Deep Sea Electronics: DSE8910 & DSE8920 Installation Instructions
Deep Sea Electronics: DSE8910 & DSE8920 Installation Instructions
Deep Sea Electronics: DSE8910 & DSE8920 Installation Instructions
ISSUE: 2
NOTE: Larger versions of the Typical Wiring Diagrams are available in the products’ operator manuals, refer to DSE
Publication: 057-310 DSE8910 Operator Manual & 057-311 DSE8920 Operator Manual, both available from DSE8910 & DSE8920 Installation Instructions
www.deepseaelectronics.com.
NOTE: The available parameters within the Main Configuration Edtior differ depending if the DSE8910 or DSE8920 software
application is selected. For a list of available configuration parameters, refer to DSE Publication: 057-310 DSE8910 Operator
Manual & 057-311 DSE8920 Operator Manual, both available from www.deepseaelectronics.com.
• Ensure the engine is at rest and the module by pressing the Stop/Reset Mode
button.
• Press the Stop/Reset Mode and Tick buttons together to enter the main
configuration editor.
• If a module security PIN has been set, the PIN request is then shown.
• Press the Tick button, the first ‘#’ changes to ‘0’. Press the Up or Down buttons to adjust it to the correct value.
• Press the Right button when the first digit is correctly entered. The digit previously entered now shows as ‘#’ for security.
• Repeat this process for the other digits of the PIN number. Press the Left button to move back to adjust one of the previous
digits.
• When the Tick button is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not correct, the
PIN must be re-entered.
• If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is displayed.
EDITING A PARAMETER
NOTE: If the editor is left inactive for the duration of the Page Timer, it is automatically exited to ensure security.
WARNING!: More than one live circuit exists, see diagram overleaf for further information.
ATTENTION!: Il existe plusieurs circuits sous tension. Voir le schéma au verso pour plus d'informations.
Specification Description
Screw Terminal Tightening Torque • 4.5 lb-in (0.5 Nm)
Conductors • Terminals suitable for connection of conductor size 13 AWG to 20 AWG (0.5 mm² to 2.5
mm²).
• Conductor protection must be provided in accordance with NFPA 70, Article 240
• Low voltage circuits (35 V or less) must be supplied from the engine starting battery or an PANEL FASCIA FIXING CLIPS
isolated secondary circuit.
• The communication, sensor, and/or battery derived circuit conductors shall be separated
NOTE: In conditions of excessive vibration, mount the module on suitable anti-vibration mountings.
and secured to maintain at least ¼ ” (6 mm) separation from the generator and mains
connected circuit conductors unless all conductors are rated 600 V or greater.
The module is held into the panel fascia using the supplied fixing clips:
Current Inputs • Must be connected through UL Listed or Recognized isolating current transformers with the • Withdraw the fixing clip screw (turn anticlockwise) until only the pointed end is protruding from the clip.
secondary rating of 5 A max. • Insert the three ‘prongs’ of the fixing clip into the slots in the side of the module case.
Communication Circuits • Must be connected to communication circuits of UL Listed equipment • Pull the fixing clip backwards (towards the back of the module) ensuring all three prongs of the clip are inside their allotted slots.
DC Output Pilot Duty • 0.5 A • Turn the fixing clip screws clockwise until they make contact with the panel fascia.
Mounting • Suitable for flat surface mounting in Type 1 Enclosure Type rating with surrounding air • Turn the screw a quarter of a turn to secure the module into the panel fascia. Care must be taken not to over tighten the fixing clip
temperature -22 ºF to +122 ºF (-30 ºC to +50 ºC) screws.
• Suitable for pollution degree 3 environments when voltage sensing inputs do not exceed
300 V. When used to monitor voltages over 300 V device to be installed in an unventilated
or filtered ventilation enclosure to maintain a pollution degree 2 environment.
Operating Temperature • -22 ºF to +122 ºF (-30 ºC to +50 ºC)