PM734B - Technical Data Sheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

AS

s
PM734B - Technical Data Sheet

n
t io
lu
So
or
at
er
en
G
PM734B
SPECIFICATIONS & OPTIONS
STANDARDS WINDINGS & ELECTRICAL PERFORMANCE

Marine generators may be certified to Lloyds, DnV, All generator stators are wound to 2/3 pitch. This
Bureau Veritas, ABS, Germanischer-Lloyd or RINA. eliminates triplen (3rd, 9th, 15th …) harmonics on the
Other standards and certifications can be considered on voltage waveform and is found to be the optimum design

AS
request. for trouble-free supply of non-linear loads. The 2/3 pitch
design avoids excessive neutral currents sometimes seen
DESCRIPTION with higher winding pitches. A fully connected damper
winding reduces oscillations during paralleling. This
The STAMFORD PM range of synchronous ac winding, with the 2/3 pitch and carefully selected pole and
generators are brushless with a rotating field. They are tooth designs, ensures very low levels of voltage waveform
separately excited by the STAMFORD Permanent distortion.
Magnet Generator (PMG). This is a shaft mounted, high

s
frequency, pilot exciter which provides a constant supply TERMINALS & TERMINAL BOX
of clean power via the Automatic Voltage Regulator (AVR)
to the main exciter. The main exciter output is fed to the

n
Standard generators feature a main stator with 6 ends
main rotor, through a full wave bridge rectifier, protected brought out to the terminals, which are mounted on the
by surge suppression. frame at the non-drive end of the generator. A sheet steel

io
terminal box contains the AVR and provides ample space
VOLTAGE REGULATORS for the customers' wiring and gland arrangements. It has
removable panels for easy access.
The PM range generators, complete with PMG, are
available with one of two AVRs. Each AVR has soft start

t
SHAFT & KEYS
voltage build up and built in protection against sustained
over-excitation, which will de-excite the generator after a
lu
All generator rotors are dynamically balanced to better
minimum of 8 seconds. than BS6861:Part 1 Grade 2.5 for minimum vibration in
Underspeed protection (UFRO) is also provided on both operation. Two bearing generators are balanced with a
So
AVRs. The UFRO will reduce the generator output voltage half key.
proportional to the speed of the generator below a pre-
settable level. INSULATION/IMPREGNATION

The MX341 AVR is two phase sensed with a voltage The insulation system is class 'H', and meets the
regulation of ± 1 %. (see the note on regulation). requirements of UL1446.
All wound components are impregnated with materials and
or

The MX321 AVR is 3 phase rms sensed with a voltage processes designed specifically to provide the high build
regulation of 0.5% rms (see the note on regulation). The required for static windings and the high mechanical
UFRO circuit has adjustable slope and dwell for controlled strength required for rotating components.
recovery from step loads. An over voltage protection
at

circuit will shutdown the output device of the AVR, it can QUALITY ASSURANCE
also trip an optional excitation circuit breaker if required.
As an option, short circuit current limiting is available with Generators are manufactured using production procedures
the addition of current transformers. having a quality assurance level to BS EN ISO 9001.
er

Newage may use a third AVR, the MA330, under certain NOTE ON REGULATION
circumstances. The stated voltage regulation may not be maintained in the
presence of certain radio transmitted signals.
en

The MA330 AVR has 3 phase rms sensing, it has similar Any change in performance will fall within the limits of
performance to the MX321. It is a Pulse Width Modulated Criteria 'B' of EN 61000-6-2:2001. At no time will the
AVR with a higher output power under short circuit steady-state voltage regulation exceed 2%.
conditions.
Note: Continuous development of our products entitles us to
All of the above AVRs require a generator mounted change specification details without notice, therefore they must
G

current transformer to provide quadrature droop not be regarded as binding.


characteristics for load sharing during parallel operation.
Provision is also made for the connection of the Front cover drawing is typical of the product range.
STAMFORD power factor controller, for embedded
applications, and a remote voltage trimmer.

2
PM734B
WINDING 312
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.

A.V.R. MX341 MX321 MA330

VOLTAGE REGULATION ± 1% ± 0.5 % ± 0.5 % With 4% ENGINE GOVERNING

SUSTAINED SHORT CIRCUIT REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7)

AS
INSULATION SYSTEM CLASS H

PROTECTION IP23

RATED POWER FACTOR 0.8

STATOR WINDING DOUBLE LAYER LAP

WINDING PITCH TWO THIRDS

WINDING LEADS 6

s
MAIN STATOR RESISTANCE 0.0016 Ohms PER PHASE AT 22°C STAR CONNECTED

n
MAIN ROTOR RESISTANCE 1.67 Ohms at 22°C

EXCITER STATOR RESISTANCE 17.5 Ohms at 22°C

io
EXCITER ROTOR RESISTANCE 0.048 Ohms PER PHASE AT 22°C

R.F.I. SUPPRESSION BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others

t
WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%
lu
MAXIMUM OVERSPEED 2250 Rev/Min

BEARING DRIVE END BALL. 6228 C3

BEARING NON-DRIVE END BALL. 6319 C3


So
1 BEARING 2 BEARING

WEIGHT COMP. GENERATOR 2760 kg 2710 kg

WEIGHT WOUND STATOR 1306 kg 1306 kg

WEIGHT WOUND ROTOR 1139 kg 1077 kg


2
WR² INERTIA 32.7498 kgm 31.7489 kgm2
or

SHIPPING WEIGHTS in a crate 2833kg 2779kg


PACKING CRATE SIZE 194 x 105 x 154(cm) 194 x 105 x 154(cm)

50 Hz 60 Hz
at

TELEPHONE INTERFERENCE THF<2% TIF<50

COOLING AIR 2.69 m³/sec 5700 cfm 3.45 m³/sec 7300 cfm
er

VOLTAGE STAR 380/220 400/231 415/240 440/254 416/240 440/254 460/266 480/277
kVA BASE RATING FOR REACTANCE
1130 1190 1230 1240 1260 1335 1395 1455
VALUES
Xd DIR. AXIS SYNCHRONOUS 2.91 2.77 2.66 2.38 3.51 3.32 3.18 3.04
en

X'd DIR. AXIS TRANSIENT 0.18 0.17 0.16 0.14 0.21 0.20 0.19 0.19

X''d DIR. AXIS SUBTRANSIENT 0.13 0.13 0.12 0.11 0.16 0.15 0.14 0.14

Xq QUAD. AXIS REACTANCE 1.88 1.78 1.71 1.54 2.26 2.14 2.05 1.96
G

X''q QUAD. AXIS SUBTRANSIENT 0.26 0.25 0.24 0.22 0.32 0.30 0.29 0.28

XL LEAKAGE REACTANCE 0.03 0.03 0.03 0.03 0.04 0.04 0.04 0.03
X2 NEGATIVE SEQUENCE 0.19 0.18 0.17 0.15 0.22 0.21 0.20 0.19
X0 ZERO SEQUENCE 0.02 0.02 0.02 0.02 0.03 0.03 0.02 0.02

REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
T'd TRANSIENT TIME CONST. 0.13s
T''d SUB-TRANSTIME CONST. 0.01s
T'do O.C. FIELD TIME CONST. 2.14s
Ta ARMATURE TIME CONST. 0.02s
SHORT CIRCUIT RATIO 1/Xd

3
PM734B
50 Winding 312
Hz THREE PHASE EFFICIENCY CURVES

AS
n s
t io
lu
So
or
at
er
en
G

4
PM734B
Winding 312
60
THREE PHASE EFFICIENCY CURVES
Hz

AS
n s
t io
lu
So
or
at
er
en
G

5
PM734B
Winding 312

Locked Rotor Motor Starting Curve


50
Hz 346V 380V 400V 415V 440V
30

AS
25
.

20

s
PER CENT TRANSIENT VOLTAGE DIP

n
15

io
10

t
5
lu
So
0
0 500 1000 1500 2000 2500 3000 3500
LOCKED ROTOR kVA

60
Hz
or

380V 416V 440V 460V 480V


30
at

25
er
.

20
PER CENT TRANSIENT VOLTAGE DIP
en

15

10
G

0
0 500 1000 1500 2000 2500 3000 3500
LOCKED ROTOR kVA

6
PM734B
MX341 or MX321
Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed
Based on star (wye) connection.
50 100000
Hz

AS
SYMMETRICAL

ASYMMETRICAL
CURRENT (Amps)

10000

n s
io
1000
0.001 0.01 0.1 1 10
TIME (secs)

Sustained Short Circuit = 4,400 Amps

t
lu
60 100000
Hz
So

SYMMETRICAL

ASYMMETRICAL
CURRENT (Amps)

or

10000
at
er

1000
0.001 0.01 0.1 1 10
TIME (secs)
en

Sustained Short Circuit = 4,650 Amps


Note 1 Note 2
The following multiplication factors should be The following multiplication factor should be used to convert the
used to adjust the values from curve between values calculated in accordance with NOTE 1 to those applicable
time 0.001 seconds and the minimum current to the various types of short circuit :
G

point in respect of nominal operating voltage :


50Hz 60Hz 3-phase 2-phase L-L 1-phase L-N
Voltage Factor Voltage Factor Instantaneous x 1.00 x 0.87 x 1.30
380v x 1.00 416v x 1.00 Minimum x 1.00 x 1.80 x 3.20
400v x 1.05 440v x 1.06 Sustained x 1.00 x 1.50 x 2.50
415v x 1.09 460v x 1.10 Max. sustained duration 10 sec. 5 sec. 2 sec.
440v x 1.16 480v x 1.15 All other times are unchanged
The sustained current value is constant irrespective
of voltage level
Note 3
Curves are drawn for Star (Wye) connected machines.

7
PM734B
MA330
Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed
Based on star (wye) connection.
50 100000
Hz

AS
SYMMETRICAL

ASYMMETRICAL
CURRENT (Amps)

10000

n s
io
1000
0.001 0.01 0.1 1 10
TIME (secs)

Sustained Short Circuit = 5,150 Amps

t
lu
60 100000
Hz
So

SYMMETRICAL

ASYMMETRICAL
CURRENT (Amps)

or

10000
at
er

1000
0.001 0.01 0.1 1 10
TIME (secs)
en

Sustained Short Circuit = 5,250 Amps


Note 1 Note 2
The following multiplication factors should be The following multiplication factor should be used to convert the
used to adjust the values from curve between values calculated in accordance with NOTE 1 to those applicable
time 0.001 seconds and the minimum current to the various types of short circuit :
G

point in respect of nominal operating voltage :


50Hz 60Hz 3-phase 2-phase L-L 1-phase L-N
Voltage Factor Voltage Factor Instantaneous x 1.00 x 0.87 x 1.30
380v x 1.00 416v x 1.00 Minimum x 1.00 x 1.80 x 3.20
400v x 1.05 440v x 1.06 Sustained x 1.00 x 1.50 x 2.50
415v x 1.09 460v x 1.10 Max. sustained duration 10 sec. 5 sec. 2 sec.
440v x 1.16 480v x 1.15 All other times are unchanged
The sustained current value is constant irrespective
of voltage level
Note 3
Curves are drawn for Star (Wye) connected machines.

8
PM734B
Winding 312 / 0.8 Power Factor

RATINGS

Class - Temp Rise Cont. B - 70/50°C Cont. F - 90/50°C Cont. H - 110/50°C

50Hz Star (V) 380 400 415 440 380 400 415 440 380 400 415 440

AS
kVA 955 1005 1010 990 955 1005 1040 1105 1130 1190 1230 1240

kW 764 804 808 792 764 804 832 884 904 952 984 992

Efficiency (%) 95.8 95.8 95.9 95.9 95.8 95.8 95.9 95.9 95.6 95.7 95.7 95.7

kW Input 797 839 843 826 797 839 868 922 946 995 1028 1037

n s
60Hz Star (V) 416 440 460 480 416 440 460 480 416 440 460 480

io
kVA 1095 1170 1190 1215 1110 1170 1220 1280 1260 1335 1395 1455

kW 876 936 952 972 888 936 976 1024 1008 1068 1116 1164

Efficiency (%) 95.7 95.7 95.8

t 95.8 95.6 95.7 95.8 95.8 95.6 95.7 95.7 95.7

kW Input 915 978


lu
994 1015 929 978 1019 1069 1054 1116 1166 1216
So
DIMENSIONS
or
at
er
en
G

Barnack Road • Stamford • Lincolnshire • PE9 2NB


Tel: 00 44 (0)1780 484000 • Fax: 00 44 (0)1780 484100
Website: www.newage-avkseg.com
© 2004 Newage International Limited.
Reprinted with permission of N.I. only.
Printed in England. TD_PM734B.GB_05.04_01_GB