Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

TG9-CO2 Duct Transmitter-1704

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

CO2 Duct Transmitter

With Temperature and RH% Detection

Model: TG9XX8

 Real time detection carbon dioxide of the air duct


 Detection high accuracy temperature and relative humidity
 Smart sensor probe can be easily installed into any air duct
 With the water-proof and porous film around the sensor probe
 Up to 3xanalog linear outputs for measurements
 Modbus RS485 interface
 With or without LCD display
 CE-approval

Features
 Designed for real time detecting carbon dioxide, can preset the inverse proportion liner outputs for some
temperature or relative humidity in air ducts. different applications.
 NDIR infrared CO2 sensor inside with special Self  With LCD or without LCD selectable
Calibration and up to 15 years’ lifetime. It makes CO2  LCD display real-time measurements of CO2,
measurement more accurate and reliable. temperature and relative humidity.
 Digital temperature & humidity sensor provides the  Simple and smart design for the installation of
high accuracy measurement in full range. sensor probe, which has a water-proof and porous
 Provides up to 3 analog outputs (0~10VDC or 4~20mA film
or 0~5VDC) for CO2 temperature and relative humidity.  Extendable probe meets more air duct systems
 Modbus RS485 communication interface.  24VAC/VDC power supply.
 The end user can adjust CO2/Temp. range which  EU standard and CE-approval.
correspond with the analog outputs via Modbus, also

Detection Focus
 Carbon Dioxide (CO2)
Indoor CO2 level is a universal accepted parameter for the condition of indoor ventilation and air quality.
A time period can be preset from 1 to 24 hours, e.g. 5 hours, then the monitor can display CO 2 average level during
this period, which provides an objective and true data for the measurement of the air quality in a certain space.
 Non-dispersive infrared (NDIR) CO2 sensor with more than 10-year lifetime
 ABC self-calibration technology guarantees reliable CO2 measurement
 CO2 range: 0~2000ppm/0~5000ppm optional
 Rapid response, high stability and consistency

1
 Temperature and humidity
Combined digital temperature and humidity sensor with high accuracy and stability. It also has compensation to
CO2 and air quality which makes the measurements more accurate by minimizing environmental effects.

Typical Applications
 Building management for office areas and residental
 Ventilation control system

Specifications
Monitoring parameters CO2 Temperature Relative humidity
Non-Dispersive Infrared Detector
Sensing element Digital combined temperature and humidity sensor
(NDIR)
0~2000ppm(default)
0℃~50℃(32℉~122℉)
Measuring range 0~5000ppm 0~100%RH
(default)
(selectable in the order)
Display Resolution 1ppm 0.1℃ 0.1%RH

Accuracy@25℃(77℉) ±60ppm + 3% of reading ±0.5℃ (0℃~50℃) ±3%RH (20%-80%RH)

Life time 15 years (normal) 10 years


ABC Logic Self
Calibration cycle —— ——
Calibration
Response Time <2 minutes for 90% change <10 seconds to reach 63%

2 hours (first time)


Warm up time
2 minutes (operation)

Electrical Characteristics

Power supply 24VAC/VDC

Consumption 3.5 W max. ; 2.5 W avg.


Two or three analog outputs
0~10VDC(default) or 4~20mA (selectable by jumpers)
Analog Outputs
0~5VDC (selected at place the order)
Can be set the inverse proportion linear output by Modbus
Modbus RS485 RS-485 with Modbus protocol, 19200bps rate, 15KV antistatic protection, independent base
interface (optional) address
Conditions of Using and Installation

Operation conditions 0~50℃(32~122℉); 0~95%RH, non condensing

Storage conditions 0~50℃(32~122℉)/ 5~80%RH

Weight 320g

Installation Fixed on the air duct with 100mm installation hole size

IP50 for no LCD


IP class of the housing
IP40 for with LCD

Standard CE-Approval

2
Dimensions & Mounting
Duct mounted
Probe Length 139.00mm
can be extended
to 139+70mm
Probe Diameter Ø26.00mm
Installation Holes 100mm

风道

气流方向

air duct
1

air flow

Install or move the probe The air flow direction

Models Information

TG9X1 X2 8 L – Y02/05 E –Tab

X1: analog output


3- 3Xanalog outputs for CO2 + Temperature + Humidity
1- 1xanalog output for CO2
0- no analog output
X2: Modbus interface
1- with Modbus interface
0- no Modbus interface
8: CO2 sensor code
L: LCD display
Non-required option. No L indicates no LCD
Y: default output type
A- 4~20mA
V- 0~10VDC (default)
V5- 0~5VDC (can’t be changed to another output by jumpers)

3
02/05: CO2 measurement range
02- 0~2000ppm (default)
05- 0~5000ppm
E: extended duct probe up to 209mm
Non-required option. No E indicates the standard probe length of 139mm
Tab: temperature scaling
T05: 0℃~50℃(32℉~122℉) (default)
T06: 0℃~60℃(32℉~140℉)
No this item indicates no output for temperature measurement.

Shipping Information
H
TH921S 0-10VDC/4-20mA AN3 5
Indiv. Ctn. Dim + G 185mm×130mm×110mm
0-10VDC/4-20mA AN2
T
4
A
A
Master Ctn. Qty 20 G
B RS485 1 2 2
B 24Vac/Vdc +
Master Ctn. Dim 24VAC/VDC 44cm(L) X32cm (W) X32cm1(H)

Master Ctn. Wt. (volume weight) 15.0KG


TG9116
+ G 0-10VDC/4-20mA AN
CO2
3
A G
A 2
1 2 24Vac/Vdc
Wiring Diagram
B
B RS485
24VAC/VDC
+
1

TG9116
TG9118/9118L
Red Black White Yellow
CO2 Blue
+ G 0-10VDC/4-20mA AN 3
24VAC/VDC
B CO2 BG A
B 2
+ A RS485
G 1 2 G 24Vac/Vdc
AN +
A +
0-10VDC RS-485 1
Red Black 24VAC/VDC
24VAC/VDC 4-20mA

TG9116 Red Black White Yello Blue


H
24VAC/VDC
TG9316
TG9318/TG9318L CO2 AN3 B
0-10VDC/4-20mA
A5
+ G 0-10VDC/4-20mA AN2
T
4
+ G G AN CO2
A + 0-10VDC/4-20mA AN1 3
A Red 0-10VDC RS-485
Black 24VAC/VDC G
B RS485 1 2 4-20mA 2
B 24Vac/Vdc +
24VAC/VDC 1

You might also like