Protection C120N circuit breakers

Circuit protection
(curves B, C, D)

IEC/EN 60898-1, CEI 60947-2


DB126596

DB126597

DB126598
(*)
C120N circuit breakers are multistandard circuit breakers that combine the following
functions:
Country approval pictograms b Circuit protection against short-circuit currents,
b Circuit protection against overload currents,
b Suitability for isolation in the industrial sector to IEC/EN 60947-2,
b Fault tripping and indication by adding auxiliaries.
056799N_SE-32

Alternating current (AC) 50/60 Hz


Breaking capacity (Icu) to IEC/EN 60947-2 Service
Type Voltage (V) breaking
capacity (Ics)
1P 130 V 230 to 400 V 400 to 415 V 440 V

18360 Rating (In) 63 to 125 A 20 kA 10 kA 3 kA (1) - 75 % Icu


2P/3P/4P 130 V 230 to 400 V 400 to 415 V 440 V
63 to 125 A - 20 kA 10 kA 6 kA 75 % Icu
Breaking capacity (Icu) to CEI/EN 60898-1
056801N_SE-32

Type Voltage (V)


1P, 2P, 3P, 4P 230 to 400 V
Rating (In) 63 to 125 A 10000 A 75 % Icu
(1) One-pole breaking capacity in IT isolated neutral system (double fault).

Direct current (DC)


Breaking capacity (Icu) to IEC/EN 60947-2 Service breaking
Type Voltage (V) capacity (Ics)
18376
1P 24/48 V 125 V 250 V
Rating (In) 63 to 125 A 10 kA 10 kA - 100 % Icu
2P (in series) 24/48 V 125 V 250 V
63 to 125 A - 10 kA 100 % Icu

Catalogue numbers
C120N circuit breaker
Type 1P 2P
1 1 3

2 2 4

Auxiliaries Remote indication and tripping, Remote indication and tripping,


CM907002F module CM907002F module
Vigi C120 Vigi C120 add-on residual current device, Vigi C120 add-on residual current device,
CM902007F module CM902007F module
Rating (In) Curve Curve
B C D B C D
63 A 18340 18356 18378 18344 18360 18382
80 A 18341 18357 18379 18345 18361 18383
100 A 18342 18358 18380 18346 18362 18384
125 A 18343 18359 18381 18347 18363 18385
Largeur en pas de 9 mm 3 6
Accessories CM907003F module CM907003F module
(*) NF B and C curves only.

2 version: 1.0 CM901025E.indd


Protection C120N circuit breakers
Circuit protection
(curves B, C, D) (cont.)

b Terminals insulated
to IP20

b Location for 4 clip-on terminal


markers

b Label holder on toggle

Positive contact indication


b Suitability for isolation in the industrial sector to
IEC/EN 60947-2.
b The presence of the green strip guarantees that
the contacts open physically and allows work to be b Longer product service life thanks to:
carried out safely on the downstream circuit. v good overvoltage withstand capacity: products designed to offer a high industrial
performance level (degree of pollution, rated impulse withstand voltage and
insulation voltage).
v high limitation performances (see limitation curves).
v fast closure independent of toggle operating speed.
b Remote indication of the open/closed/tripped state by auxiliary contacts (optional).
b Power supply from above or below.

3P 4P
1 3 5 1 3 5 7

2 4 6 2 4 6 8

Remote indication and tripping, Remote indication and tripping,


CM907002F module CM907002F module
Vigi C120 add-on residual current device, CM902007F module Vigi C120 add-on residual current device, CM902007F module

Curve Curve
B C D B C D
18348 18364 18386 18352 18371 18390
18349 18365 18387 18353 18372 18391
18350 18366 18388 18354 18374 18392
18351 18367 18389 18355 18376 18393
9 12
CM907003F module CM907003F module

CM901025E.indd version: 1.0 3


Protection C120N circuit breakers
Circuit protection
(curves B, C, D) (cont.)

Connection Without access. With accessories


DB126143

Rating Tightening Copper cables 50 mm Al Screw-on Multi-cable terminal


15 mm
torque Rigid/semi- Flexible or Terminal connection Rigid Flexible
6.5 mm rigid with ferrule for ring cables cables
terminal (1)

DB122946

DB122935

DB118789

DB118787
DB122945
PZ2

63 to 125 A 3.5 N.m 1 to 50 mm2 1.5 to 35 mm2 16 to 50 mm2 5 mm 3 x 16 mm 3 x 10 mm


(1) For lugs up to 63 A, front or rear access.

Technical data
DB118767

Main characteristics
To IEC/EN 60947-2
Insulation voltage (Ui) 500 V AC
Degree of pollution 3
Rated impulse withstand voltage (Uimp) 6 kV

Clips onto 35 mm DIN rail. Thermal Reference temperature 50 C


tripping
To IEC/EN 60898-1
Magnetic tripping Curve B 3 and 5 In
DB122831

Curve C 5 and 10 In
Curve D 10 and 14 In
Limitation class 3
Additional characteristics
Degree of protection Device only IP20
(IEC 60529) Device in a modular IP40
enclosure
Any installation position. Endurance (O-C) Electrical 63 A 10000 cycles (O-C)
80...125 A 5000 cycles (O-C)
Mechanical 20000 cycles
Operating temperature -25 C to +70 C
DB122932

IP20 IP40 Storage temperature -40 C to +85 C


Tropicalisation (IEC 60068-1) Treatment 2
(relative humidity 95 % at 55 C)

4 version: 1.0 CM901025E.indd


Protection C120N circuit breakers
Circuit protection
(curves B, C, D) (cont.)

Weight (g)
Circuit breaker
Type C120N
1P 205
2P 410
3P 615
4P 820

Dimensions (mm)