Synchro-Check Relay: 1MRS 750421-MBG Spau 140 C
Synchro-Check Relay: 1MRS 750421-MBG Spau 140 C
1MRS 750421-MBG
Issued: April 1999
Status: Updated
Version: B/08.11.2001
Data subject to change without notice
Features • Two identical operation stages allowing the • Continuous auto-diagnostic self-supervi-
closing conditions of two separate circuit sion of both relay hardware and software
breakers to be checked
• Serial interface for connecting the relay to
• Synchro-check function available for both the SPA bus and higher-level host systems
operation stages
• Powerful software support for parameter-
• Voltage-check function available for both ization of the relay, for reading measured
operation stages and recorded values, events, etc., and for
storing readings
• Two different operation modes: continuous
mode and command mode operation • Member of the SPACOM product family
and ABB’s Substation Automation system
• Numerical display of setting values, mea-
sured values and values recorded on relay • CE marking according to the EC directive
operation for EMC
Application The numerical synchro-check relay type or two electrically interconnected network
SPAU 140 C is a voltage measuring relay sections are to be connected together. The
designed to be used when two power systems voltage-check function is used when a dis-
are to be connected together. connected bus/line is to be connected to an
energized section of a network. The synchro-
The synchro-check relay SPAU 140 C can be check function allows circuit breaker closing
used for both synchro-check functions and only if the voltages on both sides of the cir-
voltage-check functions. The synchro-check cuit breaker fulfill the preset conditions as to
function is used when two separate networks magnitude, phase and frequency difference.
1
Synchro-check relay SPAU 140 C
1MRS 750421-MBG
2
Synchro-check relay SPAU 140 C
1MRS 750421-MBG
7DEOH2XWSXWFRQWDFWUDWLQJV
Type of contact Heavy-duty Signalling
Terminals 85-86, 87-88 70-71-72, 68-69
Rated voltage 250 V ac/dc
Thermal withstand Carry continuously 5A 5A
capability Make and carry for 0.5 s 30 A 10 A
Make and carry for 3 s 15 A 8A
Breaking capacity for dc, 220 V dc 1A 0.15 A
when the control circuit 110 V dc 3A 0.25 A
time constant
48 V dc 5A 1A
L/R ≤ 40 ms, at the
control voltage levels
Contact material AgCdO2
7DEOH([WHUQDOFRQWUROLQSXW
Blocking and control inputs 10-11, 22-23, 45-46, 47-48
External control voltage level 18…265 V dc or 80…265 V ac
Typical control current of activated input circuit 2…20 mA
7DEOH'DWDFRPPXQLFDWLRQ
Transmission mode Fibre-optic serial bus
Data code ASCII
Transfer rates, selectable 4800 or 9600 Bd
Optional bus connection for plastic core cables SPA-ZC 17BB
module, powered from for glass fibre cables SPA-ZC 17MM
an external power
source
Optional bus connection for plastic core cables SPA-ZC 21BB
module, powered from for glass fibre cables SPA-ZC 2 MM
the host relay
7DEOH$X[LOLDU\VXSSO\PRGXOHV
Supply and output relay operative voltage range 80…265 V ac/dc
module SPTU 240R4
Supply and output relay operative voltage range 18…80 V dc
module SPTU 48R4
Power consumption, quiescent/operation conditions ~5 W/~7 W
3
Synchro-check relay SPAU 140 C
1MRS 750421-MBG
4
Synchro-check relay SPAU 140 C
1MRS 750421-MBG
7DEOH7HVWVDQGVWDQGDUGV
Test voltages Dielectric test voltage (IEC 255-5) 2.0 kV, 50 Hz, 1 min
Impulse test voltage (IEC 255-5) 5 kV, 1.2/50 µs, 0.5 J
Insulation resistance voltage >100 MΩ, 500 V dc
(IEC 255-5)
Interference tests High-frequency (1 MHz) 2.5 kV
disturbance test (IEC 255-22-1),
common mode
High-frequency (1 MHz) 1.0 kV
disturbance test (IEC 255-22-1),
differential mode
Fast transients (IEC 255-22-4, 4 kV, 5/50 ns
class III), power supply inputs
Fast transients (IEC 255-22-4, 2 kV, 5/50 ns
class III), other inputs
Electrostatic discharge 8 kV
(IEC 255-22-2), air discharge
Electrostatic discharge 6 kV
(IEC 255-22-2), contact discharge
Environmental conditions Specified ambient service -10…+55°C
temperature range
Transport and storage -40…+70°C
temperature range
Temperature influence on the <0.1%/°C
operate values of the relay over
the specified ambient service
temperature range
Long term damp heat withstand <95%, +40°C, 96 h
(IEC 68-2-3)
Degree of protection by enclosure IP 54
of the relay case (according to
IEC 529) when the relay is panel-
mounted
Weight ~3 kg
5
Synchro-check relay SPAU 140 C
1MRS 750421-MBG
Block diagram L1
L2
L3
I
L1 I
L2
L3
I
I
Rx Tx
Uaux
SPA-ZC_
D C B A
X2
1
X3
U1 U2 U3
U1 IRF
U3 SC13
CB13
BS13 T1
NC13
SGB/1 CS13 VC13 SGR/1 T3
CSF13
SGB/3 T5
U2 SGR/3
U3 SC23 CB23
T2
BS23 NC23
SGB/2 CS23
VC23 CSF23 SGR/5
T4
T6
SGB/4 SGR/7
I/O
SPAU 140 C X1
6
Synchro-check relay SPAU 140 C
1MRS 750421-MBG
139 ±1
Panel cut-
136
162
out
dim100
Semi-flush mounting
a b
Raising frame a b
SFM100_1
SPA-ZX104 SPA-ZX110
SPA-ZX105 SPA-ZX115
SPA-ZX106
+0,4 158 263
482,6 –0 (19")
115
ø6
10
177 –0 (4U)
101,6
7
+0,4
312
292
21,5
6
115 98
104_6_10
Fig. 4 Mounting cabinets and frames as well as projecting mounting (dimensions in mm)
7
Synchro-check relay SPAU 140 C
1MRS 750421-MBG
Ordering :KHQRUGHULQJSOHDVHVSHFLI\
Ordering information Ordering example
1. Type designation and quantity SPAU 140 C, 5 pieces
2. Order number RS 488 001-AA
3. Rated values Un =110 V, fn =50 Hz
4. Auxiliary voltage Uaux =110 V dc
5. Accessories -
6. Special requirements -
2UGHUQXPEHUV
Synchro-check relay SPAU 140 C without test RS 488 001-AA, CA, DA, FA
adapter
Synchro-check relay SPAU 140 C including test RS 488 201-AA, CA, DA, FA
adapter RTXP 18
The last two letters of the order number indicate the AA equals fn = 50 Hz and Uaux = 80…265 V ac/dc
rated frequency fn and the auxiliary voltage Uaux of CA equals fn = 50 Hz and Uaux = 18…80 V dc
the relay as follows:
DA equals fn = 60 Hz and Uaux = 80…265 V ac/dc
FA equals fn = 60 Hz and Uaux = 18…80 V dc
References $GGLWLRQDOLQIRUPDWLRQ
Brochure “Synchro-check relay SPAU 140 C” 1MRS 750192-MDS EN
Manual “Synchro-check relay SPAU 140 C” 1MRS 750315-MUM EN
ABB Oy
P.O. Box 699
FIN-65101 Vaasa, Finland
Tel +358 10 224 000
Fax +358 10 224 1094
www.abb.com/substationautomation