Minimum Requirements For Design and Engineering of Buildings
Minimum Requirements For Design and Engineering of Buildings
Minimum Requirements For Design and Engineering of Buildings
DEP 34.17.00.32-Gen.
September 1992
(DEP Circular 34/96 has been incorporated)
USED BY
COMPANIES OF THE ROYAL DUTCH/SHELL GROUP
This document is confidential. Neither the whole nor any part of this document may be disclosed to any third party without the prior written consent of Shell Internationale
Petroleum Maatschappij B.V., The Hague, the Netherlands. The copyright of this document is vested in Shell Internationale Petroleum Maatschappij B.V., The Hague,
the Netherlands. All rights reserved. Neither the whole nor any part of this document may be reproduced, stored in any retrieval system or transmitted in any form or by
any means (electronic, mechanical, reprographic, recording or otherwise) without the prior written consent of the copyright owner.
PREFACE
DEPs (Design and Engineering Practice) publications reflect the views, at the time of publication, of:
Shell Global Solutions International B.V. (Shell GSI)
and
Shell International Exploration and Production B.V. (SIEP)
and
Shell International Chemicals B.V. (SIC)
and
other Service Companies.
They are based on the experience acquired during their involvement with the design, construction, operation and
maintenance of processing units and facilities, and they are supplemented with the experience of Group Operating
companies. Where appropriate they are based on, or reference is made to, international, regional, national and industry
standards.
The objective is to set the recommended standard for good design and engineering practice applied by Group
companies operating an oil refinery, gas handling installation, chemical plant, oil and gas production facility, or any other
such facility, and thereby to achieve maximum technical and economic benefit from standardization.
The information set forth in these publications is provided to users for their consideration and decision to implement.
This is of particular importance where DEPs may not cover every requirement or diversity of condition at each locality.
The system of DEPs is expected to be sufficiently flexible to allow individual operating companies to adapt the
information set forth in DEPs to their own environment and requirements.
When Contractors or Manufacturers/Suppliers use DEPs they shall be solely responsible for the quality of work and the
attainment of the required design and engineering standards. In particular, for those requirements not specifically
covered, the Principal will expect them to follow those design and engineering practices which will achieve the same
level of integrity as reflected in the DEPs. If in doubt, the Contractor or Manufacturer/Supplier shall, without detracting
from his own responsibility, consult the Principal or its technical advisor.
The right to use DEPs is granted by Shell GSI, SIEP or SIC, in most cases under Service Agreements primarily with
companies of the Royal Dutch/Shell Group and other companies receiving technical advice and services from
Shell GSI, SIEP, SIC or another Group Service Company. Consequently, three categories of users of DEPs can be
distinguished:
1) Operating companies having a Service Agreement with Shell GSI, SIEP, SIC or other Service Company. The
use of DEPs by these operating companies is subject in all respects to the terms and conditions of the relevant
Service Agreement.
2) Other parties who are authorized to use DEPs subject to appropriate contractual arrangements (whether as part
of a Service Agreement or otherwise).
3) Contractors/subcontractors and Manufacturers/Suppliers under a contract with users referred to under 1) or 2)
which requires that tenders for projects, materials supplied or - generally - work performed on behalf of the said
users comply with the relevant standards.
Subject to any particular terms and conditions as may be set forth in specific agreements with users, Shell GSI, SIEP
and SIC disclaim any liability of whatsoever nature for any damage (including injury or death) suffered by any company
or person whomsoever as a result of or in connection with the use, application or implementation of any DEP,
combination of DEPs or any part thereof, even if it is wholly or partly caused by negligence on the part of Shell GSI,
SIEP or other Service Company. The benefit of this disclaimer shall inure in all respects to Shell GSI, SIEP, SIC and/or
any company affiliated to these companies that may issue DEPs or require the use of DEPs.
Without prejudice to any specific terms in respect of confidentiality under relevant contractual arrangements, DEPs shall
not, without the prior written consent of Shell GSI and SIEP, be disclosed by users to any company or person
whomsoever and the DEPs shall be used exclusively for the purpose for which they have been provided to the user.
They shall be returned after use, including any copies which shall only be made by users with the express prior written
consent of Shell GSI, SIEP or SIC. The copyright of DEPs vests in Shell GSI and SIEP. Users shall arrange for DEPs to
be held in safe custody and Shell GSI, SIEP or SIC may at any time require information satisfactory to them in order to
ascertain how users implement this requirement.
All administrative queries should be directed to the DEP Administrator in Shell GSI.
TABLE OF CONTENTS
1. INTRODUCTION....................................................................................................... 5
1.1 SCOPE...................................................................................................................... 5
1.2 DISTRIBUTION, INTENDED USE AND REGULATORY CONSIDERATIONS..........5
1.3 CROSS-REFERENCES............................................................................................ 6
1.4 DEFINITIONS............................................................................................................ 6
2. DESIGN DRAWINGS................................................................................................ 7
2.1 BASIC INFORMATION.............................................................................................. 7
2.2 PRELIMINARY DESIGN............................................................................................ 7
2.3 FINAL DESIGN AND ENGINEERING.......................................................................7
2.4 STRUCTURAL DESIGN............................................................................................ 8
3. DESIGN LOADS....................................................................................................... 9
3.1 DEAD LOADS............................................................................................................ 9
3.2 LIVE LOADS.............................................................................................................. 9
3.3 WIND LOAD, SNOW/SAND AND EARTHQUAKE LOADS, LOADS DURING
ERECTION, DYNAMIC LOADS AND LOAD COMBINATIONS.................................9
3.4 CRANE LOADS......................................................................................................... 9
3.5 LOADS DUE TO EQUIPMENT, ETC.......................................................................10
3.6 EXPLOSION RESISTANCE....................................................................................11
4. CLIMATIC ASPECTS, INSULATION AND NOISE.................................................13
4.1 GENERAL............................................................................................................... 13
4.2 HEATING, VENTILATION AND AIR CONDITIONING OF PLANT BUILDINGS......14
4.3 HEATING, VENTILATION AND AIR-CONDITIONING OF NON-PLANT
BUILDINGS............................................................................................................. 15
4.4 COVERED WALKWAYS AND PARKING BAYS.....................................................20
4.5 INSULATION........................................................................................................... 21
4.6 NOISE ABATEMENT/VIBRATION..........................................................................22
5. MINIMUM DIMENSIONS.........................................................................................24
5.1 OFFICE BUILDINGS............................................................................................... 24
5.2 MESS ROOMS........................................................................................................ 24
5.3 SANITARY BUILDINGS.......................................................................................... 24
5.4 WORKSHOP AND WAREHOUSE BUILDINGS......................................................24
5.5 ELECTRICAL STATIONS AND ANALYSER HOUSES...........................................24
5.6 CEILING HEIGHTS.................................................................................................25
6. BUILDING ELEMENTS/COMPONENTS................................................................26
6.1 GENERAL............................................................................................................... 26
6.2 WALLS.................................................................................................................... 27
6.3 ROOFS.................................................................................................................... 29
6.4 CEILINGS................................................................................................................ 30
6.5 FLOORS.................................................................................................................. 31
6.6 DOORS................................................................................................................... 33
6.7 WINDOWS............................................................................................................... 37
6.8 SPECIAL REQUIREMENTS FOR PLANTS HANDLING TOXIC PRODUCTS........40
6.9 STAIRCASES.......................................................................................................... 41
7. UTILITIES................................................................................................................ 42
7.1 DRAINAGE AND SEWERAGE................................................................................42
7.2 WATER SUPPLY AND RELATED PLUMBING.......................................................44
7.3 TELECOMMUNICATIONS AND INSTRUMENTATION..........................................48
7.4 ELECTRICAL........................................................................................................... 49
7.5 LIGHTING................................................................................................................ 50
7.6 INSTRUMENT AND TOOL AIR, GAS, WATER AND STEAM LINES IN
WORKSHOPS AND KITCHENS.............................................................................51
8. FIRE PROTECTION................................................................................................52
8.1 GENERAL............................................................................................................... 52
8.2 SURFACE SPREAD OF FLAME.............................................................................52
8.3 FIRE RESISTANCE................................................................................................. 52
8.4 EXTERNAL FIRE EXPOSURE................................................................................53
8.5 FIRE-FIGHTING EQUIPMENT/SYSTEMS..............................................................53
9. SECURITY............................................................................................................... 54
9.1 GENERAL............................................................................................................... 54
9.2 ENTRANCE GATES................................................................................................ 54
10. SURFACE PROTECTION.......................................................................................55
10.1 PAINTING AND COLOUR SCHEMES....................................................................55
10.2 GALVANIZING AND ZINC SPRAYING...................................................................55
11. SITE PREPARATION AND FINISHING..................................................................56
11.1 SITE PREPARATION.............................................................................................. 56
11.2 LANDSCAPING AND SITE FINISHING..................................................................56
11.3 MATERIAL STORAGE YARD.................................................................................56
12. MISCELLANEOUS.................................................................................................. 57
12.1 ROOM NUMBERS AND NAMEPLATES.................................................................57
12.2 EMBLEMS AND LETTERING..................................................................................57
12.3 PROVISIONS FOR EXTERNAL CLEANING...........................................................57
12.4 ACCESS TO UTILITY PIPING, ETC.......................................................................57
12.5 FURNITURE AND FURNISHINGS..........................................................................57
12.6 FLAGPOLES........................................................................................................... 57
13. REFERENCES........................................................................................................ 58
APPENDICES............................................................................................................................... 61
APPENDICES
APPENDIX 1 FINISHES OF FLOORS, CEILINGS, AND WALLS........................................62
APPENDIX 2 TYPICAL WINDOW DETAIL..........................................................................65
APPENDIX 3 CLIMATIC CONDITIONS FOR ROOMS IN NON-PLANT BUILDINGS..........66
1. INTRODUCTION
1.1 SCOPE
Amended per
Circular 34/96
This DEP gives the minimum general requirements for the design and engineering of all
new buildings in oil refineries, gas plants, chemical plants, onshore exploration and
production facilities and, where applicable, supply/marketing installations.
This DEP is a revision of an earlier DEP of the same number and title, dated April 1989.
Additional requirements for specific buildings are specified in the following documents:
- Analyser houses DEP 32.31.50.31-Gen.
Standard Drawing S 17.001
Standard Drawing S 17.002
1.4 DEFINITIONS
For the purpose of this DEP, the following definitions shall hold:
The Contractor is the party which carries out all or part of the design, engineering,
procurement, construction, commissioning or management of a project or operation of a
facility. The Principal may undertake all or part of the duties of the Contractor.
The Manufacturer/Supplier is the party which manufactures or supplies equipment and
services to perform the duties specified by the Contractor.
The Principal is the party which initiates the project and ultimately pays for its design and
construction. The Principal will generally specify the technical requirements. The Principal
may also include an agent or consultant authorised to act for, and on behalf of, the
Principal.
The word Shall indicates a requirement.
The word Should indicates a recommendation.
2. DESIGN DRAWINGS
Bulk store 40
For structural calculations, local codes/regulations and the actual loading situation shall be
adhered to if these are more stringent.
For garages and fire stations, the live loads shall include the maximum weight of trucks
and/or fire-fighting equipment.
3.3 WIND LOAD, SNOW/SAND AND EARTHQUAKE LOADS, LOADS DURING ERECTION,
DYNAMIC LOADS AND LOAD COMBINATIONS
See DEP 34.00.01.30-Gen.
3.4.1 General
Crane loads shall be assumed at their maximum values, including the lifting capacity as
well as the maximum horizontal loads caused by braking or acceleration, producing worst
conditions but not acting simultaneously with maximum wind forces.
3.4.2 Workshop building
Unless otherwise stated in the project specification, the following cranes shall be installed:
In the workshop building two electrically operated overhead travelling cranes shall be
installed to serve the mechanical and electrical workshops.
These overhead travelling cranes shall meet the requirements for handling the heaviest
piece or part of equipment to be serviced, e.g. tube bundles or parts of stripped rotating
equipment, etc. In any case the minimum capacity shall be:
Hoisting capacity 10 tonnes
Speed data shall be as follows:
Normal hoisting speed 6 m/min
Slow hoisting speed 0.75 m/min
Crab travelling speed 18 m/min
Crane travelling speed 18 m/min
The minimum distance between the two cranes shall be 1000 mm. This distance shall be
guaranteed by spacers fixed to the crane.
In the welding area of the mechanical workshop a separate electrically or pneumatically
operated overhead crane shall be installed.
Hoisting capacity 5 tonnes
Same speeds as above
A closed trolley system with protected power tracks shall be used for the electric power
supply of these travelling cranes. See also T-1.765.282, 'Specification for electrical
overhead travelling cranes'.
A trolley beam with a hand-operated hoist, with a capacity of 1 tonne, shall be installed
in the safety relief valve test area of the mechanical workshop.
A 2-tonne jib crane with an arm of 3000 mm shall be installed on one of the steel
columns of the mechanical workshop building. As the exact location is to be decided
later on, all columns of the building shall be designed for this additional load.
A trolley beam with a hand-operated hoist, capacity 2 tonnes, shall be provided in the
instrument workshop. The beam shall extend 1500 mm outside the building.
3.6.3 General design rules for all buildings within 500 m distance from hydrocarbon
processing plants
Buildings shall be supported by a steel or reinforced concrete frame with such structural
details that plastic deformation can occur without a total collapse.
The joints shall ensure the ductile behaviour of the completed element. The supports
shall be large enough to allow horizontal movements.
Materials with a brittle behaviour, such as masonry, shall not be used in such a way that
they have a strength function.
The buildings shall have brick infill walls and/or steel cladding or shall be constructed as
prefabricated reinforced concrete modules.
Infill wall constructions shall not have a design function for either vertical loads or
bracing.
For steel structures, structural steel bracing shall be provided in roofs and walls
Roofs and ceilings, electrical fittings etc. shall be applied such that they cannot easily
collapse during an explosion in the plant. All roofs shall be made of monolithic reinforced
concrete or galvanized steel sheeting (box rib).
Loose light-weight concrete roof slabs or asbestos cement sheeting shall not be used.
Gravel as a protection of roof finish, or loose tiles for walkways on top of the roof finish,
shall not be used.
This design approach, when combined with the design wind loadings, will result in
buildings having improved structural capacity for blast resistance.
Unless otherwise specified, all buildings in the administration area shall have no more
than a ground floor and a first floor.
All windows in outer walls of all buildings shall have laminated glass.
4. CLIMATIC ASPECTS, INSULATION AND NOISE.
4.1 GENERAL
Buildings may require climatic conditioning, i.e. heating, ventilation and/or air conditioning
(HVAC), to maintain the temperature, relative humidity and air quality within defined limits,
in order to provide reliable operation of electronic equipment and acceptable human
working conditions.
Careful attention shall be paid to the prevailing climatic conditions in various seasons, and
records of all local climatic design data like air temperature, temperature differences, saline
atmosphere, sand and dust storms, infiltration of sand in buildings, humidity, solar
influence, wind, micro-climatic variations, etc. shall be used to arrive at a satisfactory
design which ensures good conditions for equipment and personnel. In addition, the
location and orientation of the building shall be taken into account.
The meteorological data required for the design of the air conditioning shall be collected by
the Contractor if not specified by the Principal in the project specification.
For various geographical locations, climatic data such as temperatures, humidity, wind,
saline content of the atmosphere, chances of sand and dust storms, micro-climatic
variations, altitude, etc. can be found in handbooks issued by, for example, the
Meteorological Office in London.
HVAC systems are generally supplied by specialized manufacturers as package units or as
single components. Standard HVAC equipment, suitable for the prevailing conditions, shall
be applied as far as possible. Where alternative suitable refrigerants exist which are less
harmful to the environment than chlorofluorohydrocarbons (CFCs), HVAC equipment shall
be capable of satisfactory operation with such refrigerants.
Sufficient space shall be reserved for positioning and maintenance of the HVAC equipment
and ducting.
4.2 HEATING, VENTILATION AND AIR CONDITIONING OF PLANT BUILDINGS
Requirements and information regarding HVAC of plant buildings are specified in
DEP 31.76.10.10-Gen.
Plant buildings are buildings such as control buildings, field auxiliary rooms (FARs),
analyser houses, electrical substations and others (e.g. dedicated flowmetering buildings).
4.3 HEATING, VENTILATION AND AIR-CONDITIONING OF NON-PLANT BUILDINGS
4.3.1 General
The category non-plant buildings includes:
- Office buildings
- Laboratories (non-plant)
- Training centre
- Workshop
- Warehouses
- Fire-station
- Guard-houses/Gate-houses/Security building
- Residential buildings
In temperate climates, air conditioning is usually not considered for this category of
buildings unless required for the proper operation of equipment. In that case air
conditioning shall be limited to the rooms concerned.
4.3.3 Heating
Heating may be required to raise the temperature inside a building to the required level.
The dissipated heat from personnel, lighting and electronic equipment etc., shall not be
taken into account for heating capacity calculations. Heat losses through walls, floors and
roofs shall be taken into account.
The Contractor shall submit the "heating load" calculations to the Principal. The calculations
shall be based on ASHRAE Fundamentals 1989, chapter 25.
4.3.4 Cooling
Cooling may be required to lower the temperature and/or humidity inside a building to the
required level.
Cooling capacity calculations shall be based on heat generation from heat sources such as:
- personnel;
- electronic equipment;
- lighting;
- (fresh) air intake;
- solar radiation through transparent surfaces such as windows;
- heat transmission through walls, roofs/ceilings, floors, etc.
Cooling load calculations shall be based on the method of calculation in ASHRAE
Handbook Fundamentals (1989), Chapter 26.
The Contractor shall submit the "cooling load" calculations to the Prinicpal.
Condensation on air ducting, chilled water piping etc. shall be avoided under all climatic
conditions specified. Reference is made to Appendix 3.
4.3.5 Humidification
Humidification may be required to increase the relative humidity inside a building to the
required level. The Contractor shall submit the humidity calculations to the Principal.
When humidification is required, steam humidification shall be employed and the
humidifiers should be connected to the drinking water system. The water quality shall be
checked with respect to the humidifiers applied.
Precautions shall be taken to avoid excessive fouling of humidifiers.
Where ventilation systems are installed in an office, a constant supply of fresh or purified air
shall be ensured. The recommended number of air changes per hour (ACH) in various
areas are as follows:
Area ACH
Control systems shall normally operate in automatic mode but manual operation shall be
possible.
HVAC alarms shall be individually displayed on local HVAC panels. Common HVAC alarm
signals generated by the HVAC control system and to be displayed on the DCS screen in
the main control room shall be routed either via potential-free contacts and interface boxes
or via software links. First failure alarm detection is not required. "Mimic" type alarm display
panels (ADP) are not required.
Control signals coming from a HVAC control system cabinet and going to a HVAC motor
control centre (power) cabinet shall pass via an interface box. The HVAC control/alarm
cabinet and the motor control centre (power) cabinet shall be physically separated. For
central air handling units, both cabinets should be located in the HVAC machine room.
4.3.9 Logging
For rooms in which vital electronic equipment is installed, permanent long-term monitoring
of temperature and relative humidity is required if specified by the Principal.
4.6.1 Reverberation
The reverberation time (for definition see ISO 31/VII) in empty rooms, but with finished
floors (in accordance with Appendix 1), shall not exceed the following values:
Office rooms, training rooms, laboratories, 1 second
control rooms, instrument and electrial shops:
250 72
500 70
1000 67
2000 58
NOTE: The standard tapping machine consists of 5 hammers of 500 gram each, falling from a height of 40
mm, 10 times per second.
NOTE: Noise that is not related to equipment but is produced by users of the various areas need not be
considered.
If noise has an impulsive and/or tonal character, the above limits shall be taken 5 dB(A)
more stringent.
For electrical stations, see drawing T-1.707.055. For analyser houses, see Standard
Drawings S 17.001 and S 17.002.
For certain applications container-size modules may be utilized if approved by the Principal.
This type of building, consisting of one or more interconnecting modules, shall comply with
the general design rules under (3.6.3).
5.6 CEILING HEIGHTS
The following minimum clear dimensions shall apply:
Height
All height dimensions are to underside of ceiling or beams, whichever is the lower.
Notes: 1. This height shall further depend on dimensions of equipment and handling space required.
2. The free space required above the (high voltage) switchgear also depends on the type of short
circuit relief devices on top of the switchgear.
6. BUILDING ELEMENTS/COMPONENTS
6.1 GENERAL
This chapter gives general information on elements and components for all buildings.
However, requirements for certain buildings are specified in more detail owing to the fact
that these requirements are not covered in separate documents such as the DEPs,
drawings, etc. mentioned in (1).
Materials containing asbestos shall not be used.
6.2 WALLS
6.4.1 Materials
Moisture-resistant materials shall be used for the ceilings of all toilet rooms, bathing
facilities, kitchens and other areas exposed to moisture and humidity. All materials to be
used for ceilings shall consist of non-combustible materials or fire-rated materials in
accordance with the applicable codes.
6.5.1 General
Floors shall be made of either:
Mass concrete supported directly on soil with an intervening vapour barrier (applicable
to ground floors only if soil conditions permit), or
reinforced concrete, or
prefabricated concrete slabs supported by concrete or steel beams, but only when no
people are accommodated underneath.
Where requirements warrant it, epoxy-based flooring could be considered. However,
alternative materials shall be used only with the Principal's approval.
All floors exposed to weather, liquid spillage or washing-down operations shall be laid with
adequate falls, e.g. a minimum of 1 in 100 to gullies or channels placed in such a way that
quick and effective drainage is possible. The falls shall be such that, allowing for normal
tolerances, there is no possibility of ponding, or water being trapped by stanchions or
footings. Drains from upper floors shall be routed in such a way that blockages are unlikely
and shall have adequate inspection covers so that, if blockages do occur, they can be
cleared easily.
The finished floor level shall be at least 150 mm above the pathway around the building.
6.5.2 Workshop
In the workshop floor, provisions shall be made to allow for cable-laying and machine
foundations.
The floor shall be constructed as follows:
A reinforced concrete construction floor to base all machine foundations.
A layer of sand about 200 mm thick to accommodate cables and piping.
A thin reinforced concrete floor, strong enough to carry all the traffic in the workshop,
which can be easily removed for relocation of equipment without disturbing the lower
construction floor. This top floor shall be level with the surrounding floors
6.6.1 General
In external walls, doors and frames shall be made of galvanized steel.
In exceptional cases, solid hardwood doors can be used, treated with a fire retardant.
NOTE: Aluminium shall not be used, because this material is too weak to hold the door or window pane in
place during an explosion.
Plastic shall not be used because of the development of dangerous gases in the case of fire.
Steel doors and frames shall also be used for internal doors in electrical stations,
basements of control buildings, bottle wash and CFR engine rooms of laboratories,
consumable stores, instrument, electrical and mechanical workshops.
Steel doors shall be double-sheeted and insulated.
In all other internal walls where doors are required, pressed steel or hardwood door
frames, solid-cored, with flush-veneered wooden doors shall be used.
All main entrances and all other entrances to buildings which are frequently used shall
have airlocks with adequately separated doors to control the indoor temperature and to
prevent sand accumulation in the case of desert conditions.
Where visibility is required, doors shall be glazed. The clear opening for glazing shall not
exceed 0.25 m2 per door. Outside doors in administration buildings may have a clear
opening for glazing not exceeding 1.0 m2 per door.
External doors shall always open outwards and in the direction of the escape route.
Revolving doors and sliding doors are not allowed for emergency exits.
If the dimensions of doors are unpractical for easy handling, a wicket door shall be
provided for frequent passage of persons, i.e. in workshop doors, the door for the
receiving bay of the store and the equipment doors of electrical stations and control
buildings.
Weather stripping to maintain the climate inside the building and to exclude all dust and
moisture infiltration. Sliding doors shall be designed in such a way that an accumulation
of dust and sand does not influence the proper functioning of the doors. The tracks shall
be easily cleanable.
The external doors of the substation shall be made tight-fitting by means of heavy-duty
PVC seals, so that no dust, gas or other foreign matter can enter the building.
The sealing of the analyser house doors, internal and external, shall be made tight-fitting
by means of heavy-duty PVC seals.
In corridors of office buildings self-closing smoke doors shall be installed at maximum
30 m intervals. These doors shall also be used for separating staircases from corridors.
Mat wells shall be installed inside all entrances of the following buildings:
Office building
Canteen
First-aid building
Laboratory
Control building
Training centre
Instrument workshop
Electrical workshop
The door frame stanchions of the sliding door between work-shop and covered area
shall not be connected by a top rail in order to allow free movement of the overhead
travelling crane with load. If required by climatic conditions, a crane door shall be
additionally installed in the above wall.
In non-freezing areas, fire-fighting garages should not have doors in front of the fire-
fighting vehicles. If doors are required for climatic reasons they shall be made of light
material so that the fire truck can break them open in case the doors are blocked during
an emergency.
Doors may be electrically operated but shall have a facility for quick disconnection of the
electric driver after which easy manual opening shall be possible (balanced doors).
Internal doors to toilets and showers shall have a 100 mm free opening from the finished
floor.
Doors in corridors of office buildings should not be located directly opposite each other.
Doors should be installed preferably in niches, in order to create more room in the
corridor near the entrance of office rooms.
6.6.2 Dimensions
Required minimum dimensions shall be as shown below. All these dimensions shall be
increased if required for installation of equipment in the buildings.
For firestations, see DEP 80.47.10.33-Gen.
MINIMUM CLEAR OPENINGS OF INTERNAL WIDTH X HEIGHT
DOORS (mm)
First-aid facsilities, for passage of stretcher 1500 x 2100
only
Instrument shop 1400 x 2100
Between electrical shop and mechanical shop 2000 x 2100
Basement of control building between 1800 x 2500
instrument and electrical room
Between warehouse and bulk store 1800 x 3000
One door in each laboratory room large enough for the
necessary equipment
(e.g. fume cupboard)
to pass through
Toilets and showers 600 x 2100
Other doors 900 x 2100
6.6.4 Fittings
Locks, handles, handle plates, barrel bolts, panic bolts, door stops, kick plates, and
automatic door closers shall be provided as necessary. For doors to air locks,
airconditioned rooms, pressurized rooms, main entrances to sanitary blocks, and for all
fire-check doors, automatic door closers or self-closing doors shall be installed. For
other external doors, door catches shall be provided.
All fittings of the same kind shall be of one make and type. Fittings shall be in anodized
aluminium and shall be fixed with non-corroding screws.
Fittings for industrial buildings shall be of steel and shall have a corrosion-resistant
finish.
The single doors of analyser houses, electrical substations and the active leaf of the
double door of electrical substations shall be provided with a single panic bolt. As only
the single doors shall be used for normal passage, the panic bolts of these doors shall
be operated by means of a cylinder lock with key and locking knob. These locks shall be
keyed to a master key system.
In each refinery one separate locking system for all electrical substations and one for all
analyser houses shall be provided. For extensions to existing refineries, door-locking
facilities shall exactly match those of the existing buildings.
Both leaves of the double doors shall be provided with a vertical grip handle on the
inside.
Doors to toilets and showers shall be provided with an indicator bolt only. On the inside
of these doors coat hooks shall be fitted, one on each toilet door and three on each
shower door. These coat hooks can also be mounted against the wall on a strip of
hardwood.
6.6.5 Finish
Doors, windows, frames and fittings made out of steel shall be hot-dip galvanized or
zinc-sprayed. See DEP 34.28.00.31-Gen.
6.7 WINDOWS
6.7.1 General
Windows, including their frames in external walls, shall be made of galvanized steel.
Other materials are not strong enough to keep the window pane in place during an
explosion.
Movable parts of external windows shall open outwards.
Where insect screens are required, they shall be easily removable and rustproof.
Electrical substations shall not be provided with any windows or other light openings.
The upper part of external doors of the analyser house shall be glazed. The maximum
pane size shall be 0.25 m2.
The underside of all windows in workshop and warehouse buildings shall be at least
1200 mm above finished floor level. The underside of all other windows, where possible,
shall be min. 1000 mm above finished floor level.
External window sills shall be set weathered, and project beyond the external wall face.
Internal sills shall be made of tiles, or similar material to suit the type of room concerned.
To prevent accumulation of dirt, these internal sills shall be set sloping inwards in control
buildings, wash and locker rooms and toilets.
All exterior windows in heated and/or air-conditioned buildings shall be designed with
weather-stripping as described for doors.
For fittings of windows, see (6.6.4).
Bracings and rainwater down-pipes shall not obstruct the windows in steel-framed
buildings.
2. When these units are to be exposed to low pressure (e.g. during air transport or if mounted at a
level above 800 m) the manufacturer of these units shall be informed and the necessary
precautions taken.
3. If considerable protection against the spread of fire is required, as well as protection during an
explosion, wired laminated glass shall be applied, e.g. in analyser houses. This glass shall consist
of one layer of wired glass, 6 mm thick and one layer of float glass, 3 mm thick with an interlayer
of PVB of 1.9 mm.
6.9.1 General
All stairs shall be designed and located to meet the local fire authority requirements for
means of escape in the case of fire. The proposed location shall be approved by the
Principal.
All doors shall open in the direction of the escape route and be positioned so as not to
block any stairway.
Signs shall be supplied and erected to indicate clearly the route of escape in an
emergency.
Hand-rails shall be provided on both sides of the stairs, except when the slope of stair is
less than 30° and the stair is not higher than 2000 mm, in which case hand-rails are not
required.
Main internal staircases of administration buildings, control buildings, laboratories, etc.,
along with their related lobbies and landings, shall be enclosed by suitable fire-resistant
materials (see 8.1.3). Winding treads shall not be used for such staircases.
Where equipment is located on top of a roof, the installation of a steel staircase or cage
ladder will depend on the maintenance/inspection/operating requirements of the equipment,
subject to the approval of the Principal. For steel staircases and ladders, see
DEP 34.28.00.31-Gen.
The concrete platforms in front of equipment doors shall be calculated to be able to bear
the equipment that will be transported through these doors.
If in an electrical substation a basement is required, two manholes of 600 x 800 mm
covered with 25 mm deep galvanized grating and located in opposite corners of the building
shall be provided in the ground floor, providing access and natural ventilation to the
basement.
A fixed vertical steel ladder leading to each manhole shall be provided in the basement.
A vertical steel handrail 38 mm diameter shall be fixed to the wall next to each manhole.
6.9.2 Dimensions
Minimum width between handrails 1250 mm.
Width and length of landings same as width of stair.
Minimum head room 2100 mm.
Height of handrail above front of tread 900 mm.
Height of handrail above landing 1100 mm.
Doorway to staircase, min. width 1250 mm.
No stairway shall exceed 16 rises in any one flight, but if more are necessary a landing
shall be provided.
The maximum slope shall be 3:4.
For risers and goings the following shall apply:
Risers (R) : in. 160 mm, max. 190 mm.
Goings (G) : in. 250 mm, max. 310 mm.
and further:
(R x G) min. 48 000 mm2, otherwise too dangerous to descend.
(R x G) max. 55 000 mm2, otherwise too tiring to ascend.
7. UTILITIES
7.1.1 General
Drainage systems outside the area of 1 m from the outside of the buildings, shall comply
with DEP 34.14.20.31-Gen. Within 1 m of the outside of the building, the following is
applicable:
A complete drainage system including floor drains and sewage piping from sanitary fitments
shall be provided. The design shall be adequate to cover future extensions of various
buildings.
Drainage lines shall be designed to provide self-cleansing velocities and easy access for
clearing of obstructions. Such access points within buildings shall have screwed or bolted
air-tight covers. Interconnecting pits outside the buildings shall be provided with cast-iron
removable covers.
In areas likely to be affected by frost, the external drain lines shall be laid at frost-free level.
Suitable intercepting chambers and vents shall be provided where required, to prevent foul
liquids or gases from flowing back into the buildings. Special attention shall be paid to
having these vents at a suitable distance from air-conditioning inlet openings.
Particular attention should be paid to the provision of seals to prevent any possible ingress
of process gas or hydrocarbon liquids.
A grease trap shall be provided for the waste water from the canteen building and mess
room. The grease traps shall be located such that the temperature does not exceed 37 °C,
as this will inhibit the grease dispersing agent.
The basements shall be provided with an emergency drain pit of 600 x 600 mm, depth
approximately 250 mm, with cover. This drain pit shall be located near the access opening
to the basement, to facilitate easy connecting of a hose from a movable emergency pump
outside the building.
Rainwater downpipes and other drainpipes shall not pass through electrical equipment
rooms or basements.
7.1.6 Testing
Prior to any back-filling, all underground drain pipes and pits shall be water-tested in
accordance with DEP 41.14.20.31-Gen.
7.2 WATER SUPPLY AND RELATED PLUMBING
For processing plants, 1 WC and 1 handwash basin shall be provided for every 10
persons on day shift. In addition, 1 urinal shall be provided for every 10 men.
Each toilet area in industrial and utility buildings, including canteens, shall have a tap
with hose connection and floor drain.
NOTE: In certain Middle East and Far East areas, local religious customs and/or regulations shall be followed
with respect to the location of WC suites and the like, including the installation of foot washing
facilities.
7.2.8 Fitments
All fitments of the same kind shall be of one uniform make and type.
7.2.8.2 Squatting-type WC
This, where required by local custom, shall consist of white vitreous fire-clay or stainless
steel washdown closet, with 'S' or 'P' trap, vertical inlet, flushing rim, integral foot treads,
and necessary flushing facilities of the same capacity as in (7.2.8.1). A pair of hand grips
and a toilet roll holder shall be provided. An extra water tap shall be installed at a
convenient location.
7.2.8.3 Urinal
This shall consist of a stainless steel or white-glazed vitreous china wall-type urinal with
flushing rim, complete with flushing facilities and trap. Where urinals are installed in multiple
units, each unit shall be separated by partitions. Flushing facilities shall be capable of
discharging five litres of water per flush per urinal.
For multiple units of urinals automatic flushing facilities may be provided, maintaining the
above capacity. In areas where smoking is allowed, an ash-tray shall be provided near
each urinal.
7.2.8.4 Hand-wash basins and foot-wash basins
Material shall be white-glazed vitreous china or stainless steel. Minimum dimensions shall
be 550 x 400 mm. Basins shall be provided with chromium-plated, easy-clean, screw-down
type pillar taps or, if hot water is also provided, mixing valves shall be installed. Waste
water shall be led through a sealed trap to the waste water system.
An overflow slot shall be provided
The drain should be provided with a plug and chain.
Each hand wash basin shall be provided with a mirror (minimum size 550 x 400 mm).
7.2.8.5 Sinks
Material shall be vitreous white-glazed fire-clay, or, if with draining boards, stainless steel.
For cold water, chromium-plated bib taps shall be installed. Where hot water facilities are
provided, a chromium-plated mixing valve with swivel spout shall be installed. Waste water
fittings shall be as in (7.2.8.4). The sink in the cleaners' cupboard shall be provided with a
chromium-plated bucket grating with hinges. Taps shall be installed at such a height as to
facilitate easy filling of buckets.
7.2.8.7 Showers
Shower basins shall be recessed in the floor, made of stainless steel and be provided with
a seal trap connected to the waste water drainage system. The shower rose shall be
connected to a hot and cold water mixing valve. Each shower shall be provided with a seat
and a recessed soap holder.
8.1 GENERAL
For explanations of terms used and tests mentioned below, see BS 476.
Where ventilation or other ducts or piping/cabling pass through roofs, walls or floors, the
surrounding gaps shall be closed air- and water-tight by using materials of the same smoke
and fire resistance of that particular element allowing essential thermal movements.
It shall be impossible for smoke or fire to travel from one floor to the other through ducting,
etc.
The layout of the building shall be such that the maximum travel distance from any point of
a floor in the building to the nearest exit of that floor shall be 25 m.
Insulation materials used inside and outside buildings shall be mineral wool blankets with
galvanized wire netting and with no flammable materials attached to them (used in wall
cladding, ceilings, partition walls, etc.). As an exception to this, translucent sheeting and
build-up bituminous roofing felt, glass fibre based, are allowed but should, where possible,
be avoided.
Staircases shall be separated from corridors by automatic closing doors. These doors shall
be smoke-tight.
All materials on the outside of the building shall be of a non-combustible type.
In order to prevent smoke or fire travelling from one room to another, separation walls shall
extend to the underside of the above laying floor or roof (or supporting beams of roof/floor
whichever is applicable).
To prevent the spreading of smoke and fire through air duct systems, the latter shall
consists of separate systems. Certain rooms may in this respect be combined. The
guidelines of NFPA 90A shall be followed and approval of the Principal shall be obtained.
Warehouses 1 1
Analyser buildings, 2 -
substations
In addition, floors in elevated buildings shall have a minimum period of smoke and fire
resistance of 1 hour.
Raised floors (computer floors) shall have a minimum period of smoke and fire-resistance
of ½ hour.
Walls of heater/boiler rooms shall have a minimum period of smoke and fire resistance of 1
hour.
9.1 GENERAL
Overall site security shall be subject to a separate security survey which is outside the
scope of this DEP.
Specific requirements resulting from this survey affecting the building(s) shall be separately
specified by the Principal.
12.6 FLAGPOLES
Three identical flagpoles shall be located in the most prominent position near the entrance
to the office area. Each flagpole shall be designed, along with its fixtures and foundations,
to carry a flag of 2500 x 4000 mm.
The effective height shall be 6500 mm and the pole shall be assembled from tapering
tubular steel sections, hot-dip galvanized inside and outside. The pole shall be hinged at
the footing so that it can be lowered to a horizontal position.
13. REFERENCES
Amended per
Circular 34/96
SHELL STANDARDS
STANDARD DRAWINGS
AMERICAN STANDARDS
ASHREA Handbook:
"Fundamentals" ASHRAE 1989
"HVAC Systems and Applications" ASHRAE 1987
"Equipment" ASHRAE 1988
"HVAC Applications" ASHRAE 1991
Issued by:
American Society of Heating, Refrigeration
and Air-Conditioning Engineers Incorporated,
1971 Tullie Circle NE, Atlanta, GA 30329, USA.
Issued by:
National Fire Protection Association
470 Atlantic Avenue,
Boston, Massachusetts, MA 02210, USA.
BRITISH STANDARD
Issued by:
British Standards Institution,
2 Park Street, London
England.
INTERNATIONAL STANDARDS
Issued by:
Central Office IEC (Sales Department)
3 rue de Varembé, CH-1211 Geneve 20,
Switzerland
Issued by:
International Organization for Standardization
PO Box 56, CH-1211 Geneve 20, Switzerland
APPENDICES
AREA FINISHES
Toilets/showers X X X X
Kitchen/pantry X X X X
Mech. training shop X X X X
El./instr. training X X X X
shop
Training laboratory X X X
Basement X X X
Canteen building/
Mess room
Sitting area X X X X X
Area around counter X X X
Kitchen/pantry X X X
Stores X X X
Where applicable other specific rooms as for Office building/Training centre above
Laboratory and
Plant Laboratory
Rooms in general X X X
Offices X X X X X
Corridors X X X X
Bottle washing X X X
Glass/chemical X X X
stores
CFR Engine room X X X
Where applicable other specific rooms as for Office building/Training centre above
First aid/Fire
brigade building
Doctors room X X X X X
First aid nurse X X X
Laboratory X X X
Waiting room X X X
Garage X X X
Stores fire-fighting X X X
Where applicable other specific rooms as for Office building/Training centre above
Gatehouse
Guards room X X X
Where applicable other specific rooms as for Office building/Training centre above
APPENDIX 1-2 FINISHES (cont'd)
AREA FINISHES
Control room X X X X X
Offices X X X X X
Computer room X X X
Laboratory X X X
Instr. aux. X X X
basement/room
Computer basement X X X
Electr. equipm. room X X X X
Battery room X X X X
Air-cond. machine X X X
room
Corridors, airlocks X X X
Locker room/toilets X X X X
Washroom X X X X
Analyser house
Analyser room X (acid resistant) X X
Sample area X X X X
Switchhouse,
substation
Switch room X X X X X
Workshops
Mechanical X X X X X
workshop
Covered area X X X X X
Electrical workshop X X X X X
Instrument workshop X X X X
(air conditioned)
Instrument workshop X X X X
Tool room X X X X
Offices X X X X X
Locker room X X X X
Washroom X X X X X
Toilets X X X X
Cleaner's cupboard X X X
Stores
Consumables store X X X X X
Bulk store X X X X
Storekeeper's office X X X X X
Covered walkways X X
LEGEND FOR APPENDIX 1.
F = Floor finishes:
Note: In order to facilitate easy maintenance of floors a minimum of different floor finishes shall be
used in one building. The use of locally available material shall be considered.
F1 = Vitreous clay tiles, min. 100 x 100 mm, with ditto skirting 100 mm high. For stairs special tiles shall be
used to prevent slippage. In showers non-slip tiles to be used. Stair treads to be fitted with non-slip
nosing.
F2 = PVC tiles with PVC skirting stair treads to be fitted with PVC nosing.
F3 = Linoleum with hardwood plinth.
F4 = Wall-to-wall carpets, if there is no chance that carpets will be damaged by oily shoes.
F5 = Steel-trowel finished green concrete with a carborundum surface finish (2.5 kg/m 2) and a 50 mm high
sand cement skirting.
F6 = Steel-trowel finished green concrete with a 50 mm high sand cement skirting and a dustproof epoxy-
resin based sealant (two layers) total min. dry film thickness 200-250 m.
F7 = Cavity floor, top finished with F3 or F4 in tiles of 600 x 600 mm. See also DEP 34.17.10.30-Gen.
C = Ceiling finishes:
Note: Ceiling materials, including the entire suspension and the fixings, shall be non-combustible.
C1 = Suspended prefabricated acoustic panels.
C2 = Suspended, plastered and painted.
C3 = Plastered and painted.
C4 = Fair-faced and painted (ceiling will be formed by underside of floor or roof construction).
C5 = Lowered egg-crate diffusing panels of aluminium. Light fittings without reflecting assemblies above,
installed in lines against concrete ceiling. Concrete ceiling to be lined with white acoustic tiles. For
computerised control buildings, a different ceiling system may be necessary to prevent glare on the
monitor screens. This shall be agreed with the Principal.
Note: In mess room, tea pantry, analyser room, battery room, only tiling above and next to sink
and sideboard, about 450 mm high and wide.
Outer walls:
Where painting of wall surface consisting of concrete or rendering work is specified, two or more coats of fungus-
resistant cement-based washable distemper shall be applied after the necessary surface treatment.
APPENDIX 2 TYPICAL WINDOW DETAIL
APPENDIX 3 CLIMATIC CONDITIONS FOR ROOMS IN NON-PLANT BUILDINGS
NOTES: (1) Clean means: Generation of fouling (polluting) substances is not expected.
Foul means: Generation of fouling (polluting) substances may take place.
(2) ac/h: air change per hour.
(3) Efficiency ASHRAE dust spot test, according to ASHRAE Standard 52-76.
(4) Separate air recirculation system is required to cope with spread of smoke in case of fire.
(5) If a raised floor is available, from the bottom.
(6) User to specify, but it is likely that ventilation rates will be dictated by the extract requirements of equipment.
(7) Ventilation rates according to guidelines ASHRAE standard HVAC.
(8) (Over)pressure control is not required.
(9) Minimum temperature in principle holds for heating capacity calculation (at minimum outdoor temperature).
Maximum temperature in principle holds for cooling capacity calculation (at maximum outdoor temperature).
(10) From top and bottom.