H2,3,4N Temperature & Humidity Transmitter

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

H2,3,4N Temperature & Humidity Transmitter Edition:A/5

H2,3,4N Temperature & Humidity Transmitter

Install Flange
H2N
H2N

H3N H4N
H3N H4N

Applications & Features Protection: IP65


Weight: H2N:360g;H3N:270g;H4N:430g
 Humidity and temperature transmitters H2N (duct), Approval: CE
H3N(outside) and H4N(remote) are designed for
environment monitoring and controlling in industrial Models
and commercial buildings.
 High performance digital sensors and circuits, ensure
Duct mount
accurate measurement and temperature compensation H2N
Temp./RH transmitter
 Digital technology applied, multiple outputs optional,
Outside air Temp./RH
over voltage and reverse polarity protection, high Model H3N
transmitter
reliability and anti-interference capability
 LCD display temperature and humidity alternatively Remote mount Temp./
H4N
 LCD & function keys can set parameters and calibrate RH transmitter
output, so the product can be a stand alone controller RH Ac- 2 ±2%RH(0.3°C )
 Good long term stability and reliability curacy 3 ±3%RH(0.4°C )
 100% field changeable sensor without re-calibration 1 0-10VDC(3 wires)
RH
 Fast response 2 4-20mA(2 wires)
Output
 High protection rate up to IP65 8 RS485/Modbus
0 No
Specifications 1 0-10VDC(3 wires)
2 4-20mA(2 wires)
Relative Humidity 3 PT1000, ±0.2°C@25°C
Sensor: Digital polymer 4 PT100, ±0.2°C@25°C
Range: 0~100%RH Temp.
5 NTC20K,±0.4°C@25°C
Output: see models Output
6 Ni 1000, ±0.4°C@25°C
Accuracy: 2%, 3%, (25°C, 20~80%RH) 7 NTC10K-II, 0.4°C@25°C
Hysteresis: <±1%RH
8 RS485/Modbus
Response time: <10s (25°C, in slow air)
9 NTC10K-III,0.4°C@25°C
Drift: <±0.5%RH / year
A NTC10K-A, 0.4°C@25°C
Temperature
Sensor: Digital temperature sensor or RTD/thermistor 0 No
Range: 0~50°C, 0~100°C, -40~60°C, or others 1 0-50°C
Temp.
Output: see models 2 0-100°C
Range
Accuracy: transmitter: ≤±0.4°C @ 5~60°C or 3 -40-60°C
0.3°C @ 5~60°C 7 others
RTD or thermistor: typical 0.2~0.4°C@ 0 No
Relay
25°C, see models 1 2×SPST(4-20mA
N/A)
Power: Current: 18.5~35VDC (Rload=500Ω) LCD & 0 No
8.5~35VDC (Rload=0Ω) Keys 1 LCD
Voltage: 16~28VAC/ 16~35VDC 2 LCD & Keys
Output Load: ≤500Ω (current), ≥2KΩ (voltage) *1. H2,3,4N series current products are powered by RH circuit, so the RH circuit
Relay output: 2×SPST, 3A/30VDC, 3A/250VAC must be powered. Otherwise it could not work.
Display and keys: 4 digits LCD, with unit *2. Only when the temperature output is 1 or 2, the temperature range 1-7 is
indication, backlight (4-20mA N/A), 3 touch applicable. Otherwise, always use 0 as temperature range selection.
keys, see more details on LCD & Keys operation *3. See resistance table on page 1 of this catalog.
Work Temp.: -30~70°C(LCD:0~50°C)
5~95%RH (Non condensing)
Housing: Fireproof ABS housing, UHMW-PE
filter(H2/H4N), SS probe and sintered filter(H3N)

1
H2,3,4N Temperature & Humidity Transmitter Edition:A/5
Connection:

. . . . .
Different models have different electrical terminals. Please wire specific model according to the wiring diagram inside the front
cover.
Relay Outputs RS485Output Voltage(0-10V)Output Current(4-20mA)Output RT Output

COM1 NO1 COM NO2


COM2 NO GND V+ B A GND V+ T RH T V+ RH Rt

V V A A

RS485 0…10VDC 4-20mA RTD


Common 1 Common 2
Normal Open 1 Normal Open 2
POWER SUPPLY
Relay 1 Relay 2 24VDC/24VAC POWER SUPPLY
POWER SUPPLY
24VDC/24VAC 24VDC

*Current 4-20mA Output: terminal RH loop should be connected, otherwise the transmitter can not work.

Installation:

H2N Flange mount H2N/H4N Flange mount holes H3N/H4N Surface mount holes

Flange mount for the remote probe of H4N H4N Surface mount H3N Surface mount

● The install flange kit is recommended for installing the H2N. The depth being inserted can be adjusted. Install the kit on the
duct with 3 screws, and use another screw to tighten the probe and the whole H2N. the duct hole(φ17.5mm) should be
air-tight after installation.
● H3/4N’s housing should be installed vertically on the wall, with the sensor probe downward. It should be far away from any
heat/cool sources. If needed, there should be a shield to prevent the sensor from direct sun light and rain. Drill 4 holes on the
wall according to the dimensions. Install the H3/4N base with the 4 screws after remove the front cover. H4N’s remote probe
can also be installed with flange kit, same as H2N.
● Open the front cover, install the drain on the base and take the wires from DDC/PLC, etc. into the base through the drain,
then finish wiring according to the diagram inside the cover and restore the front cover. Make sure to install the drain with the
base and the base with the front cover all completely air-tight (there are two seal rings between the drain and the base, and
the front cover and the base), to prove the whole housing can meet up to IP65.

Attention:
It should be power OFF during installing and wiring. When using 24VAC, it is strongly recommended to power the unit with
independent transformer. If sharing a 24VAC transformer with other equipments such as controllers, transmitters or actuators,
please make sure the terminals 24V and GND are connected correctly. Otherwise, it will perhaps reduce serious damages.

Warranty:
● It has limited warranty for eighteen (18) months after the production date.
● It does not extend to any unit that has been subjected to misuse or accident.
● It is, in any event, strictly limited to the replacement or repair of the product itself.

Shenzhen TEREN Control Technology Co. Ltd.


Add: 3F, 2nd Industrial Zone, Nankeng, Longgang
District, Shenzhen,Guangdong,P.R.CHINA
Tel: 0755-23935155 Fax: 0755-23935156
web: www.teren.com.cn
TEREN website Alibaba shop

You might also like