AM072BXVGFHAA Submital DVM+S2 230V HP 05232022A

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Page 1 of 2

SUBMITTAL AM072BXVGFH/AA
Samsung, DVM S2 Series, Heat Pump Condensing Unit

Job Name Location


Purchaser Engineer
Submitted to Reference Approval Construction
Unit Designation Schedule #
System Specifications
US Ton (nominal) 6
1
Nominal / Rated Cooling 72,000 / 69,000
Capacity (Btu/h)
Nominal / Rated Heating 81,000 / 77,000
Performance
EER Ducted / Mixed / Non-Ducted 11.50 / 12.52 / 13.55
IEER Ducted / Mixed / Non-Ducted 24.20 / 29.40 / 34.60
High Heat COP Ducted / Mixed / Non-Ducted 3.80 / 3.95 / 4.11

Voltage (ø/V/Hz) 3 / 208-230 / 60


Maximum Circuit Breaker (MCCB/ELB/ELCB) 35
Power
Minimum Circuit Ampacity (MCA) 28.0 Compatibility
SCCR kA 5 DVM S indoor units (AM****N****/AA, ACL-***NN), AHU Kits (MXD-K***AN), Universal
Communication Kits (MCM-D211UN), and Hydro Units (AM****NB***/AA).
Total Capacity (%) 50 - 184% Of outdoor unit capacity ² Construction
Indoor Units
Maximum Indoor Unit Quantity 12 The unit shall be galvanized steel with a baked on powder coated finish.
Refrigerant System
Type X Qty. Inverter Scroll X 1 The compressor shall be hermetically sealed, inverter driven, direct flash injected, DC scroll type
Compressor RLA (A) 14.3 with soft-start capability manufactured by Samsung. Flash injected compressors provide
advanced low ambient heating performance. The compressor shall feature an asymmetrical scroll
Compressor Modulation Range 9 - 100%
design.
Refrigerant R410A Factory Charge (lbs.) 13.7 The system shall have subcooling devices to maintain capacity at extreme system refrigerant pipe
lengths and to minimize refrigerant noise.
Pipe Connections Liquid X Suction (inches) 3/8 X 3/4
Heat Exchanger
Max. Length - ODU to Farthest IDU (feet) 656 (722 equivalent) The heat exchanger shall be mechanically bonded fin to copper tube. The aluminum fins of the
heat exchanger shall have a protective coating.
Refrigerant Pipe Max. Vertical ODU to IDU (feet) 4 361
Salt spray test method: ASTM-B117-18 - The heat exchanger showed no unusual rust or
Limitations 3 Separation Highest/Lowest IDU (feet) 164 corrosion development to 3,000 hours.
Max. Total Refrigerant Pipe Length (feet) 3,280
The heat exchanger shall consist of two separate circuits to enhance the heat pump defrost cycle.
The unit shall use the entire coil initially for the defrost cycle. To resume heating faster in extreme
Type X Qty. Propeller X 1
Fan conditions, the upper section shall return to heating operation while the lower section continues to
Output (CFM) 5,580 defrost.
Type DC Active Artificial Intelligence
Condenser Fan
Motor Output (W) 630 X 1 The outdoor unit shall feature Active Artificial Intelligence (AI) shall monitor environmental and
system operational data and use Deep Neural Network algorithms to provide optimal system
FLA (A) 4.6 performance and reliability.
Max. External Static Pressure (in. WC) 0.43 Active Artificial Intelligence (AI) shall be used to optimize high pressure control, low pressure
control, defrost cycle activation and operation, and low refrigerant detection.
WXHXD Inches 36 5/8 X 66 3/4 X 30 1/8
Dimensions Weight lbs. 383.6 The outdoor unit shall use Active Artificial Intelligence (AI) to monitor system refrigerant volume
in real-time while in cooling mode to detect possible leaks or low refrigerant charge and
Shipping Weight lbs. 414.5 provide an error code before system shutdown (conditions apply).

Sound Level dB (A) Max. 54 Controls


The outdoor unit shall have a removable EEPROM that stores unit serial number, startup
Operating Cooling 5 °F (°C) 5 -122 (-15 - 50) information, system settings, system tag/name, and other information.
Temperatures Heating °F (°C) -22 - 75 (-30 - 24) Control wiring shall be 16 AWG X 2 shielded wire.
Other Features
Safety Certifications ETL & ETLc
Inverter PCB cooling shall be done with liquid refrigerant and air to maintain optimal and safe
Intelligent logic to ensure proper operation within unit design limitations and operating temperatures.
operational parameters. The system shall feature advanced oil recovery cycle logic (maximum duration in cool mode: 3
High pressure sensor, low pressure sensor, over-voltage protection, compressor minutes, maximum duration in heat mode: 6 minutes, defrost cycles lasting over 3 minutes are
Protection Devices considered oil recovery cycles). Oil recovery operation shall not interrupt heating or cooling
over- current protection, current transformer, fan motor voltage protection, fan motor operation.
thermal protection, overheat protection, phase detection protection, high voltage
The outdoor unit shall feature optional night quiet modes to reduce outdoor unit sound (4 levels)
fuses
with automatic activation or manual activation (with MIM-B14 accessory).
Accessories The outdoor unit shall feature advanced intelligent defrost logic to significantly reduce defrost
cycle frequency by monitoring air resistance across the condenser coil during heating operation to
Qty. Model Number Description determine defrost operation initiation to prevent unnecessary defrost cycles.
WHG-T1-B Top wind/hail guard (6 ton outdoor units) The outdoor unit shall feature optional snow blowing logic to prevent snow accumulation on idle
WHG-SL-B Left side wind/hail guard outdoor units
WHG-SR-B Right side wind/hail guard The outdoor unit shall feature maximum current control settings to limit current (50% - 100% of
WHG-R1-B Rear wind/hail guard for 6, 16 - 20 ton units (2 required for 16 - 20 ton units) design current) adjustable at outdoor unit, supported central controls, and supported indoor unit
wired controllers.
LACH-1-KIT-B Low ambient cooling hood and side guards (small chassis, 1 required)
The outdoor unit shall feature energy savings options to reduce system energy consumption when
LACH-1-SIDE KIT-B Low ambient cooling side guards (small chassis, 1 required) average indoor room temperatures are greater than average indoor set temperatures in heating
MCM-C200 Heat pump mode selector switch mode or when average indoor room temperatures are lower than average indoor set temperatures
in cooling mode.
BPHK-230V-1 Base pan heater kit (base pan pan heater and control box, 1 required)
External contact control interface module for operation and error output and
MIM-B14
night silent mode manual activation (1 required)
1 Certified in accordance with the AHRI Variable Refrigerant Flow Multi-Split Air-Conditioners and Heat Pump (VRF) Certification Program
which is based on the latest edition of AHRI Standard 1230.
2
Restrictions apply. Refer to DVM S2 technical data books for full details.
3 Other pipe restrictions and requirements exist. Please consult technical data book or installation manuals for full details regarding
limitations and other requirements.
4 When the outdoor unit is lower than indoor units, and vertical separation is greater than 131 feet, additional conditions apply. When the
outdoor unit is higher than the indoor units, and vertical separation is greater than 163 feet, additional conditions apply. Please refer to
supporting documents at www.SamsungHVAC.com.
5 When operating in cooling mode between -13°F (-25°C) and 5°F (-15°C) OA, a low ambient cooling kit (LACH-*-KIT-B) is required. When
operating in cooling mode between 5°F (-15°C) and 23°F (-5°C) OA, a low ambient cooling side kit (LACH-*-SIDE KIT-B) is required.
Refer to technical bulletin at www.samsunghvac.com for full details and requirements.
Samsung HVAC maintains a policy of ongoing development, specifications are subject to change without notice.

© 2022 Samsung HVAC


Variable Refrigerant Flow (VRF) Multi-Split AC and HP
SHA-DVMS-05232022A
www.SamsungHVAC.com
AHRI Standard 1230
Page 2 of 2
SUBMITTAL AM072BXVGFH/AA
Samsung, DVM S2 Series, Heat Pump Condensing Unit
Dimensional Drawing

6HFWLRQ%% 'HWDLO$
 

% %






3/4




$


 


   


 

&

1RWHV 9LHZ&
1. Detail A and SECTION B-B indicate the dimensions 
after connecting piping ;



2. View C indicates knockout hole dimensions (bottom) )RXQGDWLRQEROWKROHV

1R 'HVFULSWLRQ 5HPDUN


 *DVUHIULJHUDQWSLSH 
)RXQGDWLRQKROHSLWFK


 /LTXLGUHIULJHUDQWSLSH 
 3RZHUFRQGXLWNQRFNRXW 
28 3/4

 
 &RPPXQLFDWLRQZLUHNQRFNRXW 
 .QRFNRXWIRUUHIULJHUDQWSLSLQJ %RWWRP Ø 

 .QRFNRXWIRUUHIULJHUDQWSLSLQJ )URQW
)RXQGDWLRQKROHGHWDLO

)RXQGDWLRQKROHSLWFK

ZZZ6DPVXQJ+9$&FRP