Pressure Transmitter PMC71
Pressure Transmitter PMC71
Pressure Transmitter PMC71
Pressure Transmitter
E + H Cerabar S PMC71
BA302P/00/en/04.05
52027501
valid from
Software version 02.00
Hardware version 01.00
Overview documentation Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
Overview documentation
Cerabar S Technical Information TI383P Technical data – The documentation is located on the ToF Tool
FOUNDATION Fieldbus CD. The CD is enclosed with every device
ordered with the "HistoROM/M-DAT"
option. The "HistoROM/M-DAT" option is
selected in the order code via feature 100
Additional option 1" or 110 "Additional
option 2", version "N".
– The documentation is also available via the
Internet. → See: www.endress.com →
Download
Operating Instructions BA303P – Examples of configuration for – The documentation is also available via the
pressure and level measurement Internet. → See: www.endress.com →
– Description of parameters Download
– ’Trouble-shooting
– Appendix: Illustration of menu
Brief Operating Instructions KA252P – Wiring – The documentation is supplied with the
– Description of operating elements device. See cover of the terminal
– Operation HistoROM®/M-DAT compartment.
2 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Table of contents
Table of contents
1 Safety instructions . . . . . . . . . . . . . . . . 4 8 Trouble-shooting . . . . . . . . . . . . . . . . . 50
1.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 8.1 Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
1.2 Installation, commissioning and operation . . . . . . . . 4 8.2 Response of outputs to errors . . . . . . . . . . . . . . . . . 58
1.3 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . 4 8.3 Confirming messages . . . . . . . . . . . . . . . . . . . . . . . 59
1.4 Notes on safety conventions and icons . . . . . . . . . . . 5 8.4 Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
8.5 Repair of Ex-certified devices . . . . . . . . . . . . . . . . . 60
2 Identification . . . . . . . . . . . . . . . . . . . . 6 8.6 Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
8.7 Returning the device . . . . . . . . . . . . . . . . . . . . . . . 70
2.1 Device designation . . . . . . . . . . . . . . . . . . . . . . . . . 6 8.8 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
2.2 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 8.9 Software history . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
2.3 CE mark, declaration of conformity . . . . . . . . . . . . . 7
2.4 Registered trademarks . . . . . . . . . . . . . . . . . . . . . . . 7
9 Technical data . . . . . . . . . . . . . . . . . . . 71
3 Installation . . . . . . . . . . . . . . . . . . . . . . 8
10 Appendix . . . . . . . . . . . . . . . . . . . . . . . 71
3.1 Incoming acceptance and storage . . . . . . . . . . . . . . . 8
3.2 Installation conditions . . . . . . . . . . . . . . . . . . . . . . . 8 10.1 Menu (ToF Tool) . . . . . . . . . . . . . . . . . . . . . . . . . . 71
3.3 Installation instructions . . . . . . . . . . . . . . . . . . . . . . 8 10.2 Patents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
3.4 Post-installation check . . . . . . . . . . . . . . . . . . . . . . 13
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
4 Wiring . . . . . . . . . . . . . . . . . . . . . . . . 14
4.1 Connecting the device . . . . . . . . . . . . . . . . . . . . . . 14
4.2 Connecting the measuring unit . . . . . . . . . . . . . . . 16
4.3 Overvoltage protection (optional) . . . . . . . . . . . . . . 17
4.4 Post-connection check . . . . . . . . . . . . . . . . . . . . . . 17
5 Operation . . . . . . . . . . . . . . . . . . . . . . 18
5.1 On-site display (optional) . . . . . . . . . . . . . . . . . . . . 18
5.2 Operating elements . . . . . . . . . . . . . . . . . . . . . . . . 19
5.3 FOUNDATION Fieldbus communication protocol . 21
5.4 HistoROM®/M-DAT (optional) . . . . . . . . . . . . . . 33
5.5 Locking/unlocking operation . . . . . . . . . . . . . . . . . 35
5.6 Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.7 Factory setting (reset) . . . . . . . . . . . . . . . . . . . . . . 37
6 Commissioning. . . . . . . . . . . . . . . . . . 39
6.1 Function check . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
6.2 Commissioning via an FF configuration program . . 39
6.3 Selecting the language and measuring mode . . . . . 41
6.4 Position adjustment . . . . . . . . . . . . . . . . . . . . . . . . 43
6.5 Pressure measurement . . . . . . . . . . . . . . . . . . . . . . 46
6.6 Level measurement . . . . . . . . . . . . . . . . . . . . . . . . 47
6.7 Scaling OUT parameter . . . . . . . . . . . . . . . . . . . . . 49
7 Maintenance. . . . . . . . . . . . . . . . . . . . 50
7.1 Exterior cleaning . . . . . . . . . . . . . . . . . . . . . . . . . 50
Endress+Hauser 3
Safety instructions Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
1 Safety instructions
4 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Safety instructions
Symbol Meaning
#
Warning!
A warning highlights actions or procedures which, if not performed correctly, will lead to
personal injury, a safety hazard or destruction of the instrument.
"
Caution!
Caution highlights actions or procedures which, if not performed correctly, may lead to
personal injury or incorrect functioning of the instrument.
!
Note!
A note highlights actions or procedures which, if not performed correctly, may indirectly
affect operation or may lead to an instrument response which is not planned.
0
Device certified for use in explosion hazardous area
If the device has this symbol embossed on its nameplate, it can be installed in an explosion
hazardous area or a non-explosion hazardous area, according to the approval.
% Direct voltage
A terminal to which or from which a direct current or voltage may be applied or supplied.
&
Alternating voltage
A terminal to which or from which an alternating (sine-wave) current or voltage may be
applied or supplied.
)
Grounded terminal
A grounded terminal, which as far as the operator is concerned, is already grounded by
means of an earth grounding system.
*
Protective grounding (earth) terminal
A terminal which must be connected to earth ground prior to making any other connection
to the equipment.
+
Equipotential connection (earth bonding)
A connection made to the plant grounding system which may be of type e.g. neutral star or
equipotential line according to national or company practice.
Endress+Hauser 5
Identification Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
2 Identification
2.1.1 Nameplate
Made in Germany
79689 Maulburg
ENDRESS+HAUSER 4
CERABAR-S
Order Code: 1 3
5 7 2
Ser.-No.:
MWP 6
p 8 Mat. 9
Span 10 11
U= 12 13
P01-PMx7xxxx-18-xx-xx-xx-000
Devices for use in hazardous areas are fitted with an additional nameplate.
1 7
2
4 5 Dat.: 6
P01-xMD7xxxx-18-xx-xx-xx-003
6 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Identification
! Note!
• The MWP (maximum working pressure) is specified on the nameplate. This value refers to a
reference temperature of 20°C (68°F) or 100°F for ANSI flanges.
• The test pressure PT/(Over pressure limit OPL) = MWP (nameplate) x 1.5.
• The pressure values permitted at higher temperatures can be found in the following standards:
– EN 1092-1: 2001 Tab. 18 1
– ASME B 16.5a – 1998 Tab. 2-2.2 F316
– ASME B 16.5a – 1998 Tab. 2.3.8 N10276
– JIS B 2210/B 2238
1) With regard to its stability-temperature property, the material 1.4435 is identical to 1.4404 which is grouped under
13EO in EN 1092-1 Tab. 18. The chemical composition of the two materials can be identical.
Endress+Hauser 7
Installation Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
3 Installation
3.1.2 Storage
The device must be stored in a dry, clean area and protected against damage from impact (EN 837-
2).
Storage temperature range:
• –40...+100°C (–40...+212°F)
• On-site display: –40...+85°C (–40...+185°F)
3.2.1 Dimensions
→ For dimensions, please refer to the Technical Information for Cerabar S TI383P, "Mechanical
construction" section. See page 2, "Overview documentation".
! Note!
• Cerabar S without diaphragm seal are mounted as per the norms for a manometer
(DIN EN 839-2). We recommend the use of shut-off devices an siphons. The orientation depends
on the measuring application.
• Do not clean or touch diaphragm seals with hard or pointed objects.
8 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Installation
P01-PMx7xxxx-11-xx-xx-xx-001
• Mount Cerabar S with shut-off device above the tapping point so that the condensate can flow
into the process.
➀ ➃
➁ ➁
➂ ➀
P01-PMx7xxxx-11-xx-xx-xx-002
Endress+Hauser 9
Installation Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
P01-PMx7xxxx-11-xx-xx-xx-003
• Mount Cerabar S with shut-off device below or at the same level as the tapping point.
Level measurement
P01-PMP75xxx-11-xx-xx-xx-000
PVDF adapter
! Note!
For instruments with PVDF adapter, a maximum torque of 7 Nm is permitted. The thread
connection may become loose at high temperatures and pressures. This means that the integrity of
the thread must be checked regularly and may need to be tightened using the torque given above.
Teflon tape is recommended for sealing with the 1/2 NPT thread.
10 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Installation
! Note!
• The Cerabar S with diaphragm seal is screwed in, flanged or clamped, depending on the type of
diaphragm seal.
• The diaphragm seal and the pressure sensor together form a closed an calibrated system which is
filled with filling fluid through a hole in the upper part. This hole is sealed and not to be opened.
• Do not clean or touch diaphragm seals with hard or pointed objects.
• Do not remove membrane protection until shortly before installation.
• When using a mounting bracket, sufficient strain relief must be ensured for the capillaries in order
to prevent the capillary bending down (bending radius ≥ 100 mm).
• Please note that the hydrostatic pressure of the liquid columns in the capillaries can cause zero
point shift. The zero point shift can be corrected. → See also page 43, section 6.4 "Position
adjustment".
• Please note the application limits of the diaphragm seal filling oil as detailed in the Technical
Information for Cerabar S TI383P, Section "Planning instructions for diaphragm seal systems". →
See also page 2, "Overview documentation".
In order to obtain more precise measurement results and to avoid a defect in the device, mount the
capillaries as follows:
• vibration-free (in order to avoid additional pressure fluctuations)
• not in the vicinity of heating or cooling lines
• insulate in the event of colder or warmer ambient conditions
• with a bending radius of ≥100 mm.
Vacuum application
For applications under vacuum, Endress+Hauser recommends mounting the pressure transmitter
underneath the diaphragm seal. A vacuum load of the diaphragm seal caused by the presence of
filling oil in the capillaries is hereby prevented.
When the pressure transmitter is mounted above the diaphragm seal, the maximum height
difference H1 in accordance with the illustration below on the left must not be exceeded. The
maximum height difference is dependent on the density of the filling oil and the smallest ever
pressure that is permitted to occur at the diaphragm seal (empty container), see illustration below,
on the right.
FIELD TERMINALS
14.0
12.0
Hight difference H1 [m]
10.0
High temperature oil
8.0
Vegetable oil
6.0
H1 Silicone oil
4.0
Inert oil
2.0
0.0
10 100 200 300 400 500 600 700 800 900 1000
Pressure at diaphragm seal [mbarabs]
P01-PMx7xxxx-11-xx-xx-xx-008 P01-PMx7xxxx-05-xx-xx-xx-002
Fig. 7: Installation above the diaphragm Fig. 8: Diagram of maximum installation height above the
seal diaphragm seal for vacuum applications dependent on
the pressure at the diaphragm seal
Endress+Hauser 11
Installation Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
100
P01-PMx7xxxx-11-xx-xx-xx-005
Endress+Hauser recommends the use of temperature separators in the event of constant extreme
fluid temperatures which lead to the maximum permissible electronics temperature of +85°C
(+185°F) being exceeded.
The additional installation height also brings about a zero point shift of approx. 10 mbar due to the
hydrostatic columns in the temperature separator. You can correct this zero point shift. → See also
page 43, section 6.4 "Position adjustment".
➀ ➁
P01-FMD7xxxx-11-xx-xx-xx-002
# Warning!
The seal is not allowed press on the diaphragm as this could affect the measurement result.
12 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Installation
101
118
70
P01-PMx7xxxx-06-xx-xx-xx-001
max. 380°
P01-PMx7xxxx-17-xx-xx-xx-000
Endress+Hauser 13
Wiring Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
4 Wiring
• The supply voltage must match the supply voltage on the nameplate. (→ See also page 6, section
2.1.1 Nameplate.)
• Switch off the supply voltage before connecting the device.
• Remove housing cover of the terminal compartment.
• Guide cable through the gland. → For cable specification see page 16, section 4.2.3.
• Connect device in accordance with the following diagram.
• Screw down housing cover.
• Switch on supply voltage.
➀
➃
FF FF
➁ ➄
FF FF
➂
P01-xMx7xxxx-04-xx-xx-xx-009
14 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Wiring
Cerabar S
+
+ –
7
6 8
Han7D 1 –
5 2
4 3
+ –
P01-PMx7xxxx-04-xx-xx-xx-001
Fig. 12: Left: electrical connection for devices with Harting plug Han7D
Right: view of the plug at the device
Cerabar S
+ –
BK – +
M12
+ –
P01-PMx7xxxx-04-xx-xx-xx-000
Fig. 13: Left: electrical connection for devices with M12 plug
Right: view of the plug at the device
Cerabar S
–
+ –
7/8" +
+ –
P01-PMx7xxxx-04-xx-xx-xx-003
Fig. 14: Left: electrical connection for devices with 7/8" plug
Right: view of the plug at the device
Endress+Hauser 15
Wiring Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
! Note!
• When using the measuring device in hazardous areas, the corresponding national standards and
regulations and the safety instructions (XAs) or installation or control drawings (ZDs) must also
be complied with.
• All explosion protection data are given in a separate documentation which is available upon
request. The Ex documentation is available as standard with all devices approved for use in
explosion hazardous areas.
! Note!
For further information on the cable specifications, see Operating Instructions BA013S
"FOUNDATION Fieldbus Overview", FONDATION Fieldbus Guideline and IEC 61158-2 (MBP).
Different earthing and screening installation methods are available for FOUNDATION Fieldbus
networks such as:
• Isolated installation (see also IEC 61158-2)
• Installation with multiple earthing
• Capacitive installation
16 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Wiring
# Warning!
Devices with integrated overvoltage protection must be earthed.
Endress+Hauser 17
Operation Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
5 Operation
Feature 20 "Output; operation" in the order code provides you with information on the operating
options available to you.
P Foundation Fieldbus; external operation, LCD Via on-site display and 1 key on the exterior of the device
Q Foundation Fieldbus; internal operation, LCD Via on-site display and 1 key on the inside of the device
R Foundation Fieldbus; internal operation Without on-site display, 1 key on the inside of the device
Header line
Main line
Unit
Information
line
Symbol
Bargraph
P01-xMD7xxxx-07-xx-xx-xx-001
The following table illustrates the symbols that can appear on the on-site display. Four symbols can
occur at one time.
Symbol Meaning
Alarm symbol
– Symbol flashing: warning, device continues measuring.
– Symbol permanently lit: error, device does not continue measuring.
Note: The alarm symbol may overlie the tendency symbol.
Lock symbol
The operation of the device is locked. Unlock device, → see page 35, Section 5.5.
"Locking/Unlocking operation".
Communication symbol
Data transfer via communication
Simulation symbol
Simulation mode is activated. DIP switch 2 for simulation is set to "On".
→ See also following Section 5.2.1 "Position of operating elements" and page 36, Section
5.6 "Simulation".
18 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Operation
Symbol Meaning
➄➅
Sim.
on
➀ ➀ ➁ ➂
off 1 2 0%
Zero Display ➃
Simulation
Sensor HW
0%
Zero
on
1 2
off
PC
HistoROM
FOUNDATION
P01-PMx7xxxx-19-xx-xx-xx-075 P01-xxxxxxxx-19-xx-xx-xx-106
Fig. 15: Operating keys, external Fig. 16: Operating keys, internal
1 Operating keys on the exterior of the device under 1 Green LED to indicate value is accepted
the protective flap 2 Operating key for position adjustment (zero-point
correction)
3 Slot for optional display
4 Slot for optional HistoROM®/M-DAT
5 DIP switch for locking/unlocking parameters
relevant to the measured value
6 DIP switch for simulation mode
Endress+Hauser 19
Operation Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
Key(s) Meaning
Position adjustment (zero point correction). → See also the following Section "Performing
0% position adjustment on site.''
Zero
P02-xxxxxxxx-19-xx-xx-xx-107
Sim.
on
Factory setting: off (unlocked)
→ See also page 35, Section 5.5 "Locking/unlocking operation".
– DIP switch 2: for simulation mode
1 2 off Factory setting: off (simulation mode off)
P01-xxxxxxxx-19-xx-xx-xx-109
→ See also page 36, Section 5.6 "Simulation".
! Note!
• The operation must be unlocked. → See page 35, Section 5.5 "Locking/unlocking operation".
• The device is configured for the Pressure measuring mode as standard.
– Operation via FF configuration program: In the Pressure Transducer Block, change the
measuring mode by means of the PRIMARY_VALUE_TYPE and LINEARIZATION parameters.
– Operation via ToF Tool: change the measuring mode by means of the MEASURING MODE
parameter.
→ See also page 41, Section 6.3 "Selecting language and measuring mode".
• The pressure applied must be within the nominal pressure limits of the sensor. See information
on the nameplate.
20 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Operation
Industrial Network
FF-HSE
BT
FF-H1 SB
LD
PS BT
BT
PS
FF-H1
BT
P01-xxxxxxxx-02-xx-xx-xx-001
! Note!
Further information on FOUNDATION Fieldbus can be found in Operating Instructions BA013S
"FOUNDATION Fieldbus Overview, Installation and Commissioning Guidelines", the
FOUNDATION Fieldbus Specification or on the Internet at "http://www. fieldbus.org".
Endress+Hauser 21
Operation Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
5.3.3 Operation
You can obtain special configuration and operating programs from various manufacturers for the
configuration. These configuration programs make it possible to configure FF functions and all the
device-specific parameters. The pre-defined function blocks allow uniform access to all the network
and fieldbus device data.
You can use the Endress+Hauser ToF Tool operating program to configure the Endress+Hauser
parameters and read out the HistoROM data.
To access the device by means of the ToF Tool, you need the FXA193 service interface which is
connected to the interface for the on-site display on the electronic insert. → See also page 32,
Section 5.3.10 ToF Tool operating program.
! Note!
• For more indepth information on integrating the device into the FF system, see the description for
the configuration software used.
• When integrating the field devices into the FF system, make sure you are using the right files. You
can read out the required version by means of the DEV_REV and DD_REV parameters in the
Resource Block.
22 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Operation
➀ ➁ ➂
– E+H_Cerabar_S_XXXXXXXXXXX - ID 452B481007-XXXXXXXXXXX
RS_452B481007-xxxxxxxxxxxx (RB2)
TRD1_452B481007-xxxxxxxxxxxx (PCD)
SERVICE_452B481007-xxxxxxxxxxxx (SERVICE)
DISPLAY_452B481007-xxxxxxxxxxxx (DISPLAY)
DIAGNOSTIC_452B481007-xxxxxxxxxxxx (DIAGNOSTIC)
AI1_452B481007-xxxxxxxxxxxx (AI1)
AI2_452B481007-xxxxxxxxxxxx (AI2)
DO_452B481007-xxxxxxxxxxxx (DO)
PID_452B481007-xxxxxxxxxxxx (PID)
ARTH_452B481007-xxxxxxxxxxxx (ARB)
CHAR_452B481007-xxxxxxxxxxxx (SCB)
ISEL_452B481007-xxxxxxxxxxxx (ISB)
AALM_452B481007-xxxxxxxxxxxx (AALB)
P01-PMx7xxxx-05-xx-xx-xx-010
Fig. 18: Typical Cerabar S display in a configuration program after the connection has been established
1 Device name
2 Serial number
3 Device ID, consisting of ID code for Endress+Hauser (452B48), ID code for Cerabar S (1007) and 11-digit serial
number
The function blocks can be connected by means of an FF configuration program, depending on the
automation task. The device thus takes on simple control functions, thereby relieving the workload
on the higher-order process control system.
Endress+Hauser 23
Operation Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
24 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Operation
Messgröße
Display
Transducer Block
Arithmetic Block PID Block Input Selector Block
Diagnostic
Transducer Block
Discrete Output Signal Characterizer Analog Alarm Block
Block Block
P01-PMx7xxxx-02-xx-xx-xx-004
The Pressure Transducer Block returns the Primary Value (pressure measured value) and the
Secondary Value (sensor temperature). Primary and Secondary Value each transferred to one Analog
Input Block by means of the CHANNEL parameter (→ see also the following Section).
The Discrete Output, PID, Arithmetic, Signal Characterizer, Input Selector and Analog Alarm Block
are not connected in the as-delivered state.
! Note!
Please note that the links between the blocks are deleted and the FF parameters are reset to the
default values following a reset by means of the RESTART parameter in the Resource Block,
"Default" option.
Endress+Hauser 25
Operation Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
1) Factory setting
26 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Operation
Resource Block
Parameter name as per DD Parameter name, "Label Index Data type Size Storage Read Write MODE_BLK Reset codes
Parameter" option and (Byte) Class
ToF Tool display
DEVICE_DIALOG DEVICE DIALOG1 42 Unsigned8 1 D x
SW_LOCK INSERT PIN No 43 Unsigned16 2 S x x Auto, OOS 7864, 333
ORDER_CODE DEVICE DESIGN. 44 Visible String 32 S x
HARDWARE_REVISION HARDWARE REV. 45 Visible String 8 S x
SOFTWARE_VERSION SOFTWARE VERSION 46 Visible String 8 S x
ELECTRONIC_SERIAL_NUMBER ELECTR. Serial No 47 Visible String 16 D x
DEVICE_SERIAL_NUMBER DECVICE SERIAL No 48 Visible String 16 D x
PROCESS_CONNECTION_MODEL PROC. CONN. TYPE 49 Unsigned16 2 S x x Auto, OOS
PROCESS_CONNECTION_MATERIAL_ MAT. PROC. CONN. + 50 Unsigned16 2 S x x Auto, OOS
POSITIVE
PROCESS_CONNECTION_MATERIAL_ MAT. PROC. CONN. – 51 Unsigned16 2 S x x Auto, OOS
NEGATIVE
PROCESS_FLANGE_GASKET_MATERIAL SEAL TYPE 52 Unsigned16 2 S x x Auto, OOS
SCI_OCTET_STR SCI_OCTET_STR1 53 Visible String 32 S x
Parameter name as per DD Parameter name, "Label Index Data type Size Storage Read Write MODE_BLK Reset codes
Parameter" option and (Byte) Class
ToF Tool display
DEVICE_DIALOG DEVICE DIALOG 31 Unsigned8 1 D x
LINEARIZATION LINEARIZATION 32 Unsigned8 2 S x x OOS 7864, 333
SCALE_IN SCALE IN 33 DS-65 11 S x x Auto, OOS 7864, 333
SCALE_OUT SCALE OUT 34 DS-68 11 S x x OOS 7864, 333
ACTIVE_PRESSURE_1_DAMPING DAMPING VALUE 35 Float 4 S x x Auto, OOS 7864, 333
TOTALIZER_1_FLOAT TOTALIZER 11 36 Float 4 D x
TOTALIZER_2_FLOAT TOTALIZER 21 37 Float 4 D x
PRESSURE_1_ACCEPT_ZERO_ POS. ZERO ADJUST 38 Unsigned8 1 D x x Auto, OOS
INSTALL_OFFSET
Endress+Hauser 27
Operation Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
Parameter name as per DD Parameter name, "Label Index Data type Size Storage Read Write MODE_BLK Reset codes
Parameter" option and (Byte) Class
ToF Tool display
PRESSURE_1_ACCEPT_INSTALL_ POS. INPUT VALUE 39 Float 4 S x x Auto, OOS 7864, 333,
OFFSET 2509
PRESSURE_INSTALL_OFFSET CALIB. OFFSET 40 Float 4 S x x Auto, OOS 7864, 333,
2509
PRESSURE_1_UNIT_TEXT CUSTOMER UNIT P 41 Visible String 8 S x x Auto, OOS 7864
PRESSURE_1_UNIT_SCALE CUST. UNIT FACT. P 42 Float 4 S x x Auto, OOS 7864
PRESSURE_1_LOWER_CAL_ LO TRIM MEASURED2 43 Float 4 S x 2509
MEASURED
PERSSURE_1_UPPER_CAL_ HI TRIM MEASURED2 44 Float 4 S x 2509
MEASURED
LEVEL_TYPE LEVEL MODE 45 Unsigned8 1 S x x OOS 7864, 333
MEASURAND_LINEAR LIN. MEASURAND 46 Unsigned8 1 S x x OOS 7864, 333
MEASURAND_LINEARIZED LINd. MEASURAND 47 Unsigned8 1 S x x OOS 7864, 333
MEASURAND_COMBINED COMB. MEASURAND 48 Unsigned8 1 S x x OOS 7864, 333
DENSITY_UNIT DENSITY UNIT 49 Unsigned16 2 S x x Auto, OOS 7864, 333
HEIGHT_UNIT HEIGHT UNIT 50 Unsigned16 2 S x x Auto, OOS 7864, 333
HEIGHT_UNIT_TEXT CUSTOMER UNIT H 51 Visible String 8 S x x Auto, OOS 7864
HEIGHT_UNIT_SCALE CUST. UNIT FACT. H 52 Float 4 S x x Auto, OOS 7864
VOLUME_UNIT UNIT VOLUME 53 Unsigned16 2 S x x Auto, OOS 7864, 333
VOLUME_UNIT_TEXT CUSTOMER UNIT V 54 Visible String 8 S x x Auto, OOS 7864
VOLUME_UNIT_SCALE CUST. UNIT FACT. V 55 Float 4 S x x Auto, OOS 7864
MASS_UNIT MASS UNIT 56 Unsigned16 2 S x x Auto, OOS 7864, 333
MASS_UNIT_TEXT CUSTOMER UNIT M 57 Visible String 4 S x x Auto, OOS 7864
MASS_UNIT_SCALE CUST. UNIT FACT. M 58 Float 8 S x x Auto, OOS 7864
LEVEL_ADJUST_MODE CALIBRATION MODE 59 Unsigned8 1 S x x Auo, OOS 7864, 333
LEVEL_ADJUST_DENSITY ADJUST DENSITY 60 Float 4 S x x Auto, OOS 7864, 333
LEVFL_OFFSET ZERO POSITION 61 Float 4 S x x Auto, OOS 7864, 333
LEVEL_TANK_VOLUME TANK VOLUME 62 Float 4 S x x Auto, OOS 7864, 333
LEVEL_TANK_HEIGHT TANK HEIGHT 63 Float 4 S x x Auto, OOS 7864, 333
LEVEL_100_PERCENT_VALUE 100% POINT 64 Float 4 S x x Auto, OOS 7864, 333
LINEAR_LEVEL_MIN LEVEL MIN. 65 Float 4 S x x Auto, OOS 7864, 333
LINEAR_LEVEL_MAX LEVEL MAX. 66 Float 4 S x x Auto, OOS 7864, 333
LEVEL_MEASUREMENT_DENSITY PROCESS DENSITY 67 Float 4 S x x Auto, OOS 7864, 333
FLOW_TYPE FLOW-MEAS. TYPE1 68 Unsigned8 1 S x x Auto, OOS 7864, 333
FLOW_UNIT UNIT FLOW1 69 Unsigned16 2 S x x Auto, OOS 7864, 333
FLOW_UNIT_TEXT CUSTOMER UNIT F1 70 Visible String 8 S x x Auto, OOS 7864
FLOW_UNIT_SCALE CUST. UNIT FACT. F1 71 Float 4 S x x Auto, OOS 7864
CREEP_FLOW_SUPPRESSION_ENABLE LOW FLOW CUT-OFF1 72 Unsigned8 1 S x x Auto, OOS 7864, 333
LOW_FLOW_CUT_OFF SET. L. FL. CUT-OFF1 73 Unsigned8 1 S x x Auto, OOS 7864, 333
LINEARIZATION_TABLE_MODE LIN. EDIT MODE 74 Unsigned8 1 S x x Auto, OOS 7864
TAB_ACTUAL_NUMBER TAB ACTUAL NUMBER 75 Unsigned8 1 D x
TAB_ENTRY TAB ENTRY 76 Unsigned8 1 D x x Auto, OOS 7864
TAB_MAX_NR TAB MAX NR 77 Unsigned8 1 S x
TAB_MIN_NR TAB MIN NR 78 Unsigned8 1 S x
TAB_OPCODE TABLE SELECTION 79 Unsigned8 1 S x x Auto, OOS 7864
TAB_STATE TAB STATE 80 Unsigned8 1 D x
TAB_XY_VALUE TAB XY VALUE 81 Float 8 S x x Auto, OOS 7864
LEVEL_TANK_DESCRIPTION TANK DESCRIPTION 82 Visible String 32 S x x Auto, OOS 7864
TOTALIZER_2_UNIT TOTAL. 2 ENG. UNIT1 83 Unsigned16 2 S x x Auto, OOS 7864, 333
TOTALIZER_2_UNIT_TEXT TOT. 2 UNIT TEXT1 84 Visible String 8 S x x Auto, OOS 7864
TOTALIZER_2_UNIT_SCALE FACT. U. U. TOTAL. 21 85 Float 4 S x x Auto, OOS 7864
TOTALIZER_2_MODE NEG. FLOW TOT. 21 86 Unsigned8 1 S x x Auto, OOS 7864, 333
PRESSURE_1_AFTER_SENSOR SENSOR PRESSURE 87 Float 4 S x
PRESSURE_1_AFTER_DAMPING PRESSURE 88 Float 4 S x
MEASURED_LEVEL_AFTER_ LEVEL BEFORE LIN 89 Float 4 S x
SIMULATION
SENSOR_MEASUREMENT_TYP SENSOR MEAS. TYPE 90 Unsigned16 2 S x
28 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Operation
Parameter name as per DD Parameter name, "Label Index Data type Size Storage Read Write MODE_BLK Reset codes
Parameter" option and (Byte) Class
ToF Tool display
DEVICE_DIALOG DEVICE DIALOG1 11 Unsigned8 1 D x
CONFIGURATION_COUNTER CONFIG RECORDER 12 Unsigned16 2 S x
MEASURED_TEMPERATURE_3 PCB TEMPERATURE 13 Float 4 D x
TEMPERATURE_3_LOW_LIMIT Allowed Min. TEMP 14 Float 4 S x
TEMPERATURE_3_HIGH_LIMIT Allowed Max. TEMP 15 Float 4 S x
PROCESS_CONNECTION_PRESSURE_ Pmax PROC. CONN. 16 Float 4 S x x Auto, OOS
HIGH_LIMIT
SENSOR_MEASUREMENT_TYPE SENSOR MEAS. TYPE 17 Unsigned16 2 S x
SENSOR_MIN_ABSOLUTE_LIMIT Pmin SENS. DAMAGE 18 Float 4 S x
SENSOR_MAX_ABSOLUTE_LIMIT Pmax SENS. DAMAGE 19 Float 4 S x
TEMPERATURE_1_SENSOR_LIMIT_ Tmin SENSOR 20 Float 4 S x
LOW
TEMPERATURE_1_SENSOR_LIMIT_ Tmax SENSOR 21 Float 4 S x
HIGH
SENSOR_HARDWARE_REVISION SENS H/WARE REV 22 Unsigned8 1 S x
COUNTER P_MAX COUNTER: P > Pmax 23 DS-65 5 S x
PRESSURE_1_MAX_RESETABLE MAX. MEAS. PRESS. 24 DS-65 5 S x
COUNTER_PMIN COUNTER: P < Pmin 25 Unsigned16 2 S x
PRESSURE_1_MIN_RESETABLE MIN. MEAS. PRESS. 26 Float 4 S x
COUNTER_TMAX COUNTER: T > Tmax 27 Unsigned16 2 S x
TEMPERATURE_1_MAX_RESETABLE MAX. MEAS. TEMP. 28 Float 4 S x
COUNTER_TMIN COUNTER: T < Tmin 29 Unsigned16 2 S x
TEMPERATURE_1_MIN_RESETABLE MIN. MEAS. TEMP. 30 Float 4 S x
ELECTRONIC_OVER_TEMPERATURE_ PCB COUNT: T > Tmax 31 Unsigned16 2 S x
COUNTER
ELECTRONIC_OVER_TEMPPERATURE PCB MAX. TEMP. 32 Float 4 S x
ELECTRONIC_UNDER_TEMPERATURE_ PCB COUNT: T < Tmin 33 Unsigned16 2 S x
COUNTER
ELECTRONIC_UNDER_TEMPERATURE PCB MAX. TEMP. 34 Float 4 S x
RESET_TRANSMITTER_OBSERVATION RESET PEAKHOLD 35 Unsigned8 1 D x x Auto, OOS
PRESSURE_1_AFTER_DAMPING PRESSURE 36 DS-65 5 D x
PRESSURE_1_AFTER_CALIBRATION CORRECTED PRESS. 37 Float 4 D x
TENDENCY TEAS. VAL. TREND 38 Unsigned8 1 D x
MAX_TURNDOWN MAX TURNDOWN1 39 Float 4 S x
NUMBER_OF_SENSOR_CHANGES SENSOR CHANGES1 40 Float 4 S x
PEAK_HOLD_INCREMENT_FACTOR P PEAKHOLD. STEP1 41 Float 4 S x
TEMPERATURE_1_PEAK_HOLD_ T PEAKHOLD. STEP1 42 Float 4 S x
INCREMENT_OFFSET
ACCELERATION_OF_GRAVITY ACC. OF GRAVITY1 43 Float 4 S x
CREEP_FLOW_SUPPRESSION_ CREEP FLOW HYST.1 44 Float 4 S x
HYSTERESIS
HISTOROM_SAVING_CYCLE_TIME HIST. SAVING CYCL1 45 Unsigned8 1 S x
HISTOROM_AVAIBLE HistoROM SAVING AVAIL. 46 Unsigned8 1 S x
DAT_HANDLING HistoROM CONTROL 47 Unsigned8 1 D x
PRESSURE_1_UNIT PRESS. ENG. UNIT 48 Unsigned16 2 S x
TEMPERATURE_UNIT TEMP. ENG. UNIT 49 Unsigned16 2 S x
Parameter name as per DD Parameter name, "Label Index Data type Size Storage Read Write BLK_MODE Reset codes
Parameter" option and (Byte) Class
ToF Tool display
DEVICE DIALOG DEVICE DIALOG1 10 Unsigned8 1 D x
DISPALY_MAIN_LINE_CONTENT MENU DESCRIPTOR 11 Unsigned8 1 S x x Auto, OOS 1864
AUTOMATIC_MAINLINE_FORMAT MAIN DATA FORMAT 12 Unsigned8 1 S x x Auto, OOS 1864
DISPLAY_ALTERNATING_VALUES ALTERNATE DATA 13 Unsigned8 1 S x x Auto, OOS 1864
DISPLAY_CONTRAST DISPLAY CONTRAST 14 Unsigned8 1 S x x Auto, OOS 1864
DISPLAY_LANGUAGE LANGUAGE 15 Unsigned8 1 S x x Auto, OOS 1864
SIL_DIGITS_TEST_STRNG DIGIT SETS1 16 Visible String 16 D x x
Endress+Hauser 29
Operation Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
Parameter name as per DD Parameter name, "Label Index Data type Size Storage Read Write BLK_MODE Reset codes
Parameter" option and (Byte) Class
ToF Tool display
DEVICE_DIALOG DEVICE DIALOG1 10 Unsigned8 1 D x
SIMULATION_MODE SIMULATION MODE 11 Unsigned8 1 S x x Auto, OOS 7864, 333, 62,
2710, 1846
SCALE_OUT_UNITS_INDEX UNITS INDEX 12 Unsigned16 2 S x 7864
SIMULATION_VALUE SIMULATED VALUE2 13 Float 4 D x x Auto, OOS 7864, 333, 62,
2710, 1846
ALARM_SIMULATION_VALUE SIM. ERROR NO. 14 Unsigned16 2 D x x Auto, OOS 7864, 333, 62,
2710, 1846
DIAGNOSTIC_CODE ALARM STATUS 15 Unsigned16 2 D x
LAST_DIAGNOSTIC_CODE LAST DIAG. CODE 16 Unsigned16 2 S x 7864
ACKNOWLEDGE_ALARM_MODE ACK. ALARM MODE 17 Unsigned8 1 S x x Auto, OOS 7864
ACKNOWLEDGE_ALARM ACK. ALARM 18 Unsigned8 1 D x x Auto, OOS 7864
RESET_ALARM_HISTORY RESET ALL ALARMS 19 Unsigned8 1 D x x Auto, OOS 7864
REACTION_ON_ALARM_NR ERROR NO. 20 Unsigned16 2 D x x Auto, OOS 7864
CHOOSE_ERROR_OR_WARNING SELECTED ALARMTYPE 21 Unsigned8 1 D x x Auto, OOS 7864
ALARM_SETUP_TIME ALARM DELAY 22 Float 4 S x x Auto, OOS 7864
ALARM_HOLD_TIME ALARM DISPL. TIME 23 Float 2 S x x Auto, OOS 7864
PRESSURE_1_UNIT PRESS. ENG. UNIT 24 Unsigned16 2 S x 7864, 333
PRESSURE_1_USER_LOW_LIMIT Pmin ALARM WINDOW 25 Float 4 S x x Auto, OOS 7864
PRESSURE_1_USER_HIGH_LIMIT Pmax ALARM WINDOW 26 Float 4 S x x Auto, OOS 7864
TEMPERATURE_UNIT TEMP. ENG. UNIT 27 Unsigned16 2 S x 7864, 333
TEMPERATURE_1_USER_LOW_LIMIT Tmin ALARM WINDOW 28 Float 4 S x x Auto, OOS 7864
TEMPERATURE_1_USER_HIGH_LIMIT Tmax ALARM WINDOW 29 Float 4 S x x Auto, OOS 7864
RESET_INPUT_VALUE ENTER RESET CODE 30 Unsigned16 2 D x x
OPERATING_HOURS OPERATING HOURS 31 Unsigned32 4 S x
ALARM_TABLE_ARRAY ALARM TABLE ARRAY1 32 Visible String 16 D x
Parameter name as per DD Parameter name, "Label Index Data type Size Storage Read Write BLK_MODE Reset codes
Parameter" option and (Byte) Class
ToF Tool display
FSAFE_TYPE FAIL SAFE TYPE 37 Unsigned8 1 S x x OOS, MAN
FSAFE_VALUE FAIL SAFE VALUE 38 Float 4 S x x
30 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Operation
5.3.9 Methods
The FOUNDATION Fieldbus Specification includes the use of methods to make device operation
easier. A method is a sequence of interactive steps to be carried out in the specified order so as to
configure certain device functions.
The following methods are available for Cerabar S:
• Insert Pin No. (Resource Block), → see page 36, Section 5.5.2
• Measuring mode (Pressure Transducer Block), → see page 41, Section 6.3.1
• Pos. zero adjust (Pressure Transducer Block), → see page 43, Section 6.4.1
• Low sensor trim (Pressure Transducer Block)
• High sensor trim (Pressure Transducer Block)
• Select alarm type (Diagnostic Transducer Block), → see page 59, Section 8.2.1
! Note!
For further information on accessing methods, see the description of the FF configuration program
used.
Endress+Hauser 31
Operation Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
! Note!
• You can configure the Endress+Hauser parameters by means of the ToF Tool (→ see also page 71,
Section 10.1 "Menu"). To access the device by means of the ToF Tool, you need the FXA193
service interface which is connected to the interface for the on-site display on the electronic
insert.
• Some Endress+Hauser parameters correspond to FF standard parameters. → For this purpose, see
Operating Instructions BA303P "Cerabar S/Deltabar S, Description of Device Functions". You
require an FF configuration program to configure all the FF parameters and integrate the device
into an FF network.
P01-PMx7xxxx-19-xx-xx-en-002
Fig. 20: ToF Tool operating program, the configuration is performed via a menu
Connection options:
• Service interface with adapter FXA 193
! Note!
• Further information on the ToF Tool can be found on the ToF Tool CD-ROM on the Internet
(http://www.endress.com, Download → Search for: ToF Tool). The CD is supplied with any
device ordered with the "HistoROM/M-DAT" option.
32 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Operation
# Warning!
Detach HistoROM®/M-DAT from the electronic insert or attach it to the insert in a deenergised
state only.
! Note!
• The HistoROM®/M-DAT module may be retrofitted at any time (Order No.: 52027785).
• To analyse and evaluate the data and events saved in the HistoROM®/M-DAT, you require the
Endress+Hauser ToF Tool operating program. A CD with the operating program and
documentation is provided for devices that were ordered with the "HistoROM/M-DAT" option.
→ See also page 32, Section 5.3.10 ToF Tool operating program. Copying configuration data of
one transmitter to another transmitter is also possible with an FF configuration program.
• The HistoROM data and the data in the device are analysed once a HistoROM®/M-DAT is
attached to the electronic insert and power is reestablished to the device. During the analysis, the
messages "W702, HistoROM data not consistent" and "W706, Configuration in HistoROM and
device not identical" can occur. For measures, see page 50, Section 8.1 "Messages."
➁
Sim.
on
off 1 2 0%
Zero Display
➀
Simulation
Sensor HW
on
1 2
off
PC
HistoROM
FOUNDATION
P01-xxxxxxxx-19-xx-xx-xx-123
Endress+Hauser 33
Operation Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
! Note!
The operation must be unlocked. → See also page 35, Section 5.5 "Locking/unlocking operation".
1. Disconnect device from supply voltage.
2. Attach the HistoROM®/M-DAT to the electronic insert.
3. Reestablish supply voltage to the device.
4. Operation via FF configuration program: Using the DAT_HANDLING/
HistoROM CONTROL parameter in the Service Transducer Block, select the "Device →
HistoROM" option for the data transfer direction.
Operation via the ToF Tool: Using the HistoROM CONTROL parameter, select the "Device →
HistoROM" option for the data transfer direction. (Menu path: OPERATING MENU →
OPERATING)
5. Wait approx. 20 seconds. Configuration data are loaded from the device to the
HistoROM®/M-DAT. The device is not restarted.
6. Disconnect device from the supply voltage again.
7. Detach memory module.
8. Reestablish supply voltage to the device.
! Note!
The operation must be unlocked. → See also page , Section 5.5 "Locking/unlocking operation".
1. Disconnect device from supply voltage.
2. Attach the HistoROM®/M-DAT to the electronic insert. Configuration data from another
device are stored in the HistoROM®/M-DAT.
3. Reestablish supply voltage to the device.
4. Operation via FF configuration program: using the DAT_HANDLING/
HistoROM CONTROL parameter in the Service Transducer Block, select the "HistoROM →
Device" option for the data transfer direction.
Operation via ToF Tool: Using the HistoROM CONTROL parameter, select the "HistoROM →
Device" option for the data transfer direction. (Menu path: OPERATING MENU →
OPERATING)
5. Wait approx. 20 seconds. Configuration data are loaded from the HistoROM®/M-DAT to the
device. The device is restarted.
6. Before removing the HistoROM®/M-DAT again from the electronic insert, disconnect the
device from the supply voltage.
34 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Operation
! Note!
• If operation is locked by means of the DIP-switch, you can only unlock operation again by means
of the DIP-switch. If operation is locked by means of remote operation e.g. ToF Tool, you can only
unlock operation again by means of remote operation.
1) Parameters which refer to how the display appears, e.g. DISPLAY_LANGUAGE/LANGUAGE and
DISPLAY_CONTRAST can still be altered.
➀
Simulation
Simulation
0%
➁ ➂ Sensor
Zero
Display
Simualtion
on on
on
1 2
off
PC
1 2 1 2
off off
FOUNDATION
HistoROM
P01-xxxxxxxx-19-xx-xx-xx-122
Fig. 21: DIP switch position "Hardware locking" on the electronic insert
1 If necessary, remove on-site display (optional)
2 DIP switch is set to "On": operation is locked.
3 DIP switch is set to "Off": operation is unlocked (operation possible)
Endress+Hauser 35
Operation Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
Description
Locking operation 1. Operation via FF configuration program: select SWLOCK parameter in the Resource
Block.
Operation via ToF Tool: select INSERT PIN No. parameter,
menu path: OPERATING MENU → OPERATING → INSERT PIN No.
2. To lock operation, enter a number for this parameter between 0...9999 that is ≠ 100.
Unlocking operation 1. Operation via FF configuration program: select SWLOCK parameter in the Resource
Block.
Operation via ToF Tool: select INSERT PIN No. parameter.
2. To unlock operation, enter "100" for the parameter.
! Note!
If operating via the FF configuration program, the "Insert Pin No." method is available by means of
the Resource Block. Specify the code indicated in the table to lock or unlock operation.
5.6 Simulation
The function of the Analog Input Block, such as input and output scaling, can be simulated as
follows:
1. Set the "Simulation" DIP switch on the electronic insert to "On".
2. In the Analog Input Block, select the "Active" option by means of the SIMULATION parameter,
ENABLE_DISABLE element.
3. Set the Analog Input Block to the block mode AUTO.
4. Enter the value and status for the SIMULATION_VALUE and SIMULATION_STATUS
elements. During the simulation, the output value and status of the Pressure Transducer Block
are replaced by the simulated value and status. The OUT parameter shows the result.
5. End simulation (SIMULATION parameter, ENABLE_DISABLE element,
"Disabled" option).
! Note!
You can check your adjustment for the transmitter by means of the SIMULATION_MODE and
SIMULATION_VALUE parameters in the Diagnostic Transducer Block. → See Operating
Instructions BA303 "Description of Device Functions Cerabar S/Deltabar S",
SIMULATION_MODE and SIMULATION_VALUE parameter descriptions.
36 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Operation
! Note!
• Any customer-specific configuration carried out by the factory is not affected by a reset (customer-
specific configuration remains). If, after a reset, you wish the parameters to be reset to the factory
settings, please contact Endress+Hauser Service.
• The OUT parameter may have to be rescaled after resetting with code 7864. → See also page 49,
Section 6.7 "Scaling OUT parameter".
! Note!
• The RESET FF parameter gives you the option of deleting links between function blocks and
resetting FF parameters to default values and manufacturer-specific parameters to the factory
setting. → See also Operating Instructions BA303P, RESTART parameter description.
Endress+Hauser 37
Operation Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
1) The table uses the group and parameter names as they appear in the ToF Tool. For the assignment of parameter
names of the ToF Tool and FF configuration program, see page 27, Section 5.3.8 "Index tables, Endress+Hauser
parameters".
38 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Commissioning
6 Commissioning
Endress+Hauser 39
Commissioning Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
! Note!
The block mode must be set to "Auto" for the Pressure and Service Transducer Block for the
measuring device to function correctly.
40 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Commissioning
Additional configuration
1. Depending on the control or automation task, configure additional function blocks and output
blocks. → See also Operating Instructions BA303P "Description of Device Functions
Cerabar S/Deltabar S" or page 2 "Overview of documentation".
2. Link the function blocks and output blocks.
3. After specifying the active LAS, download all the data and parameters to the field device.
Executing the measuring mode selection by means of the "Measuring mode" method
You can use the "Measuring mode" method in the Pressure Transducer Block for dialog-guided
measuring mode switchover. For switching to the "Level" measuring mode, see the following
Section "Selecting the measuring mode manually".
Endress+Hauser 41
Commissioning Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
1) For further information on the options "Level linearized", "Level combined" and "% Level combined", see Operating
Instructions BA303P, Section "Level measurement".
2) Is not available for Cerabar S
3) The measured variable is in direct proportion to the measured pressure.
4) The measured variable is not in direct proportion to the measured pressure as is the case with tanks with a conical
outlet, for example. A linearisation table has to be entered for the calibration.
5) Two measured variables are required or the tank shape is given with value pairs, e.g. height and volume. The 1st
measured variable % height or height must be in direct proportion to the measured pressure. The 2nd measured
variable volume, mass or % must not be in direct proportion to the measured pressure. A linearisation table has to be
entered for the 2nd measured variable. The 2nd measured variable is assigned to the 1st measured variable by
means of this table.
42 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Commissioning
Endress+Hauser 43
Commissioning Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
PRESSURE_1_ACCEPT_ Position adjustment – the pressure difference between zero (set point) and the measured
ZERO_INSTALL_OFFSET/ pressure need not be known. (A reference pressure is present at the device.)
POS. ZERO ADJUST 1
Example:
Entry
– PRIMARY VALUE = 2.2 mbar
– Correct the PRIMARY VALUE via the PRESSURE_1_ACCEPT_ZERO_
INSTALL_OFFSET parameter with the "Confirm" option. This means that you are
assigning the value 0.0 to the pressure present.
– PRIMARY VALUE (after pos. zero adjust) = 0.0 mbar
The PRESSURE_1_INSTALL_OFSET parameter displays the resulting pressure difference
(offset) by which the PRIMARY VALUE was corrected.
Factory setting:
0
PRESSURE_1_ACCEPT_ Position adjustment – the pressure difference between zero (set point) and the measured
INSTALL_OFFSET/ pressure need not be known. (A reference pressure is present at the device.)
POS. INPUT VALUE 2
Example:
Entry
– PRIMARY VALUE = 0.5 mbar
– For the PRESSURE_1_ACCEPT_INSTALL_OFFSET parameter, specify the desired set
point for the PRIMARY VALUE, e.g. 2 mbar.
(PRIMARY VALUEnew = PRESSURE_1_ACCEPT_INSTALL_OFFSET)
– PRIMARY VALUE (after entry for PRESSURE_1_ACCEPT_INSTALL_OFFSET)
= 2.0 mbar
– The PRESSURE_1_INSTALL_OFSET parameter displays the resulting pressure
difference (offset) by which the PRIMARY VALUE was corrected.
(The following applies: PRESSURE_1_INSTALL_OFSET = PRIMARY VALUEold –
PRESSURE_1_ACCEPT_INSTALL_OFFSET,
here: PRESSURE_1_INSTALL_OFSET = 0.5 mbar – 2.0 mbar = – 1.5 mbar)
Factory setting:
0
PRESSURE_1_INSTALL_ Position adjustment – the pressure difference between zero (set point) and the measured
OFFSET/ pressure is known. (A reference pressure is not present at the device.)
CALIB. OFFSET 3 Example:
Entry
– PRIMARY VALUE = 2.2 mbar
– Via the PRESSURE_1_INSTALL_OFSET parameter, enter the value by which the
MEASURED VALUE should be corrected. To correct the PRIMARY VALUE to 0.0
mbar, you must enter the value 2.2 here.
(The following applies:
PRIMARY VALUE new = PRIMARY VALUEold – CALIB. OFFSET)
– PRIMARY VALUE (after entry for calib. offset) = 0.0 mbar
Factory setting:
0
44 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Commissioning
POS. ZERO ADJUST Position adjustment – the pressure difference between zero (set point) and the measured
Entry pressure need not be known. (A reference pressure is present at the device.)
Example:
– MEASURED VALUE = 2.2 mbar
– Correct the MEASURED VALUE via the POS. ZERO ADJUST parameter with the
"Confirm" option. This means that you are assigning the value 0.0 to the pressure
present.
– MEASURED VALUE (after pos. zero adjust) = 0.0 mbar
The CALIB. OFFSET parameter displays the resulting pressure difference (offset) by which
the MEASURED VALUE was corrected.
Factory setting:
0
POS. INPUT VALUE Position adjustment – the pressure difference between zero (set point) and the measured
Entry pressure need not be known. (A reference pressure is present at the device.)
Example:
– MEASURED VALUE = 0.5 mbar
– For the POS. INPUT VALUE parameter, specify the desired set point for the
MEASURED VALUE, e.g. 2 mbar.
(MEASURED VALUEnew = POS. INPUT VALUE)
– MEASURED VALUE (after entry for POS. INPUT VALUE) = 2.0 mbar
– The CALIB. OFFSET parameter displays the resulting pressure difference (offset) by
which the MEASURED VALUE was corrected.
CALIB. OFFSET = MEASURED VALUEold – POS. INPUT VALUE,
here: CALIB. OFFSET = 0.5 mbar – 2.0 mbar = – 1.5 mbar)
Factory setting:
0
CALIB. OFFSET Position adjustment – the pressure difference between zero (set point) and the measured
Entry pressure is known. (A reference pressure is not present at the device.)
Example:
– MEASURED VALUE = 2.2 mbar
– Via the CALIB. OFFSET parameter, enter the value by which the MEASURED VALUE
should be corrected. To correct the MEASURED VALUE to 0.0 mbar, you must enter
the value 2.2 here.
(MEASURED VALUE new = MEASURED VALUEold – CALIB. OFFSET)
– MEASURED VALUE (after entry for calib. offset) = 0.0 mbar
Factory setting:
0
Endress+Hauser 45
Commissioning Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
! Note!
• By means of the ToF Tool operating program, a Quick Setup menu is available for each of the
measuring modes Pressure and Level which guides you through the most important basic
functions. With the setting in the MEASURING MODE parameter, you specify which Quick
Setup menu should be displayed. → See also page 41, Section 6.3 "Selecting language and
measuring mode". No Quick Setup menus are available for the FF configuration programs.
• For a detailed description of the parameters see the Operating Instructions BA303P "Cerabar S/
Deltabar S, Description of device functions"
– Table 2, Pressure Transducer Block
– ToF Tool: Table 4, POSITION ADJUSTMENT
– ToF Tool: Table 5, BASIC SETUP
– ToF Tool: Table 13, EXTENDED SETUP
→ See also page 2, Section "Overview documentation".
6.5.2 Quick Setup menu for the Pressure measuring mode (ToF Tool)
! Note!
This Quick Setup menu is only available by means of the ToF Tool. → See also page 32, Section
5.3.10 "ToF Tool operating program".
Measured value
MEASURING MODE
Pressure Level
Gauge pressure Absolut pressure sensors
sensors
POS. ZERO ADJUST POS. INPUT VALUE
DAMPING VALUE
P01-PMx7xxxx-19-xx-xx-xx-022
Fig. 22: Quick Setup menu for the "Pressure" measuring mode
ToF Tool
MEASURING MODE
Select "Pressure".
DAMPING VALUE
Enter damping time (time constant τ). The damping affects the speed at which all subsequent elements, such as the on-
site display, measured value and OUT value of the Analog Input Block react to a change in the pressure.
46 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Commissioning
! Note!
• By means of the ToF Tool operating program, a Quick Setup menu is available for each of the
measuring modes Pressure and Level guides you through the most important basic functions.
With the setting in the MEASURING MODE parameter, you specify which Quick Setup menu
should be displayed. → See also page 41, Section 6.3 "Selecting language and measuring mode".
No Quick Setup menus are available for the FF configuration programs.
• For a detailed description of the parameters see the Operating Instructions BA303P "Cerabar S/
Deltabar S, Description of device functions"
– Table 4, Pressure Transducer Block
– ToF Tool: Table 4, POSITION ADJUSTMENT
– ToF Tool: Table 6 to 9, BASIC SETUP
– ToF Tool: Table 12, EXTENDED SETUP
– ToF Tool: Table 14, LINEARISATION
→ See also page 2, Section "Overview documentation".
• For level measurement, select the "Level" option by means of the MEASURING MODE
parameter. The operating menu is structured appropriately. → See also Section 10.1.
The factory settings for the LEVEL MODE, CALIBRATION MODE, LIN. MEASURAND, EMPTY
CALIB. and FULL CALIB. parameters are as follows:
– LEVEL MODE = Linear
– CALIBRATION MODE = wet
– LIN. MEASURAND = %
– EMPTY CALIB. = 0 %
– FULL CALIB. = 100 %.
The "Wet" calibration mode (LEVEL_ADJUST_MODE) is not available by means of the FF
operating program.
Endress+Hauser 47
Commissioning Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
! Note!
• This Quick Setup menu is only available by means of the ToF Tool. → See also page 32, Section
5.3.10 "ToF Tool operating program".
• Some parameters are only displayed if other parameters are appropriately configured. For
example, the EMPTY CALIB. parameter is not displayed unless the "Linear" option was selected
for the LEVEL MODE parameter and the "Wet" option was selected for the CALIBRATION
MODE parameter. The LEVEL MODE and CALIBRATION MODE parameters can be found in
the BASIC SETUP function group (menu path: OPERATING MENU → SETTINGS → BASIC
SETUP).
MEASURED VALUE
MEASURING MODE
Pressure Level
1), 2) 3)
1) LEVEL MODE = "Linear"
EMPTY CALIB. and CALIBRATION MODE = "dry"
P01-PMx7xxxx-19-xx-xx-xx-023
Fig. 23: Quick Setup menu for the "Level" measuring mode"
ToF Tool
Measured value display
Select QUICK SETUP menu.
MEASURING MODE
Select "Level".
EMPTY CALIB. (level type "Linear"/"Height linearized" and calibration mode "Wet")
Enter level value for the lower calibration point .
For this parameter, enter a level value which is assigned to the pressure present at the device.
FULL CALIB. (level type "Linear"/"Height linearized" and calibration mode "Wet")
Enter level value for the upper calibration point .
For this parameter, enter a level value which is assigned to the pressure present at the device.
DAMPING VALUE
Enter damping time (time constant τ). The damping affects the speed at which all subsequent elements, such as the on-
site display, measured value and OUT value of the Analog Input Block react to a change in the pressure.
48 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Commissioning
EU_0 0
0 UNITS_
0 0.7 1 EU_0 EU_100 INDEX:
%
0 70 100
OUT Value = 70
P01-xMx7xxxx-05-xx-xx-xx-008
! Note!
• If you have selected the "Direct" mode for the L_TYPE parameter, you cannot change the values
and units for XD_SCALE and OUT_SCALE.
• The L_TYPE, XD_SCALE and OUT_SCALE parameters can only be changed in the OOS block
mode.
• Make sure that the output scaling of the Pressure Transducer Block SCALE_OUT matches the
input scaling of the Analog Input Block XD_SCALE.
Endress+Hauser 49
Maintenance Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
7 Maintenance
Cerabar S requires no maintenance.
8 Trouble-shooting
8.1 Messages
The following table lists all the possible messages that can occur.
The device differentiates between the message types "Alarm", "Warning" and "Error". All "Error"-
type messages are set as "Warning" messages at the factory.
→ See "Message type/NA 64" column and Section 8.2 "Response of outputs to errors".
In addition, the "Message type/NA 64" column classifies the messages in accordance with NAMUR
Recommendation NA 64:
• Break down: indicated with "B"
• Maintenance need: indicated with "C" (check request)
• Function check: indicated with "I" (in service)
The DIAGNOSTIC_CODE/DIAGNOSE_CODE parameter displays the message with the highest
priority. This parameter is displayed in the MELDUNGEN group in the Diagnostic Transducer Block
or in the ToF Tool. → See also Section 8.2 "Response of outputs to errors".
Every message is also output as per the FOUNDATION Fieldbus Specification by means of the
XD_ERROR and BLOCK_ERROR parameters in the Pressure and Service Transducer Block.
Numbers are given for these parameters in the following table which are explained on page 57.
! Note!
• For support and further information, please contact Endress+Hauser Service.
• → See also Section 8.4, 8.5 and 8.6.
101 (A101) Alarm B>Sensor electronic 20 5 – Electromagnetic effects are – Wait a few minutes. 18
B EEPROM error greater than specifications in the – Restart the device. Perform reset
technical data. (→ See Section (Code 62).
9.) This message normally only – Block off electromagnetic effects
appears briefly. or eliminate source of
disturbance.
102 (W102) Warning C>Checksum error in 23 11 – Main electronics defect. Correct – Replace main electronics. 52
C EEPROM: peakhold measurement can continue as
segment long as you do not need the
peak hold indicator function.
106 (W106) Warning C>Downloading - please 17 0 – Downloading. – Wait for download to complete. 51
C wait
50 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Trouble-shooting
110 (A110) Alarm B>Checksum error in 23 11 – The supply voltage is – Reestablish supply voltage. 6
B EEPROM: configuration disconnected when writing. Perform reset (Code 7864) if
segment necessary. Carry out calibration
again.
113 (A113) Alarm B>ROM failure in 20 9 – Main electronics defect. – Replace main electronics. 1
B transmitter electronic
115 (E115) Error C>Sensor overpressure 17 0 – Overpressure present. – Reduce pressure until message 30
C disappears.
116 (W116) Warning C>Download error, 17 0 – The file is defect. – Use another file. 37
C repeat download
– During the download, the data – Check cable connection PC –
are not correctly transmitted to transmitter.
the processor, e.g. because of – Block off electromagnetic effects
open cable connections, spikes or eliminate sources of
(ripple) on the supply voltage or disturbance.
electromagnetic effects. – Perform reset (Code 7864) and
carry out calibration again.
– Repeat download.
120 (E120) Error C>Sensor low pressure 17 0 – Pressure too low. – Increase pressure until message 31
C disappears.
121 (A121) Alarm B>Checksum error in 23 11 – Main electronics defect. – Replace main electronics. 5
B factory segment of
EEPROM
122 (A122) Alarm B>Sensor not connected 20 5 – Cable connection sensor –main – Check cable connection and 14
B electronics disconnected. repair if necessary.
130 (A130) Alarm B>EEPROM is defect. 23 11 – Main electronics defect. – Replace main electronics. 10
B
131 (A131) Alarm B>Checksum error in 23 11 – Main electronics defect. – Replace main electronics. 9
B EEPROM: min/max
segment
132 (A132) Alarm B>Checksum error in 23 11 – Main electronics defect. – Replace main electronics. 7
B totalizer EEPROM
133 (A133) Alarm B>Checksum error in 23 11 – An error occurred when – Perform reset (Code 7864) and 8
B History EEPROM writing. carry out calibration again.
134 (W134) Warning C>EEPROM lieftime 17 0 – Writing too often to EEPROM. – Reduce write accessing to 55
C WARNING EEPROM.
135 (A135) Alarm B>Checksum error in 23 11 – Main electronics defect. – Replace main electronics. 10
B EEPROM FF segment
602 (W602) Warning C>Linearisation curve 17 0 – The linearisation table is not – Add to linearisation table or 57
C not monoton monotonic increasing. perform linearisation again.
Endress+Hauser 51
Trouble-shooting Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
604 (W604) Warning C>Linearisation table 23 11 – The linearisation table consists – Add to linearisation table. If 58
C not valid. At least 2 of less than 2 points. necessary, perform linearisation
points again.
613 (W613) Warning I>Simulation is active 17 3 – Simulation is switched on, i.e. – Switch off simulation. 60
I the device is not measuring at
present.
700 (W700) Warning C>Last configuration not 23 11 – An error occurred when writing – Perform reset (Code 7864) and 53
C stored or reading configuration data or carry out calibration again.
the power supply was
disconnected.
702 (W702) Warning C>HistoROM data not 17 11 – Data were not written correctly – Repeat upload. 54
C consistent. to the HistoROM, e.g. if the – Perform reset (Code 7864) and
HistoROM was detached during carry out calibration again.
the writing process.
– HistoROM does not have any – Copy suitable data to the
data. HistoROM. (→ See also
page 33, Section 5.4.1 "Copying
configuration data".)
703 (A703) Alarm B>Measurement error 20 5 – Fault in the main electronics. – Briefly disconnect device from 23
B the power supply.
706 (W706) Warning C>Configuration in 23 11 – Configuration (parameters) in – Copy data from the device to 59
C HistoROM and device the HistoROM and in the device the HistoROM. (→ See also
not identical is not identical. page 33, Section 5.4.1 "Copying
configuration data".)
– Copy data from the HistoROM
to the device. (→ See also
page 33, Section 5.4.1 "Copying
configuration data".) The
message remains if the
HistoROM and the device have
different software versions. The
message goes out if you copy the
data from the device to the
HistoROM.
707 (A707) Alarm B>X-VAL. (TAB_XY 18 8 – At least one X-VALUE – Carry out calibration again. 38
B _VALUE) of lin. table out (TAB_XY_VALUE) in the (→ See also Operating
of edit limits. linearisation table is either Instructions BA303P, chapter 5
below the value for SCALE_IN, or these Operating Instructions,
EU_0/HYDR. PRESS MIN. or page 2.)
LINEAR_ LEVEL_MIN/MIN.
LEVEL or above the value for
SCALE_IN, EU_100/HYDR.
PRESS. MAX. or
LINEAR_LEVEL_MAX/LEVEL
MAX.
52 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Trouble-shooting
710 (W710) Warning B>Set span too small. 18 8 – Values for calibration (e.g. lower – Adjust calibration to suit sensor. 50
C Not allowed. range value and upper range (→ See also Operating
value) are too close together. Instructions BA303P, parameter
description CAL_MIN_SPAN/
MINIMUM SPAN or these
Operating Instructions, page 2.)
– The sensor was replaced and the – Adjust calibration to suit sensor.
customer-specific configuration – Replace sensor with a suitable
does not suit the sensor. sensor.
– Unsuitable download carried – Check configuration and
out. perform download again.
713 (A713) Alarm B>100% POINT 18 8 – The sensor was replaced. – Carry out calibration again. 39
B (LEVEL_100_PERCENT
_VALUE) level out of
edit limits
715 (E715) Error C>Sensor over 17 0 – The temperature measured in – Reduce process temperature/ 33
C temperature the sensor is greater than the ambient temperature.
upper nominal temperature of
the sensor. (→ See also
Operating Instructions BA303P,
parameter description
TEMPERATURE_1_SENSOR_
LIMIT_HIGH/Tmax SENSOR
or these Operating Instructions,
page 2.)
717 (E717) Error C>Transmitter over 17 0 – The temperature measured in – Reduce ambient temperature. 36
C temperature the electronics is greater than
the upper nominal temperature
of the electronics (+88 °C).
718 (E718) Error C>Transmitter under 17 0 – The temperature measured in – Increase ambient temperature. 36
C temperature the electronics is smaller than Insulate device if necessary.
the lower nominal temperature
of the electronics (–43 °C).
719 (A719) Alarm B>Y-VAL 19 8 – At least on Y-VALUE – Carry out calibration again. 40
B (TAB_XY_VALUE) of lin. (TAB_XY_VALUE) in the (→ See also Operating
table out of edit limits linearisation table is below the Instructions BA303P, chapter 5
SCALE_OUT, EU_0/MIN. or these Operating Instructions,
TANK CONTANT or above the page 2.)
SCALE_OUT, EU_100/MAX.
TANK CONTENT.
Endress+Hauser 53
Trouble-shooting Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
720 (E720) Error C>Sensor under 17 0 – The temperature measured in – Increase process temperature/ 34
C temperature the sensor is smaller than the ambient temperature.
lower nominal temperature of
the sensor. (→ See also
Operating Instructions BA303P,
parameter description
TEMPERATURE_1_SENSOR_
LIMIT_LOW/Tmin SENSOR or
Operating Instructions, page 2.)
– Unsuitable download carried – Check configuration and
out. perform download again.
721 (A721) Alarm B>ZERO POSITION 18 8 – LEVEL MIN (LINEAR_LEVEL_ – Perform reset (Code 2710) and 41
B (LEVEL OFFSET) level MIN) or LEVEL MAX carry out calibration again.
out of edit limits (LINEAR_LEVEL_MAX) has
been changed.
722 (A722) Alarm B>EMPTY CALIB. 18 8 – LINEAR_ LEVEL_MIN/LEVEL – Perform reset (Code 2710) and 42
B (SCALE_OUT, EU_0) or MIN or LINEAR_LEVEL_MAX/ carry out calibration again.
FULL CALIB. LEVEL MAX has been changed.
(SCALE_OUT, EU_100)
out of edit limits
723 (A723) Alarm B>MAX. FLOW 18 8 – FLOW_TYOPE/FLOW-MEAS. – Carry out calibration again. 43
B (SCALE_OUT, EU_100) TYPE has been changed.
out of edit limits
725 (A725) Alarm B>Sensor connection 20 5 – Electromagnetic effects are – Block off electromagnetic effects 26
B error, cycle disturbance greater than specifications in the or eliminate source of
technical data. disturbance.
(→ See Section 9.)
728 (A728) Alarm B>RAM error 20 9 – Fault in the main electronics. – Briefly disconnect device from 2
B the power supply.
729 (A729) Alarm B>RAM error 20 9 – Fault in the main electronics. – Briefly disconnect device from 3
B the power supply.
54 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Trouble-shooting
730 (E730) Error C>LRV user limits 19 8 – Pressure measured value has – Check system/pressure 47
C exceeded undershot the value specified for measured value.
the PRESSURE_1_USER_ – Change value for
LOW_LIMIT/Pmin ALARM PRESSURE_1_USER_ LOW_
WINDOW parameter. LIMIT/Pmin ALARM
WINDOW if necessary. (→ See
also Operating Instructions
BA303P, parameter description
or these Operating Instructions,
page 2.)
731 (E731) Error C>URV user limits 19 8 – Pressure measured value has – Check system/pressure 46
C exceeded overshot the value specified for measured value.
the PRESSURE_1_USER_ – Change value for
HIGH_LIMIT/Pmax ALARM PRESSURE_1_USER_ HIGH_
WINDOW parameter. LIMIT/Pmax ALARM
WINDOW if necessary. (→ See
also Operating Instructions
BA303P, parameter description
or these Operating Instructions,
page 2.)
732 (E732) Error C>LRV Temp. User 19 8 – Temperature measured value – Check system/temperature 49
C limits exceeded has undershot the value measured value.
specified for the – Change value for
TEMPERATURE_1_USER_ TEMPERATURE_1_USER_
LOW_LIMIT/Tmin ALARM LOW_ LIMIT/Tmin ALARM
WINDOW parameter. WINDOW if necessary. (→ See
also Operating Instructions
BA303P, parameter description
or these Operating Instructions,
page 2.)
733 (E733) Error C>URV Temp. User 19 8 – Temperature measured value – Check system/temperature 48
C limits exceeded has overshot the value specified measured value.
for the – Change value for
TEMPERATURE_1_USER_ TEMPERATURE_1_USER_HIG
HIGH_LIMIT/Tmax ALARM H_LIMIT/Tmax ALARM
WINDOW parameter. WINDOW if necessary. (→ See
also Operating Instructions
BA303P, parameter description
or these Operating Instructions,
page 2.)
736 (A736) Alarm B>RAM error 20 9 – Fault in the main electronics. – Briefly disconnect device from 4
B the power supply.
738 (A738) Alarm B>Measurement error 20 5 – Fault in the main electronics. – Briefly disconnect device from 20
B the power supply.
Endress+Hauser 55
Trouble-shooting Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
740 (E740) Error C>Calculation overflow, 20 5 – Level measuring mode: the – Check configuration and carry 28
C bad configuration measured pressure has out calibration again if
undershot the value for necessary.
SCALE_IN, EU_0/HYDR. – Select a device with a suitable
PRESS. MIN. or overshot the measuring range.
value for SCALE_IN, EU_100/
HYDR. PRESS MAX.
742 (A742) Alarm B>Sensor connection 20 5 – Electromagnetic effects are – Wait a few minutes. 19
B error (upload) greater than specifications in the – Perform reset (Code 7864) and
technical data. (→ See Section carry out calibration again.
9.) This message normally only
appears briefly.
743 (E743) Alarm B>Electronic PCB error 20 5 – This message normally only – Wait a few minutes. 15
B during initialisation appears briefly. – Restart the device. Perform reset
(Code 62).
744 (A744) Alarm B>Main electronic PCB 20 5 – Electromagnetic effects are – Restart the device. Perform reset 12
B error greater than specifications in the (Code 62).
technical data. – Block off electromagnetic effects
(→ See Section 9.) or eliminate source of
disturbance.
746 (W746) Warning C>Sensor connection 20 5 – Electromagnetic effects are – Wait a few minutes. 27
C error - initialising greater than specifications in the – Restart the device. Perform reset
technical data. (→ See Section (Code 62).
9.) This message normally only – Block off electromagnetic effects
appears briefly. or eliminate source of
disturbance.
– Overpressure or low pressure – Reduce or increase pressure.
present.
747 (A747) Alarm B>Sensor software not 17 0 – Sensor does not suit the device – Replace sensor with a suitable 17
B compatible to electronics (electronic sensor nameplate). sensor.
748 (A748) Alarm B>Memory failure in 20 5 – Electromagnetic effects are – Block off electromagnetic effects 16
B signal processor greater than specifications in the or eliminate source of
technical data. disturbance.
(→See Section 9.)
56 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Trouble-shooting
750 (A750) Alarm B>Configuration not 19 8 – By means of the operation – Check configuration. 45
B permitted profile, options were selected for – Perform reset (code 7864) and
the configuration of the device recalibrate the device.
but the options do not suit one
another. For example, if the
option "1" (linearisation table)
was selected for LIN_TYPE and
the unit "1347
(m3/s)" was selected for
PRIMARY_VALUE_UNIT.
Error type Code XD_ERROR XD_ERROR Text BLOCK_ BLOCK_ERROR Text PV Status
Value ERROR
Value
707, 711, 713, 721, 18 Calibration Error 8 Output Failure Uncertain Config Error
722, 723, 741
113, 728, 729, 736 20 Electronics Failure 9 Memory Failure Bad Device Failure
110, 121, 130, 131, 23 Data Integrity Error 11 Lost NV Data Bad Device Failure
132, 133, 135
Error 115, 120, 715, 717, 17 General Error 0 Other – Alarm: Bad Non Specific
718, 720 – Warning: Status Uncertain
730, 731, 732, 733 19 Configuration Error 8 Output Failure – Alarm: Bad Non Specific
– Warning: Status Uncertain
122, 727, 726, 740 20 Electronics Failure 5 Device Fault State – Alarm: Bad Non Specific
– Warning: Status Uncertain
Warning 106, 116, 134, 745 17 General Error 0 Other Uncertain Config Error
102, 700, 706 23 Data Integrity Error 11 Lost NV Data Status Uncertain
Endress+Hauser 57
Trouble-shooting Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
PFOUNDATION The process variable in question is Device continues measuring. The process For this error, you can enter whether the
Fieldbus transmitted with the status BAD. variable in question is transmitted with the device should react as in the event of an
status UNCERTAIN. alarm or as in the event of a warning. See
corresponding "Alarm" or "Warning"
column.
(→ See also Operating Instructions
BA303P, REACTION_ON_ALARM_NR/
SELECT ALARM TYPE parameter
description or these Operating Instructions,
page 2.)
On-site display – The measured value and message are – The measured value and message are – The measured value and message are
displayed alternately displayed alternately displayed alternately
– Measured value display: -symbol is – Measured value display: -symbol – Measured value display: see
permanently displayed. flashes. corresponding "Alarm" or "Warning"
column
Message display Message display: Message display:
– A + 3-digit number such as A122 and – W + 3-digit number such as W613 and – E + 3-digit number such as E713 and
– Description – Description – Description
Remote operation In the case of an alarm, the In the case of a warning, the In the case of an error, the
(FF configuration DIAGNOSTIC_CODE/ALARM STATUS DIAGNOSTIC_CODE/ALARM STATUS2 DIAGNOSTIC_CODE/ALARM STATUS
program/ToF Tool) parameter displays a 13-digit number such parameter displays a 3-digit number such as parameter2 displays a 3-digit number such
as 122 for "Sensor connection error, 613 for "Simulation is active". as 731 for "Pmax ALARM WINDOW
incorrect data." undershot".
1) FF configuration program: Diagnostic Transducer Block. Menu path ToF TooF: OPERATING MENU → MESSAGES
58 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Trouble-shooting
! Note!
The failsafe mode is also activated if the "Out of Service O/S" option was selected by means of the
TARGET_MODE parameter.
1 These parameters are not available by means of the ToF Tool operating program.
Settings 1 Measures
– ALARM_HOLD_ON_TIME// – Rectify cause of the message (see also Section 8.1).
ALARM DISPL. TIME = 0 s
– ACKNOWLEDGE_ALARM_MODE/
ACK. ALARM MODE = off
Endress+Hauser 59
Trouble-shooting Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
8.4 Repair
The Endress+Hauser repairs concept provides for measuring devices to have a modular design and
also the customer may carry out repairs.
Section "Spare parts" contains all the spare parts listed with their order numbers. You can order them
from Endress+Hauser for repairs on your Cerabar S. As far as necessary, the spare parts also include
replacement instructions.
! Note!
• For certified devices, please consult Chapter "Repair of Ex-certified devices".
• For more information on service and spare parts contact the Endress+Hauser Service. ( → See
www.endress.com/worldwide)
60 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Trouble-shooting
You can order sensor modules as spare parts for PMC71 and PMP71. For PMC71 and PMP71, see
page 65 and page 68 respectively.
The right order number for the sensor module is derived from the Order No. which is indicated on
the nameplate (→ see also page 6).
10 20 30 40 50 60 70 80 90 100 110
Order code/Order No. of the device
PMC71 – ❑ ❑ ❑ ❑❑ ❑ ❑ ❑❑ ❑ ❑ ❑ ❑ see name plate
PMP71 –
P01-PMx7xxxx-16-xx-xx-xx-003
Endress+Hauser 61
Trouble-shooting Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
20
21
20
21
40
31
30
15
13
10
12
35
21
25
P01-xMx7xxxx-09-xx-xx-xx-000
62 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Trouble-shooting
20 Cover
52020432 Cover for Aluminium T14 housing incl. gasket, not for EEx d/XP
52020433 Cover for Aluminium T14 housing incl. gasket, for EEx d/XP
52020494 Cover for Aluminium T14 housing with sight glass incl. gasket, Ex-free
52020492 Cover for Aluminium T14 housing with sight glass incl. gasket, not for EEx d/XP
52020493 Cover for Aluminium T14 housing with sight glass incl. gasket, for EEx d/XP
30 Electronics
52027697 Electronics, FOUNDATION Fieldbus, Ex, push button on electronics
52026600 Electronics, FOUNDATION Fieldbus, Ex, push button on housing
31 HistoROM/M-DAT
52027785 HistoROM/M-DAT, ToF Tool-CD included
35 Terminal block
52027691 Terminal 2-pole, RFI-filter, FOUNDATION Fieldbus Ex ia
52027962 Terminal 2-pole, RFI-filter, FOUNDATION Fieldbus Ex d (PMC71)
40 Display module
52024112 Display module VU 333 with holder (version 2.0)
Endress+Hauser 63
Trouble-shooting Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
12
50 50 50
57
55 57
57
58
P01-PMC71xxx-09-xx-xx-xx-000
57 Process gasket
52020768 O-ring 26.7x1.78 FKM 70 Viton, oil and grease free (5 pieces)
52020769 O-ring 26.7x1.78 NBR 70 (5 pieces)
52020770 O-ring 26.7x1.78 EPDM 70 (5 pieces)
52020771 O-ring 26.7x1.78 FKM Viton –40°C (5 pieces)
52020772 O-ring 26.7x1.78 FFKM 70 Kalrez (1 piece)
52020773 O-ring 26.7x1.78 FFKM 75 Chemraz (1 piece)
58 Fastening angle
52020441 Mounting angle, adapter and screws
64 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Trouble-shooting
10 Approval:
A For non-hazardous areas
1 ATEX II 1/2 G EEx ia IIC T6
6 ATEX II 1/2 G EEx ia IIC T6, overspill protection WHG
2 ATEX II 1/2 D
8 ATEX II 1 GD EEx ia II T6
3 ATEX II 1/3 GD EEx ia IIC T6
5 ATEX II 2 G EEx d[ia] IIC T6
7 ATEX II 3 G EEx nA II T6
S FM IS, Class I, II, III Division 1, Groups A – G; NI Class I Division 2, Groups A – D; AEx ia
T FM XP, Class I, Division 1, Groups A – D; AEx d
Q FM DIP, Class II, III Division 1, Groups E – G
R FM NI, Class I, Division 2, Groups A – D
U CSA IS, Class I, II, III Division 1, Groups A – G; Class I Division 2, Groups A – D, Ex ia
Endress+Hauser 65
Trouble-shooting Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
80 Seal:
A FKM Viton
B EPDM
D Kalrez
E Chemraz
F NBR
1 FKM Viton, oxygen service
66 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Trouble-shooting
Endress+Hauser 67
Trouble-shooting Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
12
50
P01-PMP71xxx-09-xx-xx-xx-000
10 Approval:
A For non-hazardous areas
1 ATEX II 1/2 G EEx ia IIC T6
6 ATEX II 1/2 G EEx ia IIC T6, overspill protection WHG
2 ATEX II 1/2 D
4 ATEX II 1/3 D
8 ATEX 1 GD EEx ia IIC T6
3 ATEX II 1/2 GD EEx ia IIC T6
5 ATEX II 2 G EEx d IIC T6
7 ATEX II 3 G EEx nA II T6
S FM IS, Class I, II, III Division 1, Groups A – G; NI Class I Division 2, Groups A – D; AEx ia
T FM XP, Class I Division 1, Groups A – D; AEx d
Q FM DIP, Class II, III Division 1, Groups E – G
R FM NI, Class I, Division 2, Groups A – D
U CSA IS, Class I, II, III Division 1, Groups A – G; Class I Division 2, Groups A – D, Ex ia
V CSA XP Class I Division 1, Groups B – D; Ex d
W CSA Class II, III Division 1, Groups E – G (Dust-Ex)
C Combi-certificate: FM IS and XP Class I Division 1, Groups A – D
D Combi-certificate: CSA IS and XP Class I Division 1, Groups A – D
E Combi-certificate: FM/CSA IS and XP Class I Division 1, Groups A – D
68 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Trouble-shooting
60 Membrane material
1 AISI 316L
2 Alloy C276
Endress+Hauser 69
Trouble-shooting Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
90 Fill fluid:
A Silicone oil
F Inert oil:
70 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Technical data
8.8 Disposal
When disposing, separate and recycle the device components based on the materials.
9 Technical data
For technical data, please refer to the Technical Information TI383P for Cerabar S.
→ See also page 2, section "Overview documentation".
10 Appendix
Endress+Hauser 71
Appendix Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
Measured value
MEASURING MODE
POS. ZERO ADJUST POS. ZERO ADJUST POSITION ADJUSTMENT BASIC SETUP
Pressure Level
* There are parameters that are only displayed if other parameters are
appropriately configured.
For example the CUSTOMER UNIT P parameter is only displayed
if the "User unit" option was selected for the PRESS. ENG. UNIT parameter.
These parameters are indicated with a "*".
P01-PMx7xxxx-19-xx-xx-xx-017
72 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Appendix
Pressure Height
Linear
Linearized Linearized E
ADJUSTED DENSITY * HEIGHT UNIT * EMPTY CALIB. DENSITY UNIT CUTOMER UNIT H *
CUSTOMER UNIT H * EMPTY PRESSURE ADJUST DENSITY CUST. UNIT FACT. H *
*
CUST. UNIT FACT. H FULL CALIB. HEIGHT UNIT * H H
100% POINT
* FULL PRESSURE CUSTOMER UNIT H *
ZERO POSITION
DAMPING VALUE
* There are parameters that are only displayed if other parameters are
appropriately configured.
For example the CUST. UNIT FACT. H parameter is only displayed
if the "User unit" option was selected for the HEIGHT UNIT parameter.
These parameters are indicated with a "*".
P01-xxxxxxxx-19-xx-xx-xx-132
Endress+Hauser 73
Appendix Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
DISPLAY
Pressure Level
TEMP. ENG UNIT TEMP. ENG UNIT TANK CONTENT MIN MENU DESCRIPTOR
Measuring LANGUAGE
Editor Table
Table
Y-VAL.
TANK DESCRIPTION
TAB. ACTIVATE
P01-PMx7xxxx-19-xx-xx-xx-018
74 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Appendix
INFO TRANSMITTER DATA PROCESS CONNECTION SENSOR DATA PROCESS VALUE PEAK HOLD INDICATOR
Pressure Level
DEVICE NAME STR. DEVICE SERIAL No Pmax PROC. CONN. SENSOR SER. NO. MEASURED VALUE MEASURED VALUE COUNTER:P > Pmax
MANUFACTURER ID ELECTR. SERIAL No PROC. CONN. TYPE PRESS. SENS LOLIM PRESSURE PRESSURE COUNTER:P < Pmin
MESSAGE TAG_DESC MAT. PROC. CONN. + PRESS. SENS HILIM CORRECTED PRESS. CORRECTED PRESS. MAX. MEAS. PRESS.
ADDITIONAL INFO MAT. PROC. CONN. – MINIMUM SPAN SENSOR PRESSURE SENSOR PRESSURE MIN. MEAS. PRESS.
DEVICE DESIGN SEAL TYPE SENSOR MEAS. TYPE SENSOR TEMP. SENSOR TEMP. COUNTER:T > Tmax
HARDWARE REV. Pmin SENS. DAMAGE MEAS. VAL. TREND MEAS. VAL. TREND COUNTER:T< Tmin
SOFTWARE VERSION Pmax SENS. DAMAGE LEVEL BEFORE LIN * MAX. MEAS. TEMP.
RESET PEAKHOLD
* There are parameters that are only displayed if other parameters are
appropriately configured.
These parameters are indicated with a "*".
P01-PMx7xxxx-19-xx-xx-xx-019
Endress+Hauser 75
Appendix Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus
OPERATION DIAGNOSTICS
ENTER RESET CODE SIMULATION MODE ALARM STATUS Pmin ALARM WINDOW
ERROR NO.
ALARM DELAY
J J J J J
* There are parameters that are only displayed if other parameters are
appropriately configured.
These parameters are indicated with a "*".
P01-PMx7xxxx-19-xx-xx-xx-020
76 Endress+Hauser
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Appendix
10.2 Patents
This product may be protected by at least one of the following patents. Further patents are pending.
• US 5,836,063 A1 i EP 0 797 084 B1
• US 5,877,424 A1 i EP 0 780 674 B1
• DE 203 05 869 U1
• US 6,363,790 A1 i EP 0 995 979 B1
• US 5,670,063 A1 i EP 0 516 579 B1
• US 5,539,611 A1
• US 5,050,034 A1 i EP 0 445 382 B1
• US 5,005,421 A1 i EP 0 351 701 B1
• EP 0 414 871 B1
• EP 1 061 351 B1
• US 5,334,344 A1 i EP 0 490 807 B1
• US 6,703,943 A1
Endress+Hauser 77
Cerabar S PMC71, PMP71/72/75 with FOUNDATION Fieldbus Index
Index
A Operating elements, position. . . . . . . . . . . . . . . . . . . . . . . 19
Alarm messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Operating menu (ToF Tool). . . . . . . . . . . . . . . . . . . . . . . . 71
Assignment of Transducer Blocks (CHANNEL) . . . . . . . . . 26 OUT value, scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Overvoltage protection . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
B
Block configuration, delivery status. . . . . . . . . . . . . . . . . . 25 P
Block model, Cerabar S . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Pipe mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Position adjustment, FF configuration program . . . . . . . . . 43
C Position adjustment, on-site . . . . . . . . . . . . . . . . . . . . . . . 20
Cable specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Position adjustment, ToF Tool. . . . . . . . . . . . . . . . . . . . . . 45
CHANNEL-Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Pressure measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Current consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Pressure measurement, Quick Setup menu (ToF Tool). . . . 46
D Q
Device addressing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Quick Setup menu level (ToF Tool) . . . . . . . . . . . . . . . . . . 48
Device identifiction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Quick Setup menu pressure . . . . . . . . . . . . . . . . . . . . . . . 46
Diaphragm seals, installation instructions . . . . . . . . . . . . . 11
Diaphragm seals, vacuum application . . . . . . . . . . . . . . . . 11 R
Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Repair. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Repair of Ex-certified devices . . . . . . . . . . . . . . . . . . . . . . 60
E Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Earthing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Rotating the housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 S
Scaling OUT parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
F Scope of delivery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Factory setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Screening . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
FOUNDATION Fieldbus system architecture . . . . . . . . . . 21 Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Slot/index tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
H Software history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Hazardous areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
HistoROM/M-DAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
I
Incoming acceptance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 T
Index tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Temperature separator, installation instructions . . . . . . . . . 12
Installation instructions for devices with diaphragm seals. . 11 ToF Tool operating program . . . . . . . . . . . . . . . . . . . . . . . 32
Installation instructions for devices without diaphragm seals 8 Trouble-shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
L U
Language, selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Unlocking operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Level measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Locking operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 W
Wall mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
M Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Measuring arrangement for level measurement . . . . . . . . . 10
Measuring arrangement for pressure measurement . . . . 9–10
Measuring mode, selection . . . . . . . . . . . . . . . . . . . . . . . . 41
Menu (ToF Tool) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
N
Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Network configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Number of devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
O
Operating elements, function . . . . . . . . . . . . . . . . . . . . . . 20
78 Endress+Hauser
Declaration of Contamination
Erklärung zur Kontamination
Because of legal regulations and for the safety of our employees and operating equipment, we need the "declaration of
contamination", with your signature, before your order can be handled. Please make absolutely sure to include it with
the shipping documents, or - even better - attach it to the outside of the packaging.
Aufgrund der gesetzlichen Vorschriften und zum Schutz unserer Mitarbeiter und Betriebseinrichtungen, benötigen wir die
unterschriebene "Erklärung zur Kontamination", bevor Ihr Auftrag bearbeitet werden kann. Legen Sie diese unbedingt den
Versandpapieren bei oder bringen Sie sie idealerweise außen an der Verpackung an.
harmful/
Medium /concentration Identification flammable toxic corrosive irritant other * harmless
Medium /Konzentration CAS No. entzündlich giftig ätzend gesundheits- sonstiges* unbedenklich
schädlich/
reizend
Process
medium
Medium im
Prozess
Medium for
process cleaning
Medium zur
Prozessreinigung
Returned part
cleaned with
Medium zur
Endreinigung
* explosive; oxidising; dangerous for the environment; biological risk; radioactive
* explosiv; brandfördernd; umweltgefährlich; biogefährlich; radioaktiv
Please tick should one of the above be applicable, include security sheet and, if necessary, special handling instructions.
Zutreffendes ankreuzen; trifft einer der Warnhinweise zu, Sicherheitsdatenblatt und ggf. spezielle Handhabungsvorschriften beilegen.
_____________________________________________ ______________________________________________
(place, date / Ort, Datum) (Company stamp and legally binding signature)
(Firmenstempel und rechtsverbindliche Unterschrift)
www.endress.com/worldwide