering 3.0.70

www.hilti.co.uk
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - 17 Jun 2021 Date: 20/06/2021
Fastening Point:

3 Tension load (EN 1992-4, Section 7.2.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel failure* 16.682 54.286 31 OK
Pull-out failure* 16.682 18.000 93 OK
Concrete Breakout failure** 16.682 17.990 93 OK
Splitting failure** N/A N/A N/A N/A

* highest loaded anchor **anchor group (anchors in tension)

3.1 Steel failure

N
NEd £ NRd,s = Rk,s EN 1992-4, Table 7.1
gM,s

NRk,s [kN] gM,s NRd,s [kN] NEd [kN]


76.000 1.400 54.286 16.682

3.2 Pull-out failure

y c · NRk,p
NEd £ NRd,p = EN 1992-4, Table 7.1
gM,p

NRk,p [kN] yc g M,p NRd,p [kN] NEd [kN]


27.000 1.000 1.500 18.000 16.682

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Hilti PROFIS Engineering 3.0.70

www.hilti.co.uk
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - 17 Jun 2021 Date: 20/06/2021
Fastening Point:

3.3 Concrete Breakout failure

N
NEd £ NRd,c = Rk,c EN 1992-4, Table 7.1
gM,c
0 Ac,N
NRk,c = NRk,c · 0
· y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
1
y ec1,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eN,1
scr,N )
1
y ec2,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eN,2
scr,N )
y M,N =1 EN 1992-4, Eq. (7.7)

2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] fc,cyl [N/mm ]
65,025 65,025 127.5 255.0 20.00

ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N


0.0 1.000 0.0 1.000 1.000 1.000
0
z [mm] y M,N k1 NRk,c [kN] gM,c NRd,c [kN] NEd [kN]
432.3 1.000 7.700 26.986 1.500 17.990 16.682

Group anchor ID
3

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Hilti PROFIS Engineering 3.0.70

www.hilti.co.uk
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - 17 Jun 2021 Date: 20/06/2021
Fastening Point:

4 Shear load (EN 1992-4, Section 7.2.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel failure (without lever arm)* N/A N/A N/A N/A
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout failure* N/A N/A N/A N/A
Concrete edge failure in direction ** N/A N/A N/A N/A

* highest loaded anchor **anchor group (relevant anchors)

5 Displacements (highest loaded anchor)


Short term loading:

NSk = 10.426 [kN] dN = 1.4006 [mm]


VSk = 0.000 [kN] dV = 0.0000 [mm]
dNV = 1.4006 [mm]
Long term loading:

NSk = 10.426 [kN] dN = 1.3227 [mm]


VSk = 0.000 [kN] dV = 0.0000 [mm]
dNV = 1.3227 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the baseplate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

6 Warnings
• The anchor design methods in PROFIS Engineering require rigid baseplates per current regulations (AS 5216:2018, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the baseplate are not considered - the
baseplate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering
calculates the minimum required baseplate thickness with CBFEM to limit the stress of the baseplate based on the assumptions explained
above. The proof if the rigid baseplate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be
checked for agreement with the existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EN 1992-4, Annex A!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 6.1 of EN 1992-4! For larger diameters
of the clearance hole see section 6.2.2 of EN 1992-4!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• For the determination of the y re,v (concrete edge failure) the minimum concrete cover defined in the design settings is used as the concrete
cover of the edge reinforcement.
• The characteristic bond resistances depend on the return period (service life in years): 50

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Hilti PROFIS Engineering 3.0.70

www.hilti.co.uk
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - 17 Jun 2021 Date: 20/06/2021
Fastening Point:

7 Installation data
2 2
Baseplate, steel: S 235; E = 210,000.00 N/mm ; fyk = 235.00 N/mm Anchor type and size: HST3 M16 hef2
Profile: Square hollow, 120 x 120 x 5,0; (L x W x T) = 120.0 mm x 120.0 mm x Item number: 2105858 HST3 M16x135 35/15
5.0 mm
Hole diameter in the fixture: df = 18.0 mm Maximum installation torque: 110 Nm
Plate thickness (input): 15.0 mm Hole diameter in the base material: 16.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 106.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 160.0 mm
Cleaning: Manual cleaning of the drilled hole according to instructions for use is
required.

Hilti HST3 stud anchor with 98 mm embedment, M16 hef2, Steel galvanized, installation per ETA-98/0001

7.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Manual blow-out pump • Torque wrench
• Properly sized drill bit • Hammer

y
250.0 250.0
50.0

3 4
250.0
400.0

x
250.0

1 2
50.0

50.0 400.0 50.0

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 -200.0 -200.0 350.0 750.0 350.0 750.0
2 200.0 -200.0 750.0 350.0 350.0 750.0
3 -200.0 200.0 350.0 750.0 750.0 350.0
4 200.0 200.0 750.0 350.0 750.0 350.0

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Hilti PROFIS Engineering 3.0.70

www.hilti.co.uk
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - 17 Jun 2021 Date: 20/06/2021
Fastening Point:

8 Drilling and installation

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Hilti PROFIS Engineering 3.0.70

www.hilti.co.uk
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - 17 Jun 2021 Date: 20/06/2021
Fastening Point:

9 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan