Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Inversor - PV35 PRO - 6K

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Low Frequency Solar Inverter Solar Power System

PV3500 PRO Series (4KW-12KW)


Specification

PV35 PRO- PV35 PRO- PV35 PRO- PV35 PRO- PV35 PRO- PV35 PRO-
Features MODEL
4K 5K 6K 8K 10K 12K
• Smart LCD setting(Working modes, Charge Current, Charge voltage, etc.) Nominal Battery System Voltage 24V 48V 24V 48V 48V 48VDC 48VDC 48VDC

Rated power 4KW 5KW 6KW 8.0KW 10.0KW 12.0KW


• Built-in MPPT solar charge controller 80A/100A/200A
Surge rating 12000VA 15000VA 18000VA 24000VA 30000VA 36000VA
• MPPT efficiency max 98% Capable of starting electric motor 2HP 2HP 3HP 4HP 5HP 6HP

• Powerful charge rate up to 140Amp Waveform Pure sine wave \ same as input (bypass mode)

INVERTER Nominal output voltage RMS 220V \ 230V \ 240VAC (±10%RMS)


• DC start &Automatic Self-Diagnostic Function OUTPUT Output frequency 50Hz \ 60Hz ± 0.3Hz

• WIFI / USB monitoring function (wi-fi optional) Inverter effciency(peak) >85% >88%
Line mode efficiency >95%
• Supporting AGS, BTS port
Power factor 1.0

• Compatible to generator Typical transfer time 20ms(max)


Voltage 230VAC
AC INPUT Selectable voltage range 90-280 VAC (APL)

Introduction Frequency range 50Hz \ 60Hz


Low battery voltage cutoff 20-24VDC for 24VDC mode (40-48VDC for 48VDC mode)
PV3500 PRO series is a multi-function inverter ,combining functions of inverter and MPPT solar charger controller, solar charger and battery charger
to offer uninterruptible power support. The comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery Low battery voltage recover 21-25VDC for 24VDC mode (42-50VDC for 48VDC mode)
charging current, AC/solar charger priority, and selectable input voltage based on different applications. BATTERY High battery voltage cutoff 30VDC for 24VDC mode (60VDC for 48VDC mode)
High battery voltage recover 28.5VDC for 24VDC mode (57VDC for 48VDC mode)
Idle consumption-search mode <30W when power saver on <80W when power saver on
Back panel printing description Solar system connection Output voltage Depends on battery type
Charger AC input breaker rating 40A 40A 50A 80A 80A 80A
AC CHARGER
Solar Panel Overcharge protection S.D. 31.4VDC for 24VDC mode (62.8VDC for 48VDC mode )
Maximum charge current 80A 60A 100A 70A 80A 100A 120A 140A

BTS Continuous output power Yes Variances in charging voltage & S.D. voltage base on the battery temperature

Input voltage waveform Sine wave (grid or generator)


Generator
Nominal input frequency 50Hz or 60Hz
1 2 3 4 5 BYPASS Overload protection (SMPS Load) Circuit breaker
&
PROTECTION Output short circuit protection Circuit breaker
1. Switch ON/OFF 11. Remote control port Bypass breaker rating 40A 63A 63A 63A
2. LCD display 12. Fan AC Input LAPTOP
Max bypass current 40Amp 80Amp
3. AC/Inverter indicator 13. BTS
4. Charging indicator 14. AGS Maximum PV charge current 80A 100A(200A optional)
5. Fault indicator 15. AC input LIGHTING
DC voltage 24V \ 48V Auto work 48V
6. BAT- 16. AC outputr AC Output
Maximim PV array power 2000W 4000W 2000W 4000W 4000W 5000W(10000W for 200A optional)
7. BAT+ 17. PV input AIR-CONDITIONER SOLAR
8. WIFI/USB communication port 18. Ground CHARGER
MPPT range @ operating voltage(VDC) 32-145VDC for 24V mode,64-145V for 48V mode 64~145VDC
9. AC input/Bypass breaker 19. PV2 input (optional) Maximum PV array open circuit voltage 145VDC
10. AC output breaker 20. PV1 input TV
Maximum effciency >98%
Standby power consumption <2W
Battery
FAN Mounting Wall mount

6 7 8 9 10 6 7 8 9 10 Dimensions (W*H*D) 620*385*215mm 670*410*215mm


MECHANICAL
Net weight (solar CHG) (kg) 36 41 41 69+2.5 75.75+2.5 75.75+2.5
SPECIFICATIONS
Shipping dimensions (W*H*D) 755*515*455mm 884*618*443mm
Shipping weight (Solar CHG) (kg) 56 61 64 82.5+2.5 89+2.5 92+2.5
Operation temperature range 0°C to 40°C
Storage temperature -15°C to 60°C
OTHER Audible noise 60dB MAX

11 12 13 14 15 16 17 18 11 12 13 14 15 16 19 20 18 Display LED+LCD

[ 4KW-6KW ] [ 8KW-12KW ] Loading (20GP/40GP/40HQ) 140pcs \ 280pcs \ 320pcs

- 27 - - 28 -