Molded Case Circuit Breakers: Unusual Operating Conditions
Molded Case Circuit Breakers: Unusual Operating Conditions
Molded Case Circuit Breakers: Unusual Operating Conditions
Altitude
Reduced air density at altitudes greater 11,000 (3,350)
6
6,000 (1,800)
400Hz Breakers
Maximum Continuous Ampere Rating 75° C (167° F) Maximum Continuous Ampere Rating 75° C (167° F)
At 40° C (104° F) 햳 Copper At 40° C (104° F) 햳 Copper
Siemens 60HZ 400HZ Cable per Pole Siemens 60HZ 400/415HZ Cable per Pole
Breaker Enclosed No of Wire Breaker Enclosed No of Wire
Type Open Air Open Air 햴 After Derating Pieces Size Type Open Air Open Air 햴 After Derating Pieces Size
015 015 012 1 #14 0250 0210 168 1 250 kcmil
020 020 016 1 #12 0300 0240 192 1 350 kcmil
025 025 020 1 #10 LD6, LXD6, 0350 0260 208 1 500 kcmil
HLD6, HLXD6,
030 030 024 1 #10 HHLD6, 0400 0300 240 2 #3/0
035 035 028 1 #10 HHLXD6, 0450 0340 272 2 #4/0
CLD6
040 040 032 1 #8 0500 0375 300 2 250 kcmil
ED2, ED4, ED6, 045 043 034 1 #8 0600 0420 336 2 350 kcmil
BQD, HED4, 050 048 038 1 #8 0250 0210 210 1 250 kcmil
HED6, CED6 060 057 046 1 #6 0300 0240 240 1 350 kcmil
070 067 054 1 #4 0350 0260 260 1 500 kcmil
6
LD6, LXD6,
080 076 061 1 #4 HLD6, HLXD6, 0400 0300 300 2 #3/0
090 086 069 1 #3 100% Rated 0450 0340 340 2 #4/0
Circuit Breakers
Molded Case
100 095 076 1 #3 0500 0375 375 2 250 kcmil
110 105 084 1 #2 0600 0420 420 2 350 kcmil
125 119 095 1 #1 0500 0400 320 2 250 kcmil
070 063 050 1 #4 MD6, MXD6, 0600 0430 360 2 350 kcmil
HMD6,
080 072 058 1 #4 HMXD6, CMD6 0700 0500 400 3 250 kcmil
090 080 064 1 #3 0800 0560 448 3 300 kcmil
QJ2, QJH2, 100 090 072 1 #3 0500 0400 400 2 250 kcmil
QJ2H, HQJ2H MD6, MXD6,
FD6, FXD6, 110 095 075 1 #2 HMD6, 0600 0430 430 2 350 kcmil
HFD6, HFXD6, 125 105 084 1 #1 HMXD6, CMD6 0700 0500 500 3 250 kcmil
CFD6 100% Rated
150 125 100 1 #1/0 0800 0560 560 3 300 kcmil
175 140 112 1 #2/0 0800 0560 448 3 300 kcmil
200 160 128 1 #3/0 ND6, NXD6 0900 0600 480 3 350 kcmil
HND6, HNXD6,
225 180 144 1 #4/0 CND6 1000 0650 520 3 400 kcmil
250 200 160 1 250 kcmil 1200 0780 624 4 350 kcmil
200 170 136 1 #3/0 ND6, NXD6 0900 0600 600 3 350 kcmil
HND6, HNXD6,
JXD2, JD6, 225 190 152 1 #4/0 CND6 1000 0650 650 3 400 kcmil
JXD6, HJD6, 250 210 168 1 250 kcmil 100% Rated 1200 0780 780 4 350 kcmil
HJXD6, HHJD6, 300 240 192 1 350 kcmil 1200 0780 624 4 400 kcmil
PD6, PXD6,
HHJXD6, CJD6 350 260 208 1 500 kcmil HPD6, HPXD6, 1400 0850 680 4 500 kcmil
400 300 240 2 #3/0 CPD6, 1600 0960 768 5 500 kcmil
200 170 170 2 #3/0 PD6, PXD6, 1200 0780 780 4 400 kcmil
HPD6, HPXD6,
225 190 190 2 #4/0 CPD6 1400 0850 850 4 500 kcmil
JD6, JXD6,
HJD6, HJXD6 250 210 210 1 250 kcmil 100% Rated 1600 0960 960 5 500 kcmil
100% Rated 300 240 240 1 350 kcmil RD6, RXD6, 1600 0960 768 5 500 kcmil
350 260 260 1 500 kcmil HRD6, HRXD6 1800 1080 864 5 500 kcmil
400 300 300 2 #3/0 80% Rated 2000 1200 960 6 500 kcmil
햲 The information provided on this page is intended for controlled testing, than on experience and engineering temperature is greater than 40°C (104°F).
reference and recommendation only. Because several judgment. Contact Siemens for further information on 햴 Calculatedafter derating to compensate for the heating
variables can act on a circuit breaker’s performance at special conditions and treatment. of the copper conductor, caused by the skin effect
the same time, the data above is based less on 햳 Additional derating may be required if the ambient generated by eddy currents produced at 400/415HZ.