D-Pro Power Meter 8080 Series
D-Pro Power Meter 8080 Series
D-Pro Power Meter 8080 Series
8080 Series
D-Pro Power Meter 8080 Series
SPECIFICATION
Neutral current 1%
Frequency 0.05%
Input voltage
Voltage range (line to line) 8 500V Maximum overload 750V
Voltage range (line to neutral) 5 290V Input impedance 200K
Input current
Current range 5A or 1A Input burden 0.1VA
Maximum overload 6A, continuous, 50A 5 sec. Isolation Each phase, 600V
15A, continuous, 250A 1 sec. (Option) Starting current 1% F.S.
Power supply
Nominal voltage AC 110V/220V 15%, 50/60HZ Burden (AC) 5VA, (DC) 5W
or DC 110V, 24V 10%
Display
Type High-brightness red LED Digital format 3 rows of 4 digits
Digital height 0.4 , 10.2mm Digits for Wh, Varh, VAh 8 digits (two rows)
Analog output(Option)
Output DC 4 20mA (0 500 ) Output points Max. 2 points, programmable
or DC 1 5V (1K DC) Output accuracy 0.5% RO.
Communication(Option)
Interface RS485 Address range 1 255 programmable
Protocol MODBUS, RTU framing Data format N.8.1/N.8.2/O.8.1/E.8.1 pro.
Baud rate 1200 38400 programmable Number of meter up to 32 on standard RS485
General
Dielectric strength IEC 688, AC 2.3KV 1 minute Storage temperature -10 70°C
between Input/Output/Power Temperature coefficient 100 PPM/°C
AC 2.8KV 1 minute between all terminal/ground Max. humidity 95%
Operating temperature 0 60°C
Electromagnetic compatibility
Withstanding impulse voltage IEC 1000-4-5 Electromagnetic fields immunity IEC 1000-4-3
Electrical transient in burst IEC 1000-4-4 Wave damping IEC 255-4
Electrostatic discharge IEC 1000-4-2
8080
Model
Input current
1: 1A
5: 5A
O: Option
RS485 output
Y: Yes
N: No
Harmonic
Y: Yes
N: No
Panel Cut-Out
D-Pro Power Meter 8080 Series
CONNECTION
RS485 Output
Relay Contacts
Output
Analog Output