Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Am048kn4dch Aa

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

19/10/2020 1

Submittal AM048KN4DCH/AA 360 CST (Circle) Latin America

Job Name Location


Purchaser Engineer
Submitted to Reference Approval Construction

Specifications
Model AM048KN4DCH/AA
Features Type
360 CST (Circle)

Power Supply (Indoor Unit) [Φ, #, V, Hz] 1,2,208-230,60


Capacity Cooling [kW] 14.07

Specifications
Cooling [Btu/h] 48,000
Heating [kW] 15.83
Heating [Btu/h] 54,000 • The indoor unit shall be compatible with Samsung DVM S and DVM Eco
Current Input (Nominal) Cooling 1 [A] 0.75
systems (AM****X*****/**).
Heating 2 [A] 0.75
• The indoor unit shall be a round ceiling cassette with 360°, even air
System Mode HP/HR distribution
Power Input (Nominal) Cooling 1 [W] 91.00
Heating 2 [W] 91.00
• Auto-restart after power loss
Fan Type Turbo Fan
• The indoor unit shall have a removable EEPROM that stores system
Motor (Output) [W] 97 x 1 programming information, unit name, and other data
Air Flow Rate (High / Mid / Low) [CFM] 1112/953/848
Air Flow Rate (High / Mid / Low) [CMM] 31.50/27.00/24.00 • All indoor unit addressing and option settings shall be done digitally; the
indoor unit does not contain rotary dials or setting switches.
Air Flow Rate (High/Mid/Low) [L/S] 525.00/450.00/400.00
External Static Pressure (Min / Std / Max) [in H20] - • Electro-static, washable, pleated filter as standard (included with fascia
External Static Pressure (Min / Std / Max) [mmAq] - panel).
External Static Pressure (Min / Std / Max) [Pa] -
• Built in condensate pump with maximum 29" lift from the bottom of the
Piping Connections Liquid Pipe (Φ, mm) 9.52
unit, check valve, and float switch that disables indoor unit during overflow
Liquid Pipe (Φ, inch) 3/8" detection
Gas Pipe (Φ, mm) 15.88
Gas Pipe (Φ, inch) 5/8" • Knock-out for outside air capability (with booster fan connection)
Drain Pipe (Φ,mm) VP25 (OD 32,ID 25)
• Fascia panel shall have LED indicator lights and an infrared receiver
Field Wiring Power Source Wire AWG 14
Transmission Cable 2 X 16 AWG SHIELDED • The indoor unit shall have two (2) fascia panel types:
Refrigerant Type R410A 1. Ceiling Type for installation applications where a ceiling textile is
Control Method
present (ex. tile ceiling,
EEV INCLUDED
gypsum). The Ceiling Type fascia panel shall be square in shape.
Sound Sound Pressure 44.0/42.0/39.0 2. Open Type for installation applications where a ceiling textile is not
Sound Power - present (ex. open
External Dimension (Indoor Unit) Net Weight(kg) 24.00 ceiling). The Open Type fascia panel shall be circular in shape.
Shipping Weight (kg) 29.00
• The indoor unit shall not have air louvers or blades allowing full airflow
Net Dimensions (WxHxD) (mm) 947 x 365 x 947 without restriction. Air direction control shall be achieved by creating a low
Shipping Dimensions (WxHxD) (mm) 990 x 414 x 990 pressure area near air outlet causing discharge air to change direction angle.
Panel Size Panel model PC4NUNMUN
Panel Net Weight (kg) • Fixed or auto-swing air direction shall be possible with wireless, touch, or
2.70
premium wired controller (10° ~ 60° angle)
Shipping Weight (kg) 5.30 • Independent air distribution control shall be possible with wireless or
Net Dimensions (WxHxD) (mm) 1050 x 94 x 1050 premium wired controller (three directions, 10° ~ 60° angle)
Shipping Dimensions (WxHxD) (mm) 1093 x 85 x 1083
Additional Accessories Drain Pump Construction
-
The indoor unit shall be have a galvanized steel frame with HIPS chassis and
Drain Pump Max. Lifting Height/Displacement - fascia panel certified to UL94 V0.
Air Filter Removable / Washable Heat Exchanger
The indoor unit heat exchanger shall be mechanically bonded aluminum fin
* Nominal cooling capacities are based on: Indoor temperature: 80 ⁰F DB, 67⁰F WB. Outdoor temperature: 95⁰F DB, 75⁰F WB.
to copper tube
* Nominal heating capacities are based on: Indoor temperature: 70 ⁰F DB, 60⁰F WB. Outdoor temperature: 47⁰F DB, 43⁰F WB.
Controls

English 1

Samsung maintains a policy of ongoing development, specifications are subject to change without notice.
19/10/2020 2

Submittal AM048KN4DCH/AA 360 CST (Circle) Latin America

Specifications

English 2

Samsung maintains a policy of ongoing development, specifications are subject to change without notice.