Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

iC60H Circuit Breakers (Curve B, C, D)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Protection iC60H circuit breakers

Circuit protection
(curve B, C, D)

BS/EN 60947-2
BS/EN 60898-1
b iC60H circuit breakers are multi-standard circuit breakers which combine the
following functions:
v circuit protection against short-circuit currents,
v circuit protection against overload currents,
v suitable for industrial isolation according to IEC/EN 60947-2, standard.
v fault tripping indication by a red mechanical indicator in circuit breaker front face.
PB111065-40

PB111069-40

Alternating current (AC) 50/60 Hz


Breaking capacity (Icu) according to IEC/EN 60947-2 Service
Voltage (Ue) breaking
capacity
Ph/Ph (2P, 3P, 4P) 12 to 133 V 220 to 240 V 380 to 415 V 440 V
(Ics)
Ph/N (1P) 12 to 60 V 100 to 133 V 220 to 240 V -
Rating (In) 1 to 4 A 70 kA 70 kA 70 kA 50 kA 100 % of Icu
6 to 40 A 42 kA 30 kA 15 kA 10 kA 50 % of Icu
50/63 A 42 kA - 15 kA 10 kA 50 % of Icu
Breaking capacity (Icn) according to IEC/EN 60898-1
Voltage (Ue)
Ph/Ph 400 V
Ph/N 230 V
Rating (In) 1 to 63 A 10000 A

Direct current (DC)


Breaking capacity (Icu) according to IEC/EN 60947-2 Service
Voltage (Ue) breaking
capacity
Between +/- 12 to 48 V 72 V 100 to 133 V 220 to 250 V
(Ics)
Number of poles 1P 2P (in series) 3P (in series) 4P (in series)
Rating (In) 1 to 63 A 20 kA 10 kA 10 kA 20 kA 10 kA 100 % of Icu

Catalogue numbers
iC60H circuit breaker
Type 1P 2P
E45092

E45094

1 1 3

2 2 4

Calibre (In) Courbe Courbe


B C D B C D
1A A9F53101 A9F54101 A9F55101 A9F53201 A9F54201 A9F55201
2A A9F53102 A9F54102 A9F55102 A9F53202 A9F54202 A9F55202
3A A9F53103 - - - - -
4A A9F53104 A9F54104 A9F55104 A9F53204 A9F54204 A9F55204
6A A9F53106 A9F54106 A9F55106 A9F53206 A9F54206 A9F55206
10 A A9F53110 A9F54110 A9F55110 A9F53210 A9F54210 A9F55210
16 A A9F53116 A9F54116 A9F55116 A9F53216 A9F54216 A9F55216
20 A A9F53120 A9F54120 A9F55120 A9F53220 A9F54220 A9F55220
25 A A9F53125 A9F54125 A9F55125 A9F53225 A9F54225 A9F55225
32 A A9F53132 A9F54132 A9F55132 A9F53232 A9F54232 A9F55232
40 A A9F53140 A9F54140 A9F55140 A9F53240 A9F54240 A9F55240
50 A A9F53150 A9F54150 A9F55150 A9F53250 A9F54250 A9F55250
63 A A9F53163 A9F54163 A9F55163 A9F53263 A9F54263 A9F55263
Width in 9-mm modules 2 4

(1) VDE approved only.

36
Protection iC60H circuit breakers
Circuit protection
(curve B, C, D) (cont.)

b Insulated terminals IP20


Visi-trip window
b Fault tripping is indicated by a red
mechanical indicator on the front face

Positive contact indication


b Suitable for industrial isolation according to
IEC/EN 60947-2 standard.
b The presence of the green strip guarantees
physical opening of the contacts and allows
operations to be performed on the downstream
circuit in complete safety
b Large circuit
labelling area

b Insulated terminals IP20

b Double clip for


dismounting with comb
busbar in place

b Increased product service life thanks to:


v overvoltage resistance by high level of industrial performances conception
(pollution degree, rated impulse withstand voltage and insulation voltage),
v high performance limitation (see limitation curves),
v fast closing independent of the speed of actuation of the toggle.
b Remote indication, open/closed/tripped, by optional auxiliary contacts.
b Top or bottom electrical feeding.

3P 4P
E45095

E45097

1 3 5 1 3 5 7

2 4 6 2 4 6 8

Courbe Courbe
B C D B C D
A9F53301 A9F54301 A9F55301 A9F53401 A9F54401 A9F55401
A9F53302 A9F54302 A9F55302 A9F53402 A9F54402 A9F55402
- - - - - -
A9F53304 A9F54304 A9F55304 A9F53404 A9F54404 A9F55404
A9F53306 A9F54306 A9F55306 A9F53406 A9F54406 A9F55406
A9F53310 A9F54310 A9F55310 A9F53410 A9F54410 A9F55410
A9F53316 A9F54316 A9F55316 A9F53416 A9F54416 A9F55416
A9F53320 A9F54320 A9F55320 A9F53420 A9F54420 A9F55420
A9F53325 A9F54325 A9F55325 A9F53425 A9F54425 A9F55425
A9F53332 A9F54332 A9F55332 A9F53432 A9F54432 A9F55432
A9F53340 A9F54340 A9F55340 A9F53440 A9F54440 A9F55440
A9F53350 A9F54350 A9F55350 A9F53450 A9F54450 A9F55450
A9F53363 A9F54363 A9F55363 A9F53463 A9F54463 A9F55463
6 8

37
Protection iC60H circuit breakers
Circuit protection
(curve B, C, D) (cont.)

Connection Without accessory With accessories


DB405585

Rating Tightening Copper cables 50 mm² Screw-on Multi-cables terminal


torque Rigid Flexible Al connection Rigid Flexible
14 mm terminal for ring
6.5 mm or ferrule cables cables
terminal
PZ2

DB122945

DB122946

DB122935

DB118789

DB118787
1 to 25 A 2 N.m 1 to 25 mm2 1 to 16 mm2 - Ø 5 mm - -
32 to 63 A 3.5 N.m 1 to 35 mm2 1 to 25 mm2 50 mm2 3 x 16 mm2 3 x 10 mm2

Technical data
DB123310

Main characteristics
According to IEC/EN 60947-2
Insulation voltage (Ui) 500 V AC
Pollution degree 3
Rated impulse withstand voltage (Uimp) 6 kV
Thermal tripping Reference temperature 50 °C

Clip on DIN rail 35 mm. Magnetic tripping B curve 4 In ± 20 %


C curve 8 In ± 20 %
D curve 12 In ± 20 %
Utilization category A
According to IEC/EN 60898-1
Limitation class 3
Rated making and breaking capacity of an Icn1 = Icn
individual pole (Icn1)
Additional characteristics
Breaking capacity 40 A 4 kA
under 1 pole with IT 50/63 A 3 kA
380-415 V isolated
neutral system
(case of double fault)
Degree of protection Device only IP20
(IEC 60529) Device in modular IP40
enclosure Insulation classe II
Endurance (O-C) Electrical 10,000 cycles
Mechanical 20,000 cycles
Overvoltage category (IEC 60364) IV
DB123312

Operating temperature -35°C to +70°C


Storage temperature -40°C to +85°C
Tropicalization (IEC 60068-1) Treatment 2 (relative humidity 95 % to 55°C)

Indifferent position of installation.


DB123314

IP20 IP40

38
Protection iC60H circuit breakers
Circuit protection
(curve B, C, D) (cont.)

Weight (g)
Circuit-breaker
Type iC60H
1P 125
2P 250
3P 375
4P 500

Dimensions (mm)
78.5
DB405584

4P 72
69.5
3P 54
50
2P 36
5.5
1P 18

85 45

64
4.6

39