Chapter Seven
Instrumentation and
Controls
PART 2 - TIER 2
Revision 5
July 2020
©2020, NuScale Power LLC. All Rights Reserved
COPYRIGHT NOTICE
This document bears a NuScale Power, LLC, copyright notice. No right to disclose, use, or copy any of
the information in this document, other than by the U.S. Nuclear Regulatory Commission (NRC), is
authorized without the express, written permission of NuScale Power, LLC.
The NRC is permitted to make the number of copies of the information contained in these reports
needed for its internal use in connection with generic and plant-specific reviews and approvals, as well
as the issuance, denial, amendment, transfer, renewal, modification, suspension, revocation, or
violation of a license, permit, order, or regulation subject to the requirements of 10 CFR 2.390 regarding
restrictions on public disclosure to the extent such information has been identified as proprietary by
NuScale Power, LLC, copyright protection notwithstanding. Regarding nonproprietary versions of
these reports, the NRC is permitted to make the number of additional copies necessary to provide
copies for public viewing in appropriate docket files in public document rooms in Washington, DC, and
elsewhere as may be required by NRC regulations. Copies made by the NRC must include this copyright
notice in all instances and the proprietary notice if the original was identified as proprietary.
NuScale Final Safety Analysis Report Table of Contents
TABLE OF CONTENTS
Tier 2 i Revision 5
NuScale Final Safety Analysis Report Table of Contents
TABLE OF CONTENTS
Tier 2 ii Revision 5
NuScale Final Safety Analysis Report List of Tables
LIST OF TABLES
Table 7.0-1: NuScale Instrumentation and Controls Design and Applicable Regulatory
Requirements Matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.0-30
Table 7.0-2: Highly Integrated Protection System Topical Report (HIPS TR)
Application Specific Information Cross References . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.0-34
Table 7.1-1: Module Protection System Design Basis Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-62
Table 7.1-2: Variables Monitored by Module Protection System . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-63
Table 7.1-3: Reactor Trip Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-65
Table 7.1-4: Engineered Safety Feature Actuation System Functions . . . . . . . . . . . . . . . . . . . . . . . 7.1-66
Table 7.1-5: Module Protection System Interlocks / Permissives / Overrides . . . . . . . . . . . . . . . . 7.1-71
Table 7.1-6: Design Basis Event Actuation Delays Assumed in the Plant Safety
Analysis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-75
Table 7.1-7: Summary of Type A, B, C, D, and E Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-76
Table 7.1-8: Variables Monitored by Plant Protection System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-78
Table 7.1-9: Sensor Inputs to Module Protection System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-79
Table 7.1-10: Intentional Differences Between Field Programmable Gate Array
Architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-81
Table 7.1-11: Partial Spurious Actuation Scenarios for Engineered Safety Features
Actuation System within Safety Block I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-82
Table 7.1-12: Consequences of Partial Spurious Reactor Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-83
Table 7.1-13: Effects of Digital-Based Common Cause Failure of Level Function Type
on Sensor Block I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-84
Table 7.1-14: Effects of Digital-Based Common Cause Failure of Digital-Based Pressure
Measuring System Function Type on Sensor Block I and II . . . . . . . . . . . . . . . . . . . . . 7.1-85
Table 7.1-15: Effects of Digital-Based Common Cause Failure of Digital-Based Flow
Function Type on Sensor Block I and II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-86
Table 7.1-16: Safety-Related Digital Sensors Used by Safety Block I and II . . . . . . . . . . . . . . . . . . . . 7.1-87
Table 7.1-17: Effect of FPGA Technology Diversity for Postulated Digital-Based CCF of
MPS Safety Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-88
Table 7.1-18: Digital Sensors Credited for Mitigating Anticipated Operational
Occurrences and Postulated Accidents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-89
Table 7.1-19: Example: Hazard Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-95
Table 7.1-20: Example: Safety Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-96
Table 7.1-21: Example: High-level Safety Constraints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-97
Table 7.1-22: Example: Safety Constraints Associated with Plant Conditions . . . . . . . . . . . . . . . . . 7.1-98
Table 7.1-23: Example: Control Action Analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-99
LIST OF TABLES
Tier 2 iv Revision 5
NuScale Final Safety Analysis Report List of Figures
LIST OF FIGURES
Figure 7.0-1: Overall Instrumentation and Controls System Architecture Diagram . . . . . . . . . . . 7.0-36
Figure 7.0-2: Module Protection System Boundaries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.0-37
Figure 7.0-3: Module Protection System Safety Architecture Overview . . . . . . . . . . . . . . . . . . . . . . 7.0-38
Figure 7.0-4: Separation Group A Communication Architecture. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.0-39
Figure 7.0-5: Separation Group A and Division I Reactor Trip System and
Engineered Safety Features Actuation System Communication Architecture . . . 7.0-40
Figure 7.0-6: Reactor Trip Breaker Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.0-41
Figure 7.0-7: Equipment Interface Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.0-42
Figure 7.0-8: Equipment Interface Module Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.0-43
Figure 7.0-9: Pressurizer Trip Breaker Arrangement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.0-44
Figure 7.0-10: Module Protection System Gateway Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.0-45
Figure 7.0-11a: Module Protection System Power Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.0-46
Figure 7.0-11b: Module Protection System Power Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.0-47
Figure 7.0-12: Neutron Monitoring System Ex-Core Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.0-48
Figure 7.0-13: Plant Protection System Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.0-49
Figure 7.0-14: Safety Display and Indication System Boundary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.0-50
Figure 7.0-15: Safety Display and Indication Hub . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.0-51
Figure 7.0-16: Display Interface Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.0-52
Figure 7.0-17: Module Control System Internal Functions and External Interfaces. . . . . . . . . . . . . 7.0-53
Figure 7.0-18: Automatic Control Shared Between Networked Processors . . . . . . . . . . . . . . . . . . . . 7.0-54
Figure 7.0-19: Automatic Control Shared Between MCS and PCS Processors . . . . . . . . . . . . . . . . . . 7.0-55
Figure 7.0-20: Plant Control System Internal Functions and External Interfaces . . . . . . . . . . . . . . . 7.0-56
Figure 7.1-1a: Module Protection System And Plant Protection System Trip or Bypass
Switch Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-101
Figure 7.1-1b: Source Range and Power Range Trips. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-102
Figure 7.1-1c: Power Range High-2 Power Trip and N-2 Interlocks, Low and Low
Low RCS Flow Trips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-103
Figure 7.1-1d: Power Range and Intermediate Range Rate Trips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-104
Figure 7.1-1e: Pressurizer Pressure and Level Trips. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-105
Figure 7.1-1f: Reactor Coolant System Hot Temperature Trip, Temperature Interlocks . . . . . . . 7.1-106
Figure 7.1-1g: Pressurizer Level Interlock and Trip, High Containment Pressure, and
High Containment Level Trips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-107
Figure 7.1-1h: Steam Generator Low and Low Low Main Steam Pressure Trips . . . . . . . . . . . . . . . 7.1-108
Tier 2 v Revision 5
NuScale Final Safety Analysis Report List of Figures
LIST OF FIGURES
Figure 7.1-1i: High Main Steam Pressure and Steam Generator Low and High Steam
Superheat Trips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-109
Figure 7.1-1j: Reactor Trip and Reactor Tripped Interlock RT-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-110
Figure 7.1-1k: ESFAS - Containment System Isolation and Chemical and Volume
Control System Isolation Interlocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-111
Figure 7.1-1l: ESFAS - Decay Heat Removal System and Secondary System Isolation
Actuation, FWIV Interlock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-112
Figure 7.1-1m: ESFAS - Demineralized Water System Isolation, Pressurizer Heater Trip . . . . . . . . 7.1-113
Figure 7.1-1n: ESFAS Emergency Core Cooling System Actuation, Low Temperature
Overpressure Protection Actuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-114
Figure 7.1-1o: Decay Heat Removal System Valve Actuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-115
Figure 7.1-1p: Main Steam Isolation Valve Actuation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-116
Figure 7.1-1q: Main Steam Isolation Bypass Valve Actuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-117
Figure 7.1-1r: Secondary Main Steam Isolation Valve Actuation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-118
Figure 7.1-1s: Secondary MSIV Bypass Valve Actuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-119
Figure 7.1-1t: Feedwater Isolation Valve Actuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-120
Figure 7.1-1u: Feedwater Regulating Valve Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-121
Figure 7.1-1v: Chemical and Volume Control System RCS Injection and Discharge
Valve Actuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-122
Figure 7.1-1w: Chemical and Volume Control System Pressurizer Spray and High Point
Degasification Valve Actuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-123
Figure 7.1-1x: Containment Flooding and Drain and Containment Evacuation Valve
Actuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-124
Figure 7.1-1y: Reactor Component Cooling Water System Valve Actuation . . . . . . . . . . . . . . . . . . 7.1-125
Figure 7.1-1z: Demineralized Water Supply Valve Actuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-126
Figure 7.1-1aa: Emergency Core Cooling System Reactor Vent Valve 1 & 2 Actuation . . . . . . . . . 7.1-127
Figure 7.1-1ab: Emergency Core Cooling System Reactor Recirculation Valve Actuation. . . . . . . 7.1-128
Figure 7.1-1ac: Emergency Core Cooling System Reactor Vent Valve 3 Actuation . . . . . . . . . . . . . 7.1-129
Figure 7.1-1ad: Reactor Trip Breaker Division I A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-130
Figure 7.1-1ae: Reactor Trip Breaker Division I B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-131
Figure 7.1-1af: Pressurizer Heater Trip Breaker Proportional Heater A . . . . . . . . . . . . . . . . . . . . . . . . 7.1-132
Figure 7.1-1ag: Pressurizer Heater Trip Breaker Proportional Heater B . . . . . . . . . . . . . . . . . . . . . . . . 7.1-133
Figure 7.1-1ah: Loss of AC Power to ELVS Battery Chargers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-134
Figure 7.1-1ai: Loss of AC Power to ELVS 24 Hour Timers Division I. . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1-135
Tier 2 vi Revision 5
NuScale Final Safety Analysis Report List of Figures
LIST OF FIGURES
LIST OF FIGURES
Figure 7.2-1: Instrumentation and Controls Safety System Development Processes. . . . . . . . . . 7.2-72
Figure 7.2-2: NuScale System and Software Technical Development Life Cycle
Processes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.2-73
Figure 7.2-3: NuScale Software Lifecycle Comparisons. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.2-74
The instrumentation and control (I&C) systems provide the capability to control the plant
systems manually and automatically during normal, steady state, and transient power
operations. The systems also provide reactor protection against unsafe plant operations by
initiating signals to mitigate the consequences of an anticipated operational occurrence or
postulated accident and ensure safe shutdown.
Section 7.0 provides an introduction and overview of I&C systems, which includes
safety-related and nonsafety-related systems. Systems addressed in Section 7.0 include the
following:
• module protection system (MPS)
• neutron monitoring system (NMS)
• plant protection system (PPS)
• safety display and indication system (SDIS)
• module control system (MCS)
• plant control system (PCS)
• in-core instrumentation system (ICIS)
• health physics network (HPN)
• fixed area radiation monitoring (RM)
Section 7.1 describes major functional and design considerations associated with I&C systems,
including system design basis and incorporation of fundamental design principles of:
• independence
• redundancy
• predictability and repeatability
• diversity and defense-in-depth
Consideration is also given to the attributes of integrated hazard analysis, system architecture,
and simplicity in the design of the NuScale Power, LLC I&C safety-related systems.
Section 7.2 addresses additional I&C system functional and design considerations contained in
IEEE Std 603-1991 and IEEE Std 7-4.3.2-2003 “IEEE Standard Criteria for Digital Computers in
Safety Systems of Nuclear Power Generating Stations” (Reference 7.0-2). This includes specific
I&C system criteria, sense and command features, and execute features that complement the
fundamental design principles discussed in Section 7.1.
NuScale I&C structures, systems, and components are classified in accordance with the
classification criteria described in Section 3.2. The I&C systems classified as safety-related
are the MPS and the NMS. The remaining NuScale I&C systems (e.g., PPS, SDIS, MCS, PCS,
ICIS, HPN and RM) are classified as nonsafety-related.
More detail of the architectural design is provided in Section 7.1 and Section 7.2.
The primary purpose of the MPS is to monitor process variables and provide automatic
initiating signals in response to out-of-normal conditions, providing protection against
unsafe NPM operation during steady state and transient power operation. Each NPM
has a single dedicated MPS. The two major functions that the MPS performs are:
• monitors plant variables and trips the reactor when specified setpoints, which are
based on the plant safety analysis analytical limits described in Chapter 15, are
reached or exceeded during anticipated operational occurrences. The NPM reactor
trip functions for the reactor trip system (RTS) are listed in Table 7.1-3
• monitors plant variables and actuates engineered safety features actuation system
(ESFAS) equipment when specified setpoints, which are based on the plant safety
analysis analytical limits described in chapter 15, are reached or exceeded during
anticipated operational occurrences. Actuation of ESFAS equipment prevents or
mitigates damage to the reactor core and reactor coolant system components and
ensures containment integrity. The ESFAS functions are summarized in Table 7.1-4
The MPS also transmits status and information signals to the nonsafety-related MCS,
maintenance workstation (MWS), and SDIS, and performs monitoring for post-accident
monitoring (PAM) functionality.
The MPS is built on the highly integrated protection system platform (See
TR-1015-18653-P-A), which is a field programmable gate array (FPGA)-based system.
The MPS incorporates the fundamental I&C design principles of independence,
redundancy, predictability and repeatability, and diversity and defense-in-depth as
used by TR-1015-18653-P-A. The information in this section satisfies the application
specific information requirements in TR-1015-18653-P-A listed in Table 7.0-2 for
application specific action item (ASAI) numbers 2, 18 and 57. There are no deviations in
the application specific NuScale I&C architecture presented in this Chapter from what is
described and approved in TR-1015-18653-P-A.
The MPS includes the following safety-related (except where noted otherwise)
elements:
• separation group sensor electronics and input panels
• four separation groups of signal conditioning
• four separation groups of trip determination
• manual actuation switches in the main control room
• main control room isolation switches in the remote shutdown station
• Class 1E components to provide isolation from the nonsafety-related highly
reliable DC power system (EDSS) power supply
• power supplies for sensors and MPS components, which also provide isolation
from the nonsafety-related EDSS
• eight voltage sensors for detecting loss of 480 VAC to the EDSS battery chargers
• four reactor trip breakers and associated cabling
• four pressurizer heater trip breakers and associated cabling
• two nonsafety-related MWSs
• two nonsafety-related MPS gateways
• three nonsafety-related 24-hour timers per division for PAM-only mode
• two divisions of RTS voting and actuation equipment (see Section 7.0.4.1.2)
• two divisions of ESFAS voting and actuation equipment (see Section 7.0.4.1.3)
• four under-the-bioshield temperature sensors
The MPS boundary extends from the output connections of the sensors and detectors
to the input connections of the actuated components as shown in Figure 7.0-2.
The safety function module (SFM) signal conditioning receives inputs from the
process sensors and detectors to measure the process variables as shown in
Figure 7.0-3. The interconnections of the process sensors and detectors to the
signal conditioning block are dedicated copper wires and are routed according to
the separation group with which they are associated. Loop power supplies are
provided where needed based on the sensor requirements.
The signal conditioning function is comprised of input modules that are part of the
SFM consisting of a signal conditioning circuit, an analog-to-digital converter, and
a serial interface. The signal condition function is responsible for conditioning,
measuring, filtering, and sampling field inputs.
The trip determination receives process and detector input values in a digital
format through a serial interface from the signal conditioning block. The trip
determination performs the safety function algorithm and makes a trip
determination based on a predetermined setpoint, and provides a trip or not-trip
demand signal to each RTS division through isolated, redundant, transmit only,
serial connections. The SFM also makes an ESFAS actuation determination based
on a predetermined setpoint, and provides an actuate or do-not-actuate demand
signal to each ESFAS division through isolated, transmit only, serial connections.
There are two other logic functions within the SFM: monitoring and indication bus
(MIB) functionality, and calibration and testing bus (CTB) functionality. The MIB
logic function obtains the parameters, trip determination, status, and diagnostic
information from each of the core logic paths and provides that to the MIB. The CTB
functional logic allows the MWS to update the tunable parameters in nonvolatile
memory when the SFM is out of service.
The SFM communication engine sends the trip and actuate data to the three safety
data buses (SDB1, SDB2, and SDB3) on the chassis backplane and the data is
received on the scheduling and bypass modules (SBM SD1, SBM SD2, and SBM
SD3). The scheduling and bypass modules (SBMs) are the bus masters of their
associated communication bus and are responsible for scheduling the
communications. The SFMs are slaves to the SBMs on the safety data
communication buses and the MIB-CM on the monitoring and indication
communication bus. If an SFM identifies a failure on a communication bus, the SFM
generates an alarm and assumes a fail-safe state for that communication bus. The
fail-safe state for the SFM on that communication bus is to not respond to the
communication bus master (e.g., SBM). The communication paths and equipment
are redundant, making the safety data fault tolerant to single failures or multiple
failures on a single data path. The SBM validates the data and transmits it through
isolated, one-way, transmit-only fiber to both divisions of RTS and ESFAS to their
respective scheduling and voting modules (SVMs). The SVMs are slaves to the SBMs
on the safety data communication buses and slaves to the MIB-CM on the
monitoring and indication communication bus. If an SVM identifies a failure on a
communication bus, the SVM generates an alarm and assumes a fail-safe state for
that communication bus. The fail-safe state for that communication bus on the
SVM is to demand a trip or actuation of all protective functions. The fail-safe state
for the SVM on the monitoring and indication communication bus is to not
respond to the communication bus master. The redundant data for the four
separation groups is received by each division of RTS and ESFAS as shown in
Figure 7.0-5.
All status and diagnostics information for the SFM and SBM is provided to the MIB.
The MIB communication module is the bus master for the MIB and schedules the
communications for the MIB. If the SFM identifies a failure on a communication bus,
the SFM generates an alarm and assumes a fail-safe state for that communication
bus. The fail-safe state for the SFM on that communication bus is to not respond to
the bus master. By not receiving a response from an SFM, the MIB communication
module also generates an alarm.The MIB communication module provides the
status and diagnostics information to the MCS and the MPS gateway through
one-way, transmit only, isolated outputs. The MPS gateway sends the data to the
MWS and SDIS. The MIB communication module also provides a communication
path from the MWS to the SFM through the CTB to allow for calibration and
parameter updates for each safety function. The safety function must be out of
service and a temporary cable from the MWS to the MIB communication module is
required to allow changing parameters or calibration of a channel. An MWS can
only access one separation group at a time using a temporary cable. For additional
information on access controls of the MWS see Section 7.2.9.1.
An MIB communication module is included for each separation group and each
division. A divisional MIB communication module only serves the function of
monitoring and indication as there is no calibration available for the divisional RTS
and ESFAS.
The RTS uses four redundant trip determination signals, one from each separation
group, to complete the logic decisions necessary to automatically open the reactor
trip breakers as shown in Figure 7.0-3. The analytical limits for the RTS are listed in
Table 7.1-3.
The EIMs in the RTS are slaves to the SVMs on the safety data communication buses
and slaves to the MIB-CM on the monitoring and indication communication bus. If
an EIM identifies a failure on a communication bus, the EIM generates an alarm and
assumes a fail-safe state for that communication bus. The fail-safe state for that
communication bus on the EIM is to demand a trip or actuation of all its protective
functions. The fail-safe state for protective functions on EIMs is to demand a trip or
actuation. The fail-safe state for the EIM on the monitoring and indication
communication bus is to not respond to the communication bus master.
Each EIM in the RTS receives redundant trip signals from outputs created in the
SFM and provides a trip signal based on two-out-of-three voting from the
incoming signals as shown in Figure 7.0-5. Two divisions of RTS circuitry and
reactor trip breakers are provided to ensure that a single failure does not cause the
loss of an RTS function. The reactor trip breakers are configured in a series-parallel
configuration as shown in Figure 7.0-6.
An EIM is included for each reactor trip breaker in both RTS divisions that are
actuated by the MPS. Each reactor trip breaker EIM has two separate logic paths.
The primary coil is connected to the undervoltage trip circuit and the secondary
coil is connected to the shunt trip circuit for each reactor trip breaker. Each RTS
division controls one reactor trip breaker in each parallel path. This configuration
allows for either division to accomplish a reactor trip. When a reactor trip signal is
generated, the EIM outputs to the undervoltage and shunt trip circuits are
de-energized, causing the undervoltage coils and the shunt trip relays to
de-energize. When the shunt trip relays drop out, the shunt trip coils are energized
with power from EDSS-MS. Either action causes the reactor trip breakers to open.
The shunt trip circuit and coil are provided as a nonsafety-related, diverse means to
open the reactor trip breakers for increased reliability should de-energization of the
undervoltage coil fail to cause a reactor trip breaker to open, and nonsafety-related
electrical power from EDSS-MS is still available. Power from the control rod drive
power supply is then interrupted and the control rods are inserted into the core by
gravity. The undervoltage and shunt trip circuits are shown in Figure 7.1-1ad
through Figure 7.1-1ae and Figure 7.1-1ak through Figure 7.1-1al for the Division I
and II reactor trip breakers, respectively.
The RTS also provides manual trip capability. Manual switches in the main control
room (MCR) allow the operator to manually initiate a reactor trip. Two manual
switches, one per division, are provided to manually initiate a reactor trip. The
manual switches are input into the actuation and priority logic (APL) associated
with the reactor trip system EIM via the hard-wired module (HWM).
The non-digital signals are diverse from the digital portion of the MPS. Discrete
logic is used by the APL for actuating a single device based on the highest priority.
Regardless of the state of the digital system, manual initiation can always be
performed at the division level. If the enable nonsafety control input is active and
there are no automatic or manual actuation signals present, the MCS is capable of
operating the reactor trip breaker.
The result from the APL is used to actuate equipment connected to the EIM.
Reactor trip breaker status is transmitted to the EIM. Breaker status information is
sent to the MIB, along with the status of the SDB signals.
The ESFAS uses four redundant actuation determination signals, one from each
separation group, to complete the logic decisions necessary to automatically
initiate the operation of necessary engineered safety features (ESFs) as shown in
Figure 7.0-3. The analytical limits for the ESFAS are listed in Table 7.1-4.
When an ESFAS parameter exceeds a predetermined limit, the SFM for each
separation group generates an actuation signal that is sent through an SBM to the
SVM in both ESFAS divisions. The SVM performs two-out-of-four coincident logic
voting on the trip determination status. If two or more actuation signals generate
an actuation of an ESF system, an actuation signal is generated in the SVM. The
signal is then sent to the associated EIMs to de-energize the solenoids of the
associated ESF system or open the breakers of the associated ESF system.
An EIM is included in each division for each ESF component actuated by the MPS.
Each EIM has two separate logic paths to allow for connection to separate ESF
components. Each component is connected to two separate EIMs, resulting in two
EIMs providing redundant control to each component as shown in Figure 7.0-7.
This allows an EIM to be taken out of service and replaced online without actuating
the connected equipment.
The EIMs in the ESFAS are slaves to the SVMs on the safety data communication
buses and slaves to the MIB-CM on the monitoring and indication communication
bus. If an EIM identifies a failure on a communication bus, the EIM generates an
alarm and assumes a fail-safe state for that communication bus. The fail-safe state
for that communication bus on the EIM is to demand a trip or actuation of all its
protective functions. The fail-safe state for protective functions on EIMs is to
demand a trip or actuation. The fail-safe state for the EIM on the monitoring and
indication communication bus is to not respond to the communication bus master.
When an ESFAS actuation signal is generated in the SVM, all four switching outputs
from the EIM open, as shown in Figure 7.0-8, power is interrupted to the
component solenoids, the solenoids are de-energized, and the components
change state to their de-energized position. For the pressurizer heater trip
breakers, the EIM outputs to the undervoltage trip and shunt trip circuits are
de-energized, causing the undervoltage coils and the shunt trip relays to
de-energize. When the shunt trip relays drop out, the shunt trip coils are energized
with power from EDSS-MS. Either action causes pressurizer heater trip breakers to
open. The shunt trip circuit and coil are provided as a nonsafety-related, diverse
means to open the pressurizer heater trip breakers for increased reliability should
Similar to the reactor trip breakers, only one division of pressurizer heater breakers
is required to trip to remove power to heaters. The pressurizer heater breakers are
configured as two separate series connections as shown in Figure 7.0-9.
The ESFAS also provides manual actuation capability. Manual switches in the MCR
allow the operator to manually initiate an ESF function. Two manual switches, one
per division, are provided to manually initiate each ESF function. These manual
switches are inputs into the APL associated with the engineering safety features
actuation system EIM via the HWM.
The non-digital signals are diverse from the digital portion of the MPS. Discrete
logic is used by the APL for actuating a single component based on the highest
priority. Regardless of the state of the digital system, manual initiation always can
be performed at the division level. If the enable nonsafety control input is active
and there are no automatic or manual actuation signals present, the MCS is capable
of controlling the ESF components.
The result from the APL is used to control and actuate equipment connected to the
EIM. Equipment status is transmitted to each EIM. Equipment status information is
sent to the MIB, along with the status of the SDB signals.
Each MPS separation group and division, as well as the MPS gateway, has a
dedicated HWM. The HWM accepts hard-wired signals external to the MPS cabinets
and makes them available on the chassis backplane for the other modules. These
signals include the manual actuation switches, operating bypasses switches,
override switches, and enable nonsafety control switches from the MCR. The
operating bypass and override switches are described in Section 7.2.4. Other inputs
to the HWM include the SFM trip/bypass switches, MCS control inputs, and
component position feedback.
Each division of MPS has a nonsafety-related MWS for the purpose of maintenance
and calibration. The one-way, read-only data are connected through the MPS
gateway for its division and are available continuously on each division's MWS. The
MWS is used to update tunable parameters in the SFMs when the safety function is
out of service. Controls are put in place, as described in Section 7.2.9 to prevent
modifications to an SFM when it is being relied upon to perform a safety function.
The MWS is used for offline maintenance and calibration, using a temporary cable
that allows two-way communication to update setpoints and tunable parameters
in the SFMs. When an SFM is placed out of service by operating its out-of-service
switch, the position of the trip/bypass switch associated with that SFM is read by
the SBM and used as the status for the SFM output. Each division of the MPS has a
nonsafety-related MWS permanently connected for the purpose of online
monitoring, using the MPS gateway through one-way isolated communication
ports over point-to-point fiber-optic cables.
Each division of MPS has a nonsafety-related MPS gateway that consolidates the
information received from the four separation groups, the two divisions of RTS, and
the ESFAS. The MPS gateway also collects equipment status feedback from the
HWM for PAM-only mode, as well as reads the status of the three 24-hour timers. All
of the information transmitted to the MPS gateway is consolidated by a single
communication module that acts as a master on the MPS gateway backplane and
then transmits the consolidated data through a qualified, isolated, one-way
communication path to the MWS and the SDIS hubs as shown in Figure 7.0-10.
There is one MPS gateway for each division.
The EDSS is the power source for the MPS as described in Section 8.1.2.2 and
8.3.2.1.1. The DC-to-DC voltage converters are used for Class 1E isolation and
protection of the MPS equipment. Division I MPS power is generated from power
channels A and C through a DC-DC converter for Class 1E isolation, and then
distributed to the loads by sharing or auctioneering. Division II power is generated
from power channels B and D, similar to Division I. Each of the separation groups is
redundantly supplied from a single EDSS channel, and then distributed to the loads
by sharing or auctioneering. Configuration of the EDSS channels and DC-to-DC
voltage converters for MPS Division I and separation groups A and C are shown in
Figure 7.0-11a. The MPS Division II and separation groups B and D are similar and
are shown in Figure 7.0-11b. The EDSS power channels A and C that supply power
to MPS Division I are completely independent from EDSS power channels B and D
that supply power to MPS Division II and are shown in Figures 8.3-7a and 8.3-7b.
To ensure EDSS batteries supply power for their full mission time of 24 hours for A
and D batteries and 72 hours for B and C batteries, only loads associated with
maintaining the ECCS valves closed or PAM instrumentation functional remain
energized during ECCS hold mode and PAM-only mode. These loads include the
MPS and NMS cabinets including power to sensors, ECCS valve solenoids, RM
bioshield radiation monitors, and the EDSS battery monitors. If two out of four
sensors detect a loss of voltage on both B and C battery charger switchgear, the
MPS automatically generates a reactor trip, decay heat removal system (DHRS)
actuation, pressurizer heater trip, demineralized water supply isolation,
containment isolation, and starts the three 24-hour timers per division. For the first
24 hours following a loss of voltage, the four separation groups of MPS equipment
and both divisions of ESFAS and RTS remain energized. If an ECCS actuation is not
required due to plant conditions, then ECCS is not actuated (ECCS trip solenoid
valves remain energized), which is defined as the ECCS hold mode, to allow time to
restore AC power and prevent actuation of ECCS. The ECCS still actuates if the
associated ESFAS signal is generated during this 24-hour period. If power has not
been restored within 24 hours to the B and C battery switchgear, the 24-hour
timers time out. At this time, the ESFAS and RTS chassis and MWS for both MPS
divisions are automatically de-energized. This action de-energizes the ECCS
solenoid trip valves and ECCS is actuated. The PAM instrumentation remains
powered by the B and C EDSS batteries for an additional 48 hours (for a total of
72 hours). This configuration is defined as the PAM-only mode.
When the NPM is in transit to or from the refueling bay of the plant, neutron
monitoring is not required. Equipment with the potential to cause core alterations,
such as control rod drives, has been disconnected or disabled prior to NPM movement.
• The NMS consists of NMS-excore, NMS-refuel, and NMS-flood.
Neutron flux level signals generated by the NMS-excore equipment are used by the
MPS to generate appropriate reactor protection trips, operating permissives,
indication, and alarms for various modes of reactor operation, including shutdown
conditions. The MPS sends neutron flux signals to other systems in order to provide
non-protective controls and indication.
The NMS-excore detectors are qualified to Seismic Category I and located within
the operation bays of the Reactor Building (RXB). They are placed outside the
containment vessel. The NMS-excore detectors are installed in support
mechanisms that are connected to the NPM operating bay structure. During
operation, the support mechanisms are positioned to place the NMS-excore
detectors just outside the containment vessel to monitor neutron flux leakage from
the reactor which is directly proportional to reactor power level.
The NMS-excore signal processing cabinets are located in the RXB. Separation
Group A and C cabinets are located in the MPS equipment rooms on the
75'0” elevation of the RXB (see Figure 1.2-14). The NMS-excore separation group B
and D equipment is located in the MPS equipment rooms on the 86' elevation of
the RXB (see Figure 1.2-15). Figure 7.0-12 shows the NMS-excore block diagram.
The NMS-refuel detectors are located within the refueling bay of the plant. There is
one NMS-refuel subsystem for the plant as each NPM is relocated to the refueling
bay for the refueling process and only one NPM is refueled at a time. The
NMS-refuel monitors neutron flux from the point of reactor pressure vessel (RPV)
head lift, until the replacement of the RPV head.
The NMS-refuel neutron monitoring capability ensures the neutron flux level is
continuously monitored during the refueling process and also provides an audible
count rate to the operator with the ability to detect and alert a spurious increase in
count rate during fuel movement. The NMS-refuel provides neutron flux signals to
the PCS.
The NMS-refuel detectors are located on the outside of the RPV. This mounting
allows the NMS-refuel to be repeatedly replaced back into the same location
between each use, allowing for the movement of NPMs between operating bay
and refueling bay.
The PPS monitors process variables at the plant level and executes actuations in
response to normal and off-normal conditions. The PPS monitors and controls systems
common to up to 12 NPMs. Selected variables monitored and equipment actuated by
the PPS require an augmented level of quality. The PPS consists of two independent
and redundant divisions. Either of the divisions is capable of accomplishing PPS
functions. Additional design considerations for the PPS are described in
Section 7.1.1.2.5. The list of PPS automatic actuation functions for the CRHS and CRVS
can be found in Section 9.4.1.
The PPS is built on the highly integrated protection system platform (See
TR-1015-18653-P-A) and is an FPGA-based system. Figure 7.0-13 displays the system
diagram of the PPS architecture.
Division I and Division II of the PPS are located in separate rooms in the Control
Building. The boundaries of the PPS extend from the output connections of the sensors
and detectors to the input connections of the actuated devices. Also included in the
PPS boundary are the ELVS AC voltage sensors, which are classified as part of the PPS.
The nonsafety-related displays, which receive data from the PPS, are either part of the
SDIS or the PCS as described in Section 7.0.4.4 and Section 7.0.4.6, respectively.
The process sensors measure different process variables, such as radiation, level, and
voltage. Separate sensors supply information to the two PPS divisions. Sensors are
qualified for the environmental conditions before, during, and after a design basis
event. The sensors provide input to the PPS, but are classified as part of the system in
which they are installed.
An individual SFM is included in each division for each function performed by the PPS.
Each SFM can accept input from up to four sensors. Signal conditioning is performed to
convert the sensor signals into a digital representation. With the digital signals, the SFM
performs algorithms and setpoint comparisons necessary to determine if actuation is
required for the function. The actuation decision is output to three separate
communication buses to provide redundant communication between the SFMs and
EIMs. The SFMs also provide communication outputs for parameter values, status
information, and alarms to be sent to the PCS and SDIS. Diagnostic information for each
SFM is also sent to the MWS.
The architecture of the PPS uses three independent data busses dedicated to actuation
signals. The three communication safety data buses (SDB1, SDB2, and SDB3) are each
configured in a master-slave communication protocol. The three redundant SBMs
(SBM1, SBM2, and SBM3) are the masters for their associated bus and provide the
redundant SDB communications from the SFM to the EIM. The SDB1, SDB2, and SDB3
are dedicated to processing the actuation signals.
The CTB communication module is the master of the CTB; however, during normal
operation there are no transactions on this bus. The CTB is only active if the channel is
removed from service during calibration or changing of parameters. The CTB
communication module isolated data path transmits one-way data to the MWS.
An EIM is included in each division for each piece of equipment actuated or monitored
by the PPS. Each EIM has two separate logic paths to allow for connection to a "primary"
component and a "secondary" component. Each component is connected to two
separate EIMs, resulting in two EIMs providing redundant control to each component.
This allows an EIM to be taken out of service and replaced online without actuating any
equipment.
The actuation signals from the redundant SDBs are combined and delivered to the APL
within the EIM. The APL accepts commands from three sources: (1) the digital actuation
signal from the SFM, (2) the non-digital manual actuate input signal from its own PPS
division, and (3) non-digital manual control signals from the PCS. The non-digital
signals are diverse from the digital portion of the PPS. Discrete logic is used by the APL
for actuating a single device based on the highest priority. Regardless of the state of
the digital system, manual initiation of actions can be initiated at the division level.
When the appropriate configuration is enabled by the operator, component-level
control can be achieved through the use of the PCS.
The result from the APL is used to control and actuate equipment connected to the
EIM. Equipment status is fed back to each EIM. Equipment feedback information is sent
to the MIB, along with the status of the SDB signals and the APL.
Each division of PPS has a dedicated MWS. In order to perform maintenance activities,
the ability to perform write commands from the MWS to the equipment is required.
The process for using the MWS to perform maintenance on the PPS is identical to the
process described for the MPS in Section 7.2.9.1.
Each PPS division cabinet has an HWM that accepts external signals and makes them
available on the backplane for the other modules. These signals include the manual
switches and nonsafety-control signals.
The SDIS provides accurate, complete, and timely information pertinent to MPS and
PPS status and information displays to support the ability to initiate protective actions
manually, if required. The SDIS displays PAM variables and meets augmented quality
criteria as described in Section 7.1.1.2.4. Display of information is designed to minimize
the possibility of ambiguous indications and to enhance the human-system interface
(HSI) for the operator.
Information regarding process variable values and equipment status is provided to the
SDIS from each separation group and each division of the MPS and PPS.
The SDIS interfaces with the MPS and PPS through communication modules. The MPS
interface is referred to as an MPS gateway, while the interface with the PPS is through
an MIB communication module. The SDIS consists of two independent divisions of
equipment. Each SDIS division consists of communication hubs, display interface
modules (DIMs), and display panels. The SDIS boundaries and interfaces are shown on
Figure 7.0-14.
The SDIS hub receives data from the MPS gateway and plant protection system MIB
communication module. Each NuScale Power Module's MPS gateway delivers data to a
separate communication module within the SDIS hub. The SDIS hub distributes the
data it receives from the MPS and PPS to the DIM associated with the respective NPM or
PPS through one-way, optically-isolated, fiber-optic cables. Data from each of the
communication modules on the SDIS hub for each SDIS hub rack is aggregated into a
single communication module. This module polls each of the communication modules
on its rack through the backplane for the rack. The communication module then sends
the aggregated information to the PCS through a unidirectional, optically-isolated
interface.
The SDIS hub is separated into two chassis of communication modules per division.
The first chassis contains the communication modules for MPS associated with NPM 1
through 6 and the PPS communication modules. The second chassis houses the
communication modules for only MPS associated with NPM 7 through 12. Both the first
and second chassis of communication modules contain a communication module for
interfacing with nonsafety systems. The SDIS hubs are located in the PPS rooms. The
SDIS hub is shown in Figure 7.0-15.
The DIM within the SDIS receives data through an isolated fiber-to-copper interface.
The received data are converted in an FPGA to a display ready format. The DIM then
sends the display ready data through a cable to the display panel. The DIM is located in
the MCR. Figure 7.0-16 represents the DIM.
The display panels display the data made available from the MPS and PPS to the plant
operators in the MCR. Data from each MPS and PPS are displayed on its own dedicated
monitor, with one monitor per division. Both divisions of MPS and PPS data are
displayed on both SDIS divisional displays.
The MCS is a distributed control system which allows monitoring and control of
NPM-specific plant components that are associated with the NPM balance-of-plant
control functions. The MCS includes manual controls and HSIs necessary to provide
operator interaction with the process control mechanism. The HSIs are provided in the
MCR and the remote shutdown station as described in Section 7.2.13 and Section
7.2.14.
The principal function of the MCS is to control and monitor nonsafety systems and
components. This includes nonsafety-related primary and secondary systems,
including chemical, utility, and support process systems to the NPM. The MCS is part of
the nonsafety-related network and includes the associated network equipment and
appurtenances necessary for network communication.
through the HWM to the EIM in the MPS, which contains priority logic that requires a
safety-related enable signal prior to allowing control of the device from the MCS.
Figure 7.0-17 represents the MCS internal functions and external interfaces.
The boundary of the MCS is at the terminations on the MCS hardware. The MCS
supplies nonsafety-related inputs to the HSIs for nonsafety displays in the MCR, the
remote shutdown station, and other locations where MCS HSIs are necessary. There are
two boundaries between MCS and MPS, the fiber-optic isolated portion and the HWM
boundary. The MCS has a direct, bi-directional interface with the PCS. The network
interface devices for the MCS domain controller/historian provide the interface
between the human machine interface (HMI) network layer and the control network
layer. A one-way deterministic isolation device between the connection from the MCS
to the plant network is provided. The one-way deterministic isolation device between
the MCS and plant network shown in Figure 7.0-1 transmits network traffic from the
MCS to the plant network in one direction only, which is enforced in the hardware
design, not software. No software configuration or misconfiguration will cause the
boundary device to reverse the direction of data flow.
The MCS uses logic processing in the cases where redundant input/output channels
are used. Some logic supports the redundant-channel architecture used by the MPS,
while other logic directly supports the process systems. The logic processing of
multiple channels can include two, three, or four input signals.
COL Item 7.0-1: A COL applicant that references the NuScale Power Plant design certification is
responsible for demonstrating the stability of the NuScale Power Module during
normal and power maneuvering operations for closed-loop module control system
subsystems that use reactor power as a control input.
The NuScale power plant normal operation and power maneuvering control functions
are provided by the following MCS functions for each NPM:
• turbine trip, throttle and governor valve control
• turbine bypass valve control
• feedwater pump speed control
• feedwater regulating valve control
• Reactor coolant system boron concentration (chemical shim) control
• control rod drive system control
• pressurizer pressure control
• pressurizer level control
The control inputs and functions for each during normal power operation are
described below.
The turbine trip, throttle, and governor controls rely on the following control inputs:
• main turbine control system (MTCS) package sensors (case temperatures, drain
valve position, eccentricity, speed sensing, shaft axial position, journal bearing
displacement, journal bearing temperature and other sensors)
• demand power level (main turbine generator load or reactor power) from MCS and
MTCS
• main steam line flow
• turbine inlet steam pressure
• secondary system calorimetric input
• target reactor power and change rate via the MCR operator workstation
• turbine generation limit and load change rate via the MCR operator workstation
During normal power operations, the turbine governor control maintains steam header
pressure as a function of reactor power demand. During load following, operator input
via the MCR human-system interface establishes the turbine generation limit. The
turbine bypass valves divert excess steam energy to the main condenser to limit
turbine generation to the power generation target. While normal turbine generator
power changes are limited to a fixed rate, the turbine generator is capable of
loading/unloading by diverting steam flow to and from the turbine bypass valves.
The turbine bypass valve control relies on the following control inputs:
• turbine trip
• reactor trip
• DHRS passive condenser steam pressure (below approximately 15 percent steam
flow)
• turbine inlet steam pressure (above 15 percent steam flow)
• secondary system calorimetric
• target reactor power and change rate via the MCR operator workstation
• turbine generation power limit and load change rate via the MCR operator
workstation
During normal power operations, the turbine bypass valves are closed. During load
following, operator input via the MCR HSI establishes the turbine generation limit. The
turbine bypass valves divert excess steam energy to the main condenser to limit
turbine generation to the generation target. On a turbine trip, turbine bypass valves
automatically open to control steam header pressure.
The feedwater pump speed control relies on the following control inputs:
• main steam line flow
• feedwater line flow
• feedwater pressure
• turbine inlet steam pressure (above approximately 15 percent steam flow)
• main steam temperature (above approximately 15 percent steam flow)
• secondary system calorimetric
• target reactor power and change rate via the MCR operator workstation
• turbine generation limit and load change rate via the MCR operator workstation
The feedwater regulating valve control relies on the following control inputs:
• decay heat removal passive condenser condensate pressure
• decay heat removal passive condenser steam pressure
• main steam line flow
• feedwater line flow
• target reactor power and change rate via the MCR operator workstation
• turbine generation limit and load change rate via the MCR operator workstation
From plant startup to approximately 25 percent reactor power, MCS controls the FWRV
position to adjust feedwater flow to maintain DHRS passive condenser steam pressure
equal to a saturation pressure slightly below the RCS average coolant temperature.
From approximately 25 percent reactor power to 100 percent reactor power the FWRVs
remain static and are opened to the optimum position to support feedwater flow
control.
The control rod drive system relies on the following control inputs:
• RCS flow
• RCS boron concentration
• RCS average coolant temperature
• CVCS letdown line flow
Controls rods are manually and automatically controlled by the control rod drive
system to maintain average RCS coolant temperature on a programmed value as a
function of reactor power. Rod position is limited by the power dependent insertion
limits described in Section 4.3.
The CVCS adjusts the boron concentration in the RCS to compensate for changes in
core reactivity over the fuel cycle. It also provides the required boration for normal
shutdowns. The CVCS makeup pumps inject borated water from the BAS to raise RCS
boron concentration. CVCS letdown flow is discharged to the liquid radwaste system
(LRWS) to maintain a nearly constant volume of reactor coolant (RCS inventory may
vary over short time periods within the pressurizer level operating band).
The boron concentration of the RCS is lowered by adding demineralized water from
the demineralized water system with the CVCS makeup pumps while discharging
coolant to the LRWS. Routine incremental boron concentration dilution of the RCS by
CVCS is performed based on operator permission. The MCS determines a desired
dilution rate and quantity which preserves shutdown margin to achieve a final RCS
boron concentration. The operator is required to review and approve the dilution
process using the MCR operator workstations and monitor the plant during dilution
evolutions.
During normal operation, pressurizer pressure control is achieved using the pressurizer
spray to lower pressurizer pressure, and three groups of pressurizer heaters are used to
raise pressurizer pressure based on the deviation from the normal operating pressure
of 1850 psia. One group of pressurizer heaters uses modulating proportional control,
and two other groups of pressurizer heaters are either on or off, depending on the
deviation of pressurizer pressure from the normal operating pressure.
During normal power operation, pressurizer water level control is achieved using the
CVCS makeup and letdown flows. The CVCS makeup and letdown flow rates are
adjusted to maintain pressurizer level on a ramped linear program from 50 percent
level at 0 percent reactor power to 60 percent level at 100 percent reactor power.
The MCS control architecture is separated into multiple control segments based on
their functions. The major MCS control segments are described below for those
segments that have a direct impact on the effects listed above and serve functions
relating to power generation; protection of plant assets; remove fuel assembly
heat; reactivity control; and radioactivity control:
• CVCS, CFDS, and DHRS segments - The chemical and volume control system
(CVCS), containment flooding and drain system (CFDS), and the decay heat
removal system (DHRS) use the same segment of the MCS for automatic and
remote control functions. Major control functions of the CVCS within the MCS
include the makeup of either borated or demineralized water into the reactor
coolant system (RCS), the letdown of used coolant into the liquid radwaste
management system, and the degasification and pressurizer spray within the
pressurizer. Due to concerns with postulated digital-based common cause
failures (CCFs) of the CVCS control functions on this segment, the CVCS
letdown function is separated onto its own separate, independent control
segment. The major control function of the CFDS within the MCS is opening
and closing the NPM-specific isolation valve that provides the inlet to the
containment module. The inlet of the piping into the NPM containment is
isolated by a containment isolation valve, which is controlled by the
safety-related MPS. There are no control functions of the DHRS provided by the
MCS; only indications are provided for certain variables. Control functions for
the DHRS are provided by the MPS.
• RCS, CFWS, MSS, and RCCWS segment - The RCS, condensate and feedwater
system (CFWS), main steam system (MSS), and reactor component cooling
water system (RCCWS) use the same segment of the MCS for automatic and
remote control functions.
• CRDS segment - The control rod drive system (CRDS) uses its own segment of
the MCS for automatic and remote control functions. The CRDS control
processor does not control the individual mechanics of each rod's movement;
rather, the CRDS control processor provides supervisory control and data
acquisition to the power converter and control assembly cabinets which is in
the scope of the CRDS. Rod withdrawal is performed by an operator, although
supervisory control of rod insertion may be performed by the MCS controller if
reactor power demand requires rod insertion to reduce power. Automatic rod
withdrawal may not be performed when thermal reactor power is between
zero and 15 percent.
• TGS and EHVS segment - The turbine generator system (TGS), and 13.8 kV and
switchyard system (EHVS) use the same segment of the MCS for automatic and
remote control functions. For the EHVS, the MCS only controls the breaker that
connects the turbine generator to the off-site customer loads. For the TGS, the
MCS provides supervisory control and data acquisition services to the
packaged control system, which is included with the TGS, as well as a means to
interface the operators in the MCR with each TGS.
Evaluation of Digital-Based CCFs of the CVCS, CFDS, and DHRS Segment of the MCS
The digital-based failure scenarios were analyzed for the CVCS, CFDS and DHRS
segments of the MCS. To preclude digital-based CCF of the CVCS segment related
to the CVCS letdown and makeup functions, the CVCS letdown function is
allocated to a separate, independent segment. The separation of CVCS letdown,
makeup and CVCS pressure control on to different MCS segments precludes
postulated digital-based CCFs causing events that are not bounded by the plant
safety analysis.
CVCS letdown segment failure 1: Postulated failures are limited to the CVCS
letdown function and are bounded by the design basis event analyses for increases
in reactor coolant inventory (see Section 15.5) and decreases in reactor coolant
inventory (Section 15.6).
CVCS, CFDS, and DHRS segment failure 1: A digital-based CCF of this segment is
postulated to result in maximum dilution of boron during startup operations,
which would be the worst case reactivity addition event in this segment. The
analysis for the inadvertent decrease in reactor coolant system boron
concentration envelopes Modes 1 through 5, and therefore, bounds all postulated
dilution scenarios with this segment (see Section 15.4.6).
Evaluation of Digital-Based CCFs of the RCS, CFWS, MSS, and RCCWS Segment of
the MCS
The most-limiting failure scenarios were analyzed for the RCS, CFWS, MSS, and
RCCWS segments of the MCS. The results are summarized below.
RCS, CFWS, MSS, and RCCWS segment failure 1: A digital-based CCF in this segment
is postulated to cause a reactivity addition event by causing the feedwater pumps
to generate excessive feedwater flow to the steam generator while the reactor is in
power operation.
The reactivity addition due to increase in feedwater flow is bounded by the design
basis analysis of the increase in feedwater flow (see Section 15.1.2).
RCS, CFWS, MSS, and RCCWS segment failure 2: A digital-based CCF is postulated to
cause both secondary main steam isolation valves to close while at 100 percent
rated thermal power (RTP). This will cause a decrease in heat removal event.
Additionally, because the pressurizer heaters are controlled by this segment, the
failure also causes all the pressurizer heaters to be continuously energized even
when the setpoint to secure the heaters is exceeded. The pressurizer heaters will
add to the RCS pressure rise. However, the pressurizer spray valve is expected to
operate since this control is not part of this segment.
The postulated failure is bounded by the design basis analysis of the closure of the
main steam isolation valve (See Section 15.2.4).
Although the analysis assumes that the pressurizer heaters remain at their initial
steady-state output level, the postulated heater controller failure at “high output”
is considered to be inconsequential to the outcome of the analysis. This is because
of generation of an early DHRS actuation signal by the MPS, which de-energizes all
three banks of the pressurizer heaters. Furthermore, the allowed credit for spray
actuation in best-estimate analysis offsets the impact of the pressurizer heater
malfunction prior to their MPS-based de-energization.
RCS, CFWS, MSS, and RCCWS segment failure 3: A digital-based CCF is postulated to
cause both feedwater regulating valves to close while at 100 percent power. The
effect of this failure is similar to the failure described above in that it will cause a
decrease in heat removal event. Because the pressurizer heaters are controlled by
this segment, the failure also causes all the pressurizer heaters to be continuously
energized even when the setpoint to secure the heaters is exceeded. The
pressurizer heaters will add to the RCS pressure rise. However, the pressurizer spray
valve is assumed to operate since this control is not part of this segment.
RCS, CFWS, MSS, and RCCWS segment failure 4: In this failure scenario, a
digital-based CCF is postulated to occur during an increase in reactor power where
the pressurizer heaters do not energize when the RCS pressure declines below the
setpoint for turning on the pressurizer heaters. This is an RCS pressure decrease
event.
In this scenario, the pressurizer heaters are not credited to arrest the
depressurization rate associated with RCS cooldown events. Furthermore, the
failure of the pressurizer heaters to energize as an initiating event is not a
design-basis accident presented in Chapter 15 or evaluated as a part of the normal
operational transients. This event would result in a reactor trip on low pressurizer
pressure or level which is bounded by other RCS overcooling scenarios (see
Section 15.1).
The two most-limiting failure scenarios were analyzed for the CRDS segment of the
MCS. The results are summarized below.
CRDS segment failure 1: A digital-based CCF in this segment causes continuous rod
withdrawal at the maximum rate of 15 inches per minute of the regulating control
rod group. The reactor is critical at 100 percent power and the regulating group is
at the power dependent insertion limit (PDIL). This postulated scenario is bounded
by the analysis of the rod withdrawal event at power, subcritical, or low-power
operation (see Sections 15.4.1 and 15.4.2).
Evaluation of Digital-Based CCFs of the TGS and EHVS Segment of the MCS
The two limiting failure scenarios were analyzed for the TGS and EHVS segment of
the MCS. The results are summarized below.
decrease in heat removal by the secondary side event. This postulated failure is
bounded by the design basis analysis of the Loss of External Load, Turbine Trip,
Loss of Condenser Vacuum (see Section 15.2). The turbine bypass function is a
nonsafety-related function and as such, it is not credited in the design-basis
accident analysis.
7.0.4.5.3 Preventive and Limiting Measures Used in the Module Control System
• Automatic control shared between the MCS and the PCS — In the case where
the process control system uses closed-loop control across multiple networked
processors, but within the same control system, the network signal path
follows the data acquisition from an analog (e.g., 4-20 mA) input card. The
process variable is first input to the remote input/output cards, after which it is
sampled and held in the firmware for the remote input/output rack. The
firmware converts the digital value corresponding to the 4-20 mA signal, then
is sent via the remote input/output protocol to the sensing segment processor,
which is communicated to another processor via the control network protocol
as input to the calculation of the control variable. The process variable is
processed by the control algorithm within the necessary control processor,
then the input/output network receives the control variable from the control
processor, which then sends a converted digital-to-analog (e.g., 4-20 mA)
output to the final control element corresponding to the processed control
variable. Figure 7.0-19 depicts a block diagram of the signal handling for this
type of control. In the case of a final control element which is placed into an
open state or closed state only (i.e., "discrete"), the digital value corresponding
to the "open" or "closed" command will be sent to the actuator. A signal is
applied to the actuator from its input/output card, which opens or closes the
actuator based on an input sensor state (in the case of a discrete input) or
based on an input process variable comparison to a setpoint held in the
processing logic for the actuator. The process systems supported by both the
MCS and the PCS, which share information and control signals between the
MCS and PCS, are not systems that would immediately or directly affect reactor
criticality. They are primarily systems which are utility in nature; that is, systems
which provide heating, cooling, water, air, chemical, or power to the process
systems.
The PCS is a distributed control system which allows monitoring and control of
non-NPM-specific plant components. The PCS includes manual controls and HSIs
necessary to provide operator interaction with the process control mechanism.
The principal function of the PCS is to control and monitor the nonsafety-related
control system components which are not specific to an NPM. The PCS is composed of
the central processor or processors, power supplies, mounting racks, input/output
racks, and associated networking equipment.
Figure 7.0-20 shows the PCS internal functions and external interfaces.
The boundary of the PCS is at the terminations on the PCS hardware. The PCS supplies
nonsafety inputs to the HSIs for nonsafety displays in the MCR, the remote shutdown
station, and other locations where PCS HSIs are necessary. The boundary between the
PPS and PCS is at the output connection of the optical isolators in the PPS. The PCS has
a direct, bi-directional interface with the MCS. The network interface devices for the
PCS domain controller/historian provide the interface between the HMI network layer
and the control network layer. A one-way deterministic isolation device between the
connection from the PCS to the plant network is provided. The one-way deterministic
isolation device between the PCS and plant network shown in Figure 7.0-1 transmits
network traffic from the PCS to the plant network in one direction only, which is
enforced in the hardware design, not software. No software configuration or
misconfiguration will cause the boundary device to reverse the direction of data flow.
The PCS uses logic processing in the cases where redundant input/output channels are
used. Some logic supports the redundant-channel architecture used by the PCS, while
other logic directly supports the process systems. The logic processing of multiple
channels can include two, three, or four input signals.
The PCS control architecture is separated into multiple control segments based on
their functions. The major PCS control segment subject to a coping analysis is
described below. This segment has a direct impact on the effects listed above and
serves functions relating to protection of plant assets, human habitability, and
radioactivity control as follows:
• EHVS, EMVS, and ELVS Segment — The EHVS, medium voltage AC electrical
distribution system (EMVS), and ELVS use the same segment of the PCS for
automatic and remote control functions. For the EHVS, the PCS controls each
breaker except for the breaker that connects the turbine generator to the
off-site customer loads.
Evaluation of Digital-Based CCFs of the EHVS, EMVS, and ELVS Segment of the PCS
The two most-limiting failure scenarios were analyzed for the EHVS, EMVS and ELVS
segments of the PCS. The results are summarized below.
This failure results in a loss of the normal balance-of-plant heat sink and therefore is
considered a decrease in heat removal event. This failure results in a loss of
condenser vacuum on all operating turbine generators. The loss of the chiller
packages would cause a loss of HVAC cooling. The postulated failure impacts
multiple modules and results in a turbine trip due to loss of condenser vacuum,
which is addressed in the design basis Loss of Condenser Vacuum Analysis (see
Section 15.2.3). HVAC cooling is a nonsafety-related function and is not credited in
the design basis accident analysis for environmental qualification of mechanical or
electrical equipment and systems.
7.0.4.6.3 Preventive and Limiting Measures Used in the Plant Control System
The ICIS monitors the neutron flux distribution within the reactor core and provides
core inlet and exit temperature information to the MPS for monitoring core cooling
during post-accident conditions. The neutron flux information is also used to verify
operation and calibrate the NMS-excore detectors. The ICIS has the ability to determine
a power shape deviation caused by stuck or misaligned control rods, when the rod
positions cannot be determined by the rod position indication system. The ICIS also
provides a pressure boundary for the RPV which is a safety-related function as
described in Section 7.1.1.2.8.
The in-core instrumentation system has a total of six detectors integral to each
instrument assembly. There are four self-powered neutron detectors and two
thermocouples. The neutron detectors are equally spaced throughout the vertical
height of the reactor core. One thermocouple is located at the inlet of the core and one
thermocouple is located at the exit of the core.
Each NPM has a total of 12 in-core instrumentation guide tubes. These rigid tubes
extend from the top of the containment to the bottom of the reactor to provide
routing and structural support for the mineral-insulated, pressure-retaining cabling
which contains the in-core instrumentation assemblies. Section 4.3.2 provides
additional information on the in-core instrumentation system. Figure 4.3-18 provides
the ICIS core locations.
The HPN is used to interconnect the radiological controls equipment as part of the
Operational Radiation Protection Program, which is established to provide an effective
means of radiation protection for station personnel, visitors, and the general public.
Radiation monitoring is performed by fixed area radiation monitors and continuous air
monitors throughout the plant.
7.0.5 References
7.0-1 Institute of Electrical and Electronics Engineers, "IEEE Standard Criteria for
Safety Systems for Nuclear Power Generating Stations," IEEE Std 603-1991,
Piscataway, NJ.
7.0-2 Institute of Electrical and Electronics Engineers, "IEEE Standard Criteria for
Digital Computers in Safety Systems of Nuclear Power Generating Stations,"
IEEE Standard 7-4.3.2-2003, Piscataway, NJ.
7.0-3 NuScale Power, LLC, "Design of the Highly Integrated Protection System
Platform," TR-1015-18653-P-A, Revision 2.
50.49 x
50.54(jj) x
GDC21 x x x x
GDC22 x x
Table 7.0-1: NuScale Instrumentation and Controls Design and Applicable Regulatory Requirements Matrix (Continued)
Tier 2
RG 1.100 x
RG 1.105 x
4.1 x
4.2 x
Table 7.0-1: NuScale Instrumentation and Controls Design and Applicable Regulatory Requirements Matrix (Continued)
Tier 2
5.3 x
5.4 x
6.4 x
6.5 x
Table 7.0-1: NuScale Instrumentation and Controls Design and Applicable Regulatory Requirements Matrix (Continued)
Tier 2
NUREG/CR-6303 x
SECY-93-087 x x
7.0-33
18.II.Q
GL 85-06 x
13 x
14 x x
15 x
32 x x x
33 x
34 x
Table 7.0-2: Highly Integrated Protection System Topical Report (HIPS TR) Application Specific Information Cross
Tier 2
49 x x x
50 x x
51 x x
('66
LVRODWLRQ
106
'HWHFWRUV 106
LVRODWLRQ
1RQ
036
6HQVRUV 57%V
DQG
87% 3=5+WU
6HQVRUV 7ULS
)LHOG7HUPLQDWLRQV
)LHOG7HUPLQDWLRQV
6HQVRU 036&DELQHWV %UHDNHUV
/RVVRI
(OHFWURQLFV 3RZHU
$& DQG 'LVWULEXWLRQ
7.0-37
6HQVRUV 6HSDUDWLRQ*URXSV
,QSXW DQG 3DQHO
3DQHO 'LYLVLRQV
0&6
&RQWURO
6LJQDOV
LVRODWLRQ LVRODWLRQ
Monitoring Monitoring
Trip Determination Trip Determination Trip Determination Trip Determination
and and
A B C D
Indication Indication
7.0-38
Monitoring Monitoring
ESFAS Voting and RTS Voting RTS Voting and ESFAS Voting
I I II II
Priority Logic I Manual Priority Logic I Priority Logic II Manual Priority Logic II
Actuation Actuation
LEGEND
RTS Reactor Trip System
ESFAS Engineered Safety Features Actuation System
Hard-wired Signal
One-way Serial Connection
Redundant One-Way Serial Data Connection
Revision 5
Tier 2
1 2 3 MIB CTB
CTB
Transmission into SFM only active
SDB1 SDB2 SDB3 when OOS switch is closed
MIB
Hard Wired Module
(HWM)
Bypass
SFMn... Trip
Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Rx
Position
Feedback 24-Hour SDIS I Hub
Timers
Revision 5
Tier 2
Division I
MWS
Backplane
MPS
Safety Function Modules SDIS I Hub
Gateway I
SFM 1 to n
24-Hour
1 2 3 MIB CTB Timers
Position
Feedback
CTB SC/TD ‘B’
Transmission into SFM only active SC/TD ‘C’
SDB1 SDB2 SDB3 when OOS switch is closed SC/TD ‘D’
MIB RTS II
Hard Wired ESFAS II
Module (HWM)
NOTE: Signals are RTS II ESFAS I RTS II ESFAS I RTS II ESFAS I Temporary CTB Connection
routed on the ESFAS ESFAS
backplane and
SVM SVM SVM SVM II
SVM SVM ESFAS MCS MPS
SD1 II SD3 II Gateway
SD1 SD2 SD2 SD3
7.0-40
BACKPLANE
Enable NS
Enable NS
Nonsafety
Nonsafety MIB MIB
SDB2 Control Signals
Control Signals SDB1 SDB3 SDB1 SDB3
SDB2
NOTE: Signals are
NOTE: Signals are routed on the
1 2 3 MIB MIB 1 2 3 MIB MIB
routed on the backplane and
backplane and isolated through the
Equipment Interface Equipment Interface HWM
isolated through the RTS I – MIB CM BACKPLANE ESFAS I – MIB CM
HWM BACKPLANE Modules Modules
EIM 1 to n EIM 1 to n
Tx Tx Tx Tx Tx Tx Tx Tx
MPS MPS
MCS Gateway I MCS Gateway I
MPS
MPS
Gateway
Gateway
II
II
Revision 5
Tier 2
Manual Manual
Priority Logic I Priority Logic II
Trip Trip
Control Rod
From EDNS Drive System
7.0-41
Coil#1
*Coil #2
Component-1
Vout
Coil #1
*Coil #2
Component-2
Vout
Hp Hs
I I
(Hp) (Hs)
Load
(Coil)
I (Load)
Lp Ls
I I
(Lp) (Ls)
Vin
Manual Manual
Priority Logic I Priority Logic II
Actuation Actuation
Gateway
Input Input Input
SFM
Sub Sub Sub
Module Module Module
Iso Iso Iso
Isolation Isolation Isolation Isolation
FPGA
FPGA FPGA FPGA FPGA
SDB 1 SDB 2 SDB 3 MIB CTB
RS-485 RS-485 RS-485 RS-485 RS-485 RS-485 RS-485 RS-485 RS-485
SG A Interface SG B Interface SG C Interface SG D Interface Interface Interface Interface Interface Interface
Backplane
Isolation
Master DIV-I DIV-II DIV-I DIV-II
Isolation
FPGA Isolation
FPGA FPGA FPGA FPGA
7.0-45
HWM Gateway
Isolation Isolation Isolation Isolation Isolation Isolation
Isolation
1RQ( '&'& '&'& '&'& '&'& '&'& '&'& 1RQ( '&'& '&'& '&'& '&'& '&'& '&'&
&219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5
32:(5 32:(5 32:(5 32:(5 32:(5 32:(5 32:(5 32:(5 32:(5 32:(5 32:(5 32:(5
( 6833/< 6833/< 6833/< 6833/< 6833/< 6833/< ( 6833/< 6833/< 6833/< 6833/< 6833/< 6833/<
6HQVRU 6HQVRU
6HQVRU 6HSDUDWLRQ*URXS$ 6HQVRU 6HSDUDWLRQ*URXS&
/RRS /RRS
(OHFWURQLFV &KDVVLV (OHFWURQLFV &KDVVLV
3RZHU 1RWH
3RZHU 1RWH
576DQG(6)$6&KDVVLV 576DQG(6)$6/RDG
7.0-46
3RZHU'LVWULEXWLRQ'LYLVLRQ, 3RZHU'LVWULEXWLRQ'LYLVLRQ,
1RQ( '&'& '&'& '&'& '&'& 1RQ( '&'& '&'& '&'& '&'&
&219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5
32:(5 32:(5 32:(5 32:(5 32:(5 32:(5 32:(5 32:(5
( 6833/< 6833/< 6833/< 6833/< ( 6833/< 6833/< 6833/< 6833/<
',675,%87('
',675,%87('
1RWH7KHWZRSRZHUVRXUFHVWRWKHFKDVVLVDUHDXFWLRQHHUHGRQHDFKPRGXOHLQWKHFKDVVLV
6KDUHGRUDXFWLRQHHUHG
Revision 5
Tier 2
1RQ( '&'& '&'& '&'& '&'& '&'& '&'& 1RQ( '&'& '&'& '&'& '&'& '&'& '&'&
&219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5
32:(5 32:(5 32:(5 32:(5 32:(5 32:(5 32:(5 32:(5 32:(5 32:(5 32:(5 32:(5
( 6833/< 6833/< 6833/< 6833/< 6833/< 6833/< ( 6833/< 6833/< 6833/< 6833/< 6833/< 6833/<
6HQVRU 6HQVRU
6HQVRU 6HSDUDWLRQ*URXS% 6HQVRU 6HSDUDWLRQ*URXS'
/RRS /RRS
(OHFWURQLFV &KDVVLV (OHFWURQLFV &KDVVLV
3RZHU 1RWH
3RZHU 1RWH
576DQG(6)$6&KDVVLV 576DQG(6)$6/RDG
7.0-47
3RZHU'LVWULEXWLRQ'LYLVLRQ, 3RZHU'LVWULEXWLRQ'LYLVLRQ,
1RQ( '&'& '&'& '&'& '&'& 1RQ( '&'& '&'& '&'& '&'&
&219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5 &219(57(5
32:(5 32:(5 32:(5 32:(5 32:(5 32:(5 32:(5 32:(5
( 6833/< 6833/< 6833/< 6833/< ( 6833/< 6833/< 6833/< 6833/<
',675,%87('
',675,%87('
1RWH7KHWZRSRZHUVRXUFHVWRWKHFKDVVLVDUHDXFWLRQHHUHGRQHDFKPRGXOHLQWKHFKDVVLV
6KDUHGRUDXFWLRQHHUHG
Revision 5
Tier 2
NMS EX-CORE
InstrumentaƟon
PPS
MWS
Sensors
SDIS SDIS
DIV I DIV II PCS
CTB
Temp Cable
Hard-Wired
Module (HWM)
Hard-Wired
Module (HWM)
Notes:
1. The MPS gateway, FPGA-CM, DIM, & display panels shown are typical for NPM 1-12.
2. Only one MPS communication module is shown. Hub communication modules for NPM 1 through 6 will be
grouped together with one PPS communication module and a nonsafety communication module. The
Hub communication modules for NPM 7 through 12 will be grouped together with only a nonsafety
communication module.
3. DIM/display panels will be separate for each NPM. PPS will have separate display panels. Although no
cabling is shown, there is a cable connection between the DIM and the display panels.
Isolation Isolation Isolation Isolation Isolation Isolation Isolation Isolation Isolation Isolation Isolation Isolation Isolation Isolation Isolation Isolation
Isolation Isolation Isolation Isolation Isolation Isolation Isolation Isolation Isolation Isolation Isolation Isolation Isolation
SDIS Hub
Isolation
FPGA DIM
Display Panel
Figure 7.0-17: Module Control System Internal Functions and External Interfaces
0RGXOH&RQWURO6\VWHP0&6
&RQGHQVDWH
/RZ9ROWDJH$&
3ROLVKHU5HVLQ
(OHFWULFDO
5HJHQHUDWLRQ
$X[LOLDU\%RLOHU 6LWH&RROLQJ:DWHU &LUFXODWLQJ:DWHU 'HPLQHUDOL]HG 'LVWULEXWLRQ
6KDUHGZLWK3&6
6\VWHP
6\VWHP 6\VWHP 6\VWHP :DWHU6\VWHP 6\VWHP
'LVSOD\2QO\
6WHDP*HQHUDWRU
&KHPLFDODQG 'HFD\+HDW
&RQWDLQPHQW
&RQGHQVDWHDQG 9ROXPH&RQWURO 5HDFWRU&RRODQW 0DLQ6WHDP 5HPRYDO6\VWHP
(YDFXDWLRQ
)HHGZDWHU6\VWHP 6\VWHP 6\VWHP 6\VWHP 'LVSOD\2QO\
6\VWHP
0363ULRULW\
/RJLF
0RGXOH&RQWURO 0RGXOH3URWHFWLRQ
6\VWHP 6\VWHP
3ODQW&RQWURO
6\VWHP
Actuator
Sensor Position
Actuator Feedback
RIO Protocol
I/O Network I/O Network
Communication Communication
Module Pair Module Pair
RIO Protocol
RIO Protocol
7.0-54
Actuator
Position
Sensor Actuator
Feedback
RIO Protocol
RIO Protocol
RIO Protocol
RIO Protocol
Control Network
Control Network
7.0-55
Protocol
Protocol
Protocol
Protocol
3ODQW&RQWURO6\VWHP3&6
/RZ9ROWDJH$& &RQGHQVDWH
(OHFWULFDO 3ROLVKHU5HVLQ
$X[LOLDU\%RLOHU 6LWH&RROLQJ:DWHU &LUFXODWLQJ:DWHU 'LVWULEXWLRQ 'HPLQHUDOL]HG 5HJHQHUDWLRQ
6KDUHGZLWK0&6
5:06±5$':DVWH0DQDJHPHQW6\VWHP 3&:6±3RRO&RROLQJ:DWHU6\VWHP
6ROLG5DG:DVWH
5DGLRDFWLYH:DVWH 0DQDJHPHQW 5HDFWRU3RRO 6SHQW)XHO3RRO 3RRO/HDNDJH
'UDLQ6\VWHP 6\VWHP &RROLQJ6\VWHP &RROLQJ6\VWHP 'HWHFWLRQ6\VWHP
1LWURJHQ
3RWDEOH:DWHU &KLOOHG:DWHU 8WLOLW\:DWHU 'LVWULEXWLRQ 7XUELQH%XLOGLQJ
6\VWHP 6\VWHP 6\VWHP 6\VWHP +9$&6\VWHP
3ODQW6\VWHPV
0HWHRURORJLFDO
5DG:DVWH (QYLURQPHQWDO 6HLVPLF0RQLWRULQJ
1065HIXHO 6\VWHP
%XLOGLQJ+9$& &RQWURO5RRP %DFNXS3RZHU 0RQLWRULQJ6\VWHP
'LVSOD\2QO\ 'LVSOD\2QO\
6\VWHP +9$&6\VWHP 6\VWHP 'LVSOD\2QO\
)L[HG$UHD
5HDFWRU%XLOGLQJ 0HGLXP9ROWDJH 3ODQW9LGHR )LUH3URWHFWLRQ
5DGLDWLRQ
+9$&6\VWHP $&(OHFWULFDO 0RQLWRULQJ6\VWHP 6\VWHP
0RQLWRULQJ6\VWHP
'LVWULEXWLRQ 'LVSOD\2QO\ 'LVSOD\2QO\
'LVSOD\2QO\
6\VWHP
5HDFWRU%XLOGLQJ 0RGXOH$VVHPEO\
'U\'RFN*DWH
&UDQH (TXLSPHQW%ROWLQJ
'LVSOD\2QO\
'LVSOD\2QO\ 'LVSOD\2QO\
7XUELQH%XLOGLQJ 5HDFWRU%XLOGLQJ
&UDQH (TXLSPHQW'RRU
'LVSOD\2QO\ 'LVSOD\2QO\
3363ULRULW\
/RJLF
3ODQW 3ODQW3URWHFWLRQ
&RQWURO6\VWHP 6\VWHP
Instrumentation and Controls - Introduction and Overview
6DIHW\'LVSOD\DQG
,QGLFDWLRQ6\VWHP
0RGXOH&RQWURO
6\VWHP
Revision 5
NuScale Final Safety Analysis Report Fundamental Design Principles
The design of NuScale safety-related instrumentation and control (I&C) systems is based on
four fundamental design principles:
• independence
• redundancy
• predictability and repeatability
• diversity and defense-in-depth (D3)
Section 7.1.1 describes the safety-related I&C system design bases and additional design
considerations.
Section 7.1.2 through Section 7.1.5 describe how the four fundamental design principles are
incorporated into the I&C system design. Functional block diagrams showing I&C architectures
are provided as part of the system descriptions in Section 7.0.4.
Section 7.1.6 is the safety evaluation and describes how the NuScale design conforms to
applicable regulations.
Section 7.1.7 describes the cross-cutting design attribute of simplicity and how it is
incorporated into the design of NuScale safety-related I&C systems.
Section 7.1.8 describes how hazard analyses have been used to examine the NuScale
safety-related I&C systems, subsystems, and components to identify unintended or unwanted
I&C system operation that could adversely affect required safety-related functions.
The safety-related module protection system (MPS) uses the highly integrated protection
system (HIPS) platform described in topical report NuScale Power, LLC, TR-1015-18653-P-A,
"Design of the Highly Integrated Protection System Platform Topical Report,"
(Reference 7.1-1). This topical report describes the HIPS platform and demonstrates
conformance to NRC Regulatory Guides (RGs) and Institute of Electrical and Electronics
Engineers (IEEE) standards applicable to safety-related I&C applications. Specifically, the
HIPS platform conforms to RG 1.153, Rev. 1, which endorses IEEE Std 603-1991 "IEEE
Standard Criteria for Safety Systems for Nuclear Power Generating Stations”
(Reference 7.1-3) and the correction sheet dated January 30, 1995. Because the HIPS
platform uses programmable digital devices, RG 1.152, Rev. 3, IEEE Std 7-4.3.2-2003 "IEEE
Standard Criteria for Digital Computers and Safety Systems of Nuclear Power Generating
Stations” (Reference 7.1-5), Digital I&C Interim Staff Guidance 04 (D&IC ISG-04), and the
Staff Requirements Memorandum for SECY 93-087 were also used for the general platform
design.
The information in this section satisfies the application specific information requirements
in TR-1015-18653-P-A listed in Table 7.0-2 for application specific action item (ASAI)
numbers 1, 3, 4, 5, and 6.
This section identifies regulatory requirements that govern the I&C system design.
Consistent with General Design Criteria (GDC) 1, I&C systems are designed to the
quality assurance program described in Section 17.5. The quality and safety
classifications of structures, systems, and components (SSC) are identified in
Section 3.2.
Consistent with GDC 2, SSC required to function during natural phenomena events are
located within structures that protect them against natural phenomena.
Consistent with GDC 4, the I&C systems are designed for environmental conditions
associated with normal operation, maintenance, testing, and postulated accidents to
which they may be subjected and be required to function.
Consistent with GDC 5, the MPS, neutron monitoring system (NMS), module control
system (MCS) and in-core instrumentation system (ICIS) are not shared between
NuScale Power Modules (NPMs). The plant control system (PCS) and plant protection
system (PPS) are shared between multiple NPMs and are designed to not adversely
affect the ability of I&C platforms that perform safety-related functions.
Consistent with GDC 10, the MPS provides reactor trips and engineered safety feature
(ESF) actuations which ensure specified fuel design limits are not exceeded during
normal operations and anticipated operational occurrences (AOOs).
Consistent with GDC 13, the I&C systems monitor variables and systems over their
anticipated ranges for normal operations, AOOs, and accident conditions.
Consistent with GDC 15, the MPS and NMS initiate safety-related functions that ensure
the design conditions of the reactor coolant pressure boundary (RCPB) are not
exceeded during normal operations or as a result of an AOO.
Consistent with GDC 16, the MPS initiates containment isolation and safety-related
functions to ensure the containment design conditions are not exceeded for the
duration of a postulated accident.
Consistent with PDC 19, the I&C systems are designed to ensure the ability to control
each NPM during normal and accident conditions. The NuScale main control room
(MCR) is designed with the ability to place the reactors in safe shutdown in the event of
an MCR evacuation event, and for safe shutdown to be maintained without operator
action thereafter. Prior to evacuating the MCR, operators trip the reactors, initiate
decay heat removal and initiate containment isolation. These actions result in passive
cooling that achieves safe shutdown of the reactors. Operators can also achieve safe
shutdown of the reactors from outside the MCR in the MPS equipment rooms within
the reactor building. Following shutdown and initiation of passive cooling from either
the MCR or the MPS equipment rooms, the NuScale design does not rely on operator
action, instrumentation, or controls outside of the MCR to maintain safe shutdown
condition. There are no displays, alarms, or controls in the RSS credited to meet the
Consistent with GDC 20, the MPS, with inputs from the NMS, senses when specified
parameters are exceeded and initiates reactor trips and ESF actuations to ensure that
specified fuel design limits are not exceeded as a result of AOOs.
Consistent with GDC 21, MPS and NMS have sufficient redundancy and independence
to ensure that no single failure results in the loss of the protection function. Individual
SSC of the MPS and NMS may be removed from service for testing without loss of
protection functions.
Consistent with GDC 22, the MPS and NMS have sufficient functional diversity and
component diversity to prevent the loss of a protection function during operations,
maintenance, testing, and postulated accidents, and to withstand the effects of natural
phenomena.
Consistent with GDC 23, the MPS fails into a safe state upon loss of electrical power or if
adverse environmental conditions are experienced.
Consistent with GDC 24, the MPS has physical, electrical, communication, and
functional independence within the system and from associated nonsafety-related
systems and components.
Consistent with GDC 25, the MPS initiates reactor trip functions to ensure that specified
fuel design limits are not exceeded for any single malfunction of the reactivity control
system. Compliance with GDC 25 is discussed in Section 4.6.2
Consistent with GDC 28, the MPS initiates reactor trip functions to limit the potential
amount and rate of reactivity increase and to ensure sufficient protection from
reactivity accidents. Compliance with GDC 28 is discussed in Section 4.6.2.
Consistent with GDC 29, the MPS and NMS are designed with redundancy and diversity
to ensure a high probability their safety-related functions are performed in the event of
AOOs.
Consistent with GDC 64, the MCS and PCS monitor radioactivity releases, the reactor
containment atmosphere, and plant environments for radioactivity that may be
released from normal operations, AOOs, and postulated accidents.
Consistent with 10 CFR 50.34(b)(2)(i), the design of the I&C systems and auxiliary
features of the I&C system design is discussed in Section 7.0.4 and Section 7.2.8
respectively.
Consistent with 10 CFR 50.34(f)(2)(iv), the I&C systems provide the capability to display
key plant variables over their anticipated ranges for normal operation, AOOs, and
accident conditions.
Consistent with 10 CFR 50.34(f)(2)(v), the MCS provides bypassed and operable status
indication of safety systems.
Consistent with 10 CFR 50.34(f)(2)(xi), the displays in the main control room (MCR)
indicate reactor safety valve position.
Consistent with 10 CFR 50.34(f)(2)(xiv)(C), the MPS initiates containment isolation and
ensures that isolation valves do not re-open upon isolation signal reset.
Consistent with 10 CFR 50.34(f)(2)(xviii), the I&C systems provide MCR indications of
inadequate core cooling.
Consistent with 10 CFR 50.34(f)(2)(xix), the I&C systems provide instrumentation for
monitoring plant conditions following an accident, including potential core damage.
Consistent with 10 CFR 50.36(c)(1)(ii)(A), the MPS initiates automatic protective actions
prior to exceeding a safety limit.
Consistent with 10 CFR 50.36(c)(3), the I&C systems are designed meet surveillance
requirements to ensure that the necessary quality of SSC is maintained such that
operation is within safety limits and limiting conditions of operations are met.
Consistent with 10 CFR 50.49, the I&C equipment that performs the functions in
10 CFR 50.49(b) will remain functional during and following design basis events (DBEs).
Consistent with 10 CFR 50.54(jj) and 10 CFR 50.55(i), I&C systems are designed, tested,
and inspected to quality standards commensurate with the safety function to be
performed.
Consistent with 10 CFR 50.55a(h), the MPS and NMS are designed in accordance with
IEEE Std 603-1991 and the correction sheet dated January 30, 1995.
As described in Table 1.9-5, 10 CFR 50.34(f)(2)(xii) and 10 CFR 50.34(f)(2)(xxii) are not
applicable to the NuScale design. As described in Table 1.9-5, the NuScale design
supports an exemption from the power supply requirements for pressurizer level
indication included in 10 CFR 50.34(f)(2)(xx).
The protection systems are used to facilitate protective actions of the MPS (reactor
trip and ESF functions) in response to monitored variables exceeding
pre-established limits. Table 7.1-1 identifies the specific DBEs and classifications for
which MPS protective actions are credited in Chapter 15 analyses. The DBEs,
including AOOs, infrequent events (IEs), and postulated accidents for the NuScale
Power Plant design are listed in Table 15.0-2. The MPS functional logic diagrams are
shown in Figure 7.1-1a through Figure 7.1-1ao.
Table 7.1-2 identifies the specific NPM variables that provide input to the MPS and
includes the instrument range for covering normal, abnormal and accident
conditions, and the nominal operating value at 100 percent rated thermal power
(RTP).
The NMS-excore subsystem monitors the continuous reactor neutron flux from
shutdown to full-rated power across three overlapping detector ranges: the source
range, intermediate range, and power range.
Certain monitored variables are relied upon to execute protective actions when
setpoints based on the analytical limits are exceeded. The analytical limits and
permissive conditions for operating bypasses are summarized in Table 7.1-3 and
Table 7.1-5 for the reactor trip system (RTS) and Table 7.1-4 and Table 7.1-5 for the
engineered safety features actuation system (ESFAS). For additional information on
the MPS interlocks and permissive, see Table 7.1-5. The NMS provides
safety-related input to the MPS to support its functions.
The ESFAS delays assumed in the plant safety analysis are a combination of sensor
response time, MPS timing budget allocation, and actuation device delays. The
sensor response delays are defined in Table 7.1-6. The delay times in Table 7.1-6
associated with ESFAS signals don’t include the delay times associated with the
actuation device (e.g. valve stroke times) with the exception of opening the
pressurizer heater breakers.
There are manual trip or actuate switches for each automatic trip or actuate
function in the MCR. These switches are connected to the hard-wired modules
(HWMs) in the RTS and ESFAS chassis where the signals are isolated and converted
to logic-level signals and placed on the backplane. These signals are provided to
the associated equipment interface module (EIM) actuation priority logic circuits
downstream of the field programmable gate array (FPGA) programmable logic.
All of the variables monitored by the MPS listed in Table 7.1-2 are sent to the safety
display and indication system (SDIS) and the MCS to be displayed in the MCR as
required by those systems. These variables include all that are needed for reactor
trip and ESF actuations, and post-accident monitoring (PAM) variables that would
be required for monitoring after an event. When allowed by plant procedures to
reconfigure systems after a reactor trip or an ESF actuation, the components can be
repositioned using the nonsafety-related MCS when the enable nonsafety control
switch is activated and no automatic or manual safety actuation signal is present.
All required protective actions by the MPS are automatic. There are no credited
manual actuations required for the MPS to accomplish its safety functions;
however, manual initiation at the division level of the automatically initiated
protective actions is provided in the MCR. The MCR environmental conditions
during manual operation are described in Section 9.4.1.
Each MPS and NMS variable used to initiate a protective action is monitored by four
independent separation groups, with one or more sensors in each separation
group. The separation of redundant sensors creates a potential for spatial
dependence for some variables as discussed below.
The physical separation of redundant MPS pressure and level sensors is not a
spatial dependence concern. Pressure and level are distributed within the vessel or
pipe so that redundant sensors do not see varying process conditions as a function
of location.
The location of NMS redundant neutron flux detectors in separate quadrants of the
NPM does not result in spatial dependence concerns because of core radial
symmetry.
The RCS narrow range Thot is measured by three RTDs in each MPS separation
group. One RTD separation group is located in each RPV quadrant at the top of the
hot leg riser. The MPS averages the three RTD inputs to compensate for
temperature-streaming effects that may be present at the RTD location.
The RCS narrow range Tcold is measured by two RTDs in each MPS separation
group. One RTD separation group is located in each RPV quadrant in the lower
downcomer. Although reactor coolant flow is expected to be thoroughly mixed as
it passes through the steam generator (SG) tube region of the RPV downcomer,
some temperature-streaming effects are possible. The MPS averages the two Tcold
inputs to compensate for temperature-streaming effects that may be present in the
RPV downcomer region.
The RCS flow is measured by four sets of digital-based flow transducers mounted in
the RPV wall in the downcomer region, one set in each MPS separation group. Each
of the four redundant sets of transducers are located in a separate quadrant of the
RPV. Reactor coolant flow is expected to be thoroughly mixed as it passes through
the SG tube region of the downcomer, so that radial flow variations between RPV
quadrants are negligible.
Each NPM contains two steam headers. Main steam temperature is measured by
four RTDs in each steamline, one per separation group, for a total of eight. The
measurement of main steam temperature is not spatially dependent because the
RTDs are located in the same section of vertical pipe where steam flow is uniform.
The MPS and NMS are designed to operate during normal, abnormal, AOO, IE, and
accident conditions for a minimum of 72 hours during a loss of alternating current
(AC) power. The MPS operates in PAM-Only mode after a loss of AC power for
The MPS and NMS rack-mounted equipment is installed in a mild environment. The
MPS rooms provide an environment that would at no time be more severe than the
environment that would occur during normal plant operation, including AOOs. The
environmental qualification requirements for the MPS and NMS rack mounted
equipment are identified in Section 3.11.
A failure modes and effects analysis (FMEA) was conducted for both the MPS and
the NMS. This is a systematic procedure for addressing failures for all components
of a system and for evaluating their consequences. The essential function of an
FMEA is to consider each part of the system, how it may fail, and what the effect of
the failure on the system would be in the presence of a single failure.
The MPS automatically initiates a reactor trip or ESF function when the associated
setpoint is exceeded. Once initiated, safety functions continue until completed.
The completion of the safety function is satisfied once all equipment is in the
actuated position and the plant conditions are stabilized. The MPS may be returned
to normal when the initiating condition is no longer present. Deliberate and
separate operator action is required to return the MPS to a normal configuration,
and is described in Section 7.2.3.3. The NMS does not initiate any protective
functions; it only provides safety-related input to the MPS.
The MPS and NMS do not contain any protective provisions that could prevent
either system from accomplishing its safety function.
Variables and their type classification are based on their accident management
function as identified in abnormal operating procedures, emergency operating
procedures, and emergency procedure guidelines. Since the abnormal and
emergency operating procedures and guidelines have not been developed,
NuScale developed an approach to identify PAM variables as described below.
The approach and basis for the identification and categorization of the variables
listed in Table 7.1-7 is:
• review of systems with radiation monitoring equipment and potential effluent
release paths.
• operator actions assumed in the probabilistic risk assessment (PRA) (see
Section 19.1).
• operator actions identified during human factors engineering (HFE) task
analysis (see Section 18.4).
• industry operating experience
• engineering judgment.
• the identification process and its results reviewed by a multidisciplinary group
(see Section 7.2.13.2).
The PAM Type B, C, D, and E variables are summarized in Table 7.1-7. Figure 7.1-2
shows the system on which the PAM variable is displayed and the power supplies
for each PAM variable. The associated system which processes the sensor input is
also provided in Table 7.1-7 and Figure 7.1-2. The NuScale reactor design has no
Type A variables because there are no operator actions credited in any Chapter 15
anticipated operational occurrence, infrequent event, or accident, nor the station
blackout or anticipated transient without scram analysis.
The only important human actions modeled in the probabilistic risk assessment are
in response to multiple failures of automatic safety systems and the actions are not
required to meet the assumptions of any accident analysis licensing basis.
Type B Variables
Type B variables are those variables that provide primary information to the control
room operators to assess the plant’s critical safety functions that have been defined
for the NuScale power plant. These are accomplishing or maintaining the following
three critical safety functions:
• reactivity control
• remove fuel assembly heat
• containment integrity
NuScale has selected these three critical safety functions based on the plant design.
The critical safety function for containment integrity has been modified to include
the aspects of radioactive effluent control. The “remove fuel assembly heat” critical
safety function includes the aspects of reactor coolant system (RCS) integrity. This is
due to the integral nature of emergency core cooling system (ECCS) and RCS
integrity—actuating ECCS opens valves to allow steam release to the containment
and return of water back to the RCS —it is done to maintain core cooling and
protect the fuel clad fission product barrier. This is automatically actuated when
there is an existing loss of RCS integrity as indicated by low reactor pressure vessel
(RPV) riser water level or high containment water level.
The Type B variables identified in Table 7.1-7 are those necessary to implement the
plant abnormal operating procedures, emergency operating procedures and
functional restoration procedures, and to maintain the plant critical safety
functions described below.
The Type B variables that provide direct indication and are used to assess the
process of accomplishing or maintaining reactivity control are neutron flux and
core inlet and exit temperature.
The Type B variables selected that provide direct indication and verification and
used to assess the process of accomplishing or maintaining the combined remove
fuel assembly heat and RCS integrity critical safety functions are core exit
temperature, RPV riser water level, wide range RCS pressure, containment water
level, degrees of subcooling, and wide-range RCS hot temperature.
Type C Variables
Type C variables are those variables that provide primary information to the control
room operators to indicate the potential for breach or the actual breach of fission
product barriers: fuel cladding, reactor coolant system, and containment pressure
boundary.
The selection of these variables represents a minimum set of plant variables that
provide the most direct indication of the integrity of the three fission product
barriers and provide the capability for monitoring beyond the design limits
(extended range).
Core exit temperature and inside the bioshield radiation monitor are the variables
related to monitoring of the fuel cladding fission product barrier. Core exit
temperature is the most direct measure of the thermodynamic state of the core—it
is used to infer when the fuel clad damage is occurring. The inside bioshield area
radiation monitor is the primary method used to assess the extent of the fuel
cladding breach and to identify fuel cladding breaches where the core is not
damaged due to inadequate core cooling.
The primary variables used to assess the status of the reactor coolant system fission
product barrier are the RPV riser level and RCS pressure. RPV riser level can show a
loss of boundary through a loss of inventory, resulting in a reduction in level. Wide
range RCS pressure is used to assess challenges to the barrier from overpressure
and as an alternate variable to RPV riser level for primary assessment.
Type D Variables
The Type D variables listed in Table 7.1-7 are those variables that are required in
procedures and licensing basis documentation to perform the following:
• indicate the performance of those safety systems and auxiliary supporting
features necessary for the mitigation of design-basis events.
• indicate the performance of other systems necessary to achieve and maintain a
safe shutdown condition.
• verify safety system status.
The Type D variables identified and listed in Table 7.1-7 are based upon the plant
accident analysis licensing basis and those necessary to implement the plant
abnormal operating procedures, emergency operating procedures and functional
restoration procedures.
Type E Variables
Type E variables identified and listed in Table 7.1-7 are used in determining the
magnitude of the release of radioactive materials and continually assessing such
releases. The variable identification was made on the following criteria:
• Variables identified and related to pathways for release of radioactive material.
If the MCR is evacuated, the RSS serves as a central location for the operators to
monitor the modules in a safe shutdown condition with DHRS in service for each
module. Additionally, the RSS provides defense-in-depth capability to monitor the
plant remotely from the MCR and control balance of plant equipment to support
asset protection and long-term plant recovery in events where the MCR becomes
uninhabitable. An MCR evacuation occurrence is a special event and is not
postulated to occur simultaneously with any DBE, nor does it cause fuel damage, or
result in consequential loss of function of the RCPB or primary containment
barriers. The RSS provides a safe alternate location during an MCR evacuation
occurrence to allow monitoring of each NPM.
The control room habitability systems are designed to allow continuous occupancy
in the MCR during radiation, hazardous chemical, or hazardous gas release. In
addition, the MCR is protected in case of a security event.
Despite these considerations, events for the RSS design and licensing basis include
smoke due to fire in the MCR and loss of the Control Building as part of a loss of a
large area.
At the onset of an MCR evacuation, the operators trip the reactors and initiate
decay heat removal and containment isolation for each reactor prior to leaving the
MCR. Following evacuation of the MCR, the ability to isolate the MPS manual
switches to prevent spurious actuations is provided in the RSS as described in
Section 7.2.12. An alarm is annunciated in the MCR when the MCR hard-wired
switches are isolated using the MCR isolation switches in the RSS, see Figure 7.1-1j.
The MPS manual isolation switches are mounted in a Seismic Class I enclosure to
allow them to remain functional following an earthquake. Controls are available
outside the MCR in the associated MPS equipment rooms that provide the
capability to trip the reactors, initiate DHRS and initiate containment isolation,
which will initiate passive cooling and places and maintains the NPMs in safe
shutdown. The MCS equipment in the RSS provides nonsafety-related
human-system interface (HSI) and direct readings of the process variables
necessary to monitor safe shutdown of each NPM. Figure 1.2-14 shows the location
of the RSS equipment.
offsite power is not available for 72 hours, dependent on the conditions described
in the fire hazards analysis as described in Section 9A.
The safety display and indication system (SDIS) as described in Section 7.0.4.4,
provides HSI for the MPS and PPS to monitor and display PAM variables, and
provides the capability for control inputs and status information. The SDIS is a
nonsafety-related, nonrisk-significant system; however, because it supports the
PAM function, the SDIS meets augmented quality and regulatory requirements as
described in Table 3.2-1.
The PPS as described in Section 7.0.4.3 provides monitoring and control of plant
systems that are common to multiple NPMs. The PPS is nonsafety-related; however,
because it supports the PAM function, the PPS is designed to meet augmented
quality and regulatory requirements as described in Table 3.2-1. The PPS functional
logics are shown in Figure 7.1-3a through Figure 7.1-3f.
All of the variables monitored by the PPS listed in Table 7.1-8 are sent to the SDIS
and the PCS to be displayed in the MCR as required by those systems. These
provide the display and indication to support actuation of the control room
habitability system and required PAM variables from the PPS.
7.1.2 Independence
The independence design principles for the NuScale I&C systems meet the criteria for
independence in IEEE Std 603-1991, Section 5.6 and GDC 13, 21, 22, and 24, as described in
this section. The systems that perform PAM functions for Type B and C variables include the
MPS and SDIS, which are designed to meet the criteria for independence in
IEEE Std 497-2002, as endorsed by RG 1.97, Rev. 4.
The physical and electrical independence attributes of the MPS and NMS meet the
guidance in RG 1.75 Rev.3, which endorses IEEE Std 384-1992 "IEEE Standard Criteria for
Independence of Class 1E Equipment and Circuits” (Reference 7.1-14).
The communication independence attributes of the MPS meet the guidance in RG 1.152,
which endorses IEEE Std 7-4.3.2-2003.
The information in this section satisfies the application specific information requirements
in TR-1015-18653-P-A listed in Table 7.0-2 for ASAI numbers 8, 9, 20, 22, 23, 46, 52, 53, 55,
60, and 61.
The MPS structures, systems, and components that comprise a separation group or
division are independent and physically separated to retain the capability of
performing required safety functions during and following a DBE.
The NMS separation groups are physically independent and separate. The NMS-excore
neutron detectors are installed 90 degrees equidistant around the NPM, and the
associated cabling is routed in physically separate cable trays and raceways. The NMS
hardware and signal processing equipment associated with the MPS divisions is
installed in separate, seismically qualified equipment rooms. The NMS Separation
Group A and C signal processing equipment is located in the MPS Separation Group A
and C (Division I) equipment rooms on the 75'-0" elevation of the RB, and NMS
Separation Group B and D signal processing equipment is located in the MPS
Separation Groups B and D (Division II) equipment rooms on the 86'-0" elevation of the
RB (see Figure 1.2-14 and Figure 1.2-15, respectively).
The SDIS has two separate and independent hubs. The SDIS hubs are located in the
seismically qualified Control Building (CRB) at the 50' level in the same divisionally
separate rooms as the PPS.
The MPS electrical isolation devices used as a safety system boundary are considered
part of the MPS and are qualified as part of the MPS in accordance with
IEEE Std 384-1992. The isolation devices are tested to confirm that credible failures on
the nonsafety side of the isolation device do not prevent the associated safety system
channel from meeting the minimum performance requirements.
• Electrical power supply. The MPS receives electrical power from the
nonsafety-related highly reliable DC power system (EDSS). The MPS provides Class
1E isolation from the nonsafety-related EDSS by using Class 1E isolation devices
that are part of the MPS and are used as the safety system boundary (see
Figure 7.0-2). The DC-to-DC voltage converters are used for Class 1E isolation and
protection of the MPS equipment. The DC power sources are redundant and an
alarm is generated if one of the redundant supplies fails (see Figures 7.0-11a and
7.0-11b).
The NMS separation groups receive isolated, independent power supplied by the EDSS
through Class 1E isolation devices that are qualified as part of the NMS.
The PPS, SDIS, ICI, MCS, and PCS are nonsafety-related SSC and are separated from
safety-related SSC in accordance with the NuScale Electrical Design Criteria. The SDIS
receives electrical power from the EDSS. The SDIS divisions are powered from
independent EDSS sources.
With the exception of interdivisional voting, the communication within the MPS
separation group is independent and does not rely on communication from outside
the respective separation group or division to perform a safety function. The MPS
separation groups perform independent signal conditioning and trip determination,
and provide that input to the scheduling and bypass module (SBM) which provides
inputs to the schedule and voting module (SVM) for the two-out-of-four voting logic.
One-way, isolated communication links are provided from the MPS to the MCS through
isolation devices that are components of the MPS. This is accomplished by the MIB
communications module within the separation group and RTS and ESFAS division.
Isolated communication links between the MPS and the nonsafety-related MWS and
SDIS hubs are provided by the MPS gateway. The MPS gateway consolidates the
information received from the four separation groups, RTS, and ESFAS, and provides a
qualified isolated one-way communication path to the MWS and the SDIS hubs. There
are two nonsafety-related MPS gateway chassis that are qualified as part of the MPS,
one for each division of MPS.
There are no shared functions between the MPS separation groups or divisions. The
MPS separation groups and divisions are self-reliant and have no dependency on
functions outside the separation groups or divisions. The MPS communication
architecture is isolated between the separation groups and other nonsafety-systems,
which supports functional independence.
To support functional independence in the EIM configurations within the MPS, there
are three rules that are applied.
7.1.3 Redundancy
The redundancy design principle is incorporated into the design of the NuScale I&C
systems, and conforms to the single-failure criterion in IEEE Std 603-1991, Section 5.1 and
the criteria of IEEE Std 497-2002, Section 6.1 for Type B and C PAM variables. The I&C system
design also conforms to GDC 21 and 24. Additionally, the redundancy attributes of the
NuScale safety-related I&C systems are designed to meet the guidance in RG 1.53, Rev. 2,
which endorses IEEE Std 379-2000 "IEEE Standard for Application of the Single-Failure
Criterion to Nuclear Power Generating Station Safety Systems” (Reference 7.1-8).
The information in this section satisfies the application specific information requirements
in TR-1015-18653-P-A listed in Table 7.0-2 for ASAI numbers 12, 13, 14, 21, and 32.
Redundancy is used to achieve system reliability goals and to demonstrate that the
safety-related I&C systems can perform the required safety functions during a DBE while
also incurring
• single detectable failures within the safety systems concurrent with identifiable but
non-detectable failures
• failures caused by the single failure
• failures and spurious system actions that cause or are caused by the DBE
The NuScale MPS incorporates redundancy into the design as summarized in Section 5
of TR-1015-18653-P-A.
Redundancy within the MPS is achieved by using four separation groups of sensors,
detectors, and trip determination, and using two divisions of RTS and ESFAS voting and
actuation circuitry.
The MPS uses two-out-of-four voting so that a single failure of an initiation signal or trip
determination does not prevent a reactor trip or ESF actuation signal from occurring
when required. The two-out-of-four design also ensures that a single failure does not
cause spurious or inadvertent reactor trips or ESF actuations.
The MPS is designed to allow repair and testing of components while still maintaining
the required level of redundancy such that the MPS remains capable of performing its
safety function during repair and testing. Section 7.2.4 provides more detail regarding
the design of the MPS operating and maintenance bypass functions.
The MPS was evaluated to determine where and how the MPS structures, systems and
components could fail, and to assess the impact of the failures on the safe operation of
the plant.
The MPS was divided into four groups to evaluate the effect of a single failure. The first
group consisted of those components in the MPS that are common to both the RTS and
ESFAS. The second group was made up of the associated RTS functions. The third
group was analyzed based on the ESFAS functions. Finally, the last group analyzed the
external communications and supporting functions associated with the MPS.
Only single failures were considered and evaluated for the MPS design. Failure effects
on the system assume no other coincident failures occur. Failures related to incorrect
transmission of test or calibration information assume a test or calibration was
initiated, successfully completed, and communicated as failed. A test or calibration
failing and being communicated as successful would only result from two concurrent
failures (whatever caused the test or calibration to fail and incorrectly communicating
the results as successful). Therefore, the MPS evaluation did not assume failures caused
by errors associated with improper tests.
As described in Section 8.1.2.2, for the EDSS design, the power supplied to the MPS by
the EDSS is monitored by the MPS Class 1E isolation devices. Therefore, failures of the
EDSS are bounded by the MPS failure modes and effects analysis portions of the system
bounded by the analysis for the Class 1E isolation devices.
There are no single failures or non-detectable failures that can prevent the MPS from
performing its required safety functions.
The NMS consists of four independent, redundant separation groups. A single failure
within the independent separation group does not prevent the NMS from performing
required safety functions. The separation groups generate NMS signals that are sent to
the MPS, and the trip determination and voting logic is then performed within the MPS.
No single failures exist within the NMS that would prevent the NMS from performing its
primary safety function. A failure of one channel (separation group) of the NMS still
allows the MPS to perform its required safety function because of the two-out-of-four
coincidence voting logic used by the MPS. The following NMS components were
evaluated to ensure the NMS remains functional in the presence of a single failure:
• NMS-excore detector and integrated mineral insulated cables
• NMS-excore pre-amplifier and soft coaxial cabling
• NMS-excore channel signal processing equipment
• NMS-excore power supply/Class 1E isolation device
• NMS-refuel sub-system (sensor, pre-amplifier, channel, and associated power
supply)
• NMS-flood sub-system (sensor, pre-amplifier, channel, and associated power
supply)
The MCS and PCS are designed with redundant control networks as described in
Section 7.0.4.5 and Section 7.0.4.6, respectively. The MCS and PCS architectures
incorporate redundancy into the nonsafety I&C architecture design at the human
machine interface layer, the control network layer, the controllers, and the remote I/O
network layer. The flow of data is uninterrupted by a single component, cable, or
device failure. In addition, redundant process system components are segregated onto
alternate I/O modules to ensure that MCS and PCS component-level failures do not
impact redundant process equipment.
Redundancy is incorporated into the RSS by providing redundant MCS and PCS
operator workstations for plant monitoring when the MCR is evacuated. When the
operators evacuate the MCR and occupy the RSS, two manual isolation switches for the
MPS divisions are provided to isolate the MPS manual actuation switches in the MCR to
prevent fires in the MCR from causing spurious actuations of associated equipment.
The PPS consists of two independent and redundant divisions. A single failure within
either division does not prevent the PPS from performing required protection
functions. The PPS failure modes and effects analysis also considered the effects of
The SDIS receives inputs from the MPS and PPS through communication interface
modules. The SDIS consists of two independent divisions of data paths to the display
panels. A single failure within either division does not prevent the SDIS from
performing required functions. Either of the SDIS divisions is capable of accomplishing
the SDIS function.
Predictability and repeatability design principles for the NuScale I&C systems are designed
to meet the criteria for system integrity in IEEE Std 603-1991, Section 5.2 and 5.5 and
GDC 13, 21, and 29 as described in this section. The information in this section satisfies the
application specific information requirements in TR-1015-18653-P-A listed in Table 7.0-2 for
ASAI numbers 19, 56, and 59.
The MPS architecture uses the HIPS platform. This platform is designed to produce the
same outputs for a given set of input signals within well-defined response time limits.
Section 7.0 of TR-1015-18653-P-A describes how the platform and components function,
and provides functional block diagrams to demonstrate how it meets the criteria for
predictability and repeatability.
The MPS response time analysis demonstrates that the MPS performs and completes its
required safety functions in a predictable and repeatable manner. Section 7.7 of
TR-1015-18653-P-A describes the calculation used to determine worst-case digital time
response for an MPS channel.
The actuation delays assumed in the plant safety analysis are listed in Table 7.1-6. The RTS
timing analysis is defined from the point in time when the monitoring process variable
exceeds its predetermined setpoint to when the reactor trip breakers open. The MPS digital
portion of the RTS function is accounted for in the safety analysis. For the RTS protective
function, the MPS response time is comprised of the analog input delay plus the digital
time response delay plus the analog output delay and includes the time for the reactor trip
breakers to open. The MPS digital time response delay is described in Section 7.7 of
TR-1015-18653-P-A.
For the ESFAS protective functions, the actuation delays in Table 7.1-6 are assumed in the
plant safety analysis and are defined as the time from when the monitored process variable
exceeds the predetermined setpoint until the EIM output is de-energized. The MPS portion
of the ESFAS functions is accounted for in the safety analysis. This time allocation budget is
comprised of the analog input delay plus the digital time response delay plus the analog
output delay and is defined from the sensor input to the SFM input terminals to the EIM
output command to the final actuation device. For the pressurizer heater trip function, this
time requirement includes the time for the pressurizer heater trip breakers to open.
The NuScale I&C system design includes features and processes to mitigate a common
cause failure (CCF) in the MPS because of digital-based failures which could disable a safety
function.
The D3 assessment of the NuScale I&C design is consistent with the guidelines in
NUREG/CR-6303. This assessment focused on the MPS which is the only safety-related
digital I&C system. The assessment is summarized in Section 7.1.5.1.
The D3 coping analysis methodology and results for postulated digital-based CCF
vulnerabilities are summarized in Section 7.1.5.2.2. Coping strategies include identification
of signals or components unaffected by the postulated CCF that can be used to perform
the safety function, different functions that can provide adequate protection, or
justification for taking no action based on meeting analytical acceptance criteria without
diverse mitigation actuation.
The information in this section satisfies the application specific information requirements
in TR-1015-18653-P-A listed in Table 7.0-2 for ASAI numbers 6, 9, 10, 11, 62, 63, 64, and 65.
For the purpose of the MPS defense-in-depth assessment, the blocks identified in
Figure 7.1-4 represent a level of detail that simplifies system examination. Blocks
have been selected to represent a physical subset of equipment and software
whose internal failures can be assumed not to propagate to other blocks based on
respective attributes that are discussed in Guideline 2 (Section 7.1.5.1.2).
The non-Class 1E monitoring and indication block represents the soft controls and
digital displays available to the operator in the MCR for module-specific systems
controlled by the MCS. These displays and controls are used by the operators for
day-to-day operations.
and software in the MCS. As a result, internal failures, including the effects of
software errors, do not propagate to other equipment or software.
The SDIS and manual controls blocks represent the respective division of SDIS and
manual controls available to the operators. As mentioned in Section 7.0.4.4, each
division of SDIS receives information from the gateway associated with the
respective MPS division. Each gateway contains information from all four
separation groups and both MPS divisions of RTS and ESFAS. The SDIS displays are
for indication only and do not provide any control functionality. Each protective
action automatically initiated by MPS can be manually actuated at the division level
by safety-related manual switches. There is a Division I containment system (CNTS)
isolation switch that closes Division I containment isolation valves (CIVs). There is
also a Division II CIV switch that closes Division II CIVs. Successful closure of one
Division completes the intended safety function.
Safety Blocks
Safety Blocks I and II in Figure 7.1-4 encompass the MPS with the exception of the
manual controls in the MCR. Each block represents a different programmable
technology. Safety Block I includes Separation Group A and C, and Division I of RTS
and ESFAS. Safety Block II includes Separation Group B and D, and Division II of RTS
and ESFAS. Figure 7.1-5 provides a visual representation using the MPS architecture
overview from Figure 7.0-3; however, for purposes of clarity, some communication
lines from the separation groups have been removed.
The safety-related manual controls within the manual controls blocks provide
division-level initiation of safety-related components; however, component-level
control of these safety-related components requires that non-Class 1E control logic
within the actuation priority logic of the EIM is enabled by a safety-related switch as
described in Section 7.0.4.1. If the operator has enabled non-Class 1E controls in
the actuation priority logic of an EIM and there are no active manual or automatic
actuation signals present, the operator can use MCS to control safety-related
components.
Sensor Blocks
Sensor Blocks I and II encompass the sensors used as inputs to the MPS. The inputs
to MPS are summarized in Table 7.1-9. For the purpose of the D3 assessment, the
evaluation of Sensor Block I and II is focused on digital sensors that have
safety-related functions. Variables that are calculated by MPS (e.g., degrees of
subcooling, high power range positive rate) are not included as part of the sensor
blocks. Analog and discrete sensors are identified for completeness, but they are
not considered to be vulnerable to digital-based CCF.
The MCS provides for NPM-specific control of nonsafety-related systems and, with
the appropriate permissives, control of safety-related equipment. The MCS block
provides information to the operators and receives input from the operators
through the non-Class 1E Monitoring and Indication block. The MCS block consists
of the control network, controllers, remote I/O network, and remote I/O modules.
The identification of blocks in the previous section allows for diversity assessment
against the following six diversity attributes:
• design diversity
• equipment diversity
• functional diversity
• human diversity
• signal diversity
• software diversity
Safety Block I or II
Software Diversity
Design Diversity
Each EIM implements a digital and analog method for initiating protective actions.
The automatic signal actuation is generated within the digital portion (FPGA) of the
EIM. The manual signal actuation originates from the physical switches in the
manual controls blocks. In the EIM, both manual and automatic actuation signals
are used by the actuation priority logic that is implemented using discrete analog
components as described in Section 7.0.4.1 and TR-1015-18653-P-A.
Functional Diversity
The SFMs are configured and programmed for different purposes. The safety
function or group of safety functions implemented within an SFM is based on its
inputs. For example, one SFM only monitors and makes a trip determination on
containment pressure, while another SFM monitors and makes a trip determination
on steamline conditions. Some SFMs are not required to perform a trip
determination. Instead, these SFMs are used only to provide accident monitoring
information to the SDIS blocks through the separation group MIB communications
modules.
Each EIM can control two groups of field components. The EIMs are configured for
functions only associated with those groups of components by limiting the
number of components that an EIM can control. For example, an EIM may be
required to close valves on a CNTS isolation signal while another EIM is dedicated
to tripping a breaker on a low pressurizer level signal. Although there are instances
where EIMs implement different safety functions, there are certain EIMs that
implement more than one safety function.
Sensor Block I or II
The safety-related digital sensors from Table 7.1-9 can be grouped into the
following function types as described in the NuScale Power, LLC, TR-0316-22048
"Nuclear Steam Supply Systems Advanced Sensor Technical Report,"
(Reference 7.1-15):
• digital-based level measurements
• digital-based pressure measurement
• digital-based flow measurement
Equipment Diversity
Each function type depends on different physical effects that require unique
processing algorithms to obtain the desired variable (e.g., flow, pressure, level).
Within a sensor block, each function type is based on different designs from
different manufacturers.
Design Diversity
The equipment diversity within each sensor block creates inherent design diversity.
Each function type is based on a different architecture (i.e., arrangement and
connection of components).
Functional Diversity
Each function type is used for a particular function: digital based level, pressure,
and flow sensors are used for these process measurements.
Human Diversity
Within a sensor block, each function type represents sensors from a different
design organization (i.e., vendor or supplier).
Software Diversity
Each function type relies on different physical effects that require different
algorithms and logic to obtain the desired variable.
Signal Diversity
The equipment diversity within each sensor block creates inherent signal diversity.
Each function type represents different process variables sensed by different
physical effects.
Division I or II of SDIS
There are no diversity attributes within this block for the monitoring functions.
Equipment Diversity
Between Safety Block I and II, different FPGA technology is used to achieve
equipment diversity. The FPGA equipment diversity in the form of two different
FPGA technologies coupled with the different development tools is an effective
solution for the digital-based CCF vulnerabilities present in the MPS, as described in
TR-1015-18653-P-A. Table 7.1-17 describes the effect of a digital-based CCF across
diverse FPGA technologies between each safety block.
Between Sensor Block I and II, there are two sets of digital-based level
measurement sensors and each set is from a different design organization (i.e.,
vendor or supplier). Although the process variable is sensed by the same physical
effect, the digital processing electronics from different companies result in
different designs. When compared to a digital I&C platform, digital-based level
measurement sensors have a simpler and specific function. As a result, equipment
diversity is an effective solution for the digital-based CCF vulnerability that may be
present in the digital-based level measurement electronics.
Design Diversity
To limit the potential for and the consequences of a digital-based CCF, Safety
Block I and Division I SDIS block use a different FPGA chip architecture than Safety
Block II and Division II SDIS block. The diverse FPGA technologies have additional
design diversity attributes, as described in TR-1015-18653-P-A and summarized in
Table 7.1-10.
The MCS block and non-Class 1E Monitoring and Indication blocks are based on a
programmable technology diverse from Safety Block I and II, and Division I and II
SDIS. Along with other attributes discussed below, different hardware designs have
different failure modes that reduce the possibility of a digital-based CCF affecting
more than one block.
Human Diversity
The use of different I&C platforms creates inherent human diversity between
certain blocks. The SDIS and safety blocks are based on an FPGA platform while the
non-Class 1E Monitoring and Indication block and MCS block are based on a
microprocessor-based or computer-based platform as described in Section 7.0.4.5.
Human diversity is an implicit attribute of the FPGA equipment, chip design, and
software tool diversity of the SDIS and safety blocks; however, it is neither explicitly
defined nor verified for these blocks.
Similar to the SDIS and sensor blocks, human diversity is an implicit attribute of the
digital-based level measurements provided by different companies; however, it is
neither explicitly defined nor verified for these blocks.
Software Diversity
Due to the design diversity discussed for the FPGA equipment, the use of different
programmable technologies results in the use of different design tools that would
not introduce the same failure modes.
Functional Diversity
Safety Blocks I and II form the MPS. These blocks initiate, as needed, to initiate a
reactor trip and ESF actuations to mitigate a DBE.
The monitoring and indication blocks allow for an operator to monitor and control
both safety and nonsafety systems. The operator can maintain a plant within
operating limits or initiate necessary protective actions.
The MCS provides automatic control of systems to maintain the plant within
operating limits including constraining certain operational transients.
Signal Diversity
Type 1 Failures
Type 2 Failures
Type 2 failures do not directly cause plant transients, but are undetected until
environmental effects or physical equipment failures cause a plant transient or DBE
to which protective equipment may not respond. Failure to respond is due to
Type 3 Failures
Type 3 failures occur because the primary sensors expected to respond to a DBE
produce anomalous readings. For instance, accident conditions may have modified
instrument response or an unanticipated event sequence may have modified the
process variable values seen by the instrumentation. Because Type 3 failures are
unpredictable by definition, a strategy dictated by experience is to ensure
sufficient signal diversity that alternate means of detecting significant events exist.
At a minimum, there is sufficient signal diversity to ensure that for each AOO in the
design basis in conjunction with postulated CCFs, the plant is brought to a stable
hot standby condition. For each accident in the design basis in conjunction with
postulated CCFs, the plant response calculated using best-estimate (using realistic
assumptions) analyses does not result in exceedance of the 10 CFR 100 dose limits,
violation of the integrity of the primary coolant pressure boundary, or violation of
the integrity of the containment. Defense-in-depth analysis that supports signal
diversity required for Type 3 failures is required by general analysis Guidelines 10
and 11.
The monitoring and indication echelon consists of five blocks: Division I SDIS,
Division I Manual Controls, Division II SDIS, Division II Manual Controls, and
non-Class 1E Monitoring and Indication.
Separation groups and the divisions of RTS, and ESFAS were grouped into Safety
Block I or II according to the programmable technology that their modules are
based on; however, the RTS and ESFAS echelon span across both safety blocks.
Because some separation group SFMs are required for both reactor trip and ESFAS
actuation, separation groups are considered to be part of the RTS and ESFAS
echelon.
The control system echelon is the MCS block. As described in Section 7.1.5.1.1, the
MCS block and the control system echelon represent a subset of the actual MCS.
The soft controls and digital displays available to the operator in the MCR are a
subset of MCS components; however, they are considered to be part of the
monitoring and indication echelon.
Blocks chosen in Guideline 1 are considered as "black boxes" so that any credible
failure required to be postulated produces the most detrimental consequence
when analyzed in accordance with Guideline 9.
Incredible Failures
The actuation priority logic within the EIMs for both Safety Block I and II are the
same; however, the actuation priority logic is composed of discrete analog
components and is not considered to be vulnerable to digital-based CCFs. The
actuation priority logic within an EIM receives commands from the automatic
actuation voting logic and external hard-wired signals as described in
Section 7.0.4.1. The actuation priority logic responds to commands from the
automatic actuation voting logic whether they are valid or spuriously generated.
The HWM for both Safety Block I and II is the same; however, it is also composed of
discrete analog components and not vulnerable to digital-based CCF.
Manual controls provided by Division I and II Manual Controls are physical switches
and not vulnerable to digital-based CCF.
When enabled by the operator in the MCR, the non-Class 1E Monitoring and
Indication block is used for component-level control of safety-related components
to permit periodic testing. It is not considered credible to have a CCF of the
non-Class 1E Monitoring and Indication block at the same time the operator has
enabled component-level control. Enabling the component-level control of
safety-related controls is expected to be for short periods of time.
Sufficient diversity exists within a sensor block to limit a digital-based CCF to one
function type.
The possible output signals for a given block are postulated below.
The SDIS and manual control blocks involve a combination of digital components
(e.g., HSIs, display interface modules, communication modules) and analog
hardware (i.e., manual controls). The SDIS blocks are designed for indication only
and do not have the capability to control equipment. The manual controls in each
manual controls block provide the operator the ability to initiate, at the
division-level, protective actions automatically performed by Safety Block I or II.
Control of ESF equipment at the component level is provided by the non-Class 1E
Monitoring and Indication block and the MCS block but only if non-Class 1E
controls are enabled from the manual control blocks.
With the indication and manual control being different hardware (i.e., digital vs.
physical hard-wired switches), a CCF can be assumed to affect only those
A fail-as-is condition within one block prior to the start of a DBE results in one
Division of operator displays indicating false safe operating conditions; however,
this would not prevent protective actions from being automatically initiated by
Safety Block I or II. Because the digital equipment within the block has no control
capability, a CCF would not automatically cause a spurious actuation. Instead, with
a digital-based CCF, the operator spends time determining which of the displays is
valid. To resolve the information discrepancy, the operator can use the
non-Class 1E Monitoring and Indication block. The information provided to the
SDIS blocks from the safety blocks is also provided to the non-Class 1E Monitoring
and Indication block through the MCS block.
Figure 7.1-7 identifies the assumed CCF in red and shows in green outline the
available blocks and signals used to resolve information discrepancy if, for
example, Division I SDIS had a CCF.
Safety Blocks I or II
The actuation priority logic within an EIM is composed of discrete components and
is not vulnerable to a digital-based CCF. The remaining portions of an EIM and the
other modules within a safety block are postulated to have a digital-based CCF.
The most significant consequences for a digital based CCF within a Safety Block are:
eight possible partial spurious actuation scenarios are identified in Table 7.1-11. For
scenarios 1 and 2, a D3 coping analysis was performed to demonstrate that the
spurious actuations result in conditions that are bounded by the plant safety
analyses, as discussed in Section 7.1.5.2.2.
Each Division of RTS has two RTBs. A partial spurious actuation of RTS within a
Division does not result in a reactor trip and, thus, is not evaluated further. This is
summarized in Table 7.1-12.
By crediting the diversity attributes between the two Safety Blocks, scenarios 3 and
4 do not prevent the unaffected Safety Block from initiating protective actions
when plant conditions require them. While Scenario 4 would result in conflicting
information in the MCR, there are other blocks available to resolve conflicting
information.
Figure 7.1-8 identifies the blocks (with green outline) relied upon to automatically
initiate safety-related functions when one of the safety blocks has a digital-based
CCF (shown in red). Figure 7.1-9 identifies in green outline the available blocks
used to resolve information discrepancy and to automatically initiate safety-related
functions if a safety block had a CCF (shown in red).
Non-Class 1E Monitoring and Indication block includes controls for safety and
nonsafety equipment. Because non-Class 1E Monitoring and Indication is used for
normal day-to-day operations, any spurious actuation of a major control function
(e.g., rod control, feedwater control) by a digital-based CCF within non-Class 1E
Monitoring and Indication block is immediately identifiable and, if it exceeds
operating limits, is mitigated by Safety Blocks I or II. Figure 7.1-10 identifies the
assumed digital-based CCF in red and shows in green outline the available blocks
and signals used to resolve information discrepancy.
The MCS block is a subset of the actual MCS. The MCS block consists of the control
network, controllers, remote I/O network, and remote I/O modules. These
components are segmented or explicitly incorporate other functional defensive
Sensor Block I or II
These blocks have been included in the analysis because safety-related sensors
that depend on digital electronics are being used as inputs to the MPS and are
subject to a digital-based CCF. Using the function types and the diversity attributes
discussed in Section 7.1.5.1.2, Table 7.1-13 through Table 7.1-16 identify how a
digital-based CCF affects either one or both sensor blocks. For Table 7.1-13, there is
sufficient diversity in the digital-based level measurement between Sensor Block I
and II such that a digital-based CCF is limited to one block.
Postulated outputs of a sensor block with a digital based CCF are fail as-is, fail low,
or fail high.
A digital-based CCF of level function type for Sensor Block I (Figure 7.1-11) causes:
• spurious actuations from MPS
• incorrect information provided to SDIS, and
• incorrect information provided to MCS
The affected variables are pressurizer level and containment water level. Because
protective actions are actuated when at least two-out-of-four separation groups
demand a reactor trip or ESF actuation, a failed low signal results in a spurious
reactor trip, containment system isolation, chemical and volume control system
(CVCS) isolation, pressurizer heater trip, and secondary system isolation.
Failed low signals received by Safety Block I are transmitted to MCS, displayed in
the MCR, and used for nonsafety control functions. With the spurious actuation of a
The affected variables are pressurizer level and containment water level. Because
protective actions are actuated when at least two-out-of-four separation groups
demand a reactor trip or ESF actuation, a failed high signal results in a spurious
reactor trip, CVCS isolation, demineralized water system isolation, and ECCS
actuation.
Failed high signals received by Safety Block I are transmitted to MCS, displayed in
the MCR, and used for nonsafety control functions. With the spurious actuation of a
reactor trip, and CVCS isolation, the MCS response to two correct and two incorrect
sensor values has a no further impact. Out of the failed high signals, pressurizer
level is the only signal used for nonsafety controls; however, with CVCS isolated,
MCS cannot use CVCS makeup and letdown pumps to change pressurizer level.
With Sensor Block II still capable of actuating on low-level signals (e.g.,
containment isolation on low-low pressurizer level), capability to initiate other ESFs
is not lost.
Failed As-Is
The affected variables are pressurizer level and containment water level. The failed
as-is condition for two of the four sensors for each affected variable does not
prevent the initiation of a reactor trip or ESF actuation. Sensor Block II is still
capable of identifying plant conditions requiring protective actions.
Failed as-is signals do not lead to spurious initiation of protective actions. Failed
as-is signals may go unnoticed until the valid signals significantly deviate from the
failed signals.
A digital-based CCF of pressure measuring system function type for Sensor Block I
(Figure 7.1-12) causes
• spurious actuations from MPS
• incorrect information provided to SDIS
• incorrect information provided to MCS
The affected variables are pressurizer pressure and wide range RCS pressure. Failed
low signals in the four sensors for each affected variable can result in a spurious
reactor trip, demineralized water system isolation, CVCS isolation, ECCS actuation,
and secondary system isolation.
Failed low signals received by Safety Block I and II are provided to MCS to be
displayed in the MCR and to be used for nonsafety controls. With the spurious
reactor trip, demineralized water system isolation, and CVCS isolation, the MCS
response to four incorrect sensor values is to turn on the pressurizer heaters, which
is bounded by the spectrum of heatup event analyses described in Chapter 15.
The affected variables are pressurizer pressure and wide-range RCS pressure. A
failed high signal affecting the four sensors for the affected variables can result in a
spurious reactor trip, CNTS isolation, DHRS actuation, demineralized water system
isolation, pressurizer heater trip, and secondary system isolation.
Failed high signals received by Safety Block I and II are provided to MCS to be
displayed in the MCR and to be used for nonsafety controls. With the spurious
reactor trip, containment system isolation, demineralized water system isolation,
and pressurizer heater trip, the MCS response to four incorrect sensor values has a
no further impact. The automatic MCS response to a rise in pressure is to use
pressurizer spray; however, with the closure of the containment isolation valves,
pressurizer spray is unavailable.
Failed As-Is
The affected variables are pressurizer pressure and wide-range RCS pressure. The
failed as-is condition for the four sensors of each affected variable does not result in
spurious actuations; however, it can prevent initiation of protective actions if a DBE
were to occur. This failure can be considered a Type 3 failure and is discussed in
Section 7.1.5.1.10 and Section 7.1.5.1.11.
The affected variable is RCS flow. A failed low signal for the four channels results in
a spurious reactor trip, demineralized water system isolation and CVCS isolation.
There is no further impact associated with a failed low signal.
The affected variable is RCS flow. A failed high signal for the four channels does not
result in spurious actuations; however, the safety blocks would be unable to
identify a low RCS flow condition and the operator would have incorrect
information.
Failure to identify a low RCS flow condition failure can be considered a Type 3
failure and is discussed in Section 7.1.5.1.10 and Section 7.1.5.1.11.
Failed As-Is
The affected variable is RCS flow. The failed as-is condition for the four channels
does not result in spurious actuations. The failed as-is condition can prevent
initiation of protective actions based on low flow conditions; however, the RCS flow
sensor is not relied upon for detection or mitigation of AOOs or postulated
accidents as described in Section 7.1.5.2 and Table 7.1-18. This failure can be
considered a Type 3 failure and is discussed in Section 7.1.5.1.10 and
Section 7.1.5.1.11.
The digital-based flow and pressure measuring system function type found in
Sensor Block I and II are considered to be identical. The other blocks are considered
to be independent such that a postulated digital-based CCF is limited to a block.
Diversity attributes within and between blocks are discussed in Section 7.1.5.1.2.
The blocks are assumed to function correctly in response to inputs that are correct
or incorrect.
The information from Safety Block I and II to SDIS blocks are through optically
isolated transmit-only communication ports as described in Section 7.0.4.1 and
Section 7.1.2.3. Signals from the manual control blocks to safety blocks are physical
switch contacts that cannot be automatically changed by a digital-based CCF in the
safety blocks.
The four separation groups are independent and redundant; however, for the
purposes of the D3 assessment, the separation groups were grouped into safety
blocks according to the FPGA architecture used. Communications from the
separation groups to both divisions of RTS and ESFAS are through optically
isolated, transmit-only communication ports. Data sent from the separation groups
to either division of the MPS gateway are through optically isolated, transmit-only
communication ports. Communication from the RTS and ESFAS to the MPS
gateways is through optically isolated, transmit-only communication ports as
described in Section 7.0.4.1.
Discrete hard-wired inputs from the MCS block to the safety blocks are to the
analog portions of ESFAS and RTS that are not vulnerable to a digital-based CCF.
Unless the operator enables nonsafety control, these inputs from the MCS block are
ignored as described in Section 7.0.4.5 and Section 7.2.3.3.
Inputs from safety blocks are from optically isolated, transmit-only communication
modules. This prevents any error in the SDIS block from automatically propagating
backwards to the safety blocks.
Outputs from the Division I and II Manual Controls block are from physical switches
in the MCR to the analog portions of ESFAS and RTS that are not vulnerable to a
digital-based CCF.
Inputs from safety blocks have been optically isolated and transmitted using
one-way communication. Any fault within the MCS block cannot propagate
backwards into the safety blocks.
hangups (control and data acquisition), and other feasibility checks that indicate
erroneous operation.
A Type 2 failure within a safety block does not prevent the unaffected safety block
from initiating the necessary protective actions. Safety Block I or II alone can initiate
necessary protective actions for AOOs. The diversity attributes between Safety
Block I and II limit a digital-based CCF to only one safety block.
Safety Block I and II depend on both analog and digital sensors for detecting the
need for protective actions. Table 7.1-16 summarizes the safety-related input
signals, sensor technology, and their function(s). The digital sensors identified are
vulnerable to a Type 3 failure; however, it is not credible to assume a concurrent
Type 3 failure of the digital sensors. Instead, a digital-based CCF is assumed to
occur with a particular subset of the digital sensors. For example, it is credible for
the pressure measuring systems to have a digital-based CCF concurrent with an
AOO. Digital-based CCF of pressure measuring system and digital-based level
sensors concurrent with an AOO is not considered credible due to the technology
diversity. The AOOs and credited digital sensors are summarized in Table 7.1-18.
For pressurizer pressure and RCS flow sensors, a D3 coping analysis was performed
to demonstrate a Type 3 failure concurrent with an AOO does not result in radiation
release exceeding 10 percent of 10 CFR 100 dose limits or violate the integrity of
the primary coolant pressure boundary, as discussed in Section 7.1.5.2.2. The D3
coping analysis considered an AOO concurrent with a digital-based CCF of a
credited signal and the sensors of the same type. The results of the D3 coping
analysis for each design basis event are shown in Table 7.1-18.
A Type 2 failure within a safety block does not prevent the unaffected safety block
from initiating the necessary protective actions. Safety Block I or II alone can initiate
necessary protective actions for postulated accidents. The diversity attributes
between Safety Block I and II limit a digital-based CCF to only one safety block.
Safety Block I and II depend on both analog and digital sensors for detecting the
need for protective actions. Table 7.1-16 summarizes the input signal, sensor
technology, and its function(s). The digital sensors identified are vulnerable to a
Type 3 failure; however, it is not credible to assume a concurrent Type 3 failure of
the digital sensors. Instead, a digital-based CCF is assumed to occur with a
particular subset of the digital sensors. For example, it is credible for the pressure
measuring systems to have a digital-based CCF concurrent with a postulated
accident. Digital-based CCF of pressure measuring systems and digital-based level
sensors concurrent with a postulated accident is not considered credible because
of the technology diversity. Postulated accidents and credited digital sensors are
summarized in Table 7.1-18. A postulated accident may have multiple credited
signals, depending on the event sequence; however, Table 7.1-18 only identifies
the digital sensors. The event and signal credited are obtained from the plant
safety analysis.
Although pressurizer level is a digital-based sensor that a credited signal for some
events, there is sufficient diversity between Sensor Block I and II to prevent Type 3
failures from affecting the pressurizer level sensors in both Sensor Block I and II.
A D3 coping analysis was used to demonstrate that a Type 3 failure concurrent with
a postulated accident does not result in radiation release exceeding 10 CFR 100
dose limits, violating the integrity of the primary coolant pressure boundary, or
violating the integrity of the containment, as described in Section 7.1.5.2.2. The D3
coping analysis considered a postulated accident concurrent with a digital-based
CCF of a credited signal and the sensors of the same function type. The results of
the D3 coping analysis for each design basis event are shown in Table 7.1-18.
As shown in Figure 7.1-6, portions of the ESFAS and RTS echelon of defense are
combined into the same block. Section 7.1.5.1.2 describes the diversity attributes
within blocks and the diversity attributes between blocks.
Signals are transmitted from the RTS and ESFAS echelons to the control systems
and monitoring and indication echelon. There are no manually controlled actions
for which no automatic control is provided and that are required for the safety
systems to accomplish their safety functions. As a result, none of the monitoring
equipment within the monitoring and indication echelon is required to be Class 1E.
Although there are no Type A variables, Division I and II manual controls blocks
provide an independent and diverse method of manually actuating the automatic
safety-related functions at the Division-level. The actuation priority logic within the
EIMs of both safety blocks is implemented in discrete analog components and
downstream of the automatic digital portion of the safety system. The SDIS and
manual controls blocks are sufficiently diverse that any failure does not prevent the
operator from obtaining or resolving conflicting information as described in
Section 7.1.5.1.6. As described in Section 7.1.1.2.3 and Section 7.1.5.1.4, the SDIS
and manual controls blocks are considered to be independent of the RTS, ESFAS,
and control system echelon.
• reactor trip
• decay heat removal system actuation
• emergency core cooling system actuation
• containment system isolation
3) Potential digital-based CCF of level function type within Sensor Block I or II may
result in one of the following (Section 7.1.5.1.6):
The plant safety analyses described in Chapter 15 credit high PZR pressure for
detection and mitigation of heatup and reactivity excursion DBEs.
There are two reactor safety valves each of which are sized to relieve the pressure
generated by a total loss of secondary cooling without credit for a reactor trip. The
D3 coping analysis concluded that a conservative postulated heatup event that did
not trip on high pressure would not violate the RCS pressure boundary integrity
due to the sizing of the reactor safety valves.
For the events described in Chapter 15 and listed in Table 7.1-18 that result in a
high RCS pressure condition, the analyses conservatively do not take credit for
normal pressurizer spray control. In the secondary plant events that result in the
loss of main steam flow, the high main steam pressure signal is credited to
generate reactor trip and DHRS actuations in addition to the high PZR pressure. In
the case of the loss of feedwater and feedwater line break events, the high RCS hot
temperature is a diverse signal. Therefore, sufficient signal diversity exists such that
postulated digital-based CCFs of the high pressurizer pressure function are
bounded by the plant safety analyses in Chapter 15.
The plant safety analyses described in Chapter 15 credit low PZR pressure in the
steam generator tube failure and CVCS line breaks outside containment events.
Both the low pressurizer pressure trip and the low low pressurizer pressure trip are
credited in the steam generator tube failure event while only the low low
pressurizer pressure trip is credited in the CVCS line breaks outside containment
event. The limiting radiological scenarios include assumed loss of AC power
concurrent with the breaks which results in an RCS pressurization that delays the
low pressurizer level and low pressurizer pressure trips. This assumption bounds
the cases where loss of offsite power is not assumed in a best-estimate analysis and
the D3 coping analysis concluded the plant safety analyses are bounding.
For the events described in Chapter 15, and listed in Table 7.1-18 that result in a low
RCS pressure condition, the analyses do not credit normal operation of the PZR
heaters. The best-estimate analysis of these events concludes that pressurizer
heaters are able to mitigate events. Low pressurizer pressure (via the low low
pressurizer pressure trip) is also credited for generating a CVCS isolation signal for
small CVCS line failure event and a DHRS actuation signal for the steam generator
tube failure event after the RTS and PZR heater trip occurs on low pressurizer level.
In these cases, the low-low PZR level trip is identified as the diverse signal for CNV
isolation, in order to mitigate the consequences of the radiological release. The
best estimate analysis of a larger break of the PZR spray line outside containment
does not generate a condition that relies on the low low pressurizer pressure
function due to the back flow and overflow prevention (check valves) located on
the CVCS lines. If the CVCS pressure drops sufficiently to seat these valves, then the
RCS inventory will be preserved and the NPM will continue to operate until
operators noticed the failed CVCS line. For breaks/leaks in the CVCS lines that are
small enough to not generate the system pressure drop required to seat the check
valves, the transient response is a slow degradation of the of RCS inventory that is
detected and mitigated by the low low PZR level actuation function.
RCS flow rate is a function of reactor power in the NuScale design, such that low
RCS flow is only possible during startup conditions. The low-low RCS flow
protective function is credited for actuating RTS and CVCS isolation in the event of
a MHS malfunction that causes an RCS flow reversal. This event is not considered
credible in combination with a digital-based CCF of the RCS flow sensor due to the
very short, and limited operating window where the MHS failure could occur.
The low RCS flow ESFAS actuation is used as a boron dilution initial condition but is
not credited as part of the transient detection or mitigation. The minimum RCS flow
is specified in order to generate the appropriate response time as part of the safety
analysis evaluation but the change in neutron flux ultimately generates the
mitigating actuations of RTS or DWS isolation. Because this is not a credited signal,
this event is non-limiting.
The plant safety analyses described in Chapter 15 credit the low wide range RCS
pressure ECCS actuation in the boron dilution-limiting scenario analyzed within the
LOCA events. The low wide range RCS pressure ECCS actuation signal is
implemented primarily to mitigate the possibility of a boron dilution scenario as a
result of a small-break LOCA. The actuation signal has interlocks on the RCS hot leg
temperature and CNV pressure to prevent unnecessary ECCS actuation for
non-LOCA events.
The limiting case analyzed for LOCA boron dilution is a smaller break in the LOCA
break spectrum described in Chapter 15. This case has an ECCS actuation on low
wide range RCS pressure. In addition, this analysis conservatively assumes that the
highest worth control rod assembly is not inserted into the core and neglects
negative reactivity insertion from xenon. The D3 coping analysis concluded that a
best-estimate case which credits xenon reactivity and an all-rods-in condition
would not require an earlier ECCS actuation on low wide range RCS pressure to
mitigate a boron dilution scenario for any break size or location in the LOCA break
spectrum. ECCS actuation in these cases occurs due to high CNV level or low
differential pressure across the ECCS valves. Sufficient diversity exists such that
ECCS is available to mitigate these small-break LOCA events.
The discussion below provides a summary of how the four-point position is either fully
or partially addressed within the I&C system design.
Point 1
"The applicant shall assess the defense-in-depth and diversity of the proposed
instrumentation and control system to demonstrate that vulnerabilities to
common-mode failures have adequately been addressed."
Point 2
"In performing the assessment, the vendor or applicant shall analyze each postulated
common-mode failure for each event that is evaluated in the accident analysis section
of the safety analysis report using best-estimate methods. The vendor or applicant shall
demonstrate adequate diversity within the design for each of these events."
The D3 assessment demonstrates that there is adequate diversity within the MPS for
each event that is evaluated in the accident analysis section of the Safety Analysis
Report.
Point 3
"If a postulated common-mode failure could disable a safety function, then a diverse
means, with a documented basis that the diverse means is unlikely to be subject to the
same common-mode failure, shall be required to perform either the same function or a
different function. The diverse or different function may be performed by a nonsafety
system if the system is of sufficient quality to perform the necessary function under the
associated event conditions."
The D3 assessment demonstrates that sufficient diversity exists within the MPS to
prevent a postulated digital-based CCF from disabling the capability to perform any of
its safety-related functions.
The D3 coping analysis identifies different sensors not vulnerable to the same
digital-based CCF that exist to mitigate the associated event conditions without
requiring a separate I&C system.
Point 4
"A set of displays and controls located in the main control room shall be provided for
manual, system-level actuation of critical safety functions and monitoring of
parameters that support the safety functions. The displays and controls shall be
independent and diverse from the safety computer system identified in Items 1 and 3
above."
Division I and II manual control switches are provided to manually initiate at the
division-level the automatic safety-related functions. Manual actuation signals are
inputs to the actuation priority logic within an EIM. The actuation priority logic within
the EIMs is implemented in discrete analog components and is downstream of the
automatic digital portion of the safety system. The MCS, SDIS, and manual controls are
sufficiently diverse that any failure does not prevent the operator from obtaining or
resolving conflicting information (Section 7.1.5.1.6).
The I&C systems are designed to the quality assurance program requirements as described
in Section 7.1.1, Section 7.2.1, and Section 17.5.
The I&C systems and components required to function during natural phenomena events
are located within structures that protect them against natural phenomena. See
Section 7.1.1 and Section 7.2.2.
The I&C systems are designed for the environmental conditions that are associated with
normal operation, maintenance, testing, and postulated accidents to which they may be
subjected and required to function. See Section 7.1.1 and Section 7.2.2.
The MPS, NMS, MCS, and ICISs are not shared between NPMs. The PCS and PPS are shared
between multiple NPMs and are designed to not adversely affect the ability of I&C
platforms to perform safety-related functions. See Section 7.1.1 and Section 7.2.11.
The MPS provides the reactor trips and ESF actuations based on analytical limits with
appropriate margin to ensure that specified acceptable fuel design limits are not exceeded
during any condition of normal operation, including the effects of AOOs. The MPS also
monitors NPM variables and provides these signals to the MCS for control and indication.
The NMS monitors and provides neutron flux levels to the MPS. See Section 7.1.1.
The I&C systems monitor variables and systems over their anticipated ranges for normal
operations, AOOs, and accident conditions to ensure adequate safety. See Section 7.1.2,
Section 7.1.4, Section 7.1.5, Section 7.2.7, and Section 7.2.13.
The MPS and NMS provide the appropriate controls to the NPM with sufficient margin to
ensure that the design conditions of the RCPB are not exceeded during normal operations
or as a result of an AOO. See Section 7.1.1.
The MPS initiates containment isolation and safety-related functions. In addition, MPS
removes power to the secondary main steam isolation valves (MSIVs) and the main
feedwater regulating valve upon DHRS actuation, providing a backup containment
isolation function. See Section 7.1.1.
The I&C systems ensure the ability to control each NPM during normal and accident
conditions. The NuScale MCR is designed with the ability to place the reactors in safe
shutdown in the event of an MCR evacuation event, and for safe shutdown to be
maintained without operator action thereafter. Prior to evacuating the MCR, operators trip
the reactors, initiate decay heat removal and initiate containment isolation. These actions
result in passive cooling that achieves safe shutdown of the reactors. Operators can also
achieve safe shutdown of the reactors from outside the MCR in the MPS equipment rooms
within the reactor building. Following shutdown and initiation of passive cooling from
either the MCR or the MPS equipment rooms, the NuScale design does not rely on operator
action, instrumentation, or controls outside of the MCR to maintain safe shutdown
condition. The design includes an RSS for monitoring of the plant if the MCR is evacuated.
There are no displays, alarms or controls in the RSS credited to meet the requirements of
principal design criterion (PDC) 19 as there is no manual control of safety-related
equipment allowed from the RSS. See Section 7.1.1 and Section 7.2.13.
The MPS, with inputs from the NMS, senses when specified parameters are exceeded and
initiates reactor trips and ESF actuations to ensure that specified fuel design limits are not
exceeded as a result of AOOs, and to sense accident conditions to initiate the operation of
appropriate systems and components. See Section 7.1.1 and Section 7.2.7.
The MPS and NMS have sufficient redundancy and independence to ensure that no single
failure results in the loss of the protection function. The MPS and NMS components may be
removed from service to permit periodic testing during operation, including the capability
to test channels independently to determine failures and losses of redundancy that may
have occurred. See Section 7.1.2, Section 7.1.3, Section 7.1.4, and Section 7.2.15.
The MPS and NMS have sufficient functional diversity to prevent the loss of a protection
function. See Section 7.1.2 and Section 7.1.5.
The MPS has sufficient functional diversity to prevent the loss of a protection function, to
fail into a safe state or into a state demonstrated to be acceptable on some other defined
basis if conditions such as disconnection of the system, loss of power, or postulated
adverse environments are experienced. See Section 7.1.1.
The MPS has sufficient separation of the protection and the control systems to satisfy
reliability, redundancy, and independence requirements even with a component or
channel failed or removed from service. See Section 7.1.2, Section 7.1.3, and Section 7.1.5.
The MPS initiates reactor trip functions to ensure that specified acceptable fuel design
limits are not exceeded for any single malfunction of the reactivity control system. See
Section 4.6.2 and Section 7.1.1.
The MPS initiates reactor trip functions to limit the potential amount and rate of reactivity
increase and to ensure sufficient protection from reactivity accidents. See Section 4.6.2, and
Section 7.1.1.
The MPS and NMS are designed with sufficient redundancy and diversity to ensure high
probability of accomplishing their safety-related functions in the event of AOOs. See
Section 7.1.3.
The MCS and PCS provide monitoring of radioactivity releases, reactor containment
atmosphere, and plant environments for radioactivity that may be released from normal
operations, AOOs, and postulated accidents. See Section 7.1.1.
10 CFR 50.34(b)(2)(i)
The NuScale I&C systems and auxiliary features of the I&C system design are discussed in
Section 7.0.4 and Section 7.2.8 respectively.
10 CFR 50.34(f)(2)(iv)
The SDIS, MCS, and PCS provide the capability to display important plant variables over
their anticipated ranges for normal operation, AOOs, and accident conditions. See
Section 7.2.13.
10 CFR 50.34(f)(2)(v)
The MCR displays bypassed and operable status indication of safety interlocks. See
Section 7.2.4 and Section 7.2.13.
10 CFR 50.34(f)(2)(xi)
The MCR displays reactor safety valve position indication. See Section 7.2.13.
10 CFR 50.34(f)(2)(xiv)(C)
Containment isolation is initiated by two diverse signals from the MPS that ensure the
isolation valves do not re-open upon logic reset, as shown in Section 7.1.5 and
Section 7.2.3.3.
10 CFR 50.34(f)(2)(xvii)
The I&C systems are designed to display appropriate variables in the MCR for monitoring
specified containment variables and site radioactive gaseous effluents from potential
accident releases. See Section 7.2.13.
10 CFR 50.34(f)(2)(xviii)
The MPS and NMS provide MCR indications of inadequate core cooling. See Section 7.2.13.
10 CFR 50.34(f)(2)(xix)
The MPS and NMS provide instrumentation for monitoring plant conditions following an
accident that includes potential core damage. See Section 7.2.13.
10 CFR 50.36(c)(1)(ii)(A)
The MPS initiates automatic protective actions prior to exceeding a safety limit. See
Section 7.2.7.
10 CFR 50.36(c)(3)
The I&C systems are designed to meet surveillance requirements to ensure that the
necessary quality of SSC is maintained such that operation is within safety limits and
limiting conditions of operations are met. See Section 7.2.7 and Section 7.2.15.
10 CFR 50.49
The I&C equipment that perform the functions in 10 CFR 50.49(b) remain functional during
and following DBEs. See Section 7.2.2.
The I&C systems are designed, tested, and inspected to quality standards commensurate
with the safety function to be performed. See Section 7.2.1.
10 CFR 50.55a(1h)
The MPS and the NMS meet the requirements for protection systems and safety systems in
accordance with IEEE Std 603-1991 and the correction sheet dated January 30, 1995 as
described in Section 7.1 and Section 7.2.
10 CFR 50.62
An ATWS was considered in the design of I&C systems as it relates to the design provisions
of subpart (c)(1). The portion of (c)(1) related to automatic initiation of the auxiliary
feedwater system is not applicable to the NuScale design. The NuScale design supports an
exemption from the portion of (c)(1) related to diverse turbine trip capability. The diversity
internal to MPS ensures safety function performance in the presence of CCF. The MPS
design leads to a simpler overall I&C architecture than other previously accepted solutions
for 10 CFR 50.62 that involved separate diverse actuation systems. The MPS design also
results in higher quality and simpler system interfaces than other previously accepted
solutions for 10 CFR 50.62 that involved nonsafety-related diverse actuation systems. The
D3 coping analyses meet the intent of the subpart (c)(2), which is not applicable to the
NuScale design, by demonstrating that MPS digital-based CCF vulnerabilities do not result
in consequences that exceed accepted regulatory criteria. See Section 7.1.5.
7.1.7 Simplicity
This section provides a description the simplicity attributes that have been considered and
incorporated into the design of the NuScale I&C system architecture. Simplicity is a
cross-cutting design element and an evaluation of the simplicity of the NuScale I&C
architecture was performed across the four fundamental design principles: independence,
redundancy, predictability and repeatability, and D3.
Independence
The overall architecture of the MPS is based on the HIPS platform architecture described in
TR-1015-18653-P-A. The simplicity of the independent design principle has been
incorporated by the following design attributes:
• For each protective function, the associated sensor, signal conditioning, and trip
determination are performed by a single, independent SFM. There is one-to-one
correspondence for each SFM and its associated protective function. This provides
independence within each separation group from other protective safety functions, as
well as independence across the separation groups and divisions within the MPS. By
adhering to this design attribute, the testing and maintenance is enhanced because
each protective function can be taken out of service or bypassed for testing,
maintenance, or repair without any adverse effect on other protective functions within
a separation group or redundant channels across the remaining separation groups.
• Communications are based on simple deterministic protocols and safety data are
communicated by redundant communication paths. Communication within the MPS is
performed by dedicated logic communication engines; there are no microprocessor
based communications as described in Section 4.6 of TR-1015-18653-P-A.
Communication is deterministic and does not use interrupts or handshaking. The MPS
Redundancy
The HIPS platform design is based on a symmetrical architecture of four separation groups
and two divisions. Each of the four separation groups is functionally equivalent to the
others and each of the two divisions is functionally equivalent. Two-out-of-four voting is
the applied voting strategy.
Through the use of identical redundant channels, testing and maintenance are simplified
such that a single SFM may be bypassed for testing or repair without affecting the other
remaining redundant separation groups. The MPS voting logic automatically accounts for
the separation group bypassed for repair or testing.
The NuScale I&C architecture design uses several simplicity design attributes related to the
predictability and reliability of the MPS. The logic processing for the reactor trip and
engineered safeguards protective functions are very simple. Trip determination is
performed by a simple comparator (e.g., bistable) or, at most, by the use of simple
arithmetic functions to perform the trip determination function. There is no closed loop
control or modulating control functions within the MPS. Protective functions are "actuate
only,” requiring no process feedback to go to completion. The voting logic is implemented
using simple finite-state machines dedicated to a particular safety function or group of
safety functions. The use of finite-state machines eliminates the need for a microprocessor
system. Therefore, no kernel, operating system, stacks, or heaps are required.
Communication paths are deterministic in design. The MPS work cycle operates on fixed,
repeatable cycles. The MPS communications are asynchronous and from input to output,
each MPS cycle performs the exact same set of operations in the exact same sequence to
complete its safety function.
Section 7.1.5 describes the overall approach to D3. With respect to simplicity, the D3
approach to the NuScale I&C design incorporates simplicity by using the same exact
building block architecture across redundant separation groups and divisions. For areas
where a digital-based CCF can be introduced, the architecture uses diverse FPGA
technologies between separate, redundant divisions.
Additionally, with the use of diverse FPGA technologies, inherent diversity attributes of
each technology type are automatically introduced, such as different design and analysis
tools, different logic programming tools, and diverse, independent verification and
validation tools.
This section provides a description of the hazards analysis methodology applied to the
design of the NuScale I&C systems and how the hazards analysis has been incorporated
into the I&C design and architecture. A system hazard analysis was performed for the MPS,
NMS, PPS, and SDIS, and considered the hardware, software, organizations, and processes
used to develop the system. The hazards analyses is used in conjunction with plant safety
analyses, FMEAs, D3 analyses, and multi-discipline design reviews as an additional means
of ensuring the correctness and completeness of the requirements for the MPS.
External hazards for the NuScale design are addressed in Section 2.2. Internal hazards are
addressed in Chapter 3. The electrical power system design conditions are described in
Section 8.3.2. The resulting independence requirements for I&C systems are described in
Section 7.1.2. The resulting qualification requirements for I&C systems are described in
Section 7.2.2.
Contributory hazards introduced as part of the software development life cycle are
addressed as part of the software safety plan that is integrated into the overall software
development life cycle described in Section 7.2.1. The software safety plan follows the
guidance prescribed in IEEE Std 1228-1994 "IEEE Standard for Software Safety Plans”
(Reference 7.1-16). The integration of software safety and hazards analyses performed
during the software development life cycle are described below.
Concept Phase
As part of the concept phase in the software life cycle, a preliminary hazards list is
prepared on the system that identifies:
• hazardous states of the system
• sequences of actions that can cause the system to enter a hazardous state
• sequences of actions intended to return the system from a hazardous state to a
nonhazardous state
• actions intended to mitigate the consequences of accidents
Requirements Phase
During the requirements phase of the software life cycle, a requirements traceability
matrix is used in accordance with the Software Requirements Management Plan, as the
tracking system to ensure that hazards, their responsibility assignment, and their status
can be tracked throughout the software life cycle, including retirement.
Design Phase
Software safety design analysis is performed during the design phase of the software
life cycle to confirm that the safety-critical portion of the software design correctly
implements the SIL 3 and 4 software or configurable logic device logic functional
requirements identified during the requirements phase and that the design introduces
no new hazards.
Implementation Phase
Software safety logic analysis is performed during the implementation phase of the
software life cycle to confirm that the SIL 3 and 4 portions of the logic design are
correctly implemented in the logic and that the logic introduces no new hazards.
Testing Phase
Software safety test analysis is performed during the test phase to confirm that the SIL
3 and 4 portions of the software or configurable logic device logic design are correctly
implemented in the logic and that the logic introduces no new hazards. For example,
software stress testing is performed to ensure that the safety-critical logic does not
cause hazards under abnormal circumstances, such as unexpected input values or
overload conditions. Regression testing is performed to ensure that changes made to
the safety critical logic do not introduce conditions for new hazards.
Throughout each phase, software verification and validation activities are performed,
and the results of the software life cycle phase is matched against the system safety
requirements and system hazard analysis to ensure
• system safety requirements have been satisfied within the software life cycle
phases.
• no additional hazards have been introduced by the work done during the software
life cycle activity.
A hazard analysis is a process for examining an I&C system to identify hazards (i.e.,
factors and causes) and system requirements or constraints to eliminate, prevent, or
control them.
The scope of the NuScale I&C system hazard analysis encompasses the system design
basis described in Section 7.1.1. The analyses performed for the system design
examined the associated I&C system, subsystems, and components and their
interrelationships and interactions with other systems, subsystems, and components
during all modes of system operation to identify unintended or unwanted I&C system
operation, including the impairment or loss of the ability to perform a safety function.
The NuScale I&C system hazard analysis is intended to evaluate those conditions and
factors associated with the system under analysis and the systems that directly interact
with it that can result in unintended or unwanted system operation, including a failure
to initiate a protective action. These conditions are designated in the analysis as
"Unsafe." Additional analysis is performed to provide guidance for the development
process where a control action could affect continuity of operation or create other
abnormal operating conditions without causing failure of a required protective action.
These conditions are designated in the analysis as "Undesired."
The STAMP model of accident causation is built on three basic concepts: safety
constraints, a hierarchical control structure, and process models, along with basic
systems theory concepts.
The STAMP is a methodology in which organizational and process control systems can
be modeled to show interactions between processes and components. The safety of
the system under consideration is viewed as a control problem. Safety violations, or
accidents, occur when a portion of the control process fails to maintain operation
within the limits set by system constraints. Accidents occur when component failures,
external disturbances, or unsafe interactions among system components are not
adequately handled, or controlled, resulting in unsafe system behavior. In a
STAMP-based analysis, after an accident or during the design process, root cause
identification is not a goal. The goal is to identify the inadequate control structure,
determine what changes need to be made in the system or control structure design,
and ensure that safety constraints are not violated.
The STPA is a process analysis method based on STAMP. In this method, control
structures within the system under analysis are identified and diagrammatic
representations (models) of those control structures are constructed. The structures
defined in this way may or may not reflect the physical structures of the system, but
represent the functional controllers, actuators, controlled processes, and sensors and
the interactions between these functional components. In many complex systems, the
control structures are presented at multiple levels of abstraction in order to capture the
levels of component interaction. This can be seen in the high-level control structure
diagram in Figure 7.1-16 and the lower level functional diagram in Figure 7.1-18.
c) A potentially safe control action is provided too early or too late (i.e., at the
wrong time or in the wrong sequence).
d) A control action required for safety is stopped too soon or applied too long.
2) Determine how each potentially hazardous control action identified in step 1 could
occur.
3) Design control procedures and mitigation measures, if they do not already exist, or
evaluate existing measures if the analysis is being performed on an existing design.
For multiple controllers of the same component or safety constraint, identify
conflicts and potential coordination problems.
Following the initial analysis, the next step is to iterate through the process again,
repeating until the system development is complete.
In order to assist in analysis of the functional controls of the system under analysis, a
brief system description of the NuScale I&C system as described in Section 7.0 was
prepared. The system description provides a high-level overview that supports the
functional descriptions used later in the analysis without introducing redundancy.
The hazards associated with the systems under consideration have been identified
in accordance with the procedures that require the performance of this hazard
analysis. In accordance with RIL-1101, the hazards of concern are "unintended or
unwanted I&C system operation including the impairment or loss of the ability to
perform a safety function."
Therefore, the high-level hazards considered were the improper operation of, or a
loss of a safety function associated with, the components of the safety systems. Any
equipment, functions, or operations outside the system under analysis, such as the
HSI and the control room, are analyzed to determine if interactions could impair
the functions of the analyzed system.
These analyses addressed the hazards from the perspective of an individual signal
processing train without the benefit of redundancies or defense-in-depth to
provide a "worst case" scenario from which the most conservative safety
constraints can be identified. The considerations may improve system reliability
and availability, but may or may not affect system safety. Other analyses address
the redundant functions to determine if they contribute to system hazards.
Examples of high-level hazards are shown in Table 7.1-19. This list is based on the
limits for the MPS as provided in Table 7.1-20.
The high-level safety constraints are derived from the identification of system
hazards. They provide the fundamental limits of system operation. The safety
constraint identification numbers shown in Table 7.1-21 indicate the hazard
conditions which dictate the requirement for the constraint. The safety functions,
based on the DBEs shown in Table 7.1-1 and their setpoints, are detailed in
Table 7.1-20. This analysis is based on the safety functions initiated by any setpoint
being exceeded and not on the processes that are measured.
Table 7.1-22 expands the safety constraints shown in Table 7.1-21 to address the
individual safety functions of Table 7.1-20. This is done because the algorithms, trip
setpoints, and feedback for each of these functions are different. Therefore, the
analysis of the associated control functions may be different.
The control structures are analyzed by identifying the functional controllers and
determining the commands or events that are represented by each input and
output for each controller. Potentially hazardous conditions for the interactions are
identified in a table. The tables are followed by a description of each hazardous
condition identified, possible causes for the inadequate control action, and
suggested safety constraints to mitigate the unsafe conditions caused by the
inadequate control action.
The remainder of this section shows how system decomposition can be performed
to capture the operation of the controllers and their interactions. It begins with a
brief system overview followed by one or more functional descriptions.
The MPS is made up of four separation groups and two divisions. The SFMs in each
separation group correspond to the module-level safety functions identified in
Table 7.1-20. The SFMs accept up to four inputs from safety-related
instrumentation, which are conditioned using filters and other conditioning
circuits and converted to digital signals. Each SFM also contains FPGA logic that
performs required mathematical functions and a comparison of the digital signals
against the safety function setpoint and three communications engines that send
the results of the comparison on dedicated, triple redundant communication buses
to the SBMs. The SBM is a communications module that manages the
asynchronous data transmission between the SFMs and the SVMs, and provides the
capability for maintenance bypass functions.
The basic system configuration showing a single SFM and a single EIM can be seen
in Figure 7.1-19.
The control structure for this analysis consists of the functional interactions
between the inputs from the nonsafety-related control system, MCS; the
safety-related protection system, MPS; operators; outputs to display and indication
systems; actuators; the outputs to the safety-related components; and the inputs
from the sensors. This structure is shown in Figure 7.1-16. Beginning at the top, the
operator interacts with the control structure using commands through workstation
HSIs and the MCS controllers or hard-wired switches to the priority logic portions of
MPS. The commands sent to the MCS allow operators to actuate individual safety
system components for maintenance, system alignment following an actuation or
other, nonsafety-related operations.
The control structure for the NMS ex-core sensors and process instrumentation
consists of the control and monitoring systems, process instrumentation, and
sensors. This structure is shown in Figure 7.1-17. Beginning at the top of
Figure 7.1-17, the control and monitoring systems manipulate the different
functions and variables that affect the reactor power level that the NMS is
monitoring. The NMS monitors the neutron flux levels of the controlled process
and supplies the control and monitoring systems with current levels and
conditions. The NMS also updates the control and monitoring systems with the
status and condition of the NMS circuits. The control and monitoring systems use
this information to update the operator.
The SFM logic (Figure 7.1-18) is a non-standard control structure in that there are
three controllers (the operator, the signal conditioning, and the trip determination
logic) and minimal control feedback. The only feedback provided is loopback input
signal verification for the signal conditioning, actuated component position
information, and process variable display feedback to the operator.
The control structure diagram shows the configuration of the input signal
conditioning and trip determination controllers with output, through the triple
redundant communications bus, directed to the associated SBMs. The division level
processes are analyzed separately.
The control actions considered in this portion of the analysis begin with the signal
conditioning. The signal conditioner is a controller to the extent that it accepts an
input from an analog or digital sensor, performs conditioning on the signal, such as
filtering and scaling, and then performs an analog-to-digital conversion, if
necessary. Signal validation is performed on the signal to reduce the possibility of
an inadvertent protective action or the failure to initiate a required protective
action. The digital representation of the original analog input signal is sent to the
associated trip determination portion of the SFM. The process variable value signal,
along with generated signal quality information, is sent to the MIB communications
module.
The control actions are analyzed by investigating the control objects in each
diagram and the interactions between them. Each interaction, command or event,
is evaluated to determine if a hazardous condition results if the interaction fails to
occur, if it occurs in an incorrect manner, if it is late or early in occurring, if it occurs
out of sequence, or if it is stopped too soon. For example, looking at the signal
Table 7.1-24 shows the basic causes of unsafe control actions identified by the MPS
hazard analysis and the system preliminary hazard list (PHL). The hazards identified
in the hazard list correlate well with the hazard analysis. The table is not intended
to indicate a one-to-one correspondence between the first (Hazards Analysis
Identified Cause) and second (PHL Identified Cause) column. For example, the
damaged cable from the hazard analysis could be caused by many of the causes
from the hazard list. The most significant differences between the lists are that the
preliminary hazard list focused primarily on failures due to physical events. The
hazard analysis identified causes such as operator error and procedural error as
well as possible design deficiencies such as software and algorithm error. These
differences support the use of the STPA methodology for analyzing complex
systems such as the MPS.
The NuScale I&C system hazard analysis is based on a view of the processes that are
performed by the systems described in Section 7.0. The hazards analysis does not
explicitly analyze the effects of redundancy and defense-in-depth; however, the
hazard conditions identified in the hazards analysis are partially or fully mitigated
through application of the fundamental design principles of redundancy
(Section 7.1.3) and D3 (Section 7.1.5). The hazards analysis methodology described
is a living process, performed through the system design life cycle described in
Section 7.2.1.1. The cross-referencing of hazard conditions, safety constraints, and
functional design requirements ensures that potentially hazardous conditions not
previously identified by other analysis methods are mitigated by feedback into the
design of the system functional requirements.
7.1.9 References
7.1-1 NuScale Power, LLC, "Design of the Highly Integrated Protection System
Platform," TR-1015-18653-P-A Revision 2.
7.1-3 Institute of Electrical and Electronics Engineers, "IEEE Standard Criteria for
Safety Systems for Nuclear Power Generating Stations," IEEE
Standard 603-1991, Piscataway, NJ.
7.1-5 Institute of Electrical and Electronics Engineers, "IEEE Standard Criteria for
Digital Computers and Safety Systems of Nuclear Power Generating Stations,"
IEEE Standard 7-4.3.2-2003, Piscataway, NJ.
7.1-8 Institute of Electrical and Electronics Engineers, "IEEE Standard for Application
of the Single-Failure Criterion to Nuclear Power Generating Station Safety
Systems," IEEE Standard 379-2000, Piscataway, NJ.
7.1-9 Leveson, N.G., Engineering a Safer World: Systems Thinking Applied to Safety,
Massachusetts Institute of Technology, Cambridge, MA, 2011.
7.1-11 Institute of Electrical and Electronics Engineers, "IEEE Standard Criteria for
Accident Monitoring Instrumentation for Nuclear Power Generating Stations,"
IEEE Standard 497-2002, Piscataway, NJ.
7.1-14 Institute of Electrical and Electronics Engineers, "IEEE Standard Criteria for
Independence of Class 1E Equipment and Circuits," IEEE Standard 384-1992,
Piscataway, NJ.
7.1-15 NuScale Power, LLC, "Nuclear Steam Supply Systems Advanced Sensor
Technical Report," TR-0316-22048-P, Revision 3.
7.1-16 Institute of Electrical and Electronics Engineers, "IEEE Standard for Software
Safety Plans," IEEE Standard 1228-1994, Piscataway, NJ.
Tier 2
Tier 2
Tier 2
(Note 4)
High Under-the-Bioshield 250°F 4 2/4↑
Temperature
High Subcritical Multiplication 3.2 4 2/4↑
(SCM)
Chemical and Volume Control High Pressurizer Level 80% 4 2/4↑ Removes electrical power to the trip
System Isolation (CVCSI) High Narrow Range 9.5 psia 4 2/4↑ solenoids of the following valves:
Containment Pressure • RCS injection valves
Low Low Pressurizer Pressure 1600 psia 4 2/4↓ • RCS discharge valves
Low Low Pressurizer Level 20% 4 2/4↓ • PZR spray valves
Low Low RCS Flow 0.0 ft3/s 4 2/4↓ • RCS high point degasification valves
Tier 2
presented in terms of elevation where reference zero is the bottom of the reactor pool. The analytical limit ranges allow ±12" from the nominal ECCS containment water level
setpoint.
Note 4: Normal AC voltage is monitored at the bus(es) supplying the battery chargers for the highly reliable DC power system.
Note 5: FSAR Section 9.3.4 describes "demineralized water supply isolation valves" as part of the CVCS system.
Note 6: Automatically bypassed when Thot < 475°F (T-6 interlock) or if containment pressure is less than < 1 psia (P-1 interlock).
N-1 Interlock Intermediate Range Log Power Automatically establishes an operating bypass of the
Interlock: Demineralized Water System Isolation on High Subcritical
Multiplication.
Interlock established when at least 3 of
4 Intermediate Range Log Power Operating bypass is automatically removed when Interlock
channels > approximately 1 decade condition is no longer satisfied.
above the channel lower range limit.
N-2L Permissive Power Range Linear Power Permissive: Allows the operator to manually establish an operating bypass
of the following:
Permissive established when at least 3 • Reactor Trip on High-1 Power Range Linear Power. This
of 4 Power Range Linear Power increases the High Power Range High Linear Power trip to the
Channels > 15% RTP High-2 trip setpoint )
• Demineralized Water System Isolation actuation on High-1
Power Range Linear Power
V-1 Interlock FWIV Closed Interlock: Automatically establishes an operating bypass of the following
when N-2H is active (below 15% RTP):
Interlock established when one FWIV • Reactor trip on Low Main Steam Superheat.
indicates closed. • Secondary system isolation on Low Main Superheat.
Table 7.1-6: Design Basis Event Actuation Delays Assumed in the Plant Safety Analysis
Signal Sensor Actuation Delay
High Power Range Linear Power Power Range Neutron Flux 2.0s
SR and IR Log Power Rate SR & IR Neutron Flux Variable
High Power Range Rate Power Range Neutron Flux 2.0s
High Source Range Count Rate Source Range Neutron Flux 3.0s
High Subcritical Multiplication Source Range Neutron Flux 150.0s
High Narrow Range RCS Hot Temperature Riser Outlet Temperature 8.0s
High Narrow Containment Pressure Containment Pressure 2.0s
High Pressurizer Pressure Pressurizer Pressure 2.0s
High Pressurizer Level Pressurizer Level 3.0s
Low Pressurizer Pressure Pressurizer Pressure 2.0s
Low Low Pressurizer Pressure Pressurizer Pressure 2.0s
Low Pressurizer Level Pressurizer Level 3.0s
Low Low Pressurizer Level Pressurizer Level 3.0s
Low RCS Pressure Wide Range RCS Pressure 2.0s
Low Main Steam Pressure Main Steam Pressure 2.0s
Low Low Main Steam Pressure Main Steam Pressure 2.0s
High Main Steam Pressure Main Steam Pressure 2.0s
Low Main Steam Superheat Main Steam Pressure & Temperature 8.0s
High Main Steam Superheat Main Steam Pressure & Temperature 8.0s
Low RCS Flow RCS Flow 6.0s
Low Low RCS Flow RCS Flow 6.0s
High Containment Water Level Containment Level 3.0s
Low AC Voltage to the Battery Chargers AC Voltage 60.0s
High Under-the-Bioshield Temperature Under-the-Bioshield Temperature 8.0s
Tier 2
Iodine:
3E-10 to 5E-8 μCi/cc
Noble Gas:
3E-7 to 1E-2 μCi/cc
[[Outside Air Toxic Gas Sensor Provided by COL applicant based on plant location]]
Outside Air Smoke Detector N/A N/A
CRE Air Delivery Line Flow Sensor 1 0-150 SCFM
CRE Air Delivery Line Flow Sensor 2 0-1000 SCFM
CRE Differential Pressure Sensor 0-2 in water column
Emergency Pressurized Air Pressure 3000-4000 psig
Reactor/Refueling Pool Level Indication 0-69 ft
Spent Fuel Pool Level Indication 0-69 ft
EDSS-C Bus Voltage 0-150 VDC
CRHS Air Supply Isolation Valve Position Open, Closed
CRHS Pressure Relief Isolation Valve Position Open, Closed
CRVS Supply Air Damper Position Open, Closed
CRVS Smoke Purge Exhaust Damper Position Open, Closed
CRVS General Exhaust Damper Position Open, Closed
CRVS Return Air Damper Position Open, Closed
CRVS Outside Air Isolation Damper Position Open, Closed
Note 1: This variable monitors AC power supplied to an EDSS-C battery charger and a CRVS air handling unit.
Note 2: This variable monitors AC power supplied to an EDSS-C battery charger.
Table 7.1-10: Intentional Differences Between Field Programmable Gate Array Architecture
Software Tool Safety Block I and Safety Block II and
Division I SDIS Division II SDIS
Design synthesis tool(s) Suite A Suite B
Design analysis tool(s)
Physical design tool(s)
Design simulation tool(s)
Physical programming tool(s)
iV&V design simulation tool(s) Different than Suite A and Suite B
Table 7.1-11: Partial Spurious Actuation Scenarios for Engineered Safety Features
Actuation System within Safety Block I
Scenario Protective Action(s) on EIM Components Actuated
1 Containment isolation, DHRS, and MSIVs
Secondary System Isolation MS isolation bypass valves
Feedwater isolation valves
Secondary MSIVs
Secondary MSIV bypass valves
Feedwater regulating valves
2 ECCS ECCS reactor recirculation valve (Note 1)
3 ECCS and LTOP ECCS reactor vent valves (Note 1)
4 Containment isolation Containment evacuation CIV
Containment flood & drain CIV
Reactor component cooling water CIVs
5 CVCS isolation and containment CVCS containment isolation valves
isolation
6 DWS isolation and loss of AC power DWS isolation valve
7 PZR heater trip PZR heater breakers
8 DHRS DHRS Actuation Valves
Note 1: The ECCS valves include an inadvertent actuation block (IAB) described in Section 7.2.5.2 that is designed to prevent
the spurious opening of the ECCS valves at normal operating pressures. The spurious opening of the ECCS valves below the
IAB setpoint is bounded by the plant safety analysis described in Chapter 15.
Table 7.1-13: Effects of Digital-Based Common Cause Failure of Level Function Type on
Sensor Block I
Function Type Process Variable Sensor Block I Sensor Block II
Digital-based level PZR level Digital-based CCF OK
measurement Containment water level Digital-based CCF OK
Digital-based pressure PZR pressure OK OK
measurement Wide-range RCS pressure OK OK
Digital-based flow measurement RCS flow OK OK
Table 7.1-17: Effect of FPGA Technology Diversity for Postulated Digital-Based CCF of
MPS Safety Blocks
Event Event Type Safety Block I Safety Block II Comments
SG A SG C SG B SG D
All Design Basis Any Event Type CCF CCF OK OK Based on the diversity attributes between Safety
Events Blocks, a digital-based CCF would be limited to
either Safety Block I or Safety Block II.
All Design Basis Any Event Type OK OK CCF CCF
Events
Tier 2
Category 3 Events
For the events listed in this section, the digital-based sensor subject to a CCF is credited in both the deterministic analyses described in Chapter 15 and best-estimate analyses;
however, multiple, diverse sensors that do not use digital-based technology provide the required protection in the best-estimate D3 coping analyses; therefore, sufficient
sensor diversity exists to provide the required safety function. The FPGA technology diversity in the MPS divisions ensures a digital-based CCF does not prevent the MPS from
performing its required safety function.
Failure of Small Lines Carrying low PZR level (digital-based) (note 1) low PZR level (digital-based) Sensor diversity ensures performance of required safety
Primary Coolant Outside low PZR pressure (digital-based) (note 1) function is satisfied. FPGA technology diversity within the MPS
Containment low PZR pressure (digital-based) limits digital-based CCF impact to one of two divisions - the
high PZR pressure (digital-based)
(note 3) other division remains fully functional.
high main steam superheat
Inadvertent Decrease in Boron high PZR pressure (digital-based) high power range linear power Sensor diversity ensures performance of required safety
Tier 2
Tier 2
high PZR pressure (digital-based) 1) function is satisfied. FPGA technology diversity within the MPS
low PZR pressure (digital-based) limits digital-based CCF impact to one of two divisions - the
high main steam pressure
(note 3) other division remains fully functional.
low PZR pressure (digital-based)
high main steam pressure
low main steam superheat
Loss-of-Coolant Accidents from high PZR pressure (digital-based) high CNV level (digital-based) Diverse sensors not subject to a digital-based CCF provide
a Spectrum of Postulated Piping high CNV level (digital-based) (note 1) (note 1) required protection. FPGA technology diversity within the MPS
Breaks inside CNV high CNV pressure high CNV pressure limits digital-based CCF impact to one of two divisions - the
low PZR level (digital-based) (note 1) other division remains fully functional.
low wide-range RCS pressure
(digital-based) (note 4)
Tier 2
Increase in Steam Flow high power range linear power high power range linear power Diverse sensors not subject to a digital-based CCF provide
7.1-93
high RCS hot temperature low main steam pressure required protection. FPGA technology diversity within the MPS
limits digital-based CCF impact to one of two divisions - the
high main steam superheat
other division remains fully functional.
high PZR pressure (digital-based)
low main steam pressure
Inadvertent Opening of Main high RCS hot temperature low main steam pressure Diverse sensors not subject to a digital-based CCF provide
Steam Safety Valve high main steam superheat high power range linear power required protection. FPGA technology diversity within the MPS
limits digital-based CCF impact to one of two divisions - the
high PZR pressure (digital-based)
other division remains fully functional.
high power range linear power
low main steam pressure
Tier 2
Note 2: The design basis for the digital-based RCS flow sensors in the plant safety analysis described in Section 15.4.6 is to ensure minimum RCS flow rates exist during dilution
events to ensure proper mixing within the RCS; therefore, the RCS flow sensors are not included in Table 7.1-18 as they are not relied upon for detection or mitigation of AOOs
or postulated accidents as described in Section 7.1.5.2. The plant safety analysis credits the high subcritical multiplication protective function for detection and mitigation of
an uncontrolled RCS dilution. Best-estimate analysis of this event concludes the event is non-limiting and does not rely on the digital-based RCS flow sensor to function. The
consequences of RCS flow stagnation or reversal during low power conditions are addressed in NuScale Power, LLC topical report, “Non-Loss-of-Coolant Accident Analysis
Methodology,” TR-0516-49416. The FPGA technology diversity in the MPS divisions ensures a digital-based CCF does not prevent the MPS from performing its required safety
function.
Note 3: Reactor module conditions that reach the pressurizer high or low pressure signal may occur in the best estimate transient progression but actuations from this process
condition are not credited in the D3 coping analysis.
Note 4: Reactor module conditions that reach the low wide range RCS pressure ECCS actuation signal may occur in the best estimate transient progression but actuation from
this process condition is not credited in the D3 coping analysis.
IF THE OOS SWITCH ON THE SFM IS IN THE OPERATE POSITION, THE TRIP DETERMINATION RESULT OF THE SAFETY FUNCTION ALGORITHM IS
SENT TO THE RTS AND ESFAS FOR THAT SAFETY FUNCTION.
IF THE OOS SWITCH IS IN THE OUT OF SERVICE POSITION, THE POSITION OF THE TRIP/BYPASS SWITCH DETERMINES WHAT IS SENT TO THE
RTS AND ESFAS. IF THE TRIP/BYPASS SWITCH IS IN BYPASS, ALL SAFETY FUNCTIONS FOR THAT SFM ARE FORCED TO NOT TRIP OR NOT
ACTUATE. IF THE TRIP/BYPASS SWITCH IS IN THE TRIP POSITION, THEN ALL SAFETY FUNCTIONS FOR THAT SFM ARE FORCED TO TRIP AND
ACTUATE.
IF THE SFM FAILS TO COMMUNICATE CORRECTLY TO SBM OR IS REMOVED, THE POSITION OF THE TRIP/BYPASS SWITCH WILL DETERMINE
THE COMMANDS SENT TO THE RTS AND ESFAS FOR THE SAFETY FUNCTION ON THAT SFM. (ASSOCIATED LOGIC IS SHOWN BELOW)
A
SFM SFM
PS SFM TRIP REMOVED FAILED
DETERMINATION
(TYP.)
OP OOS
XS
TRIP BYP
XS
7.1-101
SFM TRIP TO
CONCIDENT LOGIC
(TYP.)
Fundamental Design Principles
Revision 5
NuScale Final Safety Analysis Report Fundamental Design Principles
A B C D A B C D A B C D A B C D
BYPASS
NS NS NS NS (NOTE 2) NS NS NS NS (NOTE 2) NS NS NS NS (NOTE 2) NS NS NS NS (NOTE 2) HS
I I I I
A A A A A A A A A A A A
RTS ESFAS
P P
N-1 N-1 A A A A A A
F F F F F F
RTS ESFAS
DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I
RTS ESFAS RTS ESFAS RTS ESFAS
(NOTE 1) (NOTE 1) (NOTE 1) (NOTE 1) (NOTE 1) (NOTE 1) (NOTE 1) (NOTE 1)
RTS N-1 ESFAS N-1 RTS N-1 ESFAS N-1 RTS N-2L ESFAS N-2L
PERMISSIVE PERMISSIVE PERMISSIVE PERMISSIVE PERMISSIVE PERMISSIVE
RTS N-1 ESFAS N-1
PERMISSIVE PERMISSIVE/
REACTOR TRIP DEMINERALIZED REACTOR TRIP DEMINERALIZED REACTOR TRIP DEMINERALIZED
INTERLOCK
WATER SYSTEM WATER SYSTEM WATER SYSTEM
ISOLATION ISOLATION ISOLATION
P RTS/ESFAS N-1 PERMISSIVE/INTERLOCK STATUS P RTS/ESFAS N-1 HIGH SR COUNT RATE TRIP STATUS P RTS/ESFAS N-1 HIGH SR LOG POWER RATE TRIP STATUS P RTS/ESFAS N-2L HIGH-1 PR LINEAR POWER TRIP STATUS
ACTIVE 3oo4 IR INPUTS > N-1 SETPOINT > N-1 SETPOINT MANUAL BYPASS PERMITTED > N-1 SETPOINT MANUAL BYPASS PERMITTED > N-2L SETPOINT MANUAL BYPASS PERMITTED
NOT ACTIVE 2oo4 IR INPUTS N-1 SETPOINT N-1 SETPOINT AUTOMATICALLY ENABLED N-1 SETPOINT AUTOMATICALLY ENABLED N-2L SETPOINT AUTOMATICALLY ENABLED
NOTE 1: LOGIC IS SHOWN FOR DIVISION I ONLY. LOGIC FOR DIVISION II IS THE SAME AS DIVISION I.
NOTE 2: THERE IS A TRIP/BYPASS SWITCH FOR EACH SFM THAT HAS A SAFETY FUNCTION THAT SUPPORTS REMOVING THE SFM FROM SERVICE.
NOTE 3: THE REACTOR STARTUP SEQUENCE WILL BE PHASED WITH A STARTUP/HEATUP HOLD POINT. ONCE THIS POWER LEVEL HAS BEEN ESTABLISHED, THE HIGH-1 POWER
TRIP WILL BE BYPASSED SO THAT POWER CAN BE INCREASED TO FULL POWER. THE HIGH-2 POWER TRIP IS IN PLACE WHEN THE HIGH-1 TRIP IS BYPASSED.
Figure 7.1-1c: Power Range High-2 Power Trip and N-2 Interlocks, Low and Low Low RCS Flow Trips
LOW LOW RCS FLOW
HIGH-2 POWER RANGE LINEAR POWER RANGE LINEAR POWER POWER RANGE LINEAR POWER LOW RCS FLOW
POWER N-2H INTERLOCK N-2L PERMISSIVE/INTERLOCK A B C D
FS FS FS FS (NOTE 2)
A B C D
A B C D A B C D A B C D
NS NS NS NS (NOTE 2) (NOTE 2)
NS NS NS NS NS NS NS NS (NOTE 2) FS FS FS FS (NOTE 2)
A A A A
ESFAS REACTOR
TRIPPED
A A A A
I I I I I I I I INTERLOCK RT-1
A A A A
d
dzW/>>Kt>Kt
2/4 Z^&>Kt/EWhd
2/4 2/4 2/4 2/4 2/4 2/4 >K'/
NOTE 1: LOGIC IS SHOWN FOR DIVISION I ONLY. LOGIC FOR DIVISION II IS THE SAME AS DIVISION I.
NOTE 2: THERE IS A TRIP/BYPASS SWITCH FOR EACH SFM THAT HAS A SAFETY FUNCTION THAT SUPPORTS REMOVING THE SFM FROM SERVICE. P ESFAS F-1 LOW LOW RCS FLOW CVCSI ACTUATION INTERLOCK STATUS
3oo4 RCS FLOW INPUTS < LOW LOW SETPOINT FOR MORE
ACTIVE
THAN TD, AND RT-1 ACTIVE
2oo4 RCS FLOW INPUTS > LOW LOW SETPOINT FOR MORE
NOT ACTIVE THAN TD, OR 3oo4 RCS FLOW INPUTS < LOW LOW SETPOINT
FOR LESS THAN TD, OR RT-1 NOT ACTIVE
A B C D A B C D A B C D A B C D
NS NS NS NS (NOTE 2) NS NS NS NS (NOTE 2) (NOTE 2) (NOTE 2)
NS NS NS NS NS NS NS NS
RTS N-2H ESFAS N-2H ESFAS N-2H RTS N-2L ESFAS N-2L
RTS N-2H
INTERLOCK A INTERLOCK INTERLOCK INTERLOCK INTERLOCK
A A A INTERLOCK A A A A A A A A A A A A N-1
INTERLOCK
ESFAS
N-1
F F F F
F F
F
RTS ESFAS RTS ESFAS RTS ESFAS ESFAS
DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I
(NOTE 1) (NOTE 1) (NOTE 1) (NOTE 1) (NOTE 1) (NOTE 1) (NOTE 1)
REACTOR TRIP DEMINERALIZED REACTOR TRIP DEMINERALIZED REACTOR TRIP DEMINERALIZED DEMINERALIZED
WATER SYSTEM WATER SYSTEM WATER SYSTEM WATER SYSTEM
ISOLATION ISOLATION ISOLATION ISOLATION
NOTE 1: LOGIC IS SHOWN FOR DIVISION I ONLY. LOGIC FOR DIVISION II IS THE SAME AS DIVISION I.
NOTE 2: THERE IS A TRIP/BYPASS SWITCH FOR EACH SFM THAT HAS A SAFETY FUNCTION THAT SUPPORTS REMOVING THE SFM FROM SERVICE.
A B C D A B C D
A B C D A B C D A B C D
PS PS PS PS (NOTE 2) PS PS PS PS (NOTE 2) (NOTE 2)
PS PS PS PS (NOTE 2) LS LS LS LS (NOTE 2) LS LS LS LS
A A A A A A A A A A A A A A A A A A A A
F F F
F F
F F F F
ESFAS
RTS ESFAS RTS DIVISION I ESFAS
RTS RTS ESFAS RTS
DIVISION I DIVISION I DIVISION I (NOTE 1) ESFAS
DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I
(NOTE 1) (NOTE 1) (NOTE 1) DIVISION I
(NOTE 1) (NOTE 1) (NOTE 1) (NOTE 1) (NOTE 1)
(NOTE 1)
NOTE 1: LOGIC IS SHOWN FOR DIVISION I ONLY. LOGIC FOR DIVISION II IS THE SAME AS DIVISION I.
NOTE 2: THERE IS A TRIP/BYPASS SWITCH FOR EACH SFM THAT HAS A SAFETY FUNCTION THAT SUPPORTS REMOVING THE SFM FROM SERVICE.
Figure 7.1-1f: Reactor Coolant System Hot Temperature Trip, Temperature Interlocks
HIGH NARROW RANGE RCS
HOT TEMPERATURE
TYPICAL RCS
THOT AVERAGE ESFAS REACTOR
Thavg A A A A I I I I
CALCULATION I I I I TRIPPED I I I I I I I I I I I I
INTERLOCK RT-1
A B C D
TS TS TS TS (NOTE 2)
A A A A
ESFAS RT-1
F F
ESFAS
P
T-2
F ESFAS
ESFAS RTS ESFAS ESFAS
RTS ESFAS ESFAS
DIVISION I
DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I
DIVISION I (NOTE 1)
(NOTE 1) (NOTE 1) (NOTE 1) (NOTE 1) (NOTE 1) (NOTE 1)
(NOTE 1)
Figure 7.1-1g: Pressurizer Level Interlock and Trip, High Containment Pressure, and High Containment Level Trips
L-1
CONTAINMENT WATER LEVEL INTERLOCK LOW LOW PRESSURIZER LEVEL L-2
HIGH NARROW RANGE P-1 HIGH CONTAINMENT
PRESSURIZER LEVEL INTERLOCK
CONTAINMENT PRESSURE NR CNT PRESSURE WATER LEVEL
A B C D A B C D A B C D A B C D A B C D A B C D
ESFAS
ESFAS T-3 ESFAS L-1 ESFAS L-2 ESFAS T-3 RT-1 ESFAS T-2 ESFAS L-1
A A A A I I I I I REACTOR TRIPPED A A A A I I I I
INTERLOCK INTERLOCK INTERLOCK I I I INTERLOCK INTERLOCK
INTERLOCK INTERLOCK INTERLOCK RT-1
A A A A
ESFAS
P
P-1
F
ESFAS ESFAS
P P
RTS L-1 L-2
P
L-1 F
F
F
F ESFAS
RTS ESFAS ESFAS ESFAS ESFAS
ESFAS RTS
DIVISION I F DIVISION I DIVISION I DIVISION I DIVISION I
DIVISION I DIVISION I DIVISION I
(NOTE 1) (NOTE 1) (NOTE 1) (NOTE 1) (NOTE 1)
(NOTE 1) (NOTE 1) (NOTE 1)
ESFAS ESFAS
P NR CNT PRESSURE INTERLOCK STATUS P LOW LOW PRESSURIZER LEVEL TRIP STATUS
P-1 ESFAS L-1
ESFAS HIGH CONTAINMENT WATER LEVEL CONTAINMENT WATER LEVEL
P HIGH CONTAINMENT PRESSURE TRIP STATUS P T-3 AND L-2 RTS L-1 AND ESFAS L-1
L-1 ACTIVE 3oo4 NR CNT PRESS INPUTS < P-1 SETPOINT TRIP STATUS P > L-1 SETPOINT AUTOMATIC BYPASS
INTERLOCK STATUS ESFAS
P PRESSURIZER LEVEL INTERLOCK STATUS
> L-1 SETPOINT AUTOMATIC BYPASS 2oo4 NR CNT PRESS INPUTS P-1 SETPOINT < T-3 AND > L-2 AUTOMATIC BYPASS 3oo4 LEVEL INPUTS > L-1 SETPOINT L-1 SETPOINT L-2
NOT ACTIVE ACTIVE AUTOMATICALLY ENABLED
L-1 SETPOINT T-3 OR L-2 AND REACTOR TRIPPED
AUTOMATICALLY ENABLED AUTOMATICALLY ENABLED ACTIVE 3oo4 LEVEL INPUTS > L-2 SETPOINT
NOT ACTIVE 2oo4 THOT INPUTS L-1 SETPOINT ESFAS
P LOW LOW PRESSURIZER LEVEL TRIP STATUS
ESFAS OR REACTOR NOT TRIPPED T-2
HIGH CONTAINMENT PRESSURE TRIP STATUS NOT ACTIVE 2oo4 THOT INPUTS L-2 SETPOINT
P
T-3 < T-2 SETPOINT AUTOMATIC BYPASS
< T-3 SETPOINT AUTOMATIC BYPASS T-2 SETPOINT AUTOMATICALLY ENABLED
T-3 SETPOINT AUTOMATICALLY ENABLED
NOTE 1: LOGIC IS SHOWN FOR DIVISION I ONLY. LOGIC FOR DIVISION II IS THE SAME AS DIVISION I.
NOTE 2: THERE IS A TRIP/BYPASS SWITCH FOR EACH SFM THAT HAS A SAFETY FUNCTION THAT SUPPORTS REMOVING THE SFM FROM SERVICE.
Figure 7.1-1h: Steam Generator Low and Low Low Main Steam Pressure Trips
LOW MAIN STEAM LOW LOW MAIN STEAM LOW LOW MAIN STEAM
LOW MAIN STEAM PRESSURE
PRESSURE PRESSURE PRESSURE
STEAM GENERATOR 1
STEAM GENERATOR 2 STEAM GENERATOR 1 STEAM GENERATOR 2
A B C D A B C D A B C D A B C D
PS PS PS PS (NOTE 2) PS PS PS PS PS PS PS PS PS PS PS PS
(NOTE 2) (NOTE 2) (NOTE 2)
A A A A A A A A A A
A A A A A A
RTS N-2H ESFAS N-2H RTS N-2H ESFAS N-2H ESFAS L-1 ESFAS L-1
INTERLOCK INTERLOCK INTERLOCK INTERLOCK INTERLOCK INTERLOCK
ESFAS L-1
ESFAS N-2H ESFAS L-1
RTS N-2H ESFAS N-2H
RTS N-2H
F
F
F F
F F F F F F
RTS ESFAS RTS ESFAS RTS RTS
ESFAS ESFAS
DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I
(NOTE 1) (NOTE 1) (NOTE 1) (NOTE 1) (NOTE 1)
(NOTE 1) (NOTE 1) (NOTE 1)
REACTOR TRIP SECONDARY DEMINERALIZED REACTOR TRIP SECONDARY DEMINERALIZED REACTOR TRIP SECONDARY DEMINERALIZED REACTOR TRIP SECONDARY DEMINERALIZED
SYSTEM WATER SYSTEM SYSTEM WATER SYSTEM SYSTEM WATER SYSTEM SYSTEM WATER SYSTEM
ISOLATION ISOLATION ISOLATION ISOLATION ISOLATION ISOLATION ISOLATION ISOLATION
RTS/ESFAS RTS/ESFAS ESFAS LOW LOW MIAN STEAM PRESSURE SG 1 TRIP ESFAS LOW LOW MAIN STEAM PRESSURE SG 2 TRIP
P LOW MAIN STEAM PRESSURE SG 1 TRIP STATUS P LOW MAIN STEAM PRESSURE SG 2 TRIP STATUS P P
N-2H N-2H L-1 STATUS L-1 STATUS
N-2H SETPOINT AUTOMATICALLY ENABLED N-2H SETPOINT AUTOMATICALLY ENABLED > L-1 SETPOINT AUTOMATIC BYPASS > L-1 SETPOINT AUTOMATIC BYPASS
< N-2H SETPOINT AUTOMATIC BYPASS < N-2H SETPOINT AUTOMATIC BYPASS L-1 SETPOINT AUTOMATICALLY ENABLED L-1 SETPOINT AUTOMATICALLY ENABLED
NOTE 1: LOGIC IS SHOWN FOR DIVISION I ONLY. LOGIC FOR DIVISION II IS THE SAME AS DIVISION I.
NOTE 2: THERE IS A TRIP/BYPASS SWITCH FOR EACH SFM THAT HAS A SAFETY FUNCTION THAT SUPPORTS REMOVING THE SFM FROM SERVICE.
Figure 7.1-1i: High Main Steam Pressure and Steam Generator Low and High Steam Superheat Trips
HIGH MAIN STEAM PRESSURE HIGH MAIN STEAM PRESSURE LOW MAIN STEAM SUPERHEAT LOW MAIN STEAM SUPERHEAT HIGH MAIN STEAM SUPERHEAT HIGH MAIN STEAM SUPERHEAT
STEAM GENERATOR 1 STEAM GENERATOR 2 STEAM GENERATOR 1 STEAM GENERATOR 2 ESFAS L-1 STEAM GENERATOR 1 STEAM GENERATOR 2
INTERLOCK
f(x)
A A A A A A A A A A A A V-1 A A A A A A A A
(+) ESFAS L-1
V-1 INTERLOCK
(—) INTERLOCK
INTERLOCK TSAT RTS N-2H
INTERLOCK
TYPICAL STEAM
TSH SUPER HEAT ESFAS N-2H
RTS N-2H CALCULATION INTERLOCK ESFAS
INTERLOCK V-1
2/4 2/4 2/4 2/4 2/4 2/4 2/4 2/4 2/4 2/4
ESFAS
V-1 N-2H
A B C D INTERLOCK
RTS
TS TS TS TS (NOTE 2) N-2H
F
RTS F
V-1 A
A A A A ESFAS L-1
F (NOTE 2) F
F F
ESFAS
V-1
ESFAS
F
N-2H F
RTS 2/4 2/4
N-2H
RTS
A F
RTS ESFAS V-1 ESFAS
RTS ESFAS ESFAS L-1 RTS RTS ESFAS RTS ESFAS
DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I F DIVISION I
(NOTE 2) DIVISION I DIVISION I DIVISION I DIVISION I
(NOTE 1) (NOTE 1) (NOTE 1) (NOTE 1) (NOTE 1) F (NOTE 1)
(NOTE 1) (NOTE 1) (NOTE 1) (NOTE 1)
REACTOR TRIP DEMINERALIZED SECONDARY DECAY HEAT PRESSURIZER REACTOR TRIP SECONDARY REACTOR TRIP REACTOR TRIP SECONDARY REACTOR TRIP SECONDARY
DEMINERALIZED SECONDARY DEMINERALIZED DEMINERALIZED
WATER SYSTEM SYSTEM REMOVAL SYSTEM HEATER TRIP SYSTEM WATER SYSTEM SYSTEM WATER SYSTEM SYSTEM WATER SYSTEM
ISOLATION ISOLATION ACTUATION ISOLATION SYSTEM
F F ISOLATION ISOLATION ISOLATION ISOLATION ISOLATION
RTS ESFAS ISOLATION
DIVISION I DIVISION I
F
(NOTE 1) (NOTE 1)
ESFAS
P LOW STEAM SUPERHEAT SG 1 TRIP STATUS
L-1
DEMINERALIZED DECAY HEAT PRESSURIZER > L-1 SETPOINT AUTOMATIC BYPASS
WATER SYSTEM REMOVAL SYSTEM HEATER TRIP
ISOLATION ACTUATION L-1 SETPOINT AUTOMATICALLY ENABLED
REACTOR TRIP DEMINERALIZED P V-1 AND RTS N-2H AND ESFAS N-2H REACTOR TRIP AND
SECONDARY
WATER SYSTEM SECONDARY SYSTEM ISOLATION INTERLOCK
SYSTEM
ISOLATION 1 OR 2 FWIV CLOSED AND < N-2H SETPOINT
ISOLATION AUTOMATIC BYPASS
NOTE 1: LOGIC IS SHOWN FOR DIVISION I ONLY. LOGIC FOR DIVISION II IS THE SAME AS DIVISION I.
NO FWIV CLOSED OR N-2H SETPOINT AUTOMATICALLY ENABLED
NOTE 2: THERE IS A TRIP/BYPASS SWITCH FOR EACH SFM THAT HAS A SAFETY FUNCTION THAT SUPPORTS REMOVING THE SFM FROM SERVICE.
ESFAS
P LOW STEAM SUPERHEAT SG 1 TRIP STATUS
L-1
> L-1 SETPOINT AUTOMATIC BYPASS
L-1 SETPOINT AUTOMATICALLY ENABLED
P V-1 AND RTS N-2H AND ESFAS N-2H REACTOR TRIP AND
SECONDARY SYSTEM ISOLATION INTERLOCK
1 OR 2 FWIV CLOSED AND < N-2H SETPOINT AUTOMATIC BYPASS
NO FWIV CLOSED OR N-2H SETPOINT AUTOMATICALLY ENABLED
RTS RTS
DIVISION I DIVISION I
(NOTE 1) (NOTE 1)
NOTE 1: LOGIC IS SHOWN FOR DIVISION I ONLY. LOGIC FOR DIVISION II IS THE SAME AS DIVISION I.
Figure 7.1-1k: ESFAS - Containment System Isolation and Chemical and Volume Control System Isolation Interlocks
LOW AC HIGH UNDER-THE- LOW LOW HIGH
VOLTAGE TO BIOSHIELD LOW LOW HIGH CONTAINMENT ESFAS REACTOR PRESSURIZER LOW LOW RCS PRESSURIZER
BATTERY TEMPERATURE PRESSURIZER LEVEL PRESSURE TRIPPED PRESSURE FLOW LEVEL
CHARGERS RT-1 INTERLOCK
ACTUATE
HS
(NOTE 2)
I A I A
CONTAINMENT
CONTAINMENT REACTOR SECONDARY
FLOODING (M) (A) (M) (M) (A) (M) (M) (A) (M) (M) (A) (M)
EVACUATION COMPONENT SYSTEM
AND DRAIN
ISOLATION COOLING WATER ISOLATION
ISOLATION PRESSURIZER RCS INJECTION RCS DISCHARGE RPV HIGH POINT
ISOLATION
SPRAY ISOLATION ISOLATION DEGASIFICATION
(NOTE 1)
(NOTE 1) ISOLATION LINE ISOLATION
(NOTE 1)
(NOTE 1)
NOTE 1: LOGIC IS SHOWN FOR DIVISION I ONLY. LOGIC FOR DIVISION II IS THE SAME AS DIVISION I.
NOTE 3: MANUAL ACTUATION INITIATES CONTAINMENT SYSTEM ISOLATION AT THE DIVISION LEVEL THROUGH THE EIM APL LOGIC.
NOTE 4: MANUAL ACTUATION INITIATES CHEMICAL AND VOLUME CONTROL SYSTEM ISOLATION AT THE DIVISION LEVEL THROUGH THE EIM APL LOGIC.
Figure 7.1-1l: ESFAS - Decay Heat Removal System and Secondary System Isolation Actuation, FWIV Interlock
HIGH MAIN HIGH MAIN LOW MAIN LOW MAIN LOW LOW LOW LOW HIGH MAIN HIGH MAIN
STEAM STEAM LOW AC STEAM STEAM MAIN STEAM MAIN STEAM STEAM STEAM HIGH STEAM HIGH STEAM LOW STEAM LOW STEAM LOW AC AUTOMATIC
PRESSURE PRESSURE VOLTAGE TO LOW LOW LOW LOW HIGH PRESSURE PRESSURE PRESSURE PRESSURE
HIGH PRESSURIZER HIGH RCS HOT PRESSURE PRESSURE SUPERHEAT SUPERHEAT SUPERHEAT SUPERHEAT HIGH UNDER- HIGH VOLTAGE TO CONTIANMENT FEEDWATER
STEAM STEAM BATTERY PRESSURIZER PRESSURIZER PRESSURIZER HIGH RCS HOT STEAM STEAM FEEDWATER
PRESSURE TEMPERATURE STEAM STEAM STEAM STEAM STEAM STEAM STEAM STEAM THE-BIOSHIELD CONTAINMENT BATTERY SYSTEM
GENERATOR 1 GENERATOR 2 CHARGERS PRESSURE LEVEL PRESSURE TEMPERATURE GENERATOR 1 ISOLATION ISOLATION
GENERATOR 2 GENERATOR 1 GENERATOR 2 GENERATOR 1 GENERATOR 2 GENERATOR 1 GENERATOR 2 GENERATOR 1 GENERATOR 2 TEMPERATURE PRESSURE CHARGERS ISOLATION VALVE 1 VALVE 2
MANUAL
CONTAINMENT
SYSTEM ISOLATION
V-1
P
INTERLOCK
(NOTE 2)
I A
(NOTE 3)
(M) (A) (M) (M) (A) (M) (M) (A) (M) (M) (A) (M) (A) (M) (M) (A) (M) (M) (A) (M) (A) (M) FWIV INTERLOCK
(M) (A) (M) (A) (M) (M) (A) (M) (M) (A) (M) (M) (A) (M) (M) (A) (M) V-1
FEEDWATER FEEDWATER MAIN STEAM DHRS MAIN STEAM SECONDARY (NOTE 1)
REGULATING SECONDARY PRESSURIZER FEEDWATER FEEDWATER MAIN STEAM MAIN STEAM SECONDARY
ISOLATION ISOLATION ACTUATION ISOLATION MAIN STEAM SECONDARY
VALVES MSIV BYPASS HEATER TRIP REGULATING ISOLATION ISOLATION ISOLATION MAIN STEAM
VALVES VALVES VALVES BYPASS ISOLATION MSIV BYPASS
VALVES VALVES VALVES VALVES BYPASS ISOLATION
(NOTE 4) VALVES VALVES VALVES
(NOTE 1) VALVES VALVES
P V-1 FWIV INTERLOCK STATUS
NOTE 1: LOGIC IS SHOWN FOR DIVISION I ONLY. LOGIC FOR DIVISION II IS THE SAME AS DIVISION I. ACTIVE 1 OR 2 FWIV CLOSED
NOTE 2: TWO SWITCHES, ONE PER ESFAS DIVISION. NOT ACTIVE NO FWIV CLOSED
NOTE 3: MANUAL ACTUATE INITIATES ACTUATION AT THE DIVISION LEVEL THROUGH THE EIM APL LOGIC.
NOTE 4: DECAY HEAT REMOVAL SYSTEM ACTUATION IS DEFINED AS THE SIMULTANEOUS CLOSURE OF THE FWIV, FWRV, MSIV, SECONDARY MSIV
AND THE OPENING OF THE DHRS ACTUATION VALVES FOR A GIVEN TRAIN OF DHRS.
NOTE 5: TWO MANUAL ACTUATION ISOLATION SIGNALS, ONE PER RTS/ESFAS DIVISION.
Figure 7.1-1m: ESFAS - Demineralized Water System Isolation, Pressurizer Heater Trip
SOURCE RANGE COUNT RATE HIGH SUBCRITICAL MULTIPLICATION RATE
NOTE 5: TWO MANUAL ACTUATION ISOLATION SIGNALS, ONE PER RTS/ESFAS DIVISION.
PRESSURIZER HEATER BREAKER ARRANGEMENT
Figure 7.1-1n: ESFAS Emergency Core Cooling System Actuation, Low Temperature Overpressure Protection Actuation
WR RCS COLD
TEMPERATURE
(NOTE 5) f(x)
PS PS PS PS TS TS TS TS PS PS PS PS HS
LTOP
SP ACTUATE (NOTE 2)
f(x) f(x) f(x) f(x) I A
I I I I
A A
A A I I
I I
2/4 2/4
2/4
I A
T-1 ESFAS
P T-1
(NOTE 4)
I A
LTOP ACTUATION
I A
I A
LTOP MANUAL ACTUATION (M) (NOTE 3) ECCS MANUAL ACTUATION (M) (NOTE 3)
OPEN OPEN
ECCS REACTOR ECCS REACTOR
VENT VALVE RECIRCULATION VALVE
NOTE 1: LOGIC IS SHOWN FOR DIVISION I ONLY. LOGIC FOR DIVISION II IS THE SAME AS DIVISION I.
NOTE 2: TWO SWITCHES, ONE PER ESFAS DIVISION.
NOTE 3: MANUAL ACTUATE INITIATES LTOP ACTUATION AND EMERGENCY CORE COOLING SYSTEM ACTUATION AT THE DIVISION LEVEL THROUGH THE
EIM APL LOGIC.
NOTE 4: LOW TEMPERATURE INTERLOCK T-1: AUTOMATIC BLOCK ABOVE T-1; AUTOMATIC LTOP ENABLE BELOW T-1.
NOTE 5: LTOP SETPOINT (SP) IS CALCULATED BASED ON WR RCS COLD TEMPERATURE. LTOP ACTUATION OCCURS
WHEN 2/4 WR RCS PRESSURE INPUTS INCREASE ABOVE THE LTOP SP. (REFERENCE 3)
NOTE 6: TWO MANUAL ACTUATION ISOLATION SIGNALS, ONE PER RTS/ESFAS DIVISION.
NOTE 7: IF NR CONTAINMENT PRESSURE INTERLOCK P-1 IS ACTIVE OR NR RCS THOT INTERLOCK T-6 IS ACTIVE, THEN A BYPASS IS ACTIVE FOR
ECCS ACTUATION ON LOW RCS PRESSURE.
NS ENABLE NS ENABLE
NS ENABLE NS ENABLE
NS DISABLE NS DISABLE
NS DISABLE NS DISABLE
MANUAL MANUAL
MANUAL MANUAL
AUTO AUTO
AUTO AUTO
I I I I I I
I I
VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY
OPENED CLOSED OPENED CLOSED OPENED CLOSED OPENED CLOSED
(NOTE 4) (NOTE 4)
(NOTE 4) (NOTE 4)
(NOTE 2) (NOTE 2)
(NOTE 1) (NOTE 1) (NOTE 1) (NOTE 1)
NOTE 1: SOLENOIDS ARE ENERGIZED BY REDUNDANT EIMS TO CLOSE VALVE; SOLENOIDS ARE DE-ENERGIZED TO OPEN VALVE WHEN BOTH EIM OUTPUTS ARE DE-ENERGIZED.
DECAY HEAT REMOVAL SYSTEM
NOTE 5: LOGIC IS SHOWN FOR DIVISION I AND II. BOTH DIVISIONS ARE SHOWN TO INDICATE UNIQUE ACTUATED EQUIPMENT
NUMBERS ASSOCIATED WITH EACH REDUNDANT DIVISION. VALVE ACTUATION
NOTE 2: ONE ENABLE NONSAFETY CONTROL SWITCH PER DIVISION. THE SINGLE SWITCH ENABLES NONSAFETY CONTROL TO ALL ESF COMPONENTS.
NOTE 3: THE LOGIC SHOWN IS IMPLEMENTED IN REDUNDANT EIM ACTUATION PRIORITY LOGIC (APL) MODULES. A SINGLE EIM CAN BE REMOVED FOR MAINTENANCE, AND THE NOTE 6: NONSAFETY CONTROL INPUTS CONSIST OF 14 INDIVIDUAL HARDWIRED SIGNALS.
VALVE LOGIC WILL REMAIN FUNCTIONAL WITH THE EIM THAT REMAINS IN SERVICE.
NOTE 4: THE EIM APL LOGIC INCLUDES A SEAL-IN TO ENSURE COMPLETION OF THE PROTECTIVE ACTION. THE SEAL-IN REMAINS IN PLACE UNTIL POSITION FEEDBACK INDICATES THAT THE
VALVE HAS REACHED THE POSITION DEMANDED BY THE PROTECTIVE ACTION. THE PROTECTIVE ACTION IS FAIL-SAFE, OR DE-ENERGIZE TO ACTUATE.
SAFETY
DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I DIVISION II
AUTOMATIC MANUAL MANUAL DIVISION II DIVISION II DIVISION II DIVISION II DIVISION II DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I DIVISION II DIVISION II DIVISION II DIVISION II
MANUAL NONSAFETY NONSAFETY
DHRS OR SSI SSI DHRS CONTAINMENT AUTOMATIC MANUAL MANUAL MANUAL NONSAFETY AUTOMATIC MANUAL MANUAL MANUAL NONSAFETY AUTOMATIC MANUAL MANUAL MANUAL
CONTROL CONTROL
ACTUATION ACTUATION ACTUATION ISOLATION DHRS OR SSI SSI DHRS CONTAINMENT CONTROL DHRS OR SSI SSI DHRS CONTAINMENT CONTROL DHRS OR SSI SSI DHRS CONTAINMENT
(NOTE 2) ACTUATION ACTUATION (NOTE 2)
ACTUATION ACTUATION ACTUATION ISOLATION (NOTE 2) ACTUATION ACTUATION ACTUATION ISOLATION (NOTE 2) ACTUATION ISOLATION
(A) (M) (M) (M) (E) (D) (A) (M) (M) (M) (E) (D) (A) (M) (M) (M) (E) (D) (A) (M) (M) (M) (E) (D)
CLOSE NONSAFETY INPUT CLOSE NONSAFETY INPUT CLOSE NONSAFETY INPUT CLOSE NONSAFETY INPUT
DECODE LOGIC DECODE LOGIC DECODE LOGIC DECODE LOGIC
NS ENABLE NS ENABLE NS ENABLE NS ENABLE
I I I I I I I
I
VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY
CLOSED OPENED CLOSED OPENED CLOSED OPENED CLOSED OPENED
MAIN STEAM ISOLATION VALVE MAIN STEAM ISOLATION VALVE MAIN STEAM ISOLATION VALVE MAIN STEAM ISOLATION VALVE
(NOTE 6) (NOTE 6) (NOTE 6) (NOTE 6)
ACTUATION AND PRIORITY LOGIC (APL) (NOTE 3) EIM OUT ESFAS DIVISION I ACTUATION AND PRIORITY LOGIC (APL) (NOTE 3) EIM OUT ESFAS DIVISION II ACTUATION AND PRIORITY LOGIC (APL) (NOTE 3) EIM OUT ESFAS DIVISION I ACTUATION AND PRIORITY LOGIC (APL) (NOTE 3) EIM OUT ESFAS DIVISION II
SOLENOID VALVE VALVE SOLENOID VALVE SOLENOID VALVE VALVE SOLENOID VALVE
NOTE 1: SOLENOID IS ENERGIZED BY REDUNDANT EIMS TO OPEN VALVE; SOLENOID IS DE-ENERGIZED TO CLOSE VALVE WHEN BOTH EIM OUTPUTS ARE DE-ENERGIZED.
NOTE 2: ONE ENABLE NONSAFETY CONTROL SWITCH PER DIVISION. THE SINGLE SWITCH ENABLES NONSAFETY CONTROL TO ALL ESF COMPONENTS.
NOTE 6: LOGIC IS SHOWN FOR DIVISION I AND II. BOTH DIVISIONS ARE SHOWN TO INDICATE UNIQUE ACTUATED EQUIPMENT
NOTE 3: THE LOGIC SHOWN IS IMPLEMENTED IN REDUNDANT EIM ACTUATION PRIORITY LOGIC (APL) MODULES. A SINGLE EIM CAN BE REMOVED FOR MAINTENANCE, AND THE
NUMBERS ASSOCIATED WITH EACH REDUNDANT DIVISION.
VALVE LOGIC WILL REMAIN FUNCTIONAL WITH THE EIM THAT REMAINS IN SERVICE.
NOTE 4: THE EIM APL LOGIC INCLUDES A SEAL-IN TO ENSURE COMPLETION OF THE PROTECTIVE ACTION. THE SEAL-IN REMAINS IN PLACE UNTIL POSITION FEEDBACK INDICATES THAT THE NOTE 7: NONSAFETY CONTROL INPUTS CONSIST OF 14 INDIVIDUAL HARDWIRED SIGNALS.
VALVE HAS REACHED THE POSITION DEMANDED BY THE PROTECTIVE ACTION. THE PROTECTIVE ACTION IS FAIL-SAFE, OR DE-ENERGIZE TO ACTUATE.
NOTE 5: VALVE IS CONTROLLED BY TWO REDUNDANT SOLENOIDS. ONE FROM EACH DIVISION. THE VALVE CLOSES WHEN EITHER THE DIVISION I OR DIVISION II SOLENOID IS DE-ENERGIZED.
THE VALVE OPENS ONLY WHEN BOTH THE DIVISION I AND DIVISION II SOLENOIDS ARE ENERGIZED.
NONSAFETY
DIVISION II SAFETY
DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I DIVISION II DIVISION II DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I
DIVISION II DIVISION II NONSAFETY DIVISION II DIVISION II DIVISION II DIVISION II DIVISION II
AUTOMATIC MANUAL MANUAL MANUAL NONSAFETY AUTOMATIC MANUAL MANUAL MANUAL AUTOMATIC MANUAL MANUAL MANUAL NONSAFETY
CONTROL AUTOMATIC MANUAL MANUAL MANUAL NONSAFETY
DHRS OR SSI SSI DHRS CONTAINMENT CONTROL DHRS OR SSI SSI DHRS CONTAINMENT DHRS OR SSI SSI DHRS CONTAINMENT CONTROL
(NOTE 2) DHRS OR SSI SSI DHRS CONTAINMENT CONTROL
ACTUATION ACTUATION ACTUATION ISOLATION (NOTE 2) ACTUATION ACTUATION ACTUATION ISOLATION ACTUATION ACTUATION ACTUATION ISOLATION (NOTE 2) ACTUATION ACTUATION ACTUATION ISOLATION (NOTE 2)
(A) (M) (M) (M) (A) (M) (M) (M) (E) (D) (A) (M) (M) (M) (E) (D) (A) (M) (M) (M) (E) (D)
(E) (D)
I I I I I I I
I
VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY
CLOSED OPENED CLOSED OPENED CLOSED OPENED CLOSED OPENED
MS ISOLATION BYPASS VALVE MS ISOLATION BYPASS VALVE MS ISOLATION BYPASS VALVE MS ISOLATION BYPASS VALVE
ACTUATION AND PRIORITY LOGIC (APL) (NOTE 3) (NOTE 6) EIM OUT ESFAS DIVISION I ACTUATION AND PRIORITY LOGIC (APL) (NOTE 3) (NOTE 6) EIM OUT ESFAS DIVISION II ACTUATION AND PRIORITY LOGIC (APL) (NOTE 3) (NOTE 6) EIM OUT ESFAS DIVISION I ACTUATION AND PRIORITY LOGIC (APL) (NOTE 3) (NOTE 6) EIM OUT ESFAS DIVISION II
(NOTE 2)
SOLENOID VALVE VALVE SOLENOID VALVE SOLENOID VALVE VALVE SOLENOID VALVE
NOTE 1: SOLENOID IS ENERGIZED BY REDUNDANT EIMS TO OPEN VALVE; SOLENOID IS DE-ENERGIZED TO CLOSE VALVE WHEN BOTH EIM OUTPUTS ARE DE-ENERGIZED.
NOTE 2: ONE ENABLE NONSAFETY CONTROL SWITCH PER DIVISION. THE SINGLE SWITCH ENABLES NONSAFETY CONTROL TO ALL ESF COMPONENTS.
NOTE 6: LOGIC IS SHOWN FOR DIVISION I AND II. BOTH DIVISIONS ARE SHOWN TO INDICATE UNIQUE ACTUATED EQUIPMENT
NOTE 3: THE LOGIC SHOWN IS IMPLEMENTED IN REDUNDANT EIM ACTUATION PRIORITY LOGIC (APL) MODULES. A SINGLE EIM CAN BE REMOVED FOR MAINTENANCE, AND THE NUMBERS ASSOCIATED WITH EACH REDUNDANT DIVISION.
VALVE LOGIC WILL REMAIN FUNCTIONAL WITH THE EIM THAT REMAINS IN SERVICE.
NOTE 4: THE EIM APL LOGIC INCLUDES A SEAL-IN TO ENSURE COMPLETION OF THE PROTECTIVE ACTION. THE SEAL-IN REMAINS IN PLACE UNTIL POSITION FEEDBACK INDICATES THAT THE NOTE 7: NONSAFETY CONTROL INPUTS CONSIST OF 14 INDIVIDUAL HARDWIRED SIGNALS.
VALVE HAS REACHED THE POSITION DEMANDED BY THE PROTECTIVE ACTION. THE PROTECTIVE ACTION IS FAIL-SAFE, OR DE-ENERGIZE TO ACTUATE.
NOTE 5: VALVE IS CONTROLLED BY TWO REDUNDANT SOLENOIDS. ONE FROM EACH DIVISION. THE VALVE CLOSES WHEN EITHER THE DIVISION I OR DIVISION II SOLENOID IS DE-ENERGIZED.
THE VALVE OPENS ONLY WHEN BOTH THE DIVISION I AND DIVISION II SOLENOIDS ARE ENERGIZED.
NONSAFETY
SAFETY
DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I DIVISION II DIVISION II DIVISION II
DIVISION I DIVISION II DIVISION II DIVISION II DIVISION II DIVISION II DIVISION II DIVISION II
AUTOMATIC MANUAL AUTOMATIC MANUAL MANUAL MANUAL NONSAFETY AUTOMATIC
MANUAL MANUAL NONSAFETY AUTOMATIC MANUAL MANUAL MANUAL MANUAL MANUAL MANUAL NONSAFETY
NONSAFETY DHRS OR SSI SSI DHRS CONTAINMENT CONTROL
DHRS OR SSI SSI DHRS CONTAINMENT CONTROL DHRS OR SSI DHRS OR SSI SSI DHRS CONTAINMENT CONTROL
SSI DHRS CONTAINMENT CONTROL ACTUATION ACTUATION ACTUATION ISOLATION
ACTUATION ACTUATION ACTUATION ISOLATION (NOTE 2) ACTUATION (NOTE 2) ACTUATION ACTUATION ACTUATION ISOLATION (NOTE 2)
ACTUATION ACTUATION ISOLATION (NOTE 2)
(A) (M) (M) (M) (E) (D) (A) (M) (M) (M) (E) (D) (A) (M) (M) (M) (E) (D) (A) (M) (M) (M) (E) (D)
I I I I I I I
I
VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY
CLOSED OPENED CLOSED OPENED CLOSED OPENED CLOSED OPENED
SAFETY
SAFETY
NONSAFETY
NONSAFETY
SOLENOID VALVE VALVE SOLENOID VALVE
NONSAFETY
SAFETY
DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I DIVISION II DIVISION II DIVISION II DIVISION II DIVISION II DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I DIVISION II DIVISION II DIVISION II DIVISION II DIVISION II
AUTOMATIC MANUAL MANUAL MANUAL NONSAFETY AUTOMATIC MANUAL MANUAL MANUAL NONSAFETY AUTOMATIC MANUAL MANUAL MANUAL NONSAFETY AUTOMATIC MANUAL MANUAL MANUAL NONSAFETY
DHRS OR SSI SSI DHRS CONTAINMENT CONTROL DHRS OR SSI SSI DHRS CONTAINMENT CONTROL DHRS OR SSI SSI DHRS CONTAINMENT CONTROL DHRS OR SSI SSI DHRS CONTAINMENT CONTROL
ACTUATION ACTUATION ACTUATION ISOLATION ACTUATION ACTUATION ACTUATION ISOLATION ACTUATION ACTUATION ACTUATION ISOLATION (NOTE 2) ACTUATION ACTUATION ACTUATION ISOLATION (NOTE 2)
(NOTE 2) (NOTE 2)
(A) (M) (M) (M) (E) (D) (A) (M) (M) (M) (E) (D) (A) (M) (M) (M) (E) (D) (A) (M) (M) (M) (E) (D)
I I I I I I I
I
VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY
CLOSED OPENED CLOSED OPENED CLOSED OPENED CLOSED OPENED
SAFETY
NONSAFETY SAFETY
NONSAFETY
SAFETY
DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I DIVISION II DIVISION II DIVISION II DIVISION I DIVISION I DIVISION I DIVISION I DIVISION I DIVISION II DIVISION II DIVISION II
DIVISION II DIVISION II DIVISION II DIVISION II
AUTOMATIC MANUAL MANUAL MANUAL NONSAFETY AUTOMATIC AUTOMATIC MANUAL MANUAL MANUAL NONSAFETY AUTOMATIC
MANUAL MANUAL MANUAL NONSAFETY MANUAL MANUAL MANUAL NONSAFETY
DHRS OR SSI SSI DHRS CONTAINMENT CONTROL DHRS OR SSI DHRS OR SSI SSI DHRS CONTAINMENT CONTROL DHRS OR SSI
SSI DHRS CONTAINMENT CONTROL SSI DHRS CONTAINMENT CONTROL
ACTUATION ACTUATION ACTUATION ISOLATION (NOTE 2) ACTUATION ACTUATION ACTUATION ACTUATION ISOLATION (NOTE 2) ACTUATION
ACTUATION ACTUATION ISOLATION (NOTE 2) ACTUATION ACTUATION ISOLATION (NOTE 2)
(A) (M) (M) (M) (E) (D) (A) (M) (M) (M) (E) (D) (A) (M) (M) (M) (E) (D) (A) (M) (M) (M) (E) (D)
I I I I I I I
I
VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY
CLOSED OPENED CLOSED OPENED CLOSED OPENED CLOSED OPENED
SOLENOID VALVE VALVE SOLENOID VALVE SOLENOID VALVE VALVE SOLENOID VALVE
NOTE 1: SOLENOID IS ENERGIZED BY REDUNDANT EIMS TO OPEN VALVE; SOLENOID IS DE-ENERGIZED TO CLOSE VALVE WHEN BOTH EIM OUTPUTS ARE DE-ENERGIZED.
NOTE 2: ONE ENABLE NONSAFETY CONTROL SWITCH PER DIVISION. THE SINGLE SWITCH ENABLES NONSAFETY CONTROL TO ALL ESF COMPONENTS.
NOTE 6: LOGIC IS SHOWN FOR DIVISION I AND II. BOTH DIVISIONS ARE SHOWN TO INDICATE UNIQUE ACTUATED EQUIPMENT
NOTE 3: THE LOGIC SHOWN IS IMPLEMENTED IN REDUNDANT EIM ACTUATION PRIORITY LOGIC (APL) MODULES. A SINGLE EIM CAN BE REMOVED FOR MAINTENANCE, AND THE NUMBERS ASSOCIATED WITH EACH REDUNDANT DIVISION.
VALVE LOGIC WILL REMAIN FUNCTIONAL WITH THE EIM THAT REMAINS IN SERVICE.
NOTE 4: THE EIM APL LOGIC INCLUDES A SEAL-IN TO ENSURE COMPLETION OF THE PROTECTIVE ACTION. THE SEAL-IN REMAINS IN PLACE UNTIL POSITION FEEDBACK INDICATES THAT THE NOTE 7: NONSAFETY CONTROL INPUTS CONSIST OF 14 INDIVIDUAL HARDWIRED SIGNALS.
VALVE HAS REACHED THE POSITION DEMANDED BY THE PROTECTIVE ACTION. THE PROTECTIVE ACTION IS FAIL-SAFE, OR DE-ENERGIZE TO ACTUATE.
NOTE 5: VALVE IS CONTROLLED BY TWO REDUNDANT SOLENOIDS. ONE FROM EACH DIVISION. THE VALVE CLOSES WHEN EITHER THE DIVISION I OR DIVISION II SOLENOID IS DE-ENERGIZED.
THE VALVE OPENS ONLY WHEN BOTH THE DIVISION I AND DIVISION II SOLENOIDS ARE ENERGIZED.
NONSAFETY
(A) (M) (M) (M) (E) (D) (A) (M) (M) (M) (E) (D) (A) (M) (M) (M) (E) (D) (A) (M) (M) (M) (E) (D)
I I I I I I I
I
VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY
CLOSED OPENED CLOSED OPENED CLOSED OPENED CLOSED OPENED
SAFETY
SAFETY
NONSAFETY
NONSAFETY
SOLENOID VALVE VALVE SOLENOID VALVE
SOLENOID VALVE VALVE SOLENOID VALVE
DIVISION I (NOTE 5) DIVISION II
(NOTE 1) (NOTE 1) DIVISION I (NOTE 5) DIVISION II
(NOTE 1) (NOTE 1)
NOTE 1: SOLENOID IS ENERGIZED BY REDUNDANT EIMS TO ALLOW NONSAFETY CONTROL OF VALVE; SOLENOID IS DE-ENERGIZED TO CLOSE VALVE WHEN BOTH EIM OUTPUTS ARE DE-ENERGIZED.
NOTE 2: ONE ENABLE NONSAFETY CONTROL SWITCH PER DIVISION. THE SINGLE SWITCH ENABLES NONSAFETY CONTROL TO ALL ESF COMPONENTS.
NOTE 6: LOGIC IS SHOWN FOR DIVISION I AND II. BOTH DIVISIONS ARE SHOWN TO INDICATE UNIQUE ACTUATED EQUIPMENT
NOTE 3: THE LOGIC SHOWN IS IMPLEMENTED IN REDUNDANT EIM ACTUATION PRIORITY LOGIC (APL) MODULES. A SINGLE EIM CAN BE REMOVED FOR MAINTENANCE, AND THE NUMBERS ASSOCIATED WITH EACH REDUNDANT DIVISION.
VALVE LOGIC WILL REMAIN FUNCTIONAL WITH THE EIM THAT REMAINS IN SERVICE.
NOTE 4: THE EIM APL LOGIC INCLUDES A SEAL-IN TO ENSURE COMPLETION OF THE PROTECTIVE ACTION. THE SEAL-IN REMAINS IN PLACE UNTIL POSITION FEEDBACK INDICATES THAT THE NOTE 7: NONSAFETY CONTROL INPUTS CONSIST OF 14 INDIVIDUAL HARDWIRED SIGNALS.
VALVE HAS REACHED THE POSITION DEMANDED BY THE PROTECTIVE ACTION. THE PROTECTIVE ACTION IS FAIL-SAFE, OR DE-ENERGIZE TO ACTUATE.
NOTE 5: VALVE IS CONTROLLED BY TWO REDUNDANT SOLENOIDS. ONE FROM EACH DIVISION. THE VALVE CLOSES WHEN EITHER THE DIVISION I OR DIVISION II SOLENOID IS DE-ENERGIZED.
THE VALVE OPENS ONLY WHEN BOTH THE DIVISION I AND DIVISION II SOLENOIDS ARE ENERGIZED.
Figure 7.1-1v: Chemical and Volume Control System RCS Injection and Discharge Valve Actuation
DIVISION I DIVISION I OPEN CLOSE DIVISION I DIVISION I DIVISION II DIVISION II OPEN CLOSE DIVISION II DIVISION II
(NOTE 6) (NOTE 6) VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY (NOTE 6) (NOTE 6) VALVE FULLY VALVE FULLY
VALVE FULLY VALVE FULLY MCS
MCS CLOSED OPENED CLOSED OPENED
CLOSED OPENED CLOSED OPENED
NONSAFETY NONSAFETY
SAFETY SAFETY
DIVISION I DIVISION I DIVISION I DIVISION I DIVISION II DIVISION II DIVISION II DIVISION II
MANUAL ENABLE MANUAL ENABLE
AUTOMATIC MANUAL CONTAINMENT NONSAFETY AUTOMATIC MANUAL CONTAINMEN NONSAFETY
CVCS CVCS SYSTEM CONTROL SWITCH CVCS CVCS T SYSTEM CONTROL SWITCH
ACTUATION ACTUATION ISOLATION (NOTE 2) ACTUATION ACTUATION ISOLATION (NOTE 2)
(A) (M) (M) (D) (E) (A) (M) (M) (D) (E)
AUTO AUTO
AUTO AUTO
I I I I I I I I
VALVE FULLY VALVE FULLY VALVE FULLY
VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY
CLOSED OPENED CLOSED OPENED CLOSED OPENED CLOSED OPENED
(NOTE 4) (NOTE 4)
(NOTE 4) (NOTE 4)
RCS INJECTION CONTAINMENT ISOLATION RCS DISCHARGE CONTAINMENT RCS INJECTION CONTAINMENT RCS DISCHARGE CONTAINMENT
VALVE ISOLATION VALVE ISOLATION VALVE ISOLATION VALVE
ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION I ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION I ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION II ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION II
(NOTE 3) (NOTE 3) (NOTE 3) (NOTE 3)
(NOTE 5) EIM OUT
(NOTE 3) (NOTE 5) EIM OUT
(NOTE 3) (NOTE 5) (NOTE 3)
EIM OUT (NOTE 5) EIMEIM
2 SEC
OUTOUT 1
(NOTE 3) (NOTE 3) (NOTE 3)
(NOTE 3)
NOTE 1: SOLENOIDS ARE ENERGIZED BY REDUNDANT EIMS TO OPEN VALVE; SOLENOIDS ARE DE-ENERGIZED TO CLOSE VALVE WHEN BOTH EIM OUTPUTS ARE DE-ENERGIZED. NOTE 5: LOGIC IS SHOWN FOR DIVISION I AND II. BOTH DIVISIONS ARE SHOWN TO INDICATE UNIQUE
ACTUATED EQUIPMENT NUMBERS ASSOCIATED WITH EACH REDUNDANT DIVISION.
NOTE 2: ONE ENABLE NONSAFETY CONTROL SWITCH PER DIVISION. THE SINGLE SWITCH ENABLES NONSAFETY CONTROL TO ALL ESF COMPONENTS.
NOTE 6: NONSAFETY CONTROL INPUTS CONSIST OF 14 INDIVIDUAL HARDWIRED SIGNALS.
NOTE 3: THE LOGIC SHOWN IS IMPLEMENTED IN REDUNDANT EIM ACTUATION PRIORITY LOGIC (APL) MODULES. A SINGLE EIM CAN BE REMOVED
FOR MAINTENANCE, AND THE VALVE LOGIC WILL REMAIN FUNCTIONAL WITH THE EIM THAT REMAINS IN SERVICE.
NOTE 4: THE EIM APL LOGIC INCLUDES A SEAL-IN TO ENSURE COMPLETION OF THE PROTECTIVE ACTION. THE SEAL-IN REMAINS IN PLACE UNTIL POSITION
FEEDBACK INDICATES THAT THE VALVE HAS REACHED THE POSITION DEMANDED BY THE PROTECTIVE ACTION. THE PROTECTIVE ACTION IS FAIL-
SAFE, OR DE-ENERGIZE TO ACTUATE.
Figure 7.1-1w: Chemical and Volume Control System Pressurizer Spray and High Point Degasification Valve Actuation
DIVISION I DIVISION I DIVISION I DIVISION I DIVISION II DIVISION II DIVISION II DIVISION II
OPEN CLOSE OPEN CLOSE
VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY (NOTE 6) (NOTE 6) VALVE FULLY VALVE FULLY
CLOSED OPENED (NOTE 6) (NOTE 6) CLOSED OPENED
MCS CLOSED OPENED MCS CLOSED OPENED
NONSAFETY NONSAFETY
SAFETY SAFETY
DIVISION I DIVISION I DIVISION I DIVISION I DIVISION II DIVISION II DIVISION II DIVISION II
MANUAL ENABLE MANUAL ENABLE
AUTOMATIC MANUAL CONTAINMENT NONSAFETY AUTOMATIC MANUAL CONTAINMENT NONSAFETY
CVCS CVCS SYSTEM CONTROL SWITCH CVCS CVCS SYSTEM CONTROL SWITCH
ACTUATION ACTUATION ISOLATION (NOTE 2) ACTUATION ACTUATION ISOLATION (NOTE 2)
(A) (M) (M) (D) (E) (A) (M) (M) (D) (E)
AUTO AUTO
AUTO AUTO
I I I I I I I I
VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY
VALVE FULLY VALVE FULLY
CLOSED OPENED CLOSED OPENED CLOSED OPENED
CLOSED OPENED
(NOTE 4) (NOTE 4)
(NOTE 4) (NOTE 4)
PRESSURIZER SPRAY ISOLATION VALVE RPV HIGH POINT DEGASIFICAION ISOLATION VALVE PRESSURIZER SPRAY ISOLATION VALVE RPV HIGH POINT DEGASIFICAION ISOLATION VALVE
ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION I ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION I ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION II ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION II
(NOTE 3) (NOTE 3) (NOTE 3) (NOTE 3)
(NOTE 5) EIM OUT
(NOTE 3) (NOTE 5) (NOTE 3)
EIM OUT (NOTE 5) (NOTE 3)
EIM OUT (NOTE 5) EIMEIM
2 SEC
OUTOUT 1
(NOTE 3) (NOTE 3) (NOTE 3) (NOTE 3)
NOTE 1: SOLENOIDS ARE ENERGIZED BY REDUNDANT EIMS TO OPEN VALVE; SOLENOIDS ARE DE-ENERGIZED TO CLOSE VALVE WHEN BOTH EIM OUTPUTS ARE DE-ENERGIZED. NOTE 5: LOGIC IS SHOWN FOR DIVISION I AND II. BOTH DIVISIONS ARE SHOWN TO INDICATE UNIQUE
NOTE 2: ONE ENABLE NONSAFETY CONTROL SWITCH PER DIVISION. THE SINGLE SWITCH ENABLES NONSAFETY CONTROL TO ALL ESF COMPONENTS. ACTUATED EQUIPMENT NUMBERS ASSOCIATED WITH EACH REDUNDANT DIVISION.
NOTE 3: THE LOGIC SHOWN IS IMPLEMENTED IN REDUNDANT EIM ACTUATION PRIORITY LOGIC (APL) MODULES. A SINGLE EIM CAN BE REMOVED NOTE 6: NONSAFETY CONTROL INPUTS CONSIST OF 14 INDIVIDUAL HARDWIRED SIGNALS.
FOR MAINTENANCE, AND THE VALVE LOGIC WILL REMAIN FUNCTIONAL WITH THE EIM THAT REMAINS IN SERVICE.
NOTE 4: THE EIM APL LOGIC INCLUDES A SEAL-IN TO ENSURE COMPLETION OF THE PROTECTIVE ACTION. THE SEAL-IN REMAINS IN PLACE UNTIL POSITION
FEEDBACK INDICATES THAT THE VALVE HAS REACHED THE POSITION DEMANDED BY THE PROTECTIVE ACTION. THE PROTECTIVE ACTION IS FAIL-
SAFE, OR DE-ENERGIZE TO ACTUATE.
Figure 7.1-1x: Containment Flooding and Drain and Containment Evacuation Valve Actuation
DIVISION I DIVISION I OPEN CLOSE DIVISION I DIVISION I DIVISION II DIVISION II OPEN CLOSE DIVISION II DIVISION II
VALVE FULLY VALVE FULLY (NOTE 6) (NOTE 6) VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY (NOTE 6) (NOTE 6) VALVE FULLY VALVE FULLY
CLOSED OPENED MCS CLOSED OPENED CLOSED OPENED MCS CLOSED OPENED
NONSAFETY NONSAFETY
SAFETY SAFETY
DIVISION I DIVISION I DIVISION I DIVISION II DIVISION II DIVISION II
AUTOMATIC MANUAL ENABLE AUTOMATIC MANUAL ENABLE
CONTAINMENT CONTAINMENT NONSAFETY CONTAINMENT CONTAINMENT NONSAFETY
SYSTEM SYSTEM CONTROL SWITCH SYSTEM SYSTEM CONTROL SWITCH
ISOLATION ISOLATION (NOTE 2) ISOLATION ISOLATION (NOTE 2)
(A) (M) (D) (E) (A) (M) (D) (E)
AUTO AUTO
AUTO AUTO
I I I I I I I I
VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY
CLOSED OPENED CLOSED OPENED CLOSED OPENED CLOSED OPENED
(NOTE 4) (NOTE 4)
(NOTE 4) (NOTE 4)
CONTAINMENT EVACUATION ISOLATION VALVE CONTAINMENT FLOODING AND DRAIN ISOLATION CONTAINMENT EVACUATION ISOLATION VALVE CONTAINMENT FLOODING AND DRAIN ISOLATION
VALVE VALVE
ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION I ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION I ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION II ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION II
(NOTE 3) (NOTE 3) (NOTE 3) (NOTE 3)
EIM OUT
(NOTE 3) EIM OUT
(NOTE 3) (NOTE 3)
EIM OUT EIMEIM
2 SEC
OUTOUT 1
(NOTE 5) (NOTE 5)
(NOTE 3) (NOTE 3) (NOTE 3)
(NOTE 3)
(NOTE 5) (NOTE 5)
SOLENOID SOLENOID
SOLENOID SOLENOID SOLENOID SOLENOID
VALVE VALVE SOLENOID SOLENOID
VALVES VALVES VALVE VALVE
CE-SV-0101
(NOTE 1) CE-SV-0101 VALVES VALVES
(NOTE 1) CE-SV-0101
(NOTE 1) CE-SV-0101
(NOTE 1)
(NOTE 1) (NOTE 1) (NOTE 1) (NOTE 1)
NOTE 1: SOLENOIDS ARE ENERGIZED BY REDUNDANT EIMS TO OPEN VALVE; SOLENOIDS ARE DE-ENERGIZED TO CLOSE VALVE WHEN BOTH EIM OUTPUTS ARE DE-ENERGIZED. NOTE 5: LOGIC IS SHOWN FOR DIVISION I AND II. BOTH DIVISIONS ARE SHOWN TO INDICATE UNIQUE
NOTE 2: ONE ENABLE NONSAFETY CONTROL SWITCH PER DIVISION. THE SINGLE SWITCH ENABLES NONSAFETY CONTROL TO ALL ESF COMPONENTS. ACTUATED EQUIPMENT NUMBERS ASSOCIATED WITH EACH REDUNDANT DIVISION.
NOTE 3: THE LOGIC SHOWN IS IMPLEMENTED IN REDUNDANT EIM ACTUATION PRIORITY LOGIC (APL) MODULES. A SINGLE EIM CAN BE REMOVED NOTE 6: NONSAFETY CONTROL INPUTS CONSIST OF 14 INDIVIDUAL HARDWIRED SIGNALS.
FOR MAINTENANCE, AND THE VALVE LOGIC WILL REMAIN FUNCTIONAL WITH THE EIM THAT REMAINS IN SERVICE.
NOTE 4: THE EIM APL LOGIC INCLUDES A SEAL-IN TO ENSURE COMPLETION OF THE PROTECTIVE ACTION. THE SEAL-IN REMAINS IN PLACE UNTIL POSITION
FEEDBACK INDICATES THAT THE VALVE HAS REACHED THE POSITION DEMANDED BY THE PROTECTIVE ACTION. THE PROTECTIVE ACTION IS FAIL-
SAFE, OR DE-ENERGIZE TO ACTUATE.
NONSAFETY NONSAFETY
SAFETY SAFETY
DIVISION I DIVISION I DIVISION I DIVISION II DIVISION II DIVISION II
AUTOMATIC MANUAL ENABLE AUTOMATIC MANUAL ENABLE
CONTAINMENT CONTAINMENT NONSAFETY CONTAINMENT CONTAINMENT NONSAFETY
SYSTEM SYSTEM CONTROL SWITCH SYSTEM SYSTEM CONTROL SWITCH
ISOLATION ISOLATION (NOTE 2) ISOLATION ISOLATION (NOTE 2)
(A) (M) (D) (E) (A) (M) (D) (E)
AUTO AUTO
AUTO AUTO
I I I I I I I I
VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY
CLOSED OPENED VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY
CLOSED OPENED CLOSED CLOSED
OPENED OPENED
(NOTE 4) (NOTE 4)
(NOTE 4) (NOTE 4)
REACTOR COMPONENT COOLING WATER REACTOR COMPONENT COOLING WATER REACTOR COMPONENT COOLING WATER REACTOR COMPONENT COOLING WATER
SUPPLY ISOLATION VALVE RETURN ISOLATION VALVE SUPPLY ISOLATION VALVE RETURN ISOLATION VALVE
ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION I ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION I ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION II ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION II
(NOTE 3) (NOTE 3) (NOTE 3) (NOTE 3)
(NOTE 5) EIM OUT
(NOTE 3) (NOTE 5) EIM OUT
(NOTE 3) (NOTE 5) (NOTE 3)
EIM OUT (NOTE 5) EIMEIM
2 SEC
OUTOUT 1
(NOTE 3) (NOTE 3) (NOTE 3)
(NOTE 3)
NOTE 1: SOLENOIDS ARE ENERGIZED BY REDUNDANT EIMS TO OPEN VALVE; SOLENOIDS ARE DE-ENERGIZED TO CLOSE VALVE WHEN BOTH EIM OUTPUTS ARE DE-ENERGIZED. NOTE 5: LOGIC IS SHOWN FOR DIVISION I AND II. BOTH DIVISIONS ARE SHOWN TO INDICATE UNIQUE
NOTE 2: ONE ENABLE NONSAFETY CONTROL SWITCH PER DIVISION. THE SINGLE SWITCH ENABLES NONSAFETY CONTROL TO ALL ESF COMPONENTS. ACTUATED EQUIPMENT NUMBERS ASSOCIATED WITH EACH REDUNDANT DIVISION.
NOTE 3: THE LOGIC SHOWN IS IMPLEMENTED IN REDUNDANT EIM ACTUATION PRIORITY LOGIC (APL) MODULES. A SINGLE EIM CAN BE REMOVED NOTE 6: NONSAFETY CONTROL INPUTS CONSIST OF 14 INDIVIDUAL HARDWIRED SIGNALS.
FOR MAINTENANCE, AND THE VALVE LOGIC WILL REMAIN FUNCTIONAL WITH THE EIM THAT REMAINS IN SERVICE.
NOTE 4: THE EIM APL LOGIC INCLUDES A SEAL-IN TO ENSURE COMPLETION OF THE PROTECTIVE ACTION. THE SEAL-IN REMAINS IN PLACE UNTIL POSITION
FEEDBACK INDICATES THAT THE VALVE HAS REACHED THE POSITION DEMANDED BY THE PROTECTIVE ACTION. THE PROTECTIVE ACTION IS FAIL-
SAFE, OR DE-ENERGIZE TO ACTUATE.
NONSAFETY
SAFETY
DIVISION I DIVISION I DIVISION I DIVISION II DIVISION II DIVISION II
AUTOMATIC MANUAL ENABLE AUTOMATIC MANUAL ENABLE
DEMINERALIZED DEMINERALIZED NONSAFETY DEMINERALIZED DEMINERALIZED NONSAFETY
WATER SYSTEM WATER SYSTEM CONTROL SWITCH WATER SYSTEM WATER SYSTEM CONTROL SWITCH
ISOLATION ISOLATION (NOTE 2) ISOLATION ISOLATION (NOTE 2)
(A) (M) (E) (D) (A) (M) (E) (D)
NONSAFETY NONSAFETY
INPUT DECODE INPUT DECODE
CLOSE LOGIC OPEN CLOSE LOGIC OPEN
ENABLE NS ENABLE NS
DISABLE NS DISABLE NS
MANUAL MANUAL
AUTO AUTO
I I I I
(NOTE 4) (NOTE 4)
DEMINERALIZED WATER SUPPLY ISOLATION VALVE DEMINERALIZED WATER SUPPLY ISOLATION VALVE
ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION I ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION II
(NOTE 3) (NOTE 3)
(NOTE 5) EIM OUT
(NOTE 3) EIM OUT
(NOTE 3)
(NOTE 5)
(NOTE 3) (NOTE 3)
NOTE 3: THE LOGIC SHOWN IS IMPLEMENTED IN REDUNDANT EIM ACTUATION PRIORITY LOGIC (APL) MODULES. A SINGLE EIM CAN BE REMOVED NOTE 6: NONSAFETY CONTROL INPUTS CONSIST OF 14 INDIVIDUAL HARDWIRED SIGNALS.
FOR MAINTENANCE, AND THE VALVE LOGIC WILL REMAIN FUNCTIONAL WITH THE EIM THAT REMAINS IN SERVICE.
NOTE 4: THE EIM APL LOGIC INCLUDES A SEAL-IN TO ENSURE COMPLETION OF THE PROTECTIVE ACTUATION. THE SEAL-IN REMAINS IN PLACE UNTIL
POSITION FEEDBACK INDICATES THAT THE VALVE HAS REACHED THE POSITION DEMANDED BY THE PROTECTIVE ACTION. THE PROTECTIVE ACTION
IS FAIL-SAFE, OR DE-ENERGIZE TO ACTUATE.
Figure 7.1-1aa: Emergency Core Cooling System Reactor Vent Valve 1 & 2 Actuation
DIVISION I DIVISION I DIVISION I DIVISION I DIVISION II DIVISION II DIVISION II DIVISION II
VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY OPEN CLOSE VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY
OPENED CLOSED OPENED CLOSED (NOTE 8) (NOTE 8) OPENED
OPENED CLOSED CLOSED
MCS
NONSAFETY NONSAFETY
SAFETY SAFETY
DIVISION I DIVISION I DIVISION I DIVISION II DIVISION II DIVISION II
AUTOMATIC MANUAL AUTOMATIC MANUAL
OPEN ECCS OPEN ECCS MANUAL DIVISION I OPEN ECCS OPEN ECCS MANUAL DIVISION II
VENT VALVE VENT VALVE LTOP ENABLE NONSAFETY VENT VALVE VENT VALVE LTOP ENABLE NONSAFETY
ACTUATION ACTUATION ACTUATION CONTROL SWITCH ACTUATION ACTUATION ACTUATION CONTROL SWITCH
(A) (M) (M) (E) (NOTE 2) (D) (A) (M) (M) (E) (NOTE 2) (D)
DISABLE NS DISABLE NS
I I I I I I I I
VALVE FULLY VALVE FULLY VALVE VALVE VALVE VALVE VALVE FULLY VALVE FULLY
OPENED CLOSED FULLY FULLY FULLY FULLY OPENED CLOSED
OPENED CLOSED OPENED CLOSED
EMERGENCY CORE COOLING SYSTEM EMERGENCY CORE COOLING SYSTEM EMERGENCY CORE COOLING SYSTEM EMERGENCY CORE COOLING SYSTEM
REACTOR VENT VALVE 1 TRIP REACTOR VENT VALVE 1 RESET REACTOR VENT VALVE 2 TRIP REACTOR VENT VALVE 2 RESET
ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION I ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION I ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION II ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION II
(NOTE 3) (NOTE 3) (NOTE 3) (NOTE 3)
(NOTE 7) EIM OUT
(NOTE 3) (NOTE 7) (NOTE 3)
EIM OUT (NOTE 7) EIM OUT
(NOTE 3) (NOTE 7) EIM OUT
(NOTE 3)
(NOTE 3) (NOTE 3) (NOTE 3) (NOTE 3)
NOTE 1: THE ECCS VENT VALVE IS CLOSED WITH THE TRIP SOLENOID VALVE ENERGIZED BY REDUNDANT EIMS; NOTE 5: THE ECCS VENT VALVE DESIGN INCLUDES AN ARMING VALVE. THE ARMING VENT VALVE IMPLEMENTS THE INADVERTENT ACTUATION BLOCK (IAB)
THE TRIP SOLENOID IS DE-ENERGIZED TO OPEN THE ECCS VENT VALVE WHEN BOTH EIM OUTPUTS ARE DE-ENERGIZED. FUNCTION THAT DELAYS OPENING OF THE ECCS VENT VALVE WHEN THE TRIP SOLENOID DE-ENERGIZES UNTIL RPV TO CNV DIFFERENTIAL PRESSURE IS
NOTE 2: ONE ENABLE NONSAFTEY CONTROL SWITCH PER DIVISION. THE SINGLE SWITCH ENABLES NONSAFETY CONTROL TO ALL BELOW THE ARMING VENT VALVE SET PRESSURE.
ESF COMPONENTS. NOTE 6: THE ECCS RESET SOLENOID VALVE IS NORMALLY DE-ENERGIZED (CLOSED). THE RESET SOLENOID MUST BE ENERGIZED (OPENED) TO CLOSE THE
ECCS VALVE. THIS PROVIDES A PATH FOR CVCS MAKEUP TO THE MAIN VALVE CONTROL CHAMBER UNTIL RPV PRESSURE IS SUFFICIENT TO
NOTE 3: THE LOGIC SHOWN IS IMPLEMENTED IN REDUNDANT EIM ACTUATION PRIORITY LOGIC (APL) MODULES. A SINGLE EIM CAN BE REMOVED OVERCOME THE SPRING FORCE HOLDING THE VALVE OPEN.
FOR MAINTENANCE, AND THE VALVE LOGIC WILL REMAIN FUNCTIONAL WITH THE EIM THAT REMAINS IN SERVICE.
NOTE 7: LOGIC IS SHOWN FOR DIVISION I AND II. BOTH DIVISIONS ARE SHOWN TO INDICATE UNIQUE ACTUATED EQUIPMENT
NOTE 4: THE EIM APL LOGIC INCLUDES A SEAL-IN TO ENSURE COMPLETION OF THE PROTECTIVE ACTION. THE SEAL-IN REMAINS IN PLACE UNTIL POSITION NUMBERS ASSOCIATED WITH EACH REDUNDANT DIVISION.
FEEDBACK INDICATES THAT THE VALVE HAS REACHED THE POSITION DEMANDED BY THE PROTECTIVE ACTION. THE PROTECTIVE ACTION IS FAIL- NOTE 8: NONSAFETY CONTROL INPUTS CONSIST OF 14 INDIVIDUAL HARDWIRED SIGNALS.
SAFE, OR DE-ENERGIZE TO ACTUATE.
Figure 7.1-1ab: Emergency Core Cooling System Reactor Recirculation Valve Actuation
DIVISION I DIVISION I DIVISION I DIVISION I DIVISION II DIVISION II DIVISION II DIVISION II
VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY OPEN CLOSE VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY
OPENED CLOSED OPENED CLOSED (NOTE 8) (NOTE 8) OPENED CLOSED OPENED CLOSED
MCS
NONSAFETY NONSAFETY
DIVISION I DIVISION I SAFETY DIVISION II DIVISION II SAFETY
AUTOMATIC MANUAL AUTOMATIC MANUAL
OPEN ECCS OPEN ECCS OPEN ECCS OPEN ECCS
DIVISION I REACTOR REACTOR
REACTOR REACTOR DIVISION II
ENABLE NONSAFETY RECIRCULATION RECIRCULATION
RECIRCULATION RECIRCULATION ENABLE NONSAFETY
CONTROL SWITCH VALVE VALVE
VALVE VALVE CONTROL SWITCH
(A) (M) (E) (NOTE 2) (D) (A) (M) (E) (NOTE 2) (D)
DISABLE NS DISABLE NS
I I I I I I I I
VALVE FULLY VALVE FULLY VALVE VALVE VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY
OPENED CLOSED FULLY FULLY OPENED CLOSED OPENED CLOSED
OPENED CLOSED
EMERGENCY CORE COOLING SYSTEM EMERGENCY CORE COOLING SYSTEM EMERGENCY CORE COOLING SYSTEM EMERGENCY CORE COOLING SYSTEM
REACTOR RECIRCULATION VALVE 1 TRIP REACTOR RECIRCULATION VALVE 1 RESET REACTOR RECIRCULATION VALVE 2 TRIP REACTOR RECIRCULATION VALVE 2 RESET
ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION I ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION I ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION II ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION II
(NOTE 3) (NOTE 3) (NOTE 3) (NOTE 3)
(NOTE 7) EIM OUT
(NOTE 3) (NOTE 7) (NOTE 3)
EIM OUT EIM OUT
(NOTE 3) (NOTE 7) (NOTE 3)
EIM OUT
(NOTE 7)
(NOTE 3) (NOTE 3) (NOTE 3) (NOTE 3)
NOTE 1: THE ECCS RECIRCULATION VALVE IS CLOSED WITH THE TRIP SOLENOID VALVE ENERGIZED BY REDUNDANT EIMS; NOTE 5: THE ECCS RECIRCULATION VALVE DESIGN INCLUDES AN ARMING VALVE. THE ARMING VALVE IMPLEMENTS THE INADVERTENT ACTUATION BLOCK (IAB)
THE TRIP SOLENOID IS DE-ENERGIZED TO OPEN THE ECCS RECIRCULATION VALVE WHEN BOTH EIM OUTPUTS ARE DE-ENERGIZED. FUNCTION THAT DELAYS OPENING OF THE ECCS RECIRCULATION VALVE WHEN THE TRIP SOLENOID DE-ENERGIZES UNTIL RPV TO CNV DIFFERENTIAL
PRESSURE IS BELOW THE ARMING VALVE SET PRESSURE.
NOTE 2: ONE ENABLE NONSAFETY CONTROL SWITCH PER DIVISION. THE SINGLE SWITCH ENABLES NONSAFETY CONTROL TO ALL
ESF COMPONENTS. NOTE 6: THE ECCS RESET SOLENOID VALVE IS NORMALLY DE-ENERGIZED (CLOSED). THE RESET SOLENOID MUST BE ENERGIZED (CLOSED) TO OPEN THE
ECCS RECIRCULATION VALVE. THIS PROVIDES A PATH FOR CVCS MAKEUP TO THE MAIN VALVE CONTROL CHAMBER UNTIL RPV PRESSURE IS
NOTE 3: THE LOGIC SHOWN IS IMPLEMENTED IN REDUNDANT EIM ACTUATION PRIORITY LOGIC (APL) MODULES. A SINGLE EIM CAN BE REMOVED SUFFICIENT TO OVERCOME THE SPRING FORCE HOLDING THE VALVE OPEN.
FOR MAINTENANCE, AND THE VALVE LOGIC WILL REMAIN FUNCTIONAL WITH THE EIM THAT REMAINS IN SERVICE.
NOTE 7: LOGIC IS SHOWN FOR DIVISION I AND II. BOTH DIVISIONS ARE SHOWN TO INDICATE UNIQUE
NOTE 4: THE EIM APL LOGIC INCLUDES A SEAL-IN TO ENSURE COMPLETION OF THE PROTECTIVE ACTION. THE SEAL-IN REMAINS IN PLACE UNTIL POSITION ACTUATED EQUIPMENT NUMBERS ASSOCIATED WITH EACH REDUNDANT DIVISION.
FEEDBACK INDICATES THAT THE VALVE HAS REACHED THE POSITION DEMANDED BY THE PROTECTIVE ACTION. THE PROTECTIVE ACTION IS FAIL-
NOTE 8: NONSAFETY CONTROL INPUTS CONSIST OF 14 INDIVIDUAL HARDWIRED SIGNALS.
SAFE, OR DE-ENERGIZE TO ACTUATE.
Figure 7.1-1ac: Emergency Core Cooling System Reactor Vent Valve 3 Actuation
DIVISION II DIVISION II
DIVISION I DIVISION I DIVISION I DIVISION I (NOTE 8) (NOTE 8) VALVE FULLY VALVE FULLY
OPEN CLOSE
VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY OPENED CLOSED
OPENED CLOSED OPENED CLOSED MCS
NONSAFETY NONSAFETY
SAFETY DIVISION II DIVISION II DIVISION II SAFETY
DIVISION I DIVISION I DIVISION I
AUTOMATIC
AUTOMATIC DIVISION II
DIVISION I OPEN ECCS MANUAL MANUAL
OPEN ECCS MANUAL MANUAL ENABLE NONSAFETY
ENABLE NONSAFETY VENT VALVE ECCS LTOP
VENT VALVE ECCS LTOP CONTROL SWITCH
CONTROL SWITCH ACTUATION ACTUATION ACTUATION
ACTUATION ACTUATION ACTUATION
(A) (M) (M) (E) (NOTE 2) (D)
(A) (M) (M) (E) (NOTE 2) (D)
NONSAFETY NONSAFETY
INPUT DECODE NONSAFETY INPUT DECODE
OPEN CLOSE
OPEN LOGIC CLOSE INPUT DECODE LOGIC
CLOSE
LOGIC ENABLE NS
ENABLE NS
DISABLE NS DISABLE NS
I I I I I I
VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY VALVE FULLY
OPENED CLOSED OPENED CLOSED OPENED CLOSED
EMERGENCY CORE COOLING SYSTEM EMERGENCY CORE COOLING SYSTEM EMERGENCY CORE COOLING SYSTEM
REACTOR VENT VALVE TRIP REACTOR VENT VALVE RESET REACTOR VENT VALVE TRIP
ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION I ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION I ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION II
(NOTE 3) (NOTE 3) (NOTE 3)
(NOTE 6)
(NOTE 7) EIM OUT
(NOTE 3) (NOTE 7) (NOTE 7) EIM OUT
(NOTE 3)
RESET SOLENOID
(NOTE 3) VALVE (NOTE 3)
(NOTE 3)
EIM OUT
(NOTE 3)
NOTE 1: THE ECCS VENT VALVE IS CLOSED WITH THE TRIP SOLENOID VALVE ENERGIZED BY REDUNDANT EIMS; NOTE 5: THE ECCS VENT VALVE DESIGN INCLUDES AN ARMING VALVE. THE ARMING VALVE IMPLEMENTS THE INADVERTENT ACTUATION BLOCK (IAB)
THE TRIP SOLENOID IS DE-ENERGIZED TO OPEN THE ECCS VENT VALVE WHEN BOTH EIM OUTPUTS ARE DE-ENERGIZED. FUNCTION THAT DELAYS OPENING OF THE ECCS VENT VALVE WHEN THE TRIP SOLENOID DE-ENERGIZES UNTIL RPV TO CNV DIFFERENTIAL
NOTE 2: ONE ENABLE NONSAFETY CONTROL SWITCH PER DIVISION. THE SINGLE SWITCH ENABLES NONSAFETY CONTROL TO ALL PRESSURE IS BELOW THE ARMING VALVE SET PRESSURE.
ESF COMPONENTS. NOTE 6: THE ECCS RESET SOLENOID VALVE IS NORMALLY DE-ENERGIZED (CLOSED). THE RESET SOLENOID MUST BE ENERGIZED (CLOSED) TO OPEN THE
ECCS VENT VALVE. THIS PROVIDES A PATH FOR CVCS MAKEUP TO THE MAIN VALVE CONTROL CHAMBER UNTIL RPV PRESSURE IS SUFFICIENT TO
NOTE 3: THE LOGIC SHOWN IS IMPLEMENTED IN REDUNDANT EIM ACTUATION PRIORITY LOGIC (APL) MODULES. A SINGLE EIM CAN BE REMOVED OVERCOME THE SPRING FORCE HOLDING THE VALVE OPEN.
FOR MAINTENANCE, AND THE VALVE LOGIC WILL REMAIN FUNCTIONAL WITH THE EIM THAT REMAINS IN SERVICE.
NOTE 7: LOGIC IS SHOWN FOR DIVISION I AND II. BOTH DIVISIONS ARE SHOWN TO INDICATE UNIQUE
NOTE 4: THE EIM APL LOGIC INCLUDES A SEAL-IN TO ENSURE COMPLETION OF THE PROTECTIVE ACTION. THE SEAL-IN REMAINS IN PLACE UNTIL POSITION ACTUATED EQUIPMENT NUMBERS ASSOCIATED WITH EACH REDUNDANT DIVISION.
FEEDBACK INDICATES THAT THE VALVE HAS REACHED THE POSITION DEMANDED BY THE PROTECTIVE ACTION. THE PROTECTIVE ACTION IS FAIL-
NOTE 8: NONSAFETY CONTROL INPUTS CONSIST OF 14 INDIVIDUAL HARDWIRED SIGNALS.
SAFE, OR DE-ENERGIZE TO ACTUATE.
DIVISION I DIVISION I
AUTOMATIC MANUAL DIVISION I
REACTOR REACTOR ENABLE NONSAFETY
TRIP TRIP CONTROL SWITCH
(A) (M) (E) (NOTE 2) (D)
DISABLE NS DISABLE NS
I I I I I I
BREAKER BREAKER BREAKER BREAKER
BREAKER BREAKER
OPENED OPENED OPENED CLOSED
CLOSED CLOSED
RTS DIVISION I EIM OUT ACTUATION AND PRIORITY LOGIC (APL) RTS DIVISION I EIM OUT ACTUATION AND PRIORITY LOGIC (APL) ACTUATION AND PRIORITY LOGIC (APL) EIM OUT RTS DIVISION I
UNDERVOLTAGE SHUNT TRIP COIL (NOTE 3) REACTOR TRIP BREAKER CLOSE COIL
(NOTE 1)
TRIP COIL
NOTE 1: THE UNDERVOLTAGE (UV) TRIP COIL AND SHUNT TRIP RELAY ARE ENERGIZED WHEN OPERATING; WHEN THE EIM OUTPUTS
ARE DE-ENERGIZED, THE UV TRIP COIL AND SHUNT TRIP RELAY ARE DE-ENERGIZED TO TRIP THE BREAKER OPEN.
NOTE 2: ONE ENABLE NONSAFETY CONTROL SWITCH PER DIVISION. THE SINGLE SWITCH ENABLES NONSAFETY CONTROL TO ALL
ESF COMPONENTS.
NOTE 3: THE SHUNT TRIP COIL IS NORMALLY DE-ENERGIZED; WHEN THE SHUNT TRIP RELAY IS DE-ENERGIZED, SHUNT TRIP COIL IS ENERGIZED
TO TRIP THE BREAKER OPEN.
NOTE 4: THE EIM APL LOGIC INCLUDES A SEAL-IN TO ENSURE COMPLETION OF THE PROTECTIVE ACTION. THE SEAL-IN REMAINS IN PLACE UNTIL POSITION
FEEDBACK INDICATES THAT THE TRIP BREAKER HAS REACHED THE POSITION DEMANDED BY THE PROTECTIVE ACTION. THE PROTECTIVE ACTION
IS FAIL-SAFE, OR DE-ENERGIZE TO TRIP.
NOTE 5: NONSAFETY CONTROL INPUTS CONSIST OF 14 INDIVIDUAL HARDWIRED SIGNALS.
DIVISION I DIVISION 1
AUTOMATIC MANUAL DIVISION I
REACTOR REACTOR ENABLE NONSAFETY
TRIP TRIP CONTROL SWITCH
(A) (M) (E) (NOTE 2) (D)
ENABLE NS ENABLE NS
DISABLE NS DISABLE NS
I I I I I I
BREAKER BREAKER BREAKER BREAKER BREAKER BREAKER
OPENED OPENED OPENED CLOSED
CLOSED CLOSED
RTS DIVISION I EIM OUT ACTUATION AND PRIORITY LOGIC (APL) RTS DIVISION I EIM OUT ACTUATION AND PRIORITY LOGIC (APL) ACTUATION AND PRIORITY LOGIC (APL) EIM OUT RTS DIVISION I
NOTE 1: THE UNDERVOLTAGE (UV) TRIP COIL AND SHUNT TRIP RELAY ARE ENERGIZED WHEN OPERATING; WHEN THE EIM OUTPUTS
ARE DE-ENERGIZED, THE UV TRIP COIL AND SHUNT TRIP RELAY ARE DE-ENERGIZED TO TRIP THE BREAKER OPEN.
NOTE 2: ONE ENABLE NONSAFETY CONTROL SWITCH PER DIVISION. THE SINGLE SWITCH ENABLES NONSAFETY CONTROL TO ALL
ESF COMPONENTS.
NOTE 3: THE SHUNT TRIP COIL IS NORMALLY DE-ENERGIZED; WHEN THE SHUNT TRIP RELAY IS DE-ENERGIZED, SHUNT TRIP COIL IS ENERGIZED
TO TRIP THE BREAKER OPEN.
NOTE 4: THE EIM APL LOGIC INCLUDES A SEAL-IN TO ENSURE COMPLETION OF THE PROTECTIVE ACTION. THE SEAL-IN REMAINS IN PLACE UNTIL POSITION
FEEDBACK INDICATES THAT THE TRIP BREAKER HAS REACHED THE POSITION DEMANDED BY THE PROTECTIVE ACTION. THE PROTECTIVE ACTION
IS FAIL-SAFE, OR DE-ENERGIZE TO TRIP.
NOTE 5: NONSAFETY CONTROL INPUTS CONSIST OF 14 INDIVIDUAL HARDWIRED SIGNALS.
DISABLE NS DISABLE NS
I I I I I I
BREAKER BREAKER BREAKER BREAKER
BREAKER BREAKER
OPENED CLOSED OPENED CLOSED OPENED CLOSED
ESFAS DIVISION I EIM OUT ACTUATION AND PRIORITY LOGIC (APL) ESFAS DIVISION I EIM OUT ACTUATION AND PRIORITY LOGIC (APL) ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION I
UNDERVOLTAGE (NOTE 1) SHUNT TRIP COIL (NOTE 3) PRESSURIZER HEATER BREAKER CLOSE COIL
TRIP COIL
NOTE 1: THE UNDERVOLTAGE (UV) TRIP COIL AND SHUNT TRIP RELAY ARE ENERGIZED WHEN OPERATING; WHEN THE EIM OUTPUT IS
DE-ENERGIZED, THE UV TRIP COIL AND SHUNT TRIP RELAY ARE DE-ENERGIZED TO TRIP THE BREAKER OPEN.
NOTE 2: ONE ENABLE NONSAFETY CONTROL SWITCH PER DIVISION. THE SINGLE SWITCH ENABLES NONSAFETY CONTROL TO ALL
ESF COMPONENTS.
NOTE 3: THE SHUNT TRIP COIL IS NORMALLY DE-ENERGIZED; WHEN THE SHUNT TRIP RELAY IS DE-ENERGIZED, SHUNT TRIP COIL IS ENERGIZED
TO TRIP THE BREAKER OPEN.
NOTE 4: THE EIM APL LOGIC INCLUDES A SEAL-IN TO ENSURE COMPLETION OF THE PROTECTIVE ACTION. THE SEAL-IN REMAINS IN PLACE UNTIL POSITION
FEEDBACK INDICATES THAT THE TRIP BREAKER HAS REACHED THE POSITION DEMANDED BY THE PROTECTIVE ACTION. THE PROTECTIVE ACTION
IS FAIL-SAFE, OR DE-ENERGIZE TO TRIP.
NOTE 5: NONSAFETY CONTROL INPUTS CONSIST OF 14 INDIVIDUAL HARDWIRED SIGNALS.
DISABLE NS DISABLE NS
I I I I I I
BREAKER BREAKER BREAKER BREAKER
BREAKER BREAKER
OPENED CLOSED OPENED CLOSED OPENED CLOSED
ESFAS DIVISION I EIM OUT 1 ACTUATION AND PRIORITY LOGIC (APL) ESFAS DIVISION I EIM OUT ACTUATION AND PRIORITY LOGIC (APL) ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION I
NOTE 1: THE UNDERVOLTAGE (UV) TRIP COIL AND SHUNT TRIP RELAY ARE ENERGIZED WHEN OPERATING; WHEN THE EIM OUTPUT IS
DE-ENERGIZED, THE UV TRIP COIL AND SHUNT TRIP RELAY ARE DE-ENERGIZED TO TRIP THE BREAKER OPEN.
NOTE 2: ONE ENABLE NONSAFETY CONTROL SWITCH PER DIVISION. THE SINGLE SWITCH ENABLES NONSAFETY CONTROL TO ALL
ESF COMPONENTS.
NOTE 3: THE SHUNT TRIP COIL IS NORMALLY DE-ENERGIZED; WHEN THE SHUNT TRIP RELAY IS DE-ENERGIZED, SHUNT TRIP COIL IS ENERGIZED
TO TRIP THE BREAKER OPEN.
NOTE 4: THE EIM APL LOGIC INCLUDES A SEAL-IN TO ENSURE COMPLETION OF THE PROTECTIVE ACTION. THE SEAL-IN REMAINS IN PLACE UNTIL POSITION
FEEDBACK INDICATES THAT THE TRIP BREAKER HAS REACHED THE POSITION DEMANDED BY THE PROTECTIVE ACTION. THE PROTECTIVE ACTION
IS FAIL-SAFE, OR DE-ENERGIZE TO TRIP.
NOTE 5: NONSAFETY CONTROL INPUTS CONSIST OF 14 INDIVIDUAL HARDWIRED SIGNALS.
A B C D A B C D
VS VS VS VS (NOTE 2) VS VS VS VS (NOTE 2)
TD TD TD TD (NOTE 3) TD TD TD TD (NOTE 3)
A A A A
A A A A
A A A A
ESFAS RTS
DIVISION I DIVISION I
(NOTE 1) (NOTE 1)
RTS
DIVISION I ESFAS
(NOTE 1) F F DIVISION I
(NOTE 1)
REACTOR TRIP
CONTAINMENT CHEMICAL AND PRESSURIZER DECAY HEAT DEMINERALIZED START/STOP SECONDARY
SYSTEM VOLUME HEATER REMOVAL SYSTEM
WATER SYSTEM 24-HOUR TIMER
ISOLATION CONTROL ISOLATION
TRIP BREAKERS SYSTEM ISOLATION
ACTUATION SYSTEM
ISOLATION ACTUATION
NOTE 1: LOGIC IS SHOWN FOR DIVISION I ONLY. LOGIC FOR DIVISION II IS THE SAME AS
DIVISION I.
NOTE 2: THERE IS A TRIP/BYPASS SWITCH FOR EACH SFM THAT HAS A SAFETY FUNCTION THAT SUPPORTS REMOVING THE SFM FROM SERVICE.
NOTE 3: THE TIME DELAY (TD) IS ADDED TO DELAY THE START OF THE TIMING SEQUENCE TO PREVENT ACTUATION OF TRIP LOGIC ON MOMENTARY AC BUS VOLTAGE
TRANSIENTS. THE TIME DELAY ALSO DELAYS THE RESET OF THE TIMING SEQUENCE TO PREVENT PREMATURE RESET OF TRIP LOGIC ON MOMENTARY AC BUS
VOLTAGE TRANSIENTS.
DIVISION I
AUTOMATIC
24-HOUR TIMER
START/STOP
AUTO START/STOP
ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION I ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION I ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION I
(NOTE 1)
(NOTE 1) (NOTE 1)
2/3
DE-ENERGIZE
NOTE 1: THE EIM OUTPUT IS NORMALLY DE-ENERGIZED; THE EIM OUTPUT IS ENERGIZED TO START THE 24- DIVISION I
HOUR TIMING SEQUENCE. IF THE EIM OUTPUT IS DE-ENERGIZED AFTER THE TIMING SEQUENCE IS RTS CHASSIS
STARTED, THE TIMER IS RESET TO 0 HOURS. ESFAS CHASSIS
AND MWS
DIVISION II
AUTOMATIC
24-HOUR TIMER
START/STOP
AUTO START/STOP
ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION II ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION II ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION II
2/3
DE-ENERGIZE
DIVISION II
NOTE 1: THE EIM OUTPUT IS NORMALLY DE-ENERGIZED; THE EIM OUTPUT IS ENERGIZED TO START THE 24-HOUR
RTS CHASSIS
TIMING SEQUENCE. IF THE EIM OUTPUT IS DE-ENERGIZED AFTER THE TIMING SEQUENCE IS STARTED, THE
ESFAS CHASSIS
TIMER IS RESET TO 0 HOURS.
AND MWS
DISABLE NS DISABLE NS
I I I I I I
BREAKER BREAKER BREAKER BREAKER
BREAKER BREAKER
OPENED OPENED OPENED CLOSED
CLOSED CLOSED
RTS DIVISION II EIM OUT ACTUATION AND PRIORITY LOGIC (APL) RTS DIVISION II EIM OUT ACTUATION AND PRIORITY LOGIC (APL) ACTUATION AND PRIORITY LOGIC (APL) EIM OUT RTS DIVISION II
UNDERVOLTAGE SHUNT TRIP COIL (NOTE 3) REACTOR TRIP BREAKER CLOSE COIL
(NOTE 1)
TRIP COIL
NOTE 1: THE UNDERVOLTAGE (UV) TRIP COIL AND SHUNT TRIP RELAY ARE ENERGIZED WHEN OPERATING; WHEN THE EIM OUTPUTS
ARE DE-ENERGIZED, THE UV TRIP COIL AND SHUNT TRIP RELAY ARE DE-ENERGIZED TO TRIP THE BREAKER OPEN.
NOTE 2: ONE ENABLE NONSAFETY CONTROL SWITCH PER DIVISION. THE SINGLE SWITCH ENABLES NONSAFETY CONTROL TO ALL
ESF COMPONENTS.
NOTE 3: THE SHUNT TRIP COIL IS NORMALLY DE-ENERGIZED; WHEN THE SHUNT TRIP RELAY IS DE-ENERGIZED, SHUNT TRIP COIL IS ENERGIZED
TO TRIP THE BREAKER OPEN.
NOTE 4: THE EIM APL LOGIC INCLUDES A SEAL-IN TO ENSURE COMPLETION OF THE PROTECTIVE ACTION. THE SEAL-IN REMAINS IN PLACE UNTIL POSITION
FEEDBACK INDICATES THAT THE TRIP BREAKER HAS REACHED THE POSITION DEMANDED BY THE PROTECTIVE ACTION. THE PROTECTIVE ACTION
IS FAIL-SAFE, OR DE-ENERGIZE TO TRIP.
NOTE 5: NONSAFETY CONTROL INPUTS CONSIST OF 14 INDIVIDUAL HARDWIRED SIGNALS.
DISABLE NS DISABLE NS
I I I I I I
BREAKER BREAKER BREAKER BREAKER
BREAKER BREAKER
OPENED OPENED OPENED CLOSED
CLOSED CLOSED
RTS DIVISION II EIM OUT ACTUATION AND PRIORITY LOGIC (APL) RTS DIVISION II EIM OUT 1 ACTUATION AND PRIORITY LOGIC (APL) ACTUATION AND PRIORITY LOGIC (APL) EIM OUT RTS DIVISION II
UNDERVOLTAGE (NOTE 1) SHUNT TRIP COIL (NOTE 3) REACTOR TRIP BREAKER CLOSE COIL
TRIP COIL
NOTE 1: THE UNDERVOLTAGE (UV) TRIP COIL AND SHUNT TRIP RELAY ARE ENERGIZED WHEN OPERATING; WHEN THE EIM OUTPUTS
ARE DE-ENERGIZED, THE UV TRIP COIL AND SHUNT TRIP RELAY ARE DE-ENERGIZED TO TRIP THE BREAKER OPEN.
NOTE 2: ONE ENABLE NONSAFETY CONTROL SWITCH PER DIVISION. THE SINGLE SWITCH ENABLES NONSAFETY CONTROL TO ALL
ESF COMPONENTS.
NOTE 3: THE SHUNT TRIP COIL IS NORMALLY DE-ENERGIZED; WHEN THE SHUNT TRIP RELAY IS DE-ENERGIZED, SHUNT TRIP COIL IS ENERGIZED
TO TRIP THE BREAKER OPEN.
NOTE 4: THE EIM APL LOGIC INCLUDES A SEAL-IN TO ENSURE COMPLETION OF THE PROTECTIVE ACTION. THE SEAL-IN REMAINS IN PLACE UNTIL POSITION
FEEDBACK INDICATES THAT THE TRIP BREAKER HAS REACHED THE POSITION DEMANDED BY THE PROTECTIVE ACTION. THE PROTECTIVE ACTION
IS FAIL-SAFE, OR DE-ENERGIZE TO TRIP.
NOTE 5: NONSAFETY CONTROL INPUTS CONSIST OF 14 INDIVIDUAL HARDWIRED SIGNALS.
DISABLE NS DISABLE NS
I I I I I I
BREAKER BREAKER BREAKER BREAKER
BREAKER BREAKER
OPENED OPENED OPENED CLOSED
CLOSED CLOSED
ESFAS DIVISION II EIM OUT ACTUATION AND PRIORITY LOGIC (APL) ESFAS DIVISION II EIM OUT ACTUATION AND PRIORITY LOGIC (APL) ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION II
NOTE 1: THE UNDERVOLTAGE (UV) TRIP COIL AND SHUNT TRIP RELAY ARE NORMALLY ENERGIZED; WHEN THE EIM OUTPUT IS DE-
ENERGIZED, THE UV TRIP COIL AND SHUNT TRIP RELAY ARE DE-ENERGIZED TO TRIP THE BREAKER OPEN.
NOTE 2: ONE ENABLE NONSAFETY CONTROL SWITCH PER DIVISION. THE SINGLE SWITCH ENABLES NONSAFETY CONTROL TO ALL
ESF COMPONENTS.
NOTE 3: THE SHUNT TRIP COIL IS NORMALLY DE-ENERGIZED; WHEN THE SHUNT TRIP RELAY IS DE-ENERGIZED, SHUNT TRIP COIL IS ENERGIZED
TO TRIP THE BREAKER OPEN.
NOTE 4: THE EIM APL LOGIC INCLUDES A SEAL-IN TO ENSURE COMPLETION OF THE PROTECTIVE ACTION. THE SEAL-IN REMAINS IN PLACE UNTIL POSITION
FEEDBACK INDICATES THAT THE TRIP BREAKER HAS REACHED THE POSITION DEMANDED BY THE PROTECTIVE ACTION. THE PROTECTIVE ACTION
IS FAIL-SAFE, OR DE-ENERGIZE TO TRIP.
NOTE 5: NONSAFETY CONTROL INPUTS CONSIST OF 14 INDIVIDUAL HARDWIRED SIGNALS.
DISABLE NS DISABLE NS
I I I I I I
BREAKER BREAKER BREAKER BREAKER BREAKER BREAKER
OPENED OPENED OPENED CLOSED
CLOSED CLOSED
ESFAS DIVISION II EIM OUT ACTUATION AND PRIORITY LOGIC (APL) ESFAS DIVISION II EIM OUT ACTUATION AND PRIORITY LOGIC (APL) ACTUATION AND PRIORITY LOGIC (APL) EIM OUT ESFAS DIVISION II
NOTE 1: THE UNDERVOLTAGE (UV) TRIP COIL AND SHUNT TRIP RELAY ARE NORMALLY ENERGIZED; WHEN THE EIM OUTPUT IS DE-
ENERGIZED, THE UV TRIP COIL AND SHUNT TRIP RELAY ARE DE-ENERGIZED TO TRIP THE BREAKER OPEN.
NOTE 2: ONE ENABLE NONSAFETY CONTROL SWITCH PER DIVISION. THE SINGLE SWITCH ENABLES NONSAFETY CONTROL TO ALL
ESF COMPONENTS.
NOTE 3: THE SHUNT TRIP COIL IS NORMALLY DE-ENERGIZED; WHEN THE SHUNT TRIP RELAY IS DE-ENERGIZED, SHUNT TRIP COIL IS ENERGIZED
TO TRIP THE BREAKER OPEN.
NOTE 4: THE EIM APL LOGIC INCLUDES A SEAL-IN TO ENSURE COMPLETION OF THE PROTECTIVE ACTION. THE SEAL-IN REMAINS IN PLACE UNTIL POSITION
FEEDBACK INDICATES THAT THE TRIP BREAKER HAS REACHED THE POSITION DEMANDED BY THE PROTECTIVE ACTION. THE PROTECTIVE ACTION
IS FAIL-SAFE, OR DE-ENERGIZE TO TRIP.
NOTE 5: NONSAFETY CONTROL INPUTS CONSIST OF 14 INDIVIDUAL HARDWIRED SIGNALS.
NOTE 1 NOTE 1
MCS INPUT 02
NOTE 1 NOTE 1
MCS INPUT 06
NOTE 1 NOTE 1
MCS INPUT 07
NOTE 1 NOTE 1
NOTE 1 NOTE 1
MCS INPUT 09
NOTE 1 NOTE 1
MCS INPUT 10
NOTE 1 NOTE 1
MCS INPUT 11
NOTE 1 NOTE 1
MCS INPUT 12
NOTE 1 NOTE 1
NOTE 1: CONNECTIONS TO BE CONFIGURED WITH SWITCHES OR JUMPERS FOR EACH SPECIFIC EIM APPLICATION
TYPE D
TYPE D
TYPE D 3. THE EDSS INCLUDES TWO SUBSYSTEMS, EDSS-MS AND
REACTOR POOL COOLING SYSTEM EDSS-C. EDSS-MS BUS VOLTAGE PROVIDES INPUT TO THE
MODULE PROTECTION MPS. EDSS-C BUS VOLTAGE PROVIDES INPUT TO THE PPS.
REACTOR POOL
TEMPERATURE SYSTEM
4. AR-41 DETECTION INCLUDED AS PART OF THE NOBLE GAS
(OPERATING BAY)
DETECTION VARIABLE.
TYPE D DECAY HEAT REMOVAL SYSTEM
5. POST ACCIDENT MONITORING NEUTRON FLUX SIGNALS:
POWER RANGE LINEAR POWER
INTERMEDIATE RANGE LOG POWER
HIGHLY RELIABLE DC POWER SYSTEM MS PRESSURE
SOURCE RANGE COUNT RATE
(DHR INLET PRESSURE)
EDSS BUS NMS-FLOOD (NEUTRON MONITORING DURING FLOODED
VOLTAGE CONDENSATE AND FEEDWATER SYSTEM CONTAINMENT CONDITIONS).
TYPE D
(SEE NOTE 3)
FEEDWATER
REGULATING
TYPE D SAFETY DISPLAY AND DHRS OUTLET PRESSURE DHRS OUTLET
DHRS VALVE POSITION VALVE POSITION
INDICATION SYSTEM TEMPERATURE
TYPE D TYPE D
CONTROL ROOM HABITABILITY SYSTEM TYPE D TYPE D
CRHS AIR SUPPLY CRHS PRESSURE
ISOLATION VALVE RELIEF ISOLATION
POSITION VALVE POSITION
TYPE D TYPE D
TYPE D
TYPE E
THERE IS A TRIP/BYPASS SWITCH FOR EACH SFM THAT HAS A SAFETY FUNCTION TO ALLOW REMOVING THE SFM FROM
SERVICE.
IF THE OOS SWITCH ON THE SFM IS IN THE OPERATE POSITION, THE TRIP DETERMINATION RESULT OF THE SAFETY
FUNCTION ALGORITHM IS SENT TO THE SBM.
IF THE OOS SWITCH IS IN THE OUT OF SERVICE POSITION, THE POSITION OF THE TRIP/BYPASS SWITCH DETERMINES WHAT
IS SENT TO THE EIM. IF THE TRIP/BYPASS SWITCH IS IN BYPASS, ALL SAFETY FUNCTIONS FOR THAT SFM ARE FORCED TO
NOT TRIP OR NOT ACTUATE. IF THE TRIP/BYPASS SWITCH IS IN THE TRIP POSITION, THEN ALL SAFETY FUNCTIONS FOR
THAT SFM ARE FORCED TO TRIP AND ACTUATE.
IF THE SFM FAILS TO COMMUNICATE CORRECTLY TO THE SBM OR IS REMOVED, THE POSITION OF THE TRIP/BYPASS
SWITCH WILL DETERMINE THE COMMANDS SENT TO THE EIM FOR THE SAFETY FUNCTION ON THAT SFM. (ASSOCIATED
LOGIC IS SHOWN BELOW)
A SFM SFM
SFM TRIP
PS DETERMINATION REMOVED FAILED
(TYP.)
OP OOS
XS
TRIP BYP
XS
SFM TRIP TO
COINCIDENT LOGIC
(TYP.)
Figure 7.1-3b: Plant Protection System Loss of Normal Control Room HVAC System AC and Loss of Highly Reliable DC Power System AC
ELV BUS VOLTAGE 1 ELV BUS VOLTAGE 4 ELV BUS VOLTAGE 1 ELV BUS VOLTAGE 2 ELV BUS VOLTAGE 3 ELV BUS VOLTAGE 4
ELV BUS ELV BUS ELV BUS ELV BUS ELV BUS ELV BUS
VOLTAGE-LO VB-I (NOTE 1) VB-I VOLTAGE-LO VOLTAGE-LO VB-I VOLTAGE-LO VB-I (NOTE 1) VB-I VOLTAGE-LO VB-I VOLTAGE-LO
I I I I I I
F F F F F F
AND AND
(NOTE 2) TD
PPS
LOSS OF CRV PPS
AC LOSS OF EDS AC
Figure 7.1-3c: Plant Protection System Radiation Monitors and Actuation Logic
PPS RADIATION MONITORS CONTROL ROOM ENVELOPE CONTROL ROOM ENVELOPE
AND ACTUATION AIR SUPPLY TOXIC GAS AIR SUPPLY SMOKE
LOGIC DIV. I SENSORS DIV I DETECTORS DIV I
CRV POST FILTER AIR RADIATION PPS CRH ACTUATION & CRV ISOLATION PPS CRV OUTSIDE AIR ISOLATION LOGIC
SENSOR LOGIC DIV. I DIV. I
OR
A A A
DIVISION I DIVISION I
NOTE 1: MANUAL ACTUATE INITIATES CRH AND CRV ISOLATION AT THE COMPONENT LEVEL THROUGH THE EIM APL LOGIC. MANUAL NOTE 4: MANUAL ACTUATE INITIATES CRV OUTSIDE AIR ISOLATION AT THE COMPONENT LEVEL THROUGH THE EIM APL LOGIC. MANUAL
ACTUATE SWITCHES ARE LOCATED IN THE MCR. ACTUATE SWITCHES ARE LOCATED IN THE MCR.
NOTE 2: PPS ACTUATE CRH, WHEN ACTIVE, INITIATES CRH AND ISOLATES THE CRE BY CLOSING ASSOCIATED DAMPERS. NOTE 5: PPS ISOLATE CRV OUTSIDE AIR, WHEN ACTIVE, ISOLATES THE CRV OUTSIDE AIR INTAKE BY CLOSING ASSOCIATED DAMPERS.
ENABLE NONSAFETY
CONTROL SWITCH
DISABLE ENABLE
HS
I I I I I I
ENABLE NONSAFETY
CONTROL SWITCH
DISABLE ENABLE
HS
I I I I I I
CLOSE OPEN
HS
(NOTE 1)
ENABLE NONSAFETY
CONTROL SWITCH
DISABLE ENABLE
HS
DAMPER DAMPER
FULLY FULLY
CLOSED OPENED
I I
CLOSE OPEN
APL
Sensor Block I Safety Block I DIV I RTS AND ESFAS Safety Block II Sensor Block II
SEPARATION GROUP A AND C INFORMATION SEPARATION GROUP B AND D
DIV II RTS AND ESFAS SENSORS TO
SENSORS TO
RTS I INFORMATION RTS II SEPARATION GROUP B
SEPARATION GROUP A
OR D
OR C SG A AND C TO RTS AND ESFAS
ESFAS I SG B AND D TO RTS AND ESFAS ESFAS II
Monitoring Monitoring
Trip Determination Trip Determination Trip Determination Trip Determination
and and
A B C D
Indication Indication
7.1-150
Monitoring Monitoring
ESFAS Voting and RTS Voting RTS Voting and ESFAS Voting
I Indication I II Indication II
Priority Logic I Manual Priority Logic I Priority Logic II Manual Priority Logic II
Actuation Actuation
Safety Block II
Revision 5
Tier 2
DIVISION I DIVISION II
DIVISION I DIVISION II
SAFETY SAFETY
MANUAL MANUAL
DISPLAY AND DISPLAY AND
CONTROLS CONTROLS
INDICATION INDICATION
Sensor Block I Safety Block I DIV I RTS AND ESFAS Safety Block II Sensor Block II
SEPARATION GROUP A AND C INFORMATION SEPARATION GROUP B AND D
PRESSURE PRESSURE
DIV II RTS AND ESFAS SENSORS TO
SENSORS TO
LEVEL RTS I INFORMATION RTS II LEVEL SEPARATION
SEPARATION
GROUP B OR D
GROUP A OR C FLOW SG A AND C TO RTS AND ESFAS FLOW
ESFAS I ESFAS II
SG B AND D TO RTS AND ESFAS
DIVISION I DIVISION II
DIVISION I DIVISION II
SAFETY SAFETY
MANUAL MANUAL
DISPLAY AND DISPLAY AND
CONTROLS CONTROLS
INDICATION INDICATION
Sensor Block I Safety Block I DIV I RTS AND ESFAS Safety Block II Sensor Block II
SEPARATION GROUP A AND C INFORMATION SEPARATION GROUP B AND D
PRESSURE PRESSURE
DIV II RTS AND ESFAS SENSORS TO
SENSORS TO
LEVEL RTS I INFORMATION RTS II LEVEL SEPARATION
SEPARATION
GROUP B OR D
GROUP A OR C FLOW SG A AND C TO RTS AND ESFAS FLOW
ESFAS I ESFAS II
SG B AND D TO RTS AND ESFAS
DIVISION I DIVISION II
DIVISION I DIVISION II
SAFETY SAFETY
MANUAL MANUAL
DISPLAY AND DISPLAY AND
CONTROLS CONTROLS
INDICATION INDICATION
Sensor Block I Safety Block I DIV I RTS AND ESFAS Safety Block II Sensor Block II
SEPARATION GROUP A AND C INFORMATION SEPARATION GROUP B AND D
PRESSURE PRESSURE
DIV II RTS AND ESFAS SENSORS TO
SENSORS TO
LEVEL RTS I INFORMATION RTS II LEVEL SEPARATION
SEPARATION
GROUP B OR D
GROUP A OR C FLOW SG A AND C TO RTS AND ESFAS FLOW
ESFAS I ESFAS II
SG B AND D TO RTS AND ESFAS
DIVISION I DIVISION II
DIVISION I DIVISION II
SAFETY SAFETY
MANUAL MANUAL
DISPLAY AND DISPLAY AND
CONTROLS CONTROLS
INDICATION INDICATION
Sensor Block I Safety Block I DIV I RTS AND ESFAS Safety Block II Sensor Block II
SEPARATION GROUP A AND C INFORMATION SEPARATION GROUP B AND D
PRESSURE PRESSURE
DIV II RTS AND ESFAS SENSORS TO
SENSORS TO
LEVEL RTS I INFORMATION RTS II LEVEL SEPARATION
SEPARATION
GROUP B OR D
GROUP A OR C FLOW SG A AND C TO RTS AND ESFAS FLOW
ESFAS I ESFAS II
SG B AND D TO RTS AND ESFAS
DIVISION I DIVISION II
DIVISION I DIVISION II
SAFETY SAFETY
MANUAL MANUAL
DISPLAY AND DISPLAY AND
CONTROLS CONTROLS
INDICATION INDICATION
Sensor Block I Safety Block I DIV I RTS AND ESFAS Safety Block II Sensor Block II
SEPARATION GROUP A AND C INFORMATION SEPARATION GROUP B AND D
PRESSURE PRESSURE
DIV II RTS AND ESFAS SENSORS TO
SENSORS TO
LEVEL RTS I INFORMATION RTS II LEVEL SEPARATION
SEPARATION
GROUP B OR D
GROUP A OR C FLOW SG A AND C TO RTS AND ESFAS FLOW
ESFAS I ESFAS II
SG B AND D TO RTS AND ESFAS
DIVISION I DIVISION II
DIVISION I DIVISION II
SAFETY SAFETY
MANUAL MANUAL
DISPLAY AND DISPLAY AND
CONTROLS CONTROLS
INDICATION INDICATION
Sensor Block I Safety Block I DIV I RTS AND ESFAS Safety Block II Sensor Block II
SEPARATION GROUP A AND C INFORMATION SEPARATION GROUP B AND D
PRESSURE PRESSURE
DIV II RTS AND ESFAS SENSORS TO
SENSORS TO
LEVEL RTS I INFORMATION RTS II LEVEL SEPARATION
SEPARATION
GROUP B OR D
GROUP A OR C FLOW SG A AND C TO RTS AND ESFAS FLOW
DIVISION I DIVISION II
DIVISION I DIVISION II
SAFETY SAFETY
MANUAL MANUAL
DISPLAY AND DISPLAY AND
CONTROLS CONTROLS
INDICATION INDICATION
Sensor Block I Safety Block I DIV I RTS AND ESFAS Safety Block II Sensor Block II
SEPARATION GROUP A AND C INFORMATION SEPARATION GROUP B AND D
PRESSURE PRESSURE
DIV II RTS AND ESFAS SENSORS TO
SENSORS TO
LEVEL RTS I INFORMATION RTS II LEVEL SEPARATION
SEPARATION
GROUP B OR D
GROUP A OR C FLOW SG A AND C TO RTS AND ESFAS FLOW
ESFAS I ESFAS II
SG B AND D TO RTS AND ESFAS
DIVISION I DIVISION II
DIVISION I DIVISION II
SAFETY SAFETY
MANUAL MANUAL
DISPLAY AND DISPLAY AND
CONTROLS CONTROLS
INDICATION INDICATION
Sensor Block I Safety Block I DIV I RTS AND ESFAS Safety Block II Sensor Block II
SEPARATION GROUP A AND C INFORMATION SEPARATION GROUP B AND D
PRESSURE PRESSURE
DIV II RTS AND ESFAS SENSORS TO
SENSORS TO
LEVEL RTS I INFORMATION RTS II LEVEL SEPARATION
SEPARATION
GROUP B OR D
GROUP A OR C FLOW SG A AND C TO RTS AND ESFAS FLOW
ESFAS I ESFAS II
SG B AND D TO RTS AND ESFAS
Figure 7.1-16: Example Module Protection System High Level Control Structure
-
Figure 7.1-17: Example Neutron Monitoring System High Level Control Structure
Operator
Process Model
Maintenance Bypass Operating Conditions SDI Variable Feedback
Mode
Normal
Abnormal Nonsafety Maintenance
Accident Workstation
Network
1 2 3 4 M&I
SFM
M&I Bus
EIM
The safety-related digital instrumentation and controls (I&C) safety systems include features
that complement the fundamental design principles described in Section 7.1, and address
specific functional and design requirements contained in IEEE Std 603-1991 "IEEE Standard
Criteria for Safety Systems for Nuclear Power Generating Stations" (Reference 7.2-11), Section 5
(Safety System Criteria), Section 6 (Sense and Command Features- Functional and Design
Requirements), and Section 7 (Executive Features- Functional and Design Requirements), and
the corresponding guidance provided in IEEE Std 7-4.3.2-2003, “IEEE Standard Criteria for
Digital Computers in Safety Systems of Nuclear Power Generating Stations” (Reference 7.2-13).
Specific features that are incorporated in the NuScale safety-related I&C system designs are
described in Section 7.2.1 through Section 7.2.15 below and include the following:
• quality
• equipment qualification
• reliability, integrity, and completion of protective action
• operating and maintenance bypasses
• interlocks
• derivation of system inputs
• setpoints
• auxiliary features
• control of access, identification, and repair
• interaction between sense and command features and other systems
• multi-unit stations
• automatic and manual control
• displays and monitoring
• human factors considerations
• capability for test and calibration
7.2.1 Quality
The overall Quality Assurance Program (QAP) applied to the design of the safety-related
and risk-significant I&C systems is described in NuScale topical report, "Quality Assurance
Program Description for the NuScale Power Plant," NP-TR-1010-859-NP-A, Revision 5
(Reference 7.2-30). The QAP complies with NQA-1-2008 (Reference 7.2-2) and NQA-1a-2009
Addenda (Reference 7.2-3), Requirement 3, Sections 100 through 900 and the standards for
computer software in NQA-1-2008 and NQA-1a-2009 Addenda, Part II, Subpart 2.7.
The information in this section satisfies the application specific information requirements
in topical report NuScale Power, LLC, TR-1015-18653-P-A, "Design of the Highly Integrated
Protection System Platform Topical Report," (Reference 7.2-25) listed in Table 7.0-2 for
application specific action item (ASAI) numbers 4, 16, 47, 49, 50, and 51. The following
regulatory guidance applies to the QAP for digital I&C systems:
• Regulatory Guide 1.28, Revision 4, endorses ASME NQA-1-2008 and the
ASME NQA-1a-2009 Addenda, "Addenda to ASME NQA-1-2008, Quality Assurance
Requirements for Nuclear Facility Applications," and states that these standards
provide an adequate basis for complying with the requirements of 10 CFR Part 50
Appendix B.
Because the approved NuScale QAP is based on ASME NQA-1-2008 and the
ASME NQA-1a-2009 Addenda, it satisfies the regulatory requirements in RG 1.28.
The NuScale Digital Safety Systems Project Plan provides the foundation for the digital I&C
development effort. It defines the purpose, scope, objectives, high-level schedule, and
project team. This plan provides a description of the framework for the I&C design and
development process. This framework supplements the overall development process plans
(i.e., the NuScale Quality Management Plan and the NuScale Digital I&C Software
Development Plan) with specific system, hardware, and software development activities
and includes a description of the proposed development life cycles as well as the
management activities that are implemented in the design and development of safety and
other applicable nonsafety-related I&C systems.
The NuScale Digital I&C Software Quality Assurance Plan and the NuScale Digital I&C
Software Development Plan define the following:
• the standards, methods, tools, and procedures for the software design and
development process
• the activities performed for the phases of the software development
• requirements traceability from the software concept phase to installation and checkout
phase
• safety-related requirements documentation, evaluation, review, verification, and
testing during the software design process to minimize unknown, unreliable, and
abnormal conditions
• the organization and responsibilities of individuals or groups involved in the various
software verification and validation (V&V) and review activities
• the structure for test and review guidance for software functional testing
• the requirements and guidelines necessary to prepare, execute, and document
software tests
• the requirements for software test documentation
• the requirements for metrics that include error tracking and resolution
The NuScale Digital l&C Software Quality Assurance Plan describes the approach,
management, organization, responsibilities, and methodologies used for development of
software products and configurable logic devices for safety-related and risk-significant l&C
systems. This plan describes the following software development activities:
• regulatory requirements applicable to safety-related l&C software products
• processes for developing safety-related l&C software
• required software life cycle processes
• quality assurance (QA) activities performed during the phases of the software life cycle
• responsibilities and authorities for accomplishing software activities
• identification of tools and the resources required for plan execution
• applicable processes for certifying commercial grade software for use in safety-related
l&C systems
The NuScale Digital l&C Software Quality Assurance Plan defines requirements to ensure
compliance with applicable portions of IEEE Std 7-4.3.2-2003 for meeting the unique
quality aspects of safety-related software, as specified by Regulatory Guide 1.152, Revision
3. The plan follows the guidelines of IEEE Std 730-2002, "IEEE Standard for Software Quality
Assurance Plans" (Reference 7.2-14).
The NuScale Digital I&C Software Quality Assurance Plan applies to digital I&C software
classified as software integrity levels (SILs) 4 and 3 in accordance with the NuScale Software
Classification Procedure. The NuScale Digital I&C Software Quality Assurance Plan may be
applied to digital I&C software classified at less than SIL 3, by applying the approach
defined in the Digital I&C Software Verification and Validation Plan and Software
Management Plan which ensures nonsafety-related software or logic meets applicable
quality requirements.
Software development and QA controls are applied to the following safety-related and
nonsafety-related I&C systems:
• module protection system (MPS)
• safety display and indication system (SDIS)
• in-core instrumentation system (ICIS)
• plant protection system (PPS)
• module control system (MCS)
• plant control system (PCS)
• radiation monitoring system (RMS)
• general I&C structures, systems, and components that contain embedded digital
devices
The NuScale Digital I&C Software Quality Assurance Program applies equally in the
application of different FPGA technologies within the MPS; the program activities do not
The following items are excluded from these software development and QA controls:
• plant simulator software which is subject to ANSI/ANS 3.5-2009 , "Nuclear Power Plant
Simulators for Use in Operator Training and Examination" (Reference 7.2-1) and
RG-1.149
• software or complex logic device logic for physical security protection, as delineated
within 10 CFR 73.55
The following regulations apply to the QAP for digital I&C safety systems.
• 10 CFR 50.55a(h) requires compliance with IEEE Std 603-1991, including the correction
sheet dated January 30, 1995, which is referenced in paragraphs 10 CFR 50.55a(h)(2)
and (3). Section 5.3 requires that components and modules be of a quality that is
consistent with minimum maintenance requirements and low failure rates. It also
requires that safety system equipment be designed, manufactured, inspected,
installed, tested, operated, and maintained in accordance with a prescribed QAP.
• 10 CFR 50.54(jj) and 50.55(i) require, in part, that systems and components subject to
the codes and standards in 10 CFR 50.55a be designed, tested, and inspected to quality
standards commensurate with the importance of the safety function to be performed.
10 CFR 50.54(jj) and 10 CFR 50.55(i) do not apply to design certification applicants, and
10 CFR 50.55a(a)(1) has been modified to remove quality requirements.
• 10 CFR Part 50, Appendix A, General Design Criterion (GDC) 1, requires, in part, that
systems and components be designed, fabricated, erected, and tested to quality
standards commensurate with the importance of the safety functions to be performed.
• Appendix B to 10 CFR Part 50 establishes QA requirements for the design, manufacture,
construction, and operation of safety-related structures, systems, and components.
• Regulatory Guide 1.152, Revision 3 endorses the quality guidance for digital I&C safety
systems in IEEE Std 7-4.3.2-2003 (Section 5.3) as an acceptable method for satisfying
the NRC regulations with respect to high functional reliability and design requirements
for computers used in the safety systems of nuclear power plants. RG 1.152 does not
endorse Annexes B - F of IEEE Std 7-4.3.2-2003.
• IEEE Std 7-4.3.2-2003 Section 5.3 specifies additional requirements that are necessary
to meet the IEEE Std 603-1991 quality requirements for digital I&C for the following
topics:
− software development (Section 5.3.1)
− use of software tools (Section 5.3.2)
− verification and validation (Sections 5.3.3 and 5.3.4)
− configuration management (Section 5.3.5)
− risk management (Section 5.3.6)
− qualification of existing commercial computers (Section 5.4.2)
The life cycle process defined in the NuScale Digital Safety Systems Project Plan satisfies the
software development requirements of IEEE Std 7-4.3.2-2003 Section 5.3. The combination
of the NuScale QAP and NuScale Digital I&C Software Quality Assurance Plan satisfy the
software QA requirements of IEEE Std 7-4.3.2-2003 Section 5.3.1. The NuScale Digital I&C
Software Quality Assurance Plan requires that the NuScale Digital I&C Software
Management Plan address quality metrics, as required by IEEE Std 7-4.3.2-2003 Section
5.3.1.1; however, NuScale is maintaining flexibility for the definition of specific metrics until
a vendor is selected to implement the digital I&C designs. This approach enables NuScale
to adjust the metrics based on the technology and vendor selections. It also allows for
adoption of established metrics used by the vendor.
The NuScale Digital I&C Software Quality Assurance Plan incorporates tool requirements
from IEEE Std 7-4.3.2-2003. The NuScale Digital I&C Software Quality Assurance Plan
satisfies the software tool use requirements of IEEE Std 7-4.3.2-2003 Section 5.3.2.
The NuScale Digital I&C Software Verification and Validation Plan is based on
IEEE Std 1012-2004 (Reference 7.2-19), as endorsed by RG 1.168 Revision 2. The V&V
program for safety-related software (i.e., SIL 4) is implemented by a V&V team that is
independent from the design development team. The NuScale Digital I&C Software
Verification and Validation Plan conforms to IEEE Std 1012-2004 with adaptations, as
allowed by the standard, and exceptions:
Adaptations
• V&V activities are adapted to NuScale life cycle and Complex Logic Device technology
(i.e., field programmable gate arrays (FPGA)). In the application of different FPGA
technologies within the MPS, the V&V activities are the same; they do not differentiate
between different FPGA technologies.
• V&V tasks are adapted to Complex Logic Device technology.
Exceptions
• Documentation requirement details in Sections 6 and 7 of the standard that conflict
with NuScale standard documentation practices or QAP requirements or are
inconsistent with the platform neutral strategy (where flexibility is retained to adopt
established vendor documentation formats).
The NuScale Digital I&C Software Verification and Validation Plan, with the noted
exceptions, satisfies the requirements of IEEE Std 7-4.3.2-2003 Sections 5.3.3 and 5.3.4.
The NuScale Digital I&C Software Configuration Management Plan conforms to IEEE Std
828-2005 "IEEE Standard for Software Configuration Management Plans"
(Reference 7.2-15), as endorsed by RG 1.169 Revision 1. The NuScale Digital I&C Software
Configuration Management Plan satisfies the configuration management requirements of
IEEE Std 7-4.3.2-2003 Section 5.3.5.
Three NuScale process plans (the NuScale Digital I&C Software Development Plan, the
Digital I&C Software Management Plan, and the NuScale Digital I&C Software Quality
Assurance Plan) define expectations for risk management during the development of
digital I&C systems, based on the guidance in IEEE Std 7-4.3.2-2003. The implementation of
the risk management tasks is linked to the NuScale Project Management process, which
has risk management elements. The NuScale Digital I&C Software Development Plan and
the NuScale Digital I&C Software Quality Assurance Plan satisfy the risk management
requirements of IEEE Std 7-4.3.2-2003 Section 5.3.6.
The NuScale Digital I&C Quality Assurance Plan provides a framework for commercial grade
dedication. The NuScale Digital I&C Software Quality Assurance Plan requires use of EPRI
TR-106439, "Guidelines on Evaluation and Acceptance of Commercial Grade Digital
Equipment for Nuclear Safety Applications,” (Reference 7.2-5) for the commercial grade
dedication of digital I&C equipment. RG 1.152 notes that EPRI TR-106439 contains
adequate guidance that the NRC has endorsed. The programmatic requirements applied to
the commercial grade dedication of digital I&C equipment satisfy the requirements of IEEE
Std 7-4.3.2-2003 Section 5.4.2.
Regulatory Guide 1.152 also addresses expectations for a secure development and
operational environment (SDOE) for protection of digital safety systems. The NuScale
Digital Safety System SDOE Plan is a NuScale process plan that defines security controls for
the phases of the NuScale digital safety system development life cycle. An SDOE
Vulnerability Assessment is performed during the basic design stage to identify and
mitigate potential weaknesses or vulnerabilities in the phases of the digital safety system
life cycle that may degrade the SDOE or degrade the reliability of the system. This
assessment also identifies design requirements that are verified or added to the
requirements specification for the system. The Digital Safety System SDOE Plan and SDOE
Vulnerability Assessment satisfy the risk management SDOE requirements of RG 1.152,
Revision 3.
NuScale has taken the following general approach to using the software-based RGs and
associated IEEE standards:
• adapted to Complex Logic Device technology. In the application of different FPGA
technologies within the MPS, the V&V activities are the same; they do not differentiate
between different FPGA technologies.
• capture key aspects (i.e., those with a clear nexus to safety) while not committing to
other less important or administrative requirements (i.e., those without a clear nexus to
safety)
• maintain flexibility where warranted to support implementation of a platform neutral
strategy for the safety-related I&C systems
• specify universally important aspects of software quality that are applicable to safety
critical vendor processes and avoid over specification that limits choices or complicates
implementation of the platform neutral strategy
1) Regulatory Guide 1.173, Revision 1 endorses IEEE Std 1074-2006 "IEEE Standard for
Developing a Software Project Life Cycle Process" (Reference 7.2-22) The NuScale
digital I&C safety system development life cycle is implemented in the following
NuScale process plans:
These documents define the digital I&C safety system development life cycle, key
development activities and sequences, management responsibilities, and necessary
support activities. In addition to meeting the requirements of IEEE Std 1012-2004, the
NuScale digital I&C safety system development life cycle described in these key
planning documents conforms to the requirements in IEEE Std 1074-2006, as endorsed
by RG 1.173, Revision 1.
2) Regulatory Guide 1.172, Revision 1 endorses IEEE Std 830-1998, "IEEE Recommended
Practice for Software Requirements Specifications" (Reference 7.2-17) as an acceptable
approach for the preparation of software requirements specifications. The NuScale
Digital I&C Software Development Plan specifies the requirements for the
development of software requirements specifications for the safety-related digital I&C
systems, consistent with the technical guidance in RG 1.172, Revision 1 and IEEE Std
830-1998. For RG 1.170, the requirements of IEEE Std 829-2008 “IEEE Standard for
Software and System Test Documentation” (Reference 7.2-16) are tailored to the
NuScale I&C development life cycle, which is different than that of the conceptual
waterfall life cycle listed in RG 1.152. NuScale maps the applicable tasks from IEEE Std
829-2008 to the NuScale I&C development life cycle. NuScale also takes exception to
some of the administrative requirements in the standard that conflict with established
engineering or QA documentation requirements.
3) Regulatory Guide 1.171, Revision 1 endorses IEEE Std 1008-1987, "IEEE Standard for
Software Unit Testing" (Reference 7.2-18) as an acceptable approach for performing
unit testing of safety system software. The NuScale Digital l&C Software Master Test
Plan specifies the requirements for performing software component or unit testing for
the safety-related digital I&C systems, consistent with the technical guidance in RG
1.171, Revision 1, and IEEE Std 1008-1987 with the following exceptions:
Adaptations
• V&V activities adapted to NuScale life cycle and Complex Logic Device technology.
In the application of different FPGA technologies within the MPS, the V&V activities
are the same; they do not differentiate between different FPGA technologies.
• V&V tasks adapted to Complex Logic Device technology
Exceptions
• Consistent with the guidance in RG 1.170, Revision 1, exceptions are taken for
documentation requirement details in Sections 6 and 7 of IEEE Std 1012-2004 that
conflict with NuScale standard documentation practices or are inconsistent with
the platform neutral strategy (where flexibility is retained to adopt established
vendor documentation formats). In all cases, the approved NuScale QAP (see
Section 17.5) takes precedence.
vendor methods and documentation formats for these activities). NuScale does not
conform to the requirements in IEEE Std 1028-2008.
The I&C safety system development process is structured to follow a life cycle that
includes a top-down iterative requirement and specification development, design
implementation, and a bottoms-up V&V effort at each level of integration. The life cycle
allows iteration of requirements, design, and implementation based on the nature and
evaluations of the safety critical aspects of the system design. The system development
approach allows prototyping activities and in-process QA efforts to be executed
integral to the system and software development stages.
Figure 7.2-1 provides a graphical representation of the overall system and software life
cycle processes. The system and software life cycles for development of the I&C safety
systems consist of five major elements:
• project management and organizational processes
• safety analyses
• system and software technical development
• independent validation and verification
• configuration management
The NuScale project management and organizational processes are used to establish
the infrastructure for I&C safety system development. The system and software safety
analyses are performed throughout the system and software life cycle phases in order
to identify hazards associated with I&C system design and operation. The system and
software technical development processes establish the methodology for the system
and software design development life cycle of the I&C safety systems. Independent
V&V processes establish verification and validation methods, activities, and oversight
for development of the I&C safety systems, which is both technically, financially and
managerially independent from the development organization.
As indicated in Figure 7.2-1, technical development is split into three distinct elements:
• basic design
• detailed design
• system integration, installation, and testing
Basic design activities are the overall design requirements for the I&C systems. Lower
level digital component and software design activities are performed in accordance
with the basic design requirements and are considered to be a part of detailed design.
Figure 7.2-2 provides a detailed representation of the system and software design
technical development activities. A description of the life cycle phases associated with
system and software technical development is provided in Section 7.2.1.1.1. The
software development life cycle is the same for the two types of FPGAs used in the HIPS
platform.
The digital I&C system and software development life cycle is correlated to other life
cycles presented in various regulatory documents in Figure 7.2-3.
Basic design activities are performed in accordance with the NuScale design
control process, which is a sequential approach to system design consisting of
preliminary and final design documents. Preliminary design documents are those
issued for conceptual design or those that reference draft, preliminary, or
conceptual information. Final design documents are those issued for procurement,
fabrication, construction, or final design.
During the system development life cycle process, multiple iterations between the
system functional requirements specification phase and the system design phase
are performed. For this reason, the final activities of a successive system
development life cycle phase cannot be performed until the final design, safety
analyses, V&V, and QA activities are completed for the previous life cycle phase.
Life cycle phase entry and exit criteria are defined in the NuScale Digital I&C
Software Quality Assurance Plan.
The NuScale Digital I&C Software Quality Assurance Plan is a process plan that
identifies the QA procedures applicable to specific system and software
development processes, as well as identifying particular methods chosen to
implement QA procedures.
The NuScale Digital I&C Software Verification and Validation Plan is a process
plan that documents the V&V activities necessary for the system development
life cycle. This includes guidance for the generation of software V&V plans
specific to individual software products.
The NuScale Digital Safety System Safety Plan is a process plan that documents
the process for examining the system throughout its system and software
development life cycles to identify hazards (i.e., factors and causes), I&C
requirements, and constraints to eliminate, prevent, or control. The hazard
analyses covered in the NuScale Digital Safety System Safety Plan examine
safety-related I&C systems, subsystems, and components, interrelationships
and interactions with other systems, subsystems, and components to identify
unintended or unwanted I&C system operation including the impairment or
loss of the ability to perform a safety function.
The NuScale Digital Safety System SDOE Plan is a process plan that documents
the process for ensuring that the development processes and documentation
are secure such that the system does not contain undocumented logic,
unwanted functions or applications, and any other logic that could adversely
impact the integrity or reliability of the digital safety system. The NuScale
Digital Safety System SDOE Plan also addresses physical security requirements
and access control features.
In the conceptual system design phase, the system design team prepares the
conceptual system design documentation following the NuScale design
control process and procedures. These documents provide the system
architecture and design details and is developed based on the system
requirements documentation and safety analysis requirements as inputs.
In the system prototype development phase, the system design team develops
a system prototype as an integrated part of the system basic design process in
order to reduce the overall project risk. The prototype development activities
are not required to be performed under a 10 CFR Part 50 Appendix B program.
The prototyping is used to put together a working model in order to test
various aspects of a design, illustrate ideas, investigate new features, and
provide guidance in the development of the detailed ERS. The system hazards
analysis is reviewed when any final system design information or inputs are
revised or changed to determine whether the changes impact the inputs or
results of the hazard analysis. The hazard analysis is updated according to the
process described in Section 7.1.8.3 if the design changes are determined to
impact the existing hazards analysis or if new hazards are identified according
to the NuScale Digital I&C Software Quality Assurance Plan with the results
documented in the system protoype development phase.
The NuScale Digital I&C Software Integration Plan, NuScale Digital I&C Software
Configuration Management Plan, NuScale Digital l&C Software Master Test Plan
and NuScale Software Installation Plan are also products of this phase.
The NuScale Digital I&C Software Integration Plan is a NuScale process plan that
documents the integration and testing of all software items, hardware, manual
processes, and other system interfaces that constitute the I&C system,
consistent with the architectural design.
The NuScale Digital l&C Software Master Test Plan is a NuScale process plan
that provides guidance for test planning and management for system and
software testing for digital safety systems.
The NuScale Digital l&C Software Integration and Installation Plans together are
the NuScale process plans that describe the general procedures for installing
the finished system in the production environment.
The life cycle phase entry and exit criteria are defined in the NuScale Digital I&C
Software Quality Assurance Plan.
Hardware Planning
The Hardware Development Plan identifies the activities and associated tasks
included in each hardware development life cycle phase, the task inputs and
outputs, and establishes the review, verification, and validation of those
outputs.
Software Planning
The Digital I&C Software Development Plan defines which activities and
associated tasks are part of the software development life cycle phase, states
the task inputs and outputs, and requires the review, verification, and
validation of those outputs. The Digital I&C Software Development Plan
describes the process for the translation of the detailed design into hardware
description language.
The NuScale Digital I&C Software Verification and Validation Plan defines the
activities, expectations, processes, and base level of rigor for V&V which is to be
performed for SIL 1 through 4 software systems.
The NuScale Digital l&C Software Master Test Plan defines criteria for the test
organization, test schedule, test resources, responsibilities, tools, techniques,
and methods necessary for software testing.
The NuScale Digital I&C Software Training Plan documents the training
management, implementation, and resource characteristics necessary for the
software development project.
Hardware Requirements
Software Requirements
The independent V&V team develops the Acceptance and System Test Plans for
SIL 3 and 4 software systems during this phase.
Hardware Design
Software Design
In the software design phase, a Software Design Description for the applicable
software products is prepared according to the NuScale Digital I&C Software
Quality Assurance Plan. The Software Design Description is developed based
on the Software Requirement Specification and the system architecture
described in the ERS as inputs. The Software Design Description demonstrates
adequate coverage of the software requirements and the absence of
unnecessary functions.
The primary outputs of this phase are the approved Software Design
Description and the necessary interface design descriptions (IDDs), and the
acceptance, system, integration, and component test design documents. The
Software Design Description and IDDs are analyzed, reviewed, approved,
baselined, updated as necessary, and placed under configuration management
according to the NuScale Digital I&C Software Configuration Management
Plan. The Software Design Description is also used as input to the ongoing I&C
system safety analyses per the NuScale Digital I&C Software Safety Plan.
Additional outputs of this phase include a SDOE assessment, criticality
assessment update, RTM update, and a software safety analysis. The system
hazards analysis is reviewed when any final system design information or
inputs are revised or changed to determine whether the changes impact the
inputs or results of the hazard analysis. The hazard analysis is updated
according to the process described in Section 7.1.8.3 if the design changes are
determined to impact the existing hazards analysis or if new hazards are
identified according to the NuScale Digital I&C Software Quality Assurance Plan
with the results documented in the software design phase.
The principles applied in the software integration tests are also defined during
this phase to evaluate software performance. Software component and
integration test plans are developed according to the NuScale Digital I&C
Software Master Test Plan.
Software Implementation
The NuScale Digital I&C Software Integration Plan governs both software
implementation and integration tasks performed during the software
implementation phase. During the software implementation phase, the
implementation process transforms the detailed logic requirements into
hardware description language. The functions described in the Software
Design Description are developed in the software development environment
utilizing applicable coding standards (e.g., Hardware Description Language
Specifications and Conventions Guideline). Analysis is performed on the
software to identify potential hazards in accordance with the NuScale Digital
I&C Software Safety Plan.
This phase includes the generation, testing, and assessment of the developed
software including development of component, integration, system, factory
and site acceptance test cases. The purpose of the testing and assessments is to
support development and evaluation of the individual logic components or
units defined during the logic design phase.
Software Configuration
During this phase, the software is integrated with any software from previous
iterations and logic integration testing is performed in accordance with the test
procedures according to the NuScale Digital I&C Master Test Plan. Integration
test execution results are analyzed to determine if the system implements the
requirements and design and that the software components function correctly.
The system hazards analysis is reviewed when any final system design
information or inputs are revised or changed to determine whether the
changes impact the inputs or results of the hazard analysis. The hazard analysis
is updated according to the process described in Section 7.1.8.3 if the design
changes are determined to impact the existing hazards analysis or if new
hazards are identified according to the NuScale Digital I&C Software Quality
Assurance Plan with the results documented in the system testing phase.
Installation and checkout activities are performed when the developed system
is installed in the target environment and location and site acceptance testing
(SAT) is conducted. The installation and checkout V&V activities address system
installation and acceptance and are described in the NuScale Digital I&C
Software Development Plan.
System tests are performed in accordance with the SAT test procedures. Tests
are analyzed to determine if the system implements the system design
requirements and that the software components function correctly together.
Test results are analyzed to determine if the software satisfies system
objectives. Tests pass or fail based on the acceptance criteria stipulated in the
test plans and based on specific requirements found in the system
requirements documentation. The system hazards analysis is reviewed when
any final system design information or inputs are revised or changed to
determine whether the changes impact the inputs or results of the hazard
analysis. The hazard analysis is updated according to the process described in
Section 7.1.8.3 if the design changes are determined to impact the existing
hazards analysis or if new hazards are identified according to the NuScale
Digital I&C Software Quality Assurance Plan with the results documented in the
system installation phase.
The operation phase covers the operation of the developed and installed
system in the target environment and location. The objectives of operation
V&V tasks are to evaluate new constraints in the system, assess proposed
changes and the impact on the software, and evaluate operating procedures
for correctness and usability.
The NuScale Digital I&C Software Development Plan describes the activities employed
in the development of I&C system software. The development activities are adjusted
based on the software classification that is based on the SIL scheme defined in the
NuScale software classification procedure. This procedure governs the criticality
analysis performed to determine the SIL level of the software necessary to accomplish
the safety functions and requires that functions of lower SIL levels that support a
system safety function are reclassified to the highest SIL level appropriate for the
supported system safety function. In the application of different FPGA technologies
within the MPS, the software development activities are the same; they do not
differentiate between different FPGA technologies.
The Software Safety Analysis Report constitutes a configuration item and is placed
under configuration management, for which change control is documented
pursuant to the NuScale Digital I&C Software Configuration Management Plan.
For SIL 3 and 4, an independent V&V team performs a V&V of the digital I&C System
Requirements Specification in accordance with the NuScale Digital I&C Software
Verification and Validation Plan. For SIL 1 and 2, an independent verifier within the
engineering team performs this function. Anomalies identified during the V&V
process are documented in a V&V anomaly report and reported to the software
development team. All anomalies must be satisfactorily resolved prior to issuing a
V&V task report pursant to the NuScale Digital I&C Verification and Validation Plan.
The system design documentation documents the system architecture and design
details and uses the system requirements documentation and safety analysis
requirements as inputs. The system design documentation is analyzed, reviewed,
approved, baselined, updated as necessary, and placed under configuration
management. Bi-directional traceability is established between the system design
documentation and the system requirements documentation. The system design
documentation is also used as input to the ongoing system safety analyses per the
NuScale Digital Safety System Safety Plan.
The ERS is based on the system requirements documentation, the system design
documentation, and prototype lessons learned as inputs.
For SIL 3 and 4 software, an independent V&V team performs a V&V of the Software
Requirements Specification in accordance with the NuScale Digital I&C Software
Verification and Validation Plan. For SIL 1 and 2 software, an independent verifier
within the engineering team performs this function. Anomalies identified during
the V&V process are documented in a V&V anomaly report and reported to the
software development team. All anomalies must be satisfactorily resolved prior to
issuing a V&V task report pursant to the NuScale Digital I&C Verification and
Validation Plan.
The design of the software module is restricted to one clearly identified function
that involves minimum interaction with other functions to minimize the impact of
changes. The interfaces between the various units are simple, completely
identified, and documented.
The NuScale Digital I&C Software Development Plan requires that an assessment of
the software design is performed to ensure the software design adequately covers
the requirements in the Software Requirements Specification and does not contain
unnecessary software, complex programmable logic, or functions. The software
design is assessed to:
The NuScale Digital Safety System SDOE Plan requires that vulnerability
assessments be performed on software and complex programmable logic that is
developed and classified as SIL 4. The vulnerability assessments evaluate that the
design configuration items of the secure development environment are reviewed
to ensure they are correctly translated from the system design specification and are
correct, accurate, and complete. Details of the NuScale Secure Development
Environment are described in Section 7.2.9.1.
The NuScale Digital I&C Software Quality Assurance Plan and the NuScale Digital
I&C Software Verification and Validation Plan govern the use of support software
and tools (e.g., software and hardware description language code generating tools,
software compilers, software assemblers, software operating systems, software or
Complex Logic Device logic coverage analyzers). The NuScale Digital I&C Software
Configuration Management Plan governs the process for controlling code change
requests and modifications.
For SIL 3 and 4, an independent V&V team performs a V&V of the Digital I&C
Software Design Description in accordance with the NuScale Digital I&C Software
Verification and Validation Plan. For SIL 1 and 2 software, an independent verifier
performs this function. Anomalies identified during the V&V process are
documented in a V&V anomaly report and reported to the software development
team. All anomalies must be satisfactorily resolved prior to issuing a V&V task
report pursant to the NuScale Digital I&C Verification and Validation Plan.
The NuScale Digital I&C Software Integration Plan governs both software
implementation and integration tasks performed during the software
development life cycle. The detailed design within the Software Design Description
is translated into computer code in the selected programming language, whether a
standard software language for typical source code or hardware description
language for a Complex Logic Device. The code capability of executing the safety
design features and methods developed during the software design process is
confirmed and is documented within the Software Design Description and
Software Safety Analysis Report.
The code is confirmed using the coding rules, methods, standards, and other
applicable criteria of the NuScale Software Coding and Hardware Description
Language Coding Guidelines. Alternatively, a Software Coding Conventions and
Guidelines Document developed specifically for the product being coded may be
used so long as the following top level attributes of software safety are satisfied for
SIL 3 and 4 software or Complex Logic Device logic:
• reliability
• robustness
• traceability
• maintainability
The software code or Complex Logic Device logic is designed to facilitate analysis,
testing and readability.
For SIL 3 and 4 software, an independent V&V team performs a V&V of the software
or Complex Logic Device logic in accordance with the NuScale Digital I&C Software
Verification and Validation Plan. For SIL 1 and 2 software, an independent verifier
performs this function. Anomalies identified during the V&V process are
documented in a V&V anomaly report and reported to the software development
team. All anomalies must be satisfactorily resolved prior to issuing a V&V task
report pursant to the NuScale Digital I&C Verification and Validation Plan.
The software or Complex Logic Device logic is baselined, updated as necessary, and
placed under configuration management in accordance with the NuScale Digital
I&C Software Configuration Management Plan.
The NuScale Digital l&C Software Master Test Plan governs the generation of the
following test documents in the implementation phase of the software life cycle:
• component test case
• integration test case
• system test case
• factory acceptance test (FAT) and SAT cases
• component test procedure
• integration test procedure
• system test procedure
• component test report
For SIL 3 and 4 software or Complex Logic Device logic, a test engineer from within
an independent V&V team performs component level testing. For SIL 1 and 2
software or Complex Logic Device logic, a test engineer from within the
engineering team performs the testing.
Complex Logic Device logic component testing includes but is not limited to the
following:
• function simulation
• static analyses
• gate-level simulation
• timing simulation
• static timing analysis
− failure testing
For SIL 3 and 4 software or Complex Logic Device logic, in order to maintain the
required technical, managerial, and financial independence from the developer of
the test documentation (i.e., a test engineer within the V&V team), an independent
verifier within the engineering team performs V&V of the test documents and
records the same on corresponding V&V task reports pursuant to the NuScale
Digital I&C Software Verification and Validation Plan.
The test documents are baselined, updated as necessary, and placed under
configuration management in accordance with the NuScale Digital I&C Software
Configuration Management Plan.
The NuScale Digital l&C Software Master Test Plan governs the generation of the
following test documents in the test phase of the Software Life Cycle:
• factory acceptance test (FAT) and site acceptance test (SAT) test procedures
• integration test report
• system test report
• FAT report
For SIL 3 and 4 software or Complex Logic Device logic, a test engineer from an
independent V&V team:
• develops the test documentation listed above
• conducts software integration testing to verify that software requirements
have been adequately implemented for this phase of the software life cycle
• compares integration test results to the requirements in the Digital I&C
Software Requirements Specification and Interface Requirements Specification
to ensure satisfaction of requirements.
• identifies and resolves discrepancies between actual and expected results in
integration testing.
• ensures that the integrated software or Complex Logic Device logic modules
have successfully passed integration testing and that the software system is
integrated with applicable hardware systems.
• conducts system testing on a complete, integrated system to evaluate system
performance based on the I&C system requirements from the System
Requirements Specification and system design documentation.
• ensures the detection of any inconsistencies between the software or Complex
Logic Device logic and the hardware.
• documents system test results and analyzes test results to verify that digital I&C
system requirements from the have been satisfied.
• demonstrates that hazards identified in the Software Safety Analysis Report
have been eliminated or controlled to an acceptable level of risk and ensures
For SIL 3 and 4 software or Complex Logic Device logic, an engineer from the
engineering team performs V&V of the test documents developed by the V&V team
and documents the results on corresponding V&V task reports pursuant to the
NuScale Digital I&C Software Verification and Validation Plan. For SIL 1 and 2
software or Complex Logic Device logic, an independent verifier within the
engineering team performs the V&V of the test documents developed by the test
engineer from the engineering team and documents the results.
The test documents are baselined, updated as necessary, and placed under
configuration management in accordance with the NuScale Digital I&C Software
Configuration Management Plan.
A digital I&C system installation and site test plan is used that documents the
methods by which the I&C safety system is installed and connected to other plant
systems. The engineering team ensures that the system installation plan describes
the following:
• procedures
− software installation
− combined hardware and software installation
− systems installation
• confirmation measures
− computer system is functional
− sensors and actuators are functional and the required cards are present and
installed in the correct slots (when applicable)
− communication system is correctly installed
− correct software versions (i.e., consistent with the versions used for final
system testing) are installed on the correct digital I&C system
For SIL 3 and 4 software or Complex Logic Device logic, a team performs V&V of the
installation package and documents the results on corresponding V&V task reports
pursuant to the NuScale Digital I&C Software Verification and Validation Plan. For
SIL 1 and 2 software or Complex Logic Device logic, an independent verifier within
the engineering team does the V&V and documents the results.
The completed system installation results are documented and used as input to the
ongoing I&C system safety analysis activity.
The SAT demonstrates that the installed system performs in accordance with the
system design basis. The NuScale Digital l&C Software Master Test Plan governs the
generation of the Site Acceptance Test Report.
For SIL 3 and 4 software or Complex Logic Device logic, the independent V&V team
works with the licensee to ensure that SAT demonstrates that the installed system
performs the safety function described in the system design basis. For SIL 1 and 2
software or Complex Logic Device logic, the engineering team SAT demonstrates
that the installed system performs the safety function described in the system
design basis.
The SAT report is baselined, updated as necessary, and placed under configuration
management in accordance with the NuScale Digital I&C Software Configuration
Management Plan. The final V&V report is prepared prior to turning the system
over to the plant licensee.
COL Item 7.2-1: A COL applicant that references the NuScale Power Plant design certification is
responsible for the implementation of the life cycle processes for the operation
phase for the instrumentation and controls systems, as defined in Institute of
Electrical and Electronics Engineers (IEEE) Std 1074-2006 and IEEE Std 1012-2004.
COL Item 7.2-2: A COL applicant that references the NuScale Power Plant design certification is
responsible for the implementation of the life cycle processes for the maintenance
phase for the instrumentation and controls systems, as defined in Institute of
Electrical and Electronics Engineers (IEEE) Std 1074-2006 and IEEE Std 1012-2004.
COL Item 7.2-3: The NuScale Digital instrumentation and controls (I&C) Software Configuration
Management Plan provides guidance for the retirement and removal of a software
product from use. A COL applicant that references the NuScale Power Plant design
certification is responsible for the implementation of the life cycle processes for the
retirement phase for the instrumentation and controls systems, as defined in
Institute of Electrical and Electronics Engineers (IEEE) Std 1074-2006 and IEEE Std
1012-2004. The NuScale Digital I&C Software Configuration Management Plan
provides guidance for the retirement and removal of a software product from use.
The digital I&C safety system development life cycle is implemented using the
following key documents:
• Digital Safety Systems Project Plan
• Digital Safety Systems Safety Plan
• Digital I&C Software Management Plan
• Digital I&C Software Development Plan
• Digital l&C Software Quality Assurance Plan
• Digital l&C Software Verification and Validation Plan
• Digital l&C Software Master Test Plan
• Digital l&C Software Configuration Management Plan
• Digital I&C Software Requirements Management Plan
• NuScale Digital I&C Software Integration Plan
• NuScale Digital I&C Software Installation Plan
• NuScale Digital I&C Software Training Plan
These documents define the key development activities and sequences, management
responsibilities, and necessary support activities.
The Digital I&C Software Management Plan, in conjunction with the overall Project
Management Plan provides the framework for development of the project schedule,
including major milestones and baseline reviews at each phase of the software life
cycle, work products and project deliverables at each phase of the software life cycle.
The NuScale Digital I&C Software Quality Assurance Plan and Software Management
Plan address the aspects of risk management and development tools.
The NuScale Digital I&C Software Management Plan implements the requirements for
overall management of the I&C system design and development project life cycle. The
major project functions in the Software Management Plan include:
• Overall I&C project management
• Development of the Digital I&C software planning documents
• Development of System and Software Requirements Specifications and Design
• Descriptions by the design engineering team
• Performance of hazards analysis, and SDOE vulnerability assessments by the
Independent V&V design engineering teams respectively
• Coordination of risk analysis by the independent V&V test engineer with
generation or update of the project risk register by the project manager
• Development of software and CLD logic by the design engineering team
The NuScale Digital I&C Software Verification and Validation Plan address the aspects
of quality metrics. For additional details regarding risk management, quality metrics,
and the control of software tools, see the discussion of RG 1.28, Revision 4, RG 1.152,
Revision 3, and IEEE Std 7-4.3.2-2003 in Section 7.2.1.
For software QA, see the discussion of RG 1.28, Revision 4, RG 1.152, Revision 3, and IEEE
Std 7-4.3.2-2003 in Section 7.2.1.
For the software V&V process, see the discussion of RG 1.152, Revision 3, and IEEE Std
7-4.3.2-2003 in Section 7.2.1.
For software audits, see the discussion of RG 1.168, Revision 2, IEEE Std 1012-2004, and
IEEE Std 1028-2008 in Section 7.2.1.
For the software configuration management process, see the discussion of RG 1.152,
Revision 3, and IEEE Std 7-4.3.2-2003 in Section 7.2.1, as well as the discussion of RG
1.169, Revision 1, and IEEE Std 828-2005 in Section 7.2.1.
The safety I&C SSC are designed to perform their safety-related functional requirements
over the range of environmental conditions postulated for the area in which the
components are located and during the time period when this performance is required.
The NuScale I&C systems equipment qualification meets the criteria contained in Section
5.4 of IEEE Std 7-4.3.2-2003, and the requirements of Section 5.4 of IEEE Std 603-1991. The
equipment qualification meets the guidance contained in RG 1.209 and RG 1.151,
Revision 1.
The information in this section satisfies the application specific information requirements
in TR-1015-18653-P-A listed in Table 7.0-2 for ASAI numbers 17, 18, and 23.
Protection from natural phenomena for the MPS and NMS-excore processing
electronics is provided by the location of the MPS and NMS-excore cabinets in the
reactor building on the 75'-0" and 86'-0" elevations (Figures 1.2-14 and Figure 1.2-15,
respectively) which is a Seismic Category I, reinforced concrete structure. This location
is remote from the NMS-excore detectors and in a mild environment which provides
protection for the processing electronics portion of the NMS-excore detectors.
Separation Groups A, C, and Division I of the reactor trip system (RTS), engineered
safety features actuation system (ESFAS) and Separation Groups A and C NMS-excore
signal processing equipment are in one room, and separation groups B, D, and Division
II of the RTS, ESFAS and Separation Groups B and D NMS-excore equipment are located
in a different room.
The Reactor Building and Control Building arrangement and design enable systems
and components required for safe plant operation and shutdown to withstand or to be
protected from the effects of sabotage, environmental conditions, natural phenomena,
postulated design-basis accidents, and design-basis threats. The Reactor Building and
the Control Building (at and below elevation 120’-0”) are Seismic Category I, reinforced
concrete structures, except as noted in Section 1.2.2.2. See Section 3.2 for more details
on the design of the reactor and control buildings.
The MPS is an FPGA-based system, which does not use software in a traditional manner;
therefore, there is no software which executes while the system is in operation.
However, FPGAs are programmed, and qualification testing is performed in accordance
with IEEE Std 7-4.3.2-2003 (see Section 7.2.1).
The NMS-excore contains sensors and analog signal processing equipment and is not a
digital computer system; therefore, the requirements of IEEE Std 7-4.3.2-2003 do not
apply.
The MPS equipment and cabling are designed in accordance with the NuScale fire
protection design criteria described in Section 9.5.1. Separation Groups A, C, and
Division I of the RTS and ESFAS and Separation Groups A and C NMS-excore signal
processing equipment are located in one room and Separation Groups B, D, and
Division II of the RTS, ESFAS and Separation Groups B and D NMS-excore equipment are
located in a different room; the rooms are located in two different fire zones. MPS and
NMS-excore cables are required to pass the flame test as required in IEEE Std 1202-2006
(Reference 7.2-28) as endorsed by RG 1.189.
The MPS equipment and cable routing is designed to meet the separation
requirements of IEEE Std 384-1992 "IEEE Standard Criteria for Independence of Class 1E
Equipment and Circuits" (Reference 7.2-10) as endorsed by RG 1.75, Rev 3. These design
attributes also provide separate rooms and cable runs to prevent a fire or explosion
from affecting more than one division of MPS and NMS-excore equipment. See
Section 9.5.1.2.
The MPS manual trip/actuate, operating bypass, and enable nonsafety control switches
are located in the main control room (MCR).
The reactor trip breakers (RTBs) and the pressurizer heater trip breakers are located in
the associated MPS division room.
In the event of a fire in the MCR the operators trip the reactors, initiate decay heat
removal and initiate containment isolation prior to evacuating the MCR. These actions
result in passive cooling that achieves and maintains the modules in a safe shutdown
condition. Operators can also place the reactors in safe shutdown from outside the
MCR in the MPS equipment rooms within the reactor building. The operators then
relocate to the remote shutdown station (RSS) to monitor plant conditions. Following
shutdown and initiation of passive cooling, the NuScale design does not rely on
operator action, instrumentation, or controls outside of the MCR to maintain a safe
stable shutdown condition. There are two MCR isolation switches for each NuScale
Power Module (NPM) in the RSS that when repositioned isolate the MPS manual
actuation switches, override switches and enable nonsafety control switches for each
NPM's MPS in the MCR to prevent spurious actuation of equipment due to fire damage.
The MPS and NMS-excore equipment is designed and qualified in accordance with the
guidance provided in RG 1.180 for compliance with NRC regulations regarding
electromagnetic interference (EMI) and radio frequency interference (RFI) and power
surges on safety-related I&C systems. Regulatory Guide 1.180 provides several
acceptable methods for addressing electromagnetic compatibility consideration for
qualifying safety-related I&C systems for the expected electromagnetic environment in
nuclear power plants. The EMI and RFI, surge withstand capabilities, and operating
envelopes are elements of the total package that is needed to ensure electromagnetic
compatibility within a NuScale Power Plant.
The safety-related sensors associated with the NuScale reactor design are described in
NuScale Power, LLC, TR-0316-22048 "Nuclear Steam Supply Systems Advanced Sensor
Technical Report," (Reference 7.2-26). The sensors that utilize instrument sensing lines
are pressurizer pressure narrow range, reactor coolant system pressure wide range,
main steam pressure, feedwater outlet pressure and DHRS outlet pressure. For these
sensors, the instrument sensing lines are designed in accordance with
ISA-67.02.01-1999 "Instrument Sensing Line Piping and Tubing Standards for Use in
Nuclear Power Plants" (Reference 7.2-24), as endorsed by RG 1.151. More detailed
information is provided in technical report TR-0316-22048 on sensor functions, sensor
requirements, sensor design, sensor installation, sensor maintenance, and sensor
qualification.
This section discusses the reliability and integrity of the NuScale I&C systems, and the
ability to complete a protective action once initiated to accomplish the safety functions.
The design of the NuScale I&C systems meets the reliability, system integrity, and
completion of protective action criteria contained in Sections 5.5 and 5.15 of IEEE Std
7-4.3.2-2003, and the requirements of Sections 5.2, 5.5, 5.15 and 7.3 of IEEE Std 603-1991.
The information in this section satisfies the application specific information requirements
in TR-1015-18653-P-A listed in Table 7.0-2 for ASAI numbers 15, 18, 19, and 37.
The majority of the MPS hardware is developed and constructed using FPGA logic that
does not require the use of a central processing unit or an operating system as found in
most other digital instrumentation. The remaining hardware for the MPS is developed
and constructed using discrete analog components. The FPGA logic elements are
arranged in an array of open connections. This can be compared to a series of similar
but unconnected discrete logic elements on a breadboard, where the functionality of
the overall circuit is undetermined until the connections are made. The FPGA also
contains a series of reconfigurable interconnects that allow the logic elements to be
"wired together."
The NuScale Software QAP described in Section 7.2.1 establishes the QA requirements
applied to development of the hardware description language that is used to configure
and implement the FPGA logic within the MPS. Due to the potential for programming
errors for both hardware description language programming and traditional
programming, a well-defined, high-quality design process, and the rigorous V&V effort
described in Section 7.2.1 provide reasonable assurance that the resulting system
performs the associated safety function in a predictable and reliable manner.
Qualitative reliability goals have been established for the MPS to meet the single failure
criterion. The MPS meets the qualitative reliability goals and the requirements of IEEE
Std 379-2000 "IEEE Standard Application of the Single-Failure Criterion to Nuclear
Power Generating Station Safety Systems" (Reference 7.2-9) to satisfy the single failure
criterion through the addition of redundancy (see Section 7.1.3), diversity (see
Section 7.1.5) and testability (see Section 7.2.15). The MPS remains functional in the
presence of a single failure. An MPS hazard analysis was also performed using the
methodology described in Section 7.1.8 to evaluate potential hazards from connected
systems and establish safety constraints to meet the qualitative reliability goals
established for the system. There are no failure modes that are undetectable or prevent
the MPS from performing its RTS, ESFAS and post-accident monitoring (PAM) functions.
The NMS is an analog system, there is no software used in the runtime environment.
Qualitative reliability goals have been established for the NMS to meet the single
failure criterion. The NMS meets the qualitative reliability goals and the requirements of
IEEE Std 379-2000 to satisfy the single failure criterion and the NMS remains functional
in the presence of a single failure. The NMS hazard analysis (see Section 7.1.8) was also
performed to evaluate potential hazards from connected systems and establish safety
constraints to meet the qualitative reliability goals established for the system. Failures
resulting in a loss of neutron flux information can be identified through anomalous
indication, alarms in the MCR, or periodic testing. There are no failure modes in the
NMS that are undetectable or prevent the NMS from performing its required safety
functions.
The MPS maintains the capability to initiate protective functions during and following
anticipated operational occurrences (AOOs), postulated accidents, and design basis
events (DBEs) resulting from natural external phenomena such as earthquakes,
tornadoes, hurricanes, floods and winds. The functional capability of the system is
maintained during internal events such as fires, flooding, explosions, missiles, electrical
faults, and pipe whip. The equipment is environmentally and seismically qualified in
accordance with RG1.209 and IEEE Std 323-1974 as described in Section 7.2.2.
air conditioning (HVAC) in the area for a minimum of 72 hours, coincident with AOOs
and postulated accidents. The MPS equipment is designed to meet the normal and
abnormal environmental conditions as described in Section 3.11 and Appendix 3C.
The design of the MPS is based on FPGA technology. The MPS platform is designed
with redundancy and embedded self-test capability to ensure system integrity by
detecting and alarming faults in the MCR. Diagnostics and testing capabilities are
designed into the MPS platform to ensure there is a systematic approach to
maintaining and testing the system, see Section 7.2.15.
The MPS platform implements advanced failure detection and mitigation to ensure
system or component failures do not remain undetected. The operation of the system
is deterministic in nature and allows the system to monitor in order to validate
functional performance. The MPS is designed such that it can be tested and calibrated
while retaining the capability to accomplish the required safety functions. Testing from
the sensor inputs to the MPS through the actuated equipment is accomplished
through a series of overlapping sequential tests with the majority of the tests capable
of being performed with the plant at full power. Where testing final equipment at
power has the potential to upset plant operation or damage equipment, provisions are
made to test the equipment at reduced power or when the reactor is shut down.
Periodic surveillance testing capability is incorporated to ensure that functional tests
and checks, calibration verification, and time response measurements are validated.
Periodic surveillance testing of sensors that are part of the MPS is performed in accord
with the plant technical specifications.
Diagnostics data for the separation group and division of the MPS are provided to the
maintenance workstation (MWS). The MWS is located close to the equipment to
facilitate troubleshooting activities. The interface between the MPS and the MWS is an
optically-isolated, one-way diagnostic interface connected to the calibration and test
bus that is used to update tunable parameters. The calibration and test bus is
configured as a one-way, receive-only interface. Diagnostics data are communicated
via the monitoring and indication bus (MIB) which is a physically separate, isolated
communications path from the safety data communication paths associated with the
MPS safety functions (e.g., the safety data bus), thereby ensuring the diagnostics
functionality is independent of the safety functionality. The diagnostic data comes
across the MIB communications module via a one-way transmit-only connection
through the MPS gateway to the MWS.
The MPS is designed such that in the event of a condition such as a system
disconnection or loss of power, it fails into a safe state. The equipment interface
module (EIM) outputs are designed to remove power to the final actuation devices
causing them to go to a safe-state (e.g., reactor trip breakers open, ECCS valves open).
This ensures that a loss of power or other detected fault that causes the EIM to go into a
faulted state also causes the interface to remove power to the final actuated device.
The NMS operates throughout normal reactor operation and provides PAM data to the
MPS during and after a DBE. Failures of the NMS equipment are identified through
system health monitoring of the NMS detectors and signal processing equipment.
Periodic surveillance testing is performed on the NMS in accordance with the plant
technical specifications. Failure of NMS-excore components generate a fault signal and
an actuate/trip signal for that particular NMS-excore channel. The fault signal is
transmitted to the MPS for display to the control room operators.
The NMS incorporates four redundant sets of detectors that are completely
independent so that a failure in one redundant channel does not affect the other three.
The MPS is designed such that once a protective action is initiated, either automatically
or manually, the sequence of protective actions continues until it has reached
completion.
Seal-in of ESFAS actuation logic is provided at the EIM to account for transient process
conditions that may change during a DBE (e.g., containment pressure). This seal-in
prevents logic and final actuated devices from returning to the non-trip or non-
actuated state due to changing process conditions. Seal-in is also provided at the EIM
for the RTS actuation logic functions. The reactor trip function is inherently latched by
removing electrical power from the control rod drive mechanisms causing the control
rods to fall into the reactor core by gravity.
Deliberate operator action is required to change the state of actuated equipment and
return the MPS to a normal configuration. The operator uses the enable nonsafety
control switch and the MCS to place components in their normal configuration. The
APL circuit controls the manual control of components using the MCS as described
below.
The APL circuit is designed to give priority to safety-related RTS and ESF signals over
nonsafety-related signals in all modes of operation. The APL circuit does not contain
digital technology; it is constructed of discrete logic components and functions
separately from the FPGA logic within the EIM.
2) Manual reactor trip or ESF actuation signals from its own divisional manual
actuation switches in the main control room.
3) Enable nonsafety control switch and nonsafety-related control input signals from
the module control system. If the enable nonsafety control switch is not active (i.e.,
nonsafety-related inputs are disabled), the nonsafety-related control signal is
ignored.
The actuation priority logic evaluates these signals, and generates and provides output
signals to the EIM to actuate or trip the final actuation devices based on the logic
described in this section.
In all cases, the highest priority is given to the automatic and manual RTS and ESFAS
actuation signals. As shown in Figure 7.1-1k through 7.1-1an, these actuation signals
have equal, highest priority; they are differentiated only by the sequence by which they
are received by the APL circuit, such that the first active signal received is used to
generate the output.
If an automatic or manual RTS or ESF actuation signal is active, these signals have the
highest logic priority; the RTS and ESF signals are processed and an actuation
command is sent directly to the EIM output to actuate or trip the final actuation device.
In all cases, the position of the enable nonsafety control switch does not matter. The
enable nonsafety control switch does not impede the handling and evaluation of
active automatic or manual RTS or ESF actuation signals as these are processed at the
highest logic priority.
If the nonsafety control inputs are disabled by the enable nonsafety control switch,
then nonsafety control inputs are rejected and not processed by the APL circuit.
For cases when the enable nonsafety control switch is enabled to allow nonsafety
control inputs, there must be no active RTS or ESF manual or automatic signal present.
If the enable nonsafety control switch is enabled, and there is no RTS or ESF signal, then
the nonsafety manual control inputs from the MCS are used by the APL circuit to
control the final component (e.g., containment isolation valve).
During the time the nonsafety control inputs are enabled, if an automatic or manual
RTS or ESF signal is generated and received by the APL circuit, the actuation priority
logic immediately disables the enable nonsafety control logic input and rejects all
nonsafety control inputs. The actuation priority logic circuit processes the RTS or ESF
command to position the final actuation device to its safe state.
The actuation priority logic is based on discrete logic which allows for testing of
possible combinations of inputs and the evaluation of the associated outputs.
An operating bypass is provided for certain protective actions when they are not necessary
in a particular mode of plant operation. Different modes of plant operation may necessitate
an automatic or manual bypass of a safety function. Operating bypasses are used to permit
mode changes. A maintenance bypass is provided to bypass safety system equipment
during maintenance, testing, or repair. A maintenance bypass may reduce the degree of
redundancy of equipment, but it does not result in the loss of a safety function. Operating
and maintenance bypasses are described in the following sections.
The MPS operating and maintenance bypasses conforms to Sections 5.8, 6.6, 6.7, 7.4 and
7.5 of IEEE Std 603-1991 and the guidance contained in RG 1.47, Revision 1. The display of
bypassed and inoperable status information is described in Section 7.2.13 which conforms
to 10 CFR 50.34(f)(2)(v).
The information in this section satisfies the application specific information requirements
in TR-1015-18653-P-A listed in Table 7.0-2 for ASAI numbers 7, 42, 43, and 45.
The MPS includes interlocks, permissives, and operational and maintenance bypasses
that prohibit or permit certain protective actions either automatically or through a
combination of automatic and manual actions to allow plant mode changes.
The MPS logic automatically prevents the activation of an operating bypass or initiates
the appropriate safety function(s) when permissive or interlock conditions for the
operating bypass are not met. The operating bypass circuits contain both permissive
features that allow a protective function to be bypassed when the function is not
required and interlock features that automatically activate an operating bypass when
conditions are met. When permissive and interlock conditions are no longer met,
operating bypasses are automatically deactivated.
Operating bypasses are required to allow changing plant modes and provide operator
control of certain functions based on safety analysis or plant operations. The operating
bypasses for MPS functions, interlocks, and permissives are shown in Table 7.1-5. These
bypasses either automatically or manually block certain protective actions that
otherwise prevent mode changes during plant operation (e.g., plant startup). The
operating bypasses are automatically removed when the plant moves to an operating
condition where the protective action is required to be operable. Indication is provided
in the control room if some part of the system has been bypassed or taken out of
service. The operating bypasses are also shown on the MPS functional logic diagrams in
Figure 7.1-1b through Figure 7.1-1i.
Manual operating bypasses have two switches, one per division. The only manual
operating bypasses used for the NuScale design use a permissive in conjunction with
the manual bypass in order to achieve the function of the bypass.
The postulated failures of the operating bypass switches were evaluated, as described
in Section 7.1.3. The operating bypass switches are momentary-contact switches and
will normally be open and only closed momentarily to enact an operating bypass
function.
In the identified events evaluated, the failures are limited to one of two MPS divisions.
The other MPS division is fully operable and capable of performing the safety function
and no single failure disables a safety function. Inadvertent bypasses of a safety
function are limited to one MPS division. The other MPS division is able to perform the
required safety function.
For automatic and manual operating bypasses, a trip determination is used for the
permissive or interlock from the separation group and is similar to the trip
determination for a protective action. A three-out-of-four coincidence is used to
determine when an operating bypass is warranted. To remove the operating bypass,
two-out-of-four of the separation groups are needed to determine that the permissive
or interlock is no longer valid and the operating bypass is automatically reset.
MPS variables are monitored by four redundant channels which actuate the protective
functions utilizing two-out-of-four coincident logic. This configuration allows required
safety functions to remain operable in the event of a single random failure of a
protection channel concurrent with a channel in maintenance bypass.
The MPS is designed to permit the administrative bypass of a protection channel for
maintenance, test, or repair. Indication is provided in the control room if an MPS
channel has been administratively bypassed or taken out of service. The time period
allowed for removal from service in maintenance bypass is administratively controlled
by the plant technical specifications.
To perform maintenance on the MPS, there are two associated switches: a trip/bypass
switch associated with each SFM and an out of service switch on the front of the SFM to
allow removal of the SFM from service for maintenance and repair. With the out of
service switch activated, the safety function is placed in trip or bypass based on the
position of the trip/bypass switch for that SFM. Activating the out of service switch
permits modification of the tunable parameters and setpoints in nonvolatile memory
via the MWS. The trip bypass switch status input is received through the hard-wired
module (HWM) which converts the switch position into a logic level signal and places
this information onto the backplane.
The data packet received from the SFM contains the position of the out of service
switch on the SFM. The scheduling and bypass module (SBM) determines if the SFM is
out of service from the out of service switch position information received in the data
packet from the SFM. If the SFM is out of service and the trip/bypass switch is in bypass,
the SBM transmits a non-actuate or no-trip condition to the schedule and voting
module (SVM) regardless of the output of the SFM. There is no change to the 2-out-of-4
voting coincidence logic; with one separation group providing a no trip to the SVM,
requiring two of the remaining three channels received by the SVM to vote to
trip/actuate. In this case, the MPS is still capable of performing the safety function with
the required level of redundancy and continues to meet the single failure criteria.
If the SFM is out of service and the trip/bypass switch is in trip, the SBM transmits a
trip/actuate signal to the SVM regardless of the output of the SFM. There is no change
to the 2-out-of-4 voting coincidence logic. The SBM forces one channel to trip/actuate;
with one separation group providing a trip/actuate input to the SVM, requiring one
other separation group to issue a vote to trip/actuate to cause a trip/actuate to occur
for the particular safety function. In this case, the MPS is in a "partial trip" condition, but
still meets the single failure criteria and is capable of performing the safety function
with the required level of redundancy.
The maintenance trip/bypass switches are located on a panel in the separation group
cabinets located in the MPS equipment rooms. The switches are connected to the
HWM in the SFM chassis (See Figure 7.0-4).
If the SFM is not out of service, the SBM transmits the safety function algorithm result
that was calculated and transmitted from the SFM to the SBM.
If the SBM does not receive a valid response from the SFM, an alarm is generated and
the SBM uses the position of the trip/bypass switch to determine what to transmit to
the SVM.
Using the out of service function of the SFM allows for periodic parameter updates of
certain tunable parameters during an outage and during the fuel cycle. Periodic testing
is required to verify operability of the safety function.
The MPS is designed to allow periodic and corrective maintenance during normal
operation and during outages. For maintenance to be performed, the safety function
must be removed from service. The affected channel is placed in a trip condition or
bypass subject to technical specification limitations.
Safety functions within a separation group can be taken to bypass or trip for testing or
corrective maintenance. The RTS and ESFAS divisions do not have bypass functionality;
however the modules have continuous self-testing coverage. The reactor trip breakers
can be tested at power because of the breaker configuration by opening one breaker at
a time. This allows for reactor trip breaker testing without the need for a maintenance
bypass associated with the reactor trip breakers. Most of the ESFAS components are
not tested at power since they cause a trip or engineered safety feature (ESF) actuation
and need to be tested during an outage. The manual trip and actuate switches in the
MCR cannot be tested at power and are tested during shutdown conditions in
accordance with plant technical specifications.
Four reactor trip breakers are associated with each of two divisions of the MPS. The
MPS divisions are configured so that opening a single division of breakers de-energizes
the control rod drive mechanisms, thus causing the reactor trip (See Figure 7.0-6).
During testing of the trip actuation logic, the trip signals to the undervoltage trip
mechanism of the reactor trip breakers are not actuated. The MPS is designed to permit
overlapping online testing of MPS logic and reactor trip breakers.
The part of MPS that is not tested at power is the actuation priority logic circuit on the
EIM. This includes the manual MCR switches and the enable nonsafety control switch
that provide inputs to the actuation priority logic. The actuation priority logic consists
of discrete components and directly causes actuation of field components that cause
the reactor to shutdown or adversely affect operation. The actuation priority logic is
tested when the reactor is shut down. Due to the simplicity of the actuation priority
logic circuit, testing during shutdown conditions is sufficient to ensure the actuation
priority logic function performs as required.
For maintenance bypass purposes, the NMS is treated as a sensor input into the MPS
where the MPS provides the bypass capability for maintenance purposes.
Indication is provided in the control room if an MPS channel has been administratively
bypassed or taken out-of-service. The time period allowed for removal from service in
maintenance bypass is administratively controlled by the technical specifications.
The MPS conforms to the guidance in RG 1.47, revision 1. The MPS equipment status
information is automatically sent to the MCS and SDIS. The MCS and SDIS will provide
the operator with continuous indication of bypass, trip, and out of service status. The
display of the status information allows the operator to identify the operability of the
safety functions. The capability to manually activate the bypass indication in the
control room is provided by the MCS.
7.2.5 Interlocks
Interlocks ensure the reactor trip and engineered safety feature actuations are in the
correct configuration for the current plant status. They ensure protection system functions
are available and operational during plant conditions under which the interlocks are
assumed to function in the plant safety analyses.
The design of MPS interlocks conforms to the requirements of IEEE Std 603-1991.
Computer-based interlocks conform to the requirments of IEEE Std 7-4.3.2-2003.
The I&C interlocks performed within the MPS are summarized in Table 7.1-5. The I&C
interlocks used to maintain the ESFAS variables within the ranges of values specified in
the safety analyses are summarized in Table 7.1-5.
The MPS interlocks and operating bypasses are implemented within the individual
divisions, which ensures that the applicable requirements of IEEE Std 603-1991 for
redundancy, independence, satisfaction of the single failure criterion, qualification,
bypasses, status indication, and testing are met.
NMS sensors and signal processing equipment are used to provide signal inputs for
reactor trip functions and MPS interlocks. The NMS equipment used to provide the MPS
functions meet the NMS single failure requirements.
The MPS interlocks are compatible with the functions and performance assumed in the
events analyzed in Chapter 15.
The emergency core cooling system (ECCS) valves contain an inadvertent actuation
block feature which minimizes the probability of a spurious opening of an ECCS valve
at operating pressure (see Section 6.3). In the unlikely event of an inadvertent signal
from MPS to actuate the ECCS valves at nominal plant pressure, the valves will not open
until a sufficiently low differential pressure between the reactor pressure vessel and the
containment vessel is reached. This allows the operator to respond to the inadvertent
signal without the opening of the ECCS valves and the resulting plant transient.
Plant conditions during a valid ECCS actuation per the nominal trip setpoint should
allow the ECCS valves to open when the inadvertent actuation block interlock is
satisfied. If plant conditions do not allow the inadvertent actuation block interlock to
be satisfied, the completion of the ECCS protective action will not occur until the
inadvertent actuation block has allowed the ECCS valves to fully open and the open
valve position signal is received by the MPS. There are no other safety-related
mechanical system interlocks.
This section describes the derivation of system inputs to the MPS used for the
safety-related protective functions performed by the MPS. The MPS and NMS sensor and
process measurement design conforms to the requirements of Section 6.4 of IEEE
Std 603-1991.
The information in this section satisfies the application specific information requirements
in TR-1015-18653-P-A listed in Table 7.0-2 for ASAI number 41.
The process variables associated with MPS safety-related functions are listed in Table 7.1-3
and Table 7.1-4. These process variables are used by the redundant sense and command
features of MPS to generate required protective actions. These variables are monitored by
variables identified in Table 7.1-2. The instrument range that accounts for normal,
abnormal, and accident conditions is also specified for each variable. All but one MPS
variable identified and used for safety-related functions is derived from process signals that
are direct measurements of the process variables credited in the plant safety analysis (see
Chapter 15). The exception is steam superheat, that is a variable calculated from steam
pressure and steam temperature. Use of steam pressure and temperature is the only
practical and feasible approach to obtaining the steam superheat variable credited in the
plant safety analysis. Additional sensor measurement details for variables associated with
the nuclear steam supply system are provided in the TR-0316-22048.
The safety-related NMS sense and command features provide input to the MPS. The four
redundant inputs to the MPS are direct measurements of the variables credited in the plant
safety analysis. The ranges which account for normal, abnormal, and accident conditions
for these variables are also provided in Table 7.1-2.
7.2.7 Setpoints
the automatic and manual operating bypasses are automatically removed, and the more
restrictive setpoint is automatically enabled. These are positive means to ensure the more
restrictive setpoint is used when required and conform to IEEE Std 603-1991 Section 6.8.2.
The operating bypasses are described in Section 7.2.4.1 and Table 7.1-5.
The information in this section satisfies the application specific information requirements
in TR-1015-18653-P-A listed in Table 7.0-2 for ASAI number 44.
The methodology described has been established to ensure that the RTS and ESFAS
setpoints are consistent with the assumptions made in the plant safety analysis and
conform to the setpoint-related requirements of industry standard ISA-67.04.01-2006,
"Setpoints for Nuclear Safety-Related Instrumentation," (Reference 7.2-29) and addresses
the regulatory issues identified in U.S. Nuclear Regulatory Commission Regulatory Issue
Summary 2006-17. Table 1.9-2 addresses the partial conformance with Regulatory Guide
1.105, revision 3 that endorses ISA-S67.04-1994, "Setpoints for Nuclear Safety-Related
Instrumentation," (Reference 7.2-23).
Setpoints for the RTS and ESFAS are selected to provide sufficient allowance between the
trip setpoint and the analytical limit to account for instrument channel uncertainties. The
instrument setpoint methodology determines calibration uncertainty allowances,
including as-found and as-left tolerances, that are used in plant surveillance tests to verify
that setpoints for safety-related protective functions are within technical specification
limits. The methodology also establishes acceptance criteria to evaluate setpoints during
surveillance testing and calibration for setpoint drift.
The methodology includes uncertainty and calculated setpoints based on assumptions for
instrument uncertainties. The detailed setpoint calculation processes for the MPS are
described in TR-616-49121 and may change according to the plant-specific instrument
accuracy and uncertainty data. This methodology only applies to safety-related
instrumentation used for RTS and ESFAS functions and does not include provisions for
using a graded approach for nonsafety-related or less important instrumentation.
This section describes the auxiliary features associated with the safety-related I&C systems
described in Section 7.0 and 7.1. These features meet the requirements of
IEEE Std 603-1991, Section 5.12.
The information in this section satisfies the application specific information requirements
in TR-1015-18653-P-A listed in Table 7.0-2 for ASAI numbers 34, 47, and 49.
There are no auxiliary supporting features that are part of the safety-related module
protection system (MPS) or neutron monitoring system (NMS). The MPS and NMS are
designed to not rely on auxiliary supporting features such as electrical power or
environmental controls to perform their safety functions; therefore, IEEE Std 603-1991
sub-clause 5.12.1 does not apply to the design of the MPS and NMS.
Other auxiliary features of the MPS that are part of the MPS by association (i.e., not
isolated from the MPS) but are not required for the MPS to perform its safety functions
include the following:
1) Continuous online self-testing and diagnostics. The continuous online self-testing
and diagnostic functions are described in Section 7.2.15. These functions are
designed and qualified as part of the MPS as described in TR-1015-18653-P-A such
that the self-testing and diagnostics functions do not adversely affect the MPS from
performing its safety functions.
4) Isolation devices and circuitry. Electrical power for the MPS is supplied by the
nonsafety-related highly reliable DC power system (EDSS) as described in
Section 8.3 through a Class 1E isolation device that provides isolation between the
Class 1E components within the MPS and non-Class 1E components as described in
Section 7.1.2. The Class 1E isolation devices are designed and qualified to comply
with IEEE Std 603-1991.
5) Shunt trip relay/coil circuitry in reactor trip breakers and pressurizer heater
breakers. The shunt trip coil and relays of the reactor trip breakers and the
pressurizer heater trip breakers do not affect the MPS in accomplishing its safety
functions. Each breaker utilizes its own nonsafety-related shunt trip coil and relay
as a backup to the safety-related undervoltage coil as described in Section 7.0.4.1.
The shunt trip coil and relay are nonsafety-related diverse means for opening the
reactor trip and pressurizer heater trip breakers and are not capable of closing
these breakers once opened.
6) 24 Hour Timers for post-accident monitoring (PAM) only mode. The 24-hour timers
and associated components of the MPS are used to ensure a 72-hour EDSS-MS
battery capacity by shedding loads on EDSS as described in Section 7.0.4.1.4. These
components do not affect the ability of the MPS in accomplishing its safety
functions. The 24-hour timers are normally de-energized and are energized by an
MPS equipment interface module (EIM). When plant conditions require MPS to
initiate the 24-hour timers, MPS also initiates a reactor trip, decay heat removal
system actuation, demineralized water supply isolation, and containment isolation
using separate EIMs. Failure of the 24-hour timers or failure to shed loads does not
impact the MPS capability of initiating protective actions. Instead, these failures
have the potential of impacting the nonsafety-related function of providing PAM
Type B, Type C, and Type D variable information to the operator.
Other auxiliary features of the NMS-excore that are part of the NMS-excore by
association (i.e., not isolated from the NMS-excore) but are not required for the
NMS-excore to perform its safety functions include the electrical isolation devices and
circuitry. Electrical power for the NMS-excore is supplied by the EDSS as described in
Section 8.3 through a Class 1E isolation device that provides isolation between the
Class 1E components within the NMS-excore and non-Class 1E components as
described in Section 7.1.2. The Class 1E isolation devices are designed and qualified to
comply with IEEE Std 603-1991.
The design of the MPS control of access, identification and repair features conforms to
IEEE Std 603-1991, Sections 5.9, 5.10, and 5.11, IEEE Std 7-4.3.2-2003, Section 5.11, and
conforms to the guidance contained in RG 1.75, Revision 3 and RG 1.152, Revision 3.
The information in this section satisfies the application specific information requirements
in TR-1015-18653-P-A listed in Table 7.0-2 for ASAI numbers 11, 22, 31, 32, 33, 53, 54, and
58.
The NuScale Digital Safety System SDOE Plan establishes the approach for applying
security-related regulatory guidance to the digital I&C system life cycle.
Regulatory Guide 1.152, Revision 3 provides guidance for an SDOE. The SDOE for the
development of digital safety-related system software satisfies the requirements of
10 CFR 50.55a(h) and IEEE Std 603-1991, Sections 5.6 and 5.9.
The digital I&C system platform development process is outlined in the NuScale Digital
Safety System Project Plan and the Digital I&C Software Quality Assurance Plan that
provide detailed information on the life cycle processes (see Section 7.2.1).
As documented in the Digital Safety System Project Plan (see Section 7.2.1), there are
three distinct digital system life cycle development elements: basic design, detailed
design, and system integration, installation and testing.
Regulatory Guide 1.173, Revision 1 endorses IEEE Std 1074-2006 with several
clarifications. The security objectives for development of a system with high functional
reliability commensurate with the safety functions performed include a secure
software and system development environment, secure operational environment, and
cyber-security controls of the installed system.
Security analyses are performed in accordance with IEEE Std 1012-2004 as endorsed by
RG 1.168.
Digital system software is assigned a SIL per the Software Level Classification Procedure
at the beginning of the software development life cycle.
For systems that are classified as SIL 4, the Digital I&C Software Development Plan
requires the software development life cycle and any procurement activities to be in
accordance with the SDOE plan.
An initial SDOE Vulnerability Assessment is performed during the basic design stage to
identify design requirements that are verified or added to the requirements
specification for each system.
The detailed design process element includes production hardware, software, and
programmable logic development. The detailed design activities correspond to the
planning, requirements, design, and implementation, and test phases of a typical
software life cycle.
During the detailed design process element, production software, firmware, and
programmable logic are developed and implemented. The controls established by the
Secure Development Environment ensure that unwanted, unneeded, and
undocumented functionality (e.g., superfluous code) is not introduced.
When the system ownership transfers from NuScale or the vendor to the licensee, the
system transitions from a secure development environment to a secure operational
environment. The licensee is required to develop procedures to describe the
Access to protected areas that contain MPS equipment is controlled with the use of
security devices. Separation Group A and C, and Division I are in different rooms from
Separation Group B and D, and Division II. Each separation group, MWS, and division
cabinet of the MPS is locked using different keys. During plant operations, routine
planned maintenance activities are limited to one division and one separation group at
a time.
Remote access to the MPS is prohibited. However the MPS permits administrative
control of direct access to safety system equipment. Access to manually bypassed
protection channels and manually blocked protective functions is limited by
administrative controls. Administrative controls are also provided for access to MWS
test points, setpoint adjustments, and channel calibration.
Additional physical and logical controls also prevent modifications to a MPS safety
channel when being relied upon to perform a safety function. Protection from a faulted
MWS when not in use is provided through a qualified physical hardware disconnect
and a qualified safety-related isolation device. To enable MWS communication, the
hardware disconnect must be physically enabled and the affected safety channel must
be placed into bypass, either of which generates an alarm in the control room. By
placing the safety channel in bypass, the channel is no longer being relied upon to
perform a safety function.
The MPS gateway which supplies information to the SDIS hub is located in the MPS
room dedicated to each module. The SDIS hub is located in the PPS room. SDIS displays
and the associated display interface modules (DIMs) are located in the MCR.
The communication interfaces for each MPS separation group have uni-directional
links to nonsafety-related plant systems.
The FPGA logic in the MPS can only be modified using special tools and only upon
removal of an SFM. Certain MPS parameters, such as setpoints, can be adjusted using
the MWS during plant operation when the equipment is bypassed or when its safety
function is no longer required to be operable.
changes. Enabling MWS communication initiates alarms at the device level and in the
MCR.
The MPS provides status and diagnostics information to the MCS, SDIS, and the MWS
through one-way, transmit only, isolated outputs.
The I&C architecture is designed with 4 security levels of which Security Level 4 is the
highest. The MPS is identified as a Security Level 4 digital system. The design of the MPS
prohibits remote access to systems within the Security Level 4 domain.
The NMS is an analog system with no digital components, and therefore has no
vulnerabilities that require assessment.
7.2.9.2 Identification
Redundant divisions of MPS equipment are marked so that equipment can be clearly
identified without frequent referral to reference material. Redundant divisions are
distinguished by color-coded equipment tags or nameplates.
The MPS equipment is divided into four separation groups and two divisions. Non-rack
mounted MPS SSC are provided with an identification tag or nameplate. Small
electrical components such as power supplies and logic cards have nameplates on the
enclosure that houses them. Cables are provided with identification tags.
Electrical and control equipment, assemblies, devices, and cables are grouped into
separate divisions and are identified such that the electrical divisional assignment is
apparent. The identification method utilizes color coding and the markers within a
division are the same color.
The cables and raceways for Class 1E systems (except those routed in conduits) are
tagged at periodic intervals prior to or during installation. Cables and raceways are
marked in a manner of sufficient durability to be legible throughout the life of the
plant, and to facilitate initial verification that the installation is in conformance with the
separation criteria. Cable and raceway markings are colored to uniquely identify the
division (or non-division) of the cable. Any non-divisional cable within such cabinets is
appropriately marked to distinguish it from the divisional cables. The method used for
identification is readily distinguished between different divisions of Class 1E systems,
between Class 1E and non- Class 1E systems, and between associated cables of
different divisions. Associated cables are uniquely identified as such by a longitudinal
stripe or other color-coded method.
Class 1E cable raceways are marked with the division color, and with their proper
raceway identification at periodic intervals. Neutron-monitoring cables carry the
unique voltage class markings superimposed on the divisional color markings, and
placed at the same nominal intervals.
For computer systems, software and hardware identification is used to verify that the
correct software is installed in the correct hardware component. A configuration
control document or drawing is used to identify the correct software, including version,
installed in digital I&C systems in accordance with IEEE Std 7-4.3.2-2003, as endorsed by
RG 1.152, Revision 3 (see Section 7.2.1).
The additional requirements from IEEE Std 7-4.3.2-2003 are not applicable to NMS
because the NMS is an entirely analog design.
The NuScale Digital I&C Software Configuration Management Plan describes the
following related to identification with digital I&C systems (see Section 7.2.1):
• identification of the program version as well as a means to identify the version after
the software has been compiled and loaded onto a computer or the FPGA
programming has been completed
• assurance that the correct control parameters and constants are initially installed in
the computers and digital devices and that these control parameters and constants
are maintained and updated correctly
• identification that includes a unique revision identifier and that is traceable to
configuration control documentation that identifies and justifies the changes
made by that revision
• how computer hardware, programs, and software are distinctly identified in
accordance with the guidance in Section 5.11 of IEEE Std 7-4.3.2-2003
7.2.9.3 Repair
The MPS facilitates the recognition, location, replacement, repair, and adjustment of
malfunctioning components or modules. The built-in diagnostics support timely
recognition of problems by providing a mechanism for periodically verifying the
operability of MPS modules, and of rapidly locating malfunctioning assemblies.
Continuous online error checking detects and locates failures. Channel bypass for the
Without the use of MWS, a status light is provided on the module to indicate any issues
with that component. Timely replacement is dependent on the licensee and the
component needing replacement. Sensors located in harsh environments or
inaccessible areas may be replaceable during an outage. In this instance, the channel
may be placed in bypass or trip depending on the technical specifications. This permits
continued operation while still meeting the single-failure criterion. For SFMs, SBMs,
SVMs, and EIMs self-test and operability checks are performed in accordance with the
technical specifications. Detected failures or inoperable status are provided to the
operators as an alarm and the channel can be bypassed for repair. Adjustments are
only possible on tunable parameters through the use of the MWS.
The MPS allows periodic and corrective maintenance during normal power operation
and during outages. For maintenance to be performed, the equipment must be
removed from service. The affected channel in a separation group can be placed in a
trip condition or bypass subject to technical specification requirements.
Safety functions within a separation group can be taken to bypass or trip for testing or
corrective maintenance. The RTS and ESFAS divisions do not have bypass functionality,
however the modules have continuous self-testing coverage. The reactor trip breaker
configuration can be tested at power by opening one breaker at a time.
3) place the out of service switch on the associated SFM to the out of service position
4) verify the correct out of service and bypass or trip alarms have been received in the
MCR
The safety function is now out of service. The maintenance trip/bypass switches are
located on a panel in the separation group's cabinet. The switches are connected to the
HWM in the SFM chassis and the bypass or trip signal is placed on the backplane to
make it available to the modules in the chassis TR-1015-18653-P-A.
The normal configuration of MPS is designed with one-way communication from the
MPS SFMs to the MWS through the MIB communications module and the MPS
gateway. The MIB communications module provides Class 1E isolation from safety to
nonsafety and communicates status and data to be displayed on the MWS. Changing
of parameters is not possible with the SFM in service.
In order to write parameters to the SFM the following steps are required:
1) verify the SFM is removed from service as described above
2) connect a temporary calibration and test bus cable from the MWS to the associated
separation group's MIB communications module calibration and test bus
connection
The removal from service of a SFM, corrective maintenance, parameter update, and
return to service processes are administratively controlled with approved plant
procedures.
The safety function logic cannot be changed on a module when it is installed in the
chassis. It must be removed and special equipment used to modify the logic. The MPS
design meets the guidance of DI&C-ISG-04 for changing of parameters by requiring the
SFM to be removed from service and a temporary cable to be connected. There is one
cable from the MWS so one separation group or division in the MPS room can be
connected and updated at one time. Because there are two separate MPS rooms with
an MWS, the limitation of having one separation group or division being changed at a
time is administratively controlled. The out of service switch on the SFM provides one
more level of defense-in-depth where no parameters can be changed unless the SFM is
out of service. The switch provides a physical disconnect between the calibration and
test bus data and the SFM.
During outage periods when the MPS is not required to be in service, multiple MWSs
could be connected to multiple separation groups at the same time. This is
administratively controlled.
7.2.10 Interaction between Sense and Command Features and Other Systems
The I&C systems minimize the interactions between safety and nonsafety systems to those
that are necessary for the proper functioning of the plant. The boundaries between safety
and nonsafety systems are formed by isolation devices that prevent failures or
malfunctions in the nonsafety systems from interfering with the safety systems; therefore,
conditions that prevent the safety systems from completing protective functions within
the sense and command features do not exist in the MPS.
The MPS sense and command features and interaction with other nonsafety systems are
designed to meet the requirements of IEEE Std 603-1991, Section 6.3.
The information in this section satisfies the application specific information requirements
in TR-1015-18653-P-A listed in Table 7.0-2 for ASAI number 40.
Variables used for both protection and control are inputs into the MPS for monitoring,
signal conditioning, and trip determination. These variables are then provided to the MCS
for plant control functions via isolated, one-way communication paths (see Section 7.1.2).
Variables monitored by MPS channels (Table 7.1-2) such as pressurizer pressure or main
steam pressure are also used to control the NPM via the nonsafety MCS. This reduces the
number of penetrations into critical pressure boundaries, such as the reactor pressure
vessel and steam lines. Isolated output signals maintain MPS channel independence (see
Section 7.1.2). The MCS uses a median signal select algorithm to prevent a single failure in
MPS from causing a transient in the control system that would require a protective action.
MPS safety-related variables are monitored by four redundant channels with safety
functions actuated by two-out-of-four coincident logic. This logic ensures the required
safety function remains operable in the event of a single random failure of a protection
channel concurrent with a channel in maintenance bypass, as described in Section 7.1.3
and Section 7.2.4.
When the sense and command features equipment for the MPS are in maintenance bypass,
the capability of a safety system to accomplish the safety function is retained, and during
such operation, the sense and command features continue to meet the single failure
requirements contained in Section 7.2.4.
The MCS utilizes logic processing in the cases where redundant input/output (I/O) channels
are utilized. Some logic supports the redundant-channel architecture used by the MPS,
while other logic directly supports the process systems. The logic processing of multiple
channels can include two, three, or four input signals.
The MCS performs quality and validation checks on the input process variable data. The
MCS determines if the process value is "good." The operator has the ability to select a signal
for control if the inputs are determined to be good. If four process values are good, MCS
will use the median value of all four inputs. If one of the inputs is "bad" due to a failure or
bypass, a notification is sent to the operator workstation. MCS selects the appropriate
selection methodology for the number of remaining good signals for utilization.
For a two signal input, there are three possible configurations for a selection algorithm.
When both inputs are good, the operator has the option to select which signal is used as an
input to the process controller. When both signals are bad the loop control is transferred to
the operator for manual control. When one signal is good, then the process controller uses
that signal.
For a three input signal, a determination is made on the value of three inputs: lowest,
median and highest. When three inputs are determined to be good, the median signal is
transferred as the input to the control process. If one of the input signals is tagged as bad,
then an average of the two remaining signals is used as the input to the control process.
When two of the inputs are marked as bad, the one remaining good signal is used by the
control process. When all signals are bad, the loop control is transferred to the operator for
manual control and the operator is alerted.
For four input signals, if the four channel inputs are determined by MCS to be good, MCS
uses the median value of the four inputs. If one channel has been bypassed for
maintenance, or if the channel has failed (i.e. marked as bad), the channel is disregarded by
the signal select algorithm. The signals from the remaining three channels are then
processed as described for three inputs. When two of the four signals are bad, the MCS will
use the average value of the remaining two valid inputs. When a single value is good, MCS
uses the value of the single good input for control. When four signals are bad, the loop
control is transferred to the operator for manual control and the operator is alerted.
This section describes the multi-unit station design of the NuScale Power Plant. The I&C
safety systems use the term modules vice units to describe the individual NPMs. The design
of the I&C systems conforms to the requirements of IEEE Std 603-1991, Section 5.13.
The information in this section satisfies the application specific information requirements
in TR-1015-18653-P-A listed in Table 7.0-2 for ASAI number 35.
The NuScale Power Plant may include up to twelve individual NPMs. The modules have a
separate MPS and NMS-excore to provide safety-related protective functions. The MPS and
NMS-excore for the NPM do not share information with the other NPMs and are isolated
from them. DBEs occurring in one module do not impair the ability of the I&C systems in
another module from performing their required safety functions. See Chapter 21 for more
details on multi-module effects on safety systems.
The electrical power provided by the module-specific EDSS is not shared between NPMs.
The common portion of EDSS provides electrical power to shared plant SSC (see Section
8.3). Class 1E isolation is provided between the EDSS and MPS, and the isolation devices are
classified as part of the safety system. Cross-tie capabilities between NPMs are not provided
in the EDSS design.
The NuScale Power Plant is designed to monitor and control up to 12 NPMs from a single
control room by utilizing human factors engineering (HFE) and increased automation to
optimize staffing levels and reduce human errors. The operator staffing requirements
associated with multi-module operations are described in Section 18.5. There is no sharing
of safety-related I&C SSC between modules. PPS, PCS, and SDIS, which are all
nonsafety-related I&C systems, are the I&C systems that are shared across multiple NPMs.
Electrical power supply for the PPS and SDIS is provided by the Common portion of the
EDSS (see Section 8.3.2.1). There are no interfaces or connections between the PPS or PCS
to any NPMs' MPS or NMS. The SDIS is isolated from the MPS through the MPS gateways, as
described in Section 7.1.2. The multi-module effects of the PCS and PPS are discussed in
Chapter 21. The SDIS has been analyzed such that no credible failure of the SDIS can cause
a loss of multiple NuScale Power Module display functions. The SDIS human system
interface is designed in accordance with human system interface design principles that
conform to NUREG-0711 as described in Section 18.7.
The independence and redundancy discussions in Section 7.1.2 and Section 7.1.3, along
with the hazards analyses described in Section 7.1.8, demonstrate that single failure or
transient within an I&C safety system of one NPM does not adversely affect or propagate to
another NPM. The safety-related I&C systems are module-specific, and there are no safety
systems that share functions across multiple NPMs.
The MPS provides means for automatic and manual initiation of required functions;
however, there are no credited manual actions required to enable the plant to mitigate
AOOs and postulated accidents. The automatic and manual features accomplish the
reactor trip and engineered safety features actuation functions necessary to shut down and
maintain the reactor in a safe condition, thereby restricting the release of radionuclides to
the environment.
The automatic and manual control functions of the MPS are designed to conform to
Sections 6.1, 6.2, 7.1, and 7.2 of IEEE Std 603-1991, and meet the guidance of RG 1.62,
Revision 1.
The information in this section satisfies the application specific information requirements
in TR-1015-18653-P-A listed in Table 7.0-2 for ASAIs 38 and 39.
The MPS automatically initiates the protective actions necessary to mitigate the effects
of the DBEs identified in Table 7.1-1. The variables monitored by MPS to initiate
safety-related functions are identified in Table 7.1-2. The safety-related reactor trip and
ESFAS functions of MPS are listed in Table 7.1-3 and Table 7.1-4, respectively.
The MPS has been designed using the HIPS platform. The HIPS platform is designed to
have predictable and repeatable time responses. Information for how the MPS utilizes
the predictable and repeatable features of the HIPS platform is detailed in Section 7.1.4.
Functional logic implemented within MPS is shown in Figure 7.1-1a through
Figure 7.1-1ao.
The MPS conforms to RG 1.62, Revision 1, and is designed to manually initiate the
protective actions listed in Table 7.1-4 at the divisional level. Manual initiation of a
protective action is a backup to the automatic function.
A Division I and Division II set of manual switches are provided for manual initiation of
protective actions and are connected to the HWM of the corresponding RTS and ESFAS
division. Input signals to the HWM are isolated, converted to logic level signals and
placed on the backplane. These signals are provided to the associated EIM actuation
priority logic circuits downstream of the FPGA logic components that generate
automatic signals.
A Division I and Division II manual actuation switch is provided in the MCR for each of
the following protective actions. Each manual actuation switch actuates the respective
protective function within its associated division. Actuation of either divisional switch is
sufficient to complete the safety function. The manual actuation switches are shown in
the MPS functional logic diagrams as shown in Figure 7.1-1j through Figure 7.1-1n:
• reactor trip
• ECCS actuation
• decay heat removal actuation
• containment isolation
• demineralized water system isolation
• chemical and volume control system isolation
• pressurizer heater trip
• secondary system isolation
• low temperature over pressure protection
If enabled by the operator using the safety-related enable nonsafety control switch, the
capability for manual component level control of ESF equipment is possible using
nonsafety discrete hard-wired inputs from the MCS to the HWM. These signals are then
input to the actuation priority logic circuit on the EIM. Any automatic or manual
safety-related signal will override the nonsafety signal and is prioritized within the
actuation priority logic. For beyond DBEs and for a limited number of actuated
equipment, a safety-related override switch can be used to prioritize a nonsafety signal
over certain automatic signals. Override switches are provided for the containment
system isolation override function as shown below.
See the MPS functional logic diagrams (Figure 7.1-1j through Figure 7.1-1ao). The
manual controls are controlled administratively through approved plant procedures.
No manually controlled actions are assumed in the NuScale Power Plant safety analyses
in order to accomplish required safety-related functions. No Type A post-accident
monitoring variables have been identified as defined in IEEE Std 497-2002 “IEEE
Standard Criteria for Accident Monitoring Instrumentation for Nuclear Power
Generating Stations,” (Reference 7.2-31). The MPS provides outputs of monitored
variables to two redundant divisions of the MCR SDIS displays for accident monitoring
and to aid in manual operations. MCS human system interface displays in the MCR are
also used to support manual controls.
In the event of a fire in the MCR, the operators evacuate the MCR and relocate to the
RSS. There are two MCR isolation switches for each NPM that when repositioned, isolate
the MPS manual actuation switches and the enable nonsafety switch for each NPM's
MPS in the MCR to prevent spurious actuation of equipment due to fire damage. An
alarm is annunciated in the MCR when the MCR hard-wired switches are isolated using
the MCR isolation switches in the RSS, see Figure 7.1-1j.
This section describes the I&C display and monitoring systems, which provide information
for the safe operation of the plant during normal operation, AOOs and postulated
accidents, for supporting manual initiation and control of safety systems, for the normal
status and the bypassed and inoperable status of safety systems, and for satisfying
applicable requirements of 10 CFR 50.34(f).
The design of the SDIS conforms to IEEE Std 603-1991, Section 5.8, and the guidance in RG
1.97, Revision 4 with exceptions as described in this section.
The information in this section satisfies the application specific information requirements
in TR-1015-18653-P-A listed in Table 7.0-2 for ASAI numbers 27, 28, 29, and 30.
The displays for the SDIS are located in the MCR and provide accurate, complete, and
timely information pertinent to MPS and PPS status and informational displays. These
displays minimize the possibility of ambiguous indications to the operator. SDIS displays
may be used to support manual initiation of protective actions, but the SDIS does not
directly initiate protective actions.
The SDIS receives inputs from the MPS and PPS through communication modules. Status
information regarding process variable values, logic status, equipment status, and
actuation device status are provided to the SDIS from the separation group and each
division of the RTS, ESFAS, and PPS. The MPS interfaces through the divisional MPS gateway
while the PPS interfaces through its MIB communication module.
The principal function of the SDIS is to display PAM variables used by plant operators to
assess plant conditions during and following an accident. The principal functions of PAM
instrumentation are to provide
• primary information to the control room operators to assess the plant critical safety
functions
• primary information to the control room operators to indicate the potential for breach
or the actual breach of fission product barriers
• information to the control room operators indicating the performance of those safety
systems and auxiliary supporting features necessary for mitigating DBEs
• information to the control room operators indicating the performance of other systems
necessary to achieve and maintain a safe shutdown condition
• information to the control room operators to verify safety system status
• information to the control room operators for determining the magnitude of the
release of radioactive materials and continually assessing such releases
Manual controls are a backup to the automatic functions provided by the MPS. There
are no credited manual actions required to mitigate DBEs, and there are no Type A
post-accident monitoring variables. There are no safety-related information displays in
the MCR.
Deviations from normal operating conditions using any combination of these four
variable types are alerted to the operator through the use of alarms and annunciators.
The task analysis process that was used to identify the controls, alarms, and displays
needed in the MCR to manage the plant safety functions and remote shutdown
capability are detailed in Section 18.7.2.
The Human Factors Program is described in Chapter 18, which includes the application
of Functional Requirements Analysis and Function Allocation (Section 18.3) and Task
Analysis (Section 18.4) in the design of the I&C human system interfaces for the NuScale
Power Plant design.
Post-accident monitoring variables are displayed in the MCR on the SDIS, MCS, and
PCS. The PAM variables displayed on SDIS are also displayed on MCS or PCS. Some PAM
variables are only displayed on MCS and PCS. Additional description on PAM is in the
PAM Section 7.1.1.2.2.
The NuScale HFE Program Management Plan (Reference 18.1-1) outlines how human
factors are incorporated into the SDIS. The SDIS displays are designed to minimize the
possibility of ambiguous indications that could be confusing to the operator. The SDIS
displays continuous real time data of Type B, C and D PAM variables. There are no
identified Type A PAM variables required to be displayed by the SDIS. The SDIS has the
capability of displaying up to 30 minutes of trending data. Continuous self-tests within
the SDIS detect and annunciate any signal validation errors.
The SDIS displays are in a separate location in the MCR from those used during normal
plant operations. The SDIS displays the PAM variables to the operator during both
normal plant operation as well as during post-accident conditions. All information sent
to the SDIS from the MPS and PPS is also made available to the plant historian for
recording and trending purposes.
The RSS is described in Section 7.1.1.2.3. There is an identical set of MCS and PCS
displays located in the RSS provided for the operator to monitor the plant operation if
evacuation of the MCR is required. SDIS displays are not provided in the RSS as there is
no manual control of safety-related equipment allowed from the RSS.
The MCS provides continuous indication of the MPS protective actions that are
bypassed or deliberately rendered inoperable. The display of the status information
allows the operator to identify the specific bypassed functions and to determine
system status and operability. In addition to the status indication, an alarm is sounded
in the MCR by the MCS if more than one MPS bypass is attempted for a given
protection function. See Section 7.2.4 for details on the operating and maintenance
bypasses.
Equipment status information is automatically sent from the MPS to the MCS and SDIS.
The MCS displays provide the operator with continuous indications of bypass, trip, and
out of service status. The display of the status information allows the operator to
identify the operability of the safety functions.
The capability to manually activate the bypass indication in the control room is
provided by the MCS.
The display and bypass status information functions were evaluated as part of the MPS
failure modes and effects analysis. There are no safety-related trips or actuation
functions associated with the display and bypass status information function. Loss of
displayed indication would be readily apparent and noticed by MCR operators.
Alarms are available for deviation from setpoint, excessive rate-of-change, high or low
process value, and contact change of state from normal. Generation of alarms and
notifications integrate the requirements from HFE task analysis and alarm philosophy
as defined in the Human System Interface Design Results Summary Report
(Reference 18.7-2).
Alarms are not required to support manually controlled actions relied upon to enable
the safety systems to accomplish their safety functions. Manually controlled actions are
not assumed in the safety analyses in order to accomplish required safety functions.
Operator actions are not required to maintain the plant in a safe and stable condition.
The MCS provides the operators with alarm and status information for viewing and
historical trending. The MCS provides the alarms, alarm history, and trending
information to the plant operators via the MCS human-system interfaces.
The alarms generated by the MCS for each NPM and PCS, are aggregated for display to
the operator by the PCS HSIs in the MCR and RSS. The MCS and PCS operator
workstations are separate and independent from the control processors such that a
failure of the control processors will not affect the MCS or PCS operator workstations’
alarm functions. Additionally, an independent monitoring system monitors the mutual
status of the MCS and PCS to detect and alert the operator to a loss of the overall I&C
system.
The MCS and PCS provide redundancy in the control processors, networking
components, power supplies, power sources and operator workstation displays to
maintain alarm system reliability in the MCR and RSS in accordance with item II.T of
SECY-93-087.
The MCS provides a first-out alarm resolution capacity. In the case of an avalanche of
alarms, the system is able to discriminate between them and date tag the alarms in
order of their occurrence. Process alarms are logged with a time stamp that includes
the year, month, day, hour, minutes, and second which provides the operator the
ability to understand and diagnose major plant upsets.
following variables that are used to identify inadequate core cooling to satisfy the
requirements of 10 CFR 50.34(f)(2)(xviii):
• core exit temperatures
• wide range reactor coolant system pressure
• degrees of subcooling
• wide range reactor coolant system hot temperature
• RPV water level
• containment water level
The SDIS conforms to 10 CFR 50.34(f)(2)(iv) by providing the capability to display the
Type B and Type C variables identified in Table 7.1-7 over anticipated ranges for normal
operation, for anticipated operational occurrences, and for accident conditions.
The reactor safety valve position indication is processed by the MPS and then sent to
the SDIS and the MCS for display in the MCR. The reactor safety valve position
indication is seismically qualified to Seismic Category I requirements and meets the
requirements of 10 CFR 50.34(f)(2)(xi).
Consistent with 50.34(f)(2)(xvii) the SDI system provides the capability to monitor
containment pressure, containment water level, and the reactor containment
atmosphere for radioactivity released from postulated accidents. The MCS provides the
recording function for the containment parameters.
Consistent with 10 CFR 50.34(f)(2)(xvii)(C) and 10 CFR 50.44(c)(4), The PSS containment
sampling system includes oxygen and hydrogen analyzers to monitor the containment
environment. These monitors are nonsafety-related instruments that continuously
monitor oxygen and hydrogen concentrations in containment during operation and
are capable of monitoring during beyond design-basis conditions. The analyzers are
designed to be functional, reliable, and will meet design criteria discussed in
Regulatory Position C.2 of RG 1.7. The hydrogen analyzer output signal is sent to the
MCS, which can provide readout in the main control room. Additionally, local
indication is also provided as a backup display/indication in event that information
from MCS cannot be displayed in the control room post-accident.
Consistent with 10 CFR 50.34(f)(2)(xvii)(E), the PCS displays and records in the MCR
information on noble gas effluent release points for the NuScale plant.
As described in Table 1.9-5, the NuScale design supports an exemption from the power
supply requirements for pressurizer level indication included in 10 CFR 50.34(f)(2)(xx).
There is a unidirectional communication interface between the MCS and PCS networks
and the plant network and is shown in Figure 7.0-1. The one-way deterministic
isolation devices transmits network traffic from the MCS and PCS to the plant network
in one direction only, which is enforced in the hardware design, not software. No
software configuration or misconfiguration will cause the boundary device to reverse
the direction of data flow. The MCS and PCS systems provide monitoring data via
one-way communication interfaces to the plant network which provides data
recording, trending, and historical retention that can be retrieved on the emergency
operations facility stations and technical support center (TSC) engineering
workstations.
Additionally, there is a link from the plant network to the NRC emergency response
data system via dedicated communication servers that connect to the plant network
and provide data communication of required plant data to offsite emergency response
facilities.
The TSC engineering work stations are located on the 100' level of the Control Building
and separated from the operator workstations, which are located in the MCR on the
76'-6" level in the control building. The TSC engineering work stations have fully
licensed operating systems, all configuration software, and a software package for
complete configuration, tuning, trending, and diagnostics of the system. The TSC
engineering work stations provide a means to make changes and test software code
prior to loading into the controllers.
The non-operator workstation PCS displays (TSC engineering, shift manager, shift
technical advisor, and emergency operations facility) provide monitoring functionality
to plant process and equipment controls.
The NuScale HFE program is described in Chapter 18. The program provides a systematic
method for integrating HFE into plant analysis, design, evaluation, and implementation to
achieve safe, efficient, and reliable operation, maintenance, testing, inspection, and
surveillance of the plant. It also ensures the application of HFE principles in the design and
verification of the following:
• physical control room structures
• MCR and RSS equipment and furnishings
• environments and structures where human tasks must be performed
• control panels and instruments throughout the plant
• controls and tools
• operating procedures
• operator training
• staffing planning
The information in this section satisfies the application specific information requirements
in TR-1015-18653-P-A listed in Table 7.0-2 for ASAI number 36.
Human interface considerations for the MPS, PPS, and SDIS alarms and plant status
information, as well as the nonsafety-related MCS and PCS are provided in this section.
2) logic status
3) equipment status
The alarms and status information provided by MPS are used to confirm that protective
actions have been actuated as required and that plant conditions have stabilized.
Alarms and status information may be used for manual initiation of protective actions;
however, there are no manual protective actions for which no automatic action exists.
Alarms associated with MPS are designed to alert the operator of abnormal conditions
that may lead to automatic reactor trip or engineered safety feature (ESF) actuation, of
inoperable channel or division-level components, or of a need for maintenance
activities.
The MPS provides status information for all its sensors and equipment to the SDIS and
the MCS for indication and alarms. The display instrumentation provides accurate,
complete, and timely information which improves operator awareness and assists in
making appropriate decisions. The MPS provides information for PAM variables
through the MPS gateway to the SDIS displays in the MCR.
Logic Status
MPS utilizes four separation groups to make a reactor trip or ESF actuation
determination. An alarm is provided at the separation group and division-level for the
protective action. As an example, when an overpower condition is identified in one
separation group, an alarm is generated. With two or more separation groups
indicating an overpower condition, a first out alarm is generated to indicate the cause
of the reactor trip. A first out alarm identifies the first condition to cause a major change
in plant state. This is illustrated in the MPS functional logic diagrams in Figure 7.1-1a
through Figure 7.1-1ao. This information is made available to the operators in the MCR
and, in more detail, through the MWS.
Equipment Status
These notifications allow operators to remain aware of system status during the
performance of maintenance or testing.
A component of human interface with the PPS is the MWS. The MWS is located close to
the PPS equipment to facilitate troubleshooting activities. Diagnostics data for the PPS,
as well as sensor and equipment status information, are accessible via the MWS.
The PPS provides status information for sensors and equipment to the SDIS and the
PCS for indication and alarms. The PPS status information provided to the operator is of
four types:
• process variable values and setpoints
• logic status
• equipment status
• actuation device status
The alarms and status information provided for PPS are used to confirm that the
required PPS actions have been actuated, and remain actuated, as required, and that
plant conditions have stabilized. Alarms and status information may be used for
manual initiation of the required PPS actions; however, there are no manual PPS
actions for which automatic action does not exist. Alarms associated with PPS are
designed to alert the operator of abnormal plant conditions, equipment actuation,
inoperable division-level components, or malfunctions that require maintenance.
Variables monitored by PPS, including setpoints, are provided for display to the
operator via the PCS and the SDIS. Accident monitoring variables are available through
the SDIS. The display instrumentation provides accurate, complete, and timely
information which improves operator awareness and assists in making appropriate
decisions.
Logic Status
PPS utilizes two fully redundant divisions to perform required functions. When process
logic determines that a protective function actuation is required (e.g., control room
habitability system actuation), an alarm is provided at the division level for the required
PPS protective function actuation. There are no connections between divisions. In
terms of human factors, this ensures that the source of the alarm can be readily
determined.
Equipment Status
With continuous self-diagnostics, system modules generate a trouble alarm if there are
equipment errors or inoperable channels or divisions. Detailed information regarding
the trouble alarm is available from the MWS. This aids in determining the course of
action to correct any problems.
The PPS allows periodic testing during normal operation. The affected channel can be
placed in bypass in accordance with applicable technical specification limits. Any
channel in bypass generates an alarm for that particular function. These notifications
allow operators to remain aware of system status during the performance of
maintenance or testing.
Status feedback is provided for the execute features relied on by the PPS to accomplish
a required action.
Component feedback is essential in confirming that the required actions have been
initiated and completed. Valve position, for example, is shown on MCR displays and
allows an operator to identify valves in motion or in their actuated position. Due to the
simplistic design of the NuScale Power Plant, actuation device status in the PPS is
limited to valve or damper positions.
The SDIS is designed to meet the requirements of IEEE Std 1023-1988. The HFE Program
Management Plan (Reference 18.1-1) outlines how human factors are incorporated into
the design of systems such as the SDIS.
The operator uses the SDIS for validation that a protective action has gone to
completion and that the NPMs are being maintained in a safe condition. Because the
SDIS does not perform actions, the operators use the SDIS to aid in decision making
regarding plant operations.
Variables monitored by the MPS and PPS identified for PAM (Table 7.1-7) are available
on the SDIS displays for the operator in an accurate, complete and timely manner.
Process variables are displayed such that when they exceed set limits, they are easily
noticeable by the operator.
The SDIS displays the availability of the equipment of the MPS, PPS and SDIS. With
continuous self-diagnostics in the systems, the SDIS is able to immediately alert the
operator when equipment is no longer available.
Alarms associated directly with the SDIS are for failures of a communication module or
a display. If an alarm occurs, the identified piece of equipment must be removed and
replaced. The SDIS displays the status of the actuation devices controlled by MPS and
PPS. The operators use this information to verify the completion of protective actions
during DBEs requiring actuation of devices through the MPS or PPS.
The MCS and PCS human-system interface design is described in the Human-System
Interface Design Results Summary Report (Reference 18.7-2).
The MCS and PCS human-system interface is developed with integration of the HFE
functional allocation, task analysis and alarm philosophy. The HFE functional allocation,
task analysis, and alarm philosophy specify the level of automation and indication
required for each process and electrical system.
The MCS and PCS provide a high level of automation with minimal local operation to
reduce operator burden and optimize staffing levels while ensuring personnel safety,
equipment protection, and system availability.
Coordination with HFE analysis determines the level of automation for the various
plant systems and components. This process determines the need for human interfaces
to be manual control, shared control, or automatic control. Alarms are developed in
accordance with the HFE alarm philosophy and are described in the Human-System
Interface Design Results Summary Report (Reference 18.7-2).
The MCS and PCS human-system interface is a collection of both hardware, in the form
of physical screens and input devices, and software, in the context of the displays
designed to represent real-time plant operations and enable the user to monitor and
manage the process.
The human-system interface has a windowing type display that can display multiple
windows and any combination of graphic pictorials, bar charts, and trend displays as
selected by the operator. Displays are hierarchical and are designed in accordance with
the HFE function allocation, minimum inventory of controls, task analysis and alarm
philosophy.
The MCS operator workstation displays are located in the MCR and the RSS.
The PCS operator workstation displays are located in the MCR, the radwaste building
control room, and the RSS.
Diagnostic displays are provided at operator workstations that allow the operator to
identify system faults. Diagnostic displays provide sufficient detail to allow the
operator to determine if a problem is hardware or software related and which system
node, card input or output (I/O) point, power supply, etc. has failed.
The HSIs in the locations outside of the MCR (TSC, emergency operations facility, and
the RSS) are all MCR derivatives, i.e., operated from the same platform and connected
to either the MCS or PCS network.
The I&C systems provide testing and calibration features for functional tests and checks,
calibration verification, and time response measurements. Online testing and periodic
testing during outages in conjunction with continuous self-testing are used to verify the
performance of I&C systems.
The testing and calibration functions of the MPS and NMS are designed to conform to
Sections 5.7 and 6.5 of IEEE Std 603-1991, Section 5.7 of IEEE Std 7-4.3.2-2003, and meet the
guidance in RG 1.22, Revision 0, RG 1.118, Revision 3, and RG 1.47, Revision 1.
The information in this section satisfies the application specific information requirements
in TR-1015-18653-P-A listed in Table 7.0-2 for ASAI numbers 14, 24, 25, 26, 32, 47, 49, 50,
and 51.
The MPS and NMS are designed with the capability for calibration and surveillance
testing, including channel checks, calibration verification, and time response
The normal configuration of MPS is designed with one-way communication from the
MPS safety function modules to the MWS through the MPS gateway. Adjustments to
parameters are performed in accordance with plant operating procedures that govern
the parameter adjustment. Technical specifications establish the minimum number of
redundant safety channels that must remain operable for the current operating mode
and conditions.
Changing of setpoints and tunable parameters within the MPS is not allowed when the
SFM is in service. Using one MWS, only one separation group may be calibrated at a
time during normal operation at power. To perform calibrations on the MPS, the
affected SFM must be taken out of service subject to technical specification limits (see
Section 7.2.4). Any SFM in maintenance bypass will generate an alarm in the MCR.
While a channel is bypassed, the redundant MPS separation groups are fully capable of
completing the safety function with the remaining three redundant channels.
Once the SFM is out of service, a temporary cable is connected between the MWS and
the calibration and test bus communication port on the associated monitoring and
indication bus communications module. The removal from service of an SFM,
corrective maintenance, parameter update, and return to service processes are
administratively controlled.
The MPS provides the capability to bypass an NMS channel to support NMS system
calibration.
The MPS is designed to support testing as specified in IEEE Std 338-1987 “Standard
Criteria for the Periodic Surveillance Testing of Nuclear Power Generating Station
Safety Systems,” (Reference 7.2-32) as endorsed and modified by RG 1.118, Revision 3,
and IEEE Std 603-1991 with supplemental guidance in RG 1.22, Revision 0, and RG 1.47,
Revision 1.
The MPS and NMS allow SSC to be tested while retaining the capability to accomplish
required safety functions. The MPS uses modules from the HIPS platform which are
designed to eliminate non-detectable failures through a combination of built-in
self-testing and periodic surveillance testing.
Testing from the sensor inputs of the MPS through to the actuated equipment is
accomplished through a series of overlapping sequential tests, and the majority of the
tests may be performed with the NPM at power. Where testing final equipment at
power has the potential to upset plant operation or damage equipment, provisions are
made to test the equipment when the NPM is shut down.
The part of MPS that cannot be tested at power is the actuation priority logic circuit on
the EIM. This includes the manual MCR switches and the nonsafety-related control that
provide inputs to the actuation priority logic. The actuation priority logic consists of
discrete components and directly causes actuation of field components that cause the
reactor to shutdown or adversely affect operation. The actuation priority logic is a very
simple circuit and has acceptable reliability to be tested when the reactor is shut down.
The manual trip and actuate switches in the MCR cannot be tested at power and
require an outage. These switches are standby, low demand components such that
testing every refueling outage is acceptable to maintain sufficient system reliability.
The SDIS supports MPS and PPS by providing the displays for Type B, Type C and Type
D post-accident monitoring variables. Post-accident monitoring instrument channels
have testing capability to verify, on a periodic basis, functional requirements to support
calibration of the channels.
Continuous self-tests within the SDIS will detect and annunciate communication
failures.
The SDIS and PPS are designed to support periodic testing, calibration and
maintenance. Either division of SDIS and PPS can fully accomplish their required
functions, such that if a single division is removed from service for testing,
maintenance, or calibration the other division remains available to perform the
required functions. SDIS and PPS are not required to meet the single failure criterion
during maintenance, test or calibration activities consistent with the guidance
contained in IEEE Std 497-2002. The time periods during which SDIS and PPS may be
bypassed or removed from service is administratively controlled.
While the MPS is in normal operation, self-tests run without affecting the performance
of the safety function, including its response time.
MPS data communications are designed with error detection to enhance data integrity.
The protocol features ensure communications are robust and reliable with the ability to
detect transmission faults. Similar data integrity features are used to transfer
diagnostics data.
The MPS provides a means for checking the operational availability of the sense and
command feature input sensors relied upon for a safety function during reactor
operation.
The MPS platform incorporates failure detection and isolation techniques. Fault
detection and indication occurs at the module level, which enables plant personnel to
identify the module that needs to be replaced. Built-in self-testing will generate an
alarm and report a failure to the operator and place the component (e.g., SFM, SVM, or
EIM components) in a fail-safe state.
Diagnostic data for the separation group and division of the MPS are provided to the
MWS for the division. The MWS is located close to the equipment to facilitate
troubleshooting activities. The interface between the MPS gateway and the MWS is an
optically-isolated, one-way diagnostic interface. Diagnostics data are communicated
via the MIB which is a physically separate communications path from the safety data
path, ensuring the diagnostics functionality is independent of the safety functionality.
Further discussion on how the MWS does not prevent or have adverse influence on the
MPS performing safety functions can be found in Section 7.1.2.
The operation of the MPS is deterministic in nature and allows the systems to monitor
themselves in order to validate functional performance. The self-test features provide a
comprehensive diagnostic system ensuring system status is continually monitored.
Detectable failures are alarmed to the operator in the MCR, and an indication of the
impact of failure is provided to determine the overall status of the system. More detail
on the MPS diagnostics functions are provided in TR-1015-18653-P-A.
The NMS uses a health monitoring circuit in the electronic process blocks that checks
the continuity of the circuit inputs. Detected faults within the NMS are provided to the
MPS to trip the channel and for alarm and display in the MCR.
7.2.16 References
7.2-6 Institute of Electrical and Electronics Engineers, "IEEE Application Guide for
Surge Protection of Electric Generating Plants,” IEEE Std C62.23-1995 (R2001),
Piscataway, NJ.
7.2-7 Institute of Electrical and Electronics Engineers, "IEEE Standard for Qualifying
Class IE Equipment for Nuclear Power Generating Stations,” IEEE Std 323-2003,
Piscataway, NJ.
7.2-8 Institute of Electrical and Electronics Engineers, "IEEE Standard for Qualifying
Class IE Equipment for Nuclear Power Generating Stations." IEEE Std 323-1974,
Piscataway, NJ.
7.2-10 Institute of Electrical and Electronics Engineers, "IEEE Standard Criteria for
Independence of Class 1E Equipment and Circuits,” IEEE Std 384-1992 (R1998),
Piscataway, NJ.
7.2-11 Institute of Electrical and Electronics Engineers, "IEEE Standard Criteria for
Safety Systems for Nuclear Power Generating Stations," IEEE Std 603-1991,
Piscataway, NJ.
7.2-12 Institute of Electrical and Electronics Engineers, "IEEE Guide for Generating
Station Grounding," IEEE Std 665-1995 (R2001), Piscataway, NJ.
7.2-13 Institute of Electrical and Electronics Engineers, "IEEE Standard Criteria for
Digital Computers in Safety Systems of Nuclear Power Generating Stations,"
IEEE Std 7-4.3.2-2003, Piscataway, NJ.
7.2-14 Institute of Electrical and Electronics Engineers, "IEEE Standard for Software
Quality Assurance Plans," IEEE Std 730-2002, Piscataway, NJ.
7.2-15 Institute of Electrical and Electronics Engineers, "IEEE Standard for Software
Configuration Management Plans," IEEE Std 828-2005, Piscataway, NJ.
7.2-16 Institute of Electrical and Electronics Engineers, "IEEE Standard for Software and
System Test Documentation," IEEE Std 829-2008, Piscataway, NJ.
7.2-18 Institute of Electrical and Electronics Engineers, "IEEE Standard for Software
Unit Testing," IEEE Std 1008-1987 (R2009), Piscataway, NJ.
7.2-19 Institute of Electrical and Electronics Engineers, "IEEE Standard for Software
Verification and Validation," IEEE Std 1012-2004, Piscataway, NJ.
7.2-20 Institute of Electrical and Electronics Engineers, "IEEE Standard for Software
Reviews and Audits," IEEE Std 1028-2008, Piscataway, NJ.
7.2-21 Institute of Electrical and Electronics Engineers, "IEEE Guide for Instrumentation
Control Equipment Grounding in Generating Stations," IEEE Std 1050-1996,
Piscataway, NJ.
7.2-22 Institute of Electrical and Electronics Engineers, "IEEE Standard for Developing a
Software Project Life Cycle Process," IEEE Std 1074-2006, Piscataway, NJ.
7.2-25 NuScale Power, LLC, "Design of the Highly Integrated Protection System
Platform," TR-1015-18653-P-A, Revision 2.
7.2-26 NuScale Power, LLC, "Nuclear Steam Supply Systems Advanced Sensor
Technical Report," TR-0316-22048-P, Revision 3.
7.2-30 NuScale Power, LLC, “NuScale Topical Report: Quality Assurance Program
Description for the NuScale Power Plant,” NP-TR-1010-859-NP-A, Revision 5.
7.2-31 Institute of Electrical and Electronics Engineers, “IEEE Standard Criteria for
Accident Monitoring Instrumentation for Nuclear Power Generating Stations,”
IEEE Std 497-2002, Piscataway, NJ.
7.2-32 Institute of Electrical and Electronics Engineers, “Standard Criteria for the
Periodic Surveillance Testing of Nuclear Power Generating Station Safety
Systems,” IEEE Std 338-1987, Piscataway, NJ.
7.2-72
System Features
Revision 5
Tier 2
System Design
Review
System Operations and Maintenance
Design
Model
System
Design Acceptance
Build Integration
Testing Testing*
System
Prototype
Requirements
and Design
Review*
Equipment Requirements
Non Appendix B Information Only Input Specification System Installation
Software/CLD
Requirements
Plan
Review*
Requirements
Review* Hardware
Software/CLD Requirements
Requirements
Design Hardware
Review* Testing
Hardware
Software/CLD Design System Testing*
Design Code Review
and Logic
If not ready Testing*
Software/CLD
Implementation
Integration
If not ready Testing*
Software/CLD
Integration After Final
If not ready Iteration
Acceptance
Testing*
If not ready Software/CLD
Configuration
System Integration,
Iterate
Testing, and Installation
System Features
Revision 5
Tier 2
Software
Development System Design
DSRS 7.2.1.III.1.L,
Retirement
System Maintenance
System Features
Revision 5