TG9-CO2 Duct Transmitter-1704
TG9-CO2 Duct Transmitter-1704
TG9-CO2 Duct Transmitter-1704
Model: TG9XX8
Features
Designed for real time detecting carbon dioxide, can preset the inverse proportion liner outputs for some
temperature or relative humidity in air ducts. different applications.
NDIR infrared CO2 sensor inside with special Self With LCD or without LCD selectable
Calibration and up to 15 years’ lifetime. It makes CO2 LCD display real-time measurements of CO2,
measurement more accurate and reliable. temperature and relative humidity.
Digital temperature & humidity sensor provides the Simple and smart design for the installation of
high accuracy measurement in full range. sensor probe, which has a water-proof and porous
Provides up to 3 analog outputs (0~10VDC or 4~20mA film
or 0~5VDC) for CO2 temperature and relative humidity. Extendable probe meets more air duct systems
Modbus RS485 communication interface. 24VAC/VDC power supply.
The end user can adjust CO2/Temp. range which EU standard and CE-approval.
correspond with the analog outputs via Modbus, also
Detection Focus
Carbon Dioxide (CO2)
Indoor CO2 level is a universal accepted parameter for the condition of indoor ventilation and air quality.
A time period can be preset from 1 to 24 hours, e.g. 5 hours, then the monitor can display CO 2 average level during
this period, which provides an objective and true data for the measurement of the air quality in a certain space.
Non-dispersive infrared (NDIR) CO2 sensor with more than 10-year lifetime
ABC self-calibration technology guarantees reliable CO2 measurement
CO2 range: 0~2000ppm/0~5000ppm optional
Rapid response, high stability and consistency
1
Temperature and humidity
Combined digital temperature and humidity sensor with high accuracy and stability. It also has compensation to
CO2 and air quality which makes the measurements more accurate by minimizing environmental effects.
Typical Applications
Building management for office areas and residental
Ventilation control system
Specifications
Monitoring parameters CO2 Temperature Relative humidity
Non-Dispersive Infrared Detector
Sensing element Digital combined temperature and humidity sensor
(NDIR)
0~2000ppm(default)
0℃~50℃(32℉~122℉)
Measuring range 0~5000ppm 0~100%RH
(default)
(selectable in the order)
Display Resolution 1ppm 0.1℃ 0.1%RH
Electrical Characteristics
Weight 320g
Installation Fixed on the air duct with 100mm installation hole size
Standard CE-Approval
2
Dimensions & Mounting
Duct mounted
Probe Length 139.00mm
can be extended
to 139+70mm
Probe Diameter Ø26.00mm
Installation Holes 100mm
风道
气流方向
air duct
1
air flow
Models Information
3
02/05: CO2 measurement range
02- 0~2000ppm (default)
05- 0~5000ppm
E: extended duct probe up to 209mm
Non-required option. No E indicates the standard probe length of 139mm
Tab: temperature scaling
T05: 0℃~50℃(32℉~122℉) (default)
T06: 0℃~60℃(32℉~140℉)
No this item indicates no output for temperature measurement.
Shipping Information
H
TH921S 0-10VDC/4-20mA AN3 5
Indiv. Ctn. Dim + G 185mm×130mm×110mm
0-10VDC/4-20mA AN2
T
4
A
A
Master Ctn. Qty 20 G
B RS485 1 2 2
B 24Vac/Vdc +
Master Ctn. Dim 24VAC/VDC 44cm(L) X32cm (W) X32cm1(H)
TG9116
TG9118/9118L
Red Black White Yellow
CO2 Blue
+ G 0-10VDC/4-20mA AN 3
24VAC/VDC
B CO2 BG A
B 2
+ A RS485
G 1 2 G 24Vac/Vdc
AN +
A +
0-10VDC RS-485 1
Red Black 24VAC/VDC
24VAC/VDC 4-20mA