Auto Transformer Module
Auto Transformer Module
7
Transformer
Version 2 EE IIT, Kharagpur
Lesson
27
Auto-Transformer
Version 2 EE IIT, Kharagpur
Contents
27 Auto-Transformer 4
27.1 Goals of the lesson ………………………………………………………………. 4
27.2 Introduction ……………………………………………………………………… 4
27.3 2-winding transformer as Autotransformer ……………………………………... 5
27.4 Autotransformer as a single unit ………………………………………………… 6
27.5 Tick the correct answers ………………………………………………………… 9
27.6 Problems …………………………………………………………………………. 9
27.2 Introduction
So far we have considered a 2-winding transformer as a means for changing the level of a given
voltage to a desired voltage level. It may be recalled that a 2-winding transformer has two
separate magnetically coupled coils with no electrical connection between them. In this lesson
we shall show that change of level of voltage can also be done quite effectively by using a single
coil only. The idea is rather simple to understand. Suppose you have a single coil of 200 turns (=
NBC) wound over a iron core as shown in figure 27.1. If we apply an a.c voltage of 400 V, 50 Hz
to the coil (between points B and C), voltage per turn will be 400/200 = 2 V. If we take out a
wire from one end of the coil say C and take out another wire tapped from any arbitrary point E,
we would expect some voltage available between points E and C. The magnitude of the voltage
will obviously be 2 × NEC where NEC is the number of turns between points E and C. If tapping
has been taken in such a way that NEC = 100, voltage between E and C would be 200 V. Thus we
have been able to change 400 V input voltage to a 200 V output voltage by using a single coil
only. Such transformers having a single coil with suitable tapings are called autotransformers.
It is possible to connect a conventional 2-winding transformer as an autotransformer or
one can develop an autotransformer as a single unit.
B
B
Tapping
400 V 400 V E
E
50 Hz output 50 Hz
C
C C
C
Figure 27.1: Transformer with a single coil.
Version 2 EE IIT, Kharagpur
27.3 2-winding transformer as Autotransformer
Suppose we have a single phase 200V/100V, 50Hz, 10kVA two winding transformer with
polarity markings. Then the coils can be connected in various ways to have voltage ratios other
than 2 also, as shown in figure 27.2.
HV LV HV LV
200V 100V 200V 100V
150A 150A 150A 150A
300V 300V 300V 300V
E A
C
C A
Figure 27.3: Autotransformer or Figure 27.4: Schematic representation
Variac. of autotransformer.
Input voltage = V1
Output voltage required across the load = V2
Rated current to be supplied to the load = I2
Current drawn from the supply at rated condition = I1
KVA to be handled by both types of transformers = V1I1 = V2I2
The above situation is pictorially shown in figures 27.5(a) and (b). Let for the two winding
transformer,
I2
V1 V2 V1 E
I2 – I1
V2
C
(a) (b)
Figure 27.5: A two winding transformer and an autotransformer
of same rating.
Let us now right down the mmf balance equation of the transformers.
Volume of copper ∝ length of the wire × cross sectional area of copper wire
∝N×I
Hence,
Here we have assumed that N1 is greater than N2 i.e., a is greater than 1. The savings will
of course be appreciable if the value of a is close to unity. For example if a = 1.2, copper
required for autotransformer will be only 17% compared to a two winding transformer, i.e,
saving will be about 83%. On the other hand, if a = 2, savings will be only 50%. Therefore, it is
always economical to employ autotransformer where the voltage ratio change is close to unity. In
fact autotransformers could be used with advantage, to connect two power systems of voltages
say 11 kV and 15 kV.
Three similar single units of autotransformers could connected as shown in the figure
27.6 to get variable balanced three phase output voltage from a fixed three phase voltage. Such
connections are often used in the laboratory to start 3-phase induction motor at reduced voltage.
A1
3 – phase input voltage
E1
3 – phase
C1 C2 output voltage
C3 A2
A3
E3 E2
Apart from being economical, autotransformer has less leakage flux hence improved
regulation. Copper loss in the common portion of the winding will be less, so efficiency will be
slightly more. However its one major disadvantage is that it can not provide isolation between
HV and LV side. In fact, due to an open circuit in the common portion between E & C, the
voltage on the load side may soot up to dangerously high voltage causing damage to equipment.
This unexpected rise in the voltage on the LV side is potentially dangerous to the personnel
working on the LV side.
2. 110 V, 50 Hz single phase supply is needed from a 220 V, 50 Hz source. The ratio of
weights of copper needed for a two winding and an autotransformer employed for the
purpose is:
3. The two winding transformer and the autotransformer of the circuit shown in Figure 27.7
are ideal. The current in the section BC of the autotransformer is
A
N1=200 NBC=20
N2=100 NBA=30
10A B
200 V
50 Hz
C
N1 : N2
Figure 27.7:
27.6 Problems
1. The following figure 27.8 shows an ideal autotransformer with number of turns of
various sections as NAB = 100, NCB = 60 and NDB = 80. Calculate the current drawn from
the supply and the input power factor when the supply voltage is 400V, 50Hz.
60 Ω
D C 20 Ω
A
B
400 V
50 Hz
Figure 27.8:
Version 2 EE IIT, Kharagpur
2. An ideal autotransformer steps down a 400 V, single phase voltage to 200 V, single phase
voltage. Across the secondary an impedance of (6 + j8)Ω is connected. Calculate the
currents in all parts of the circuit.
3. Calculate the values of currents and show their directions in the various branches of a 3-
phase, star connected autotransformer of ratio of 400 / 500 V and loaded with 600 kW at
0.85 lagging. Autotransformer may be considered to be ideal. It may be noted that,
unless otherwise specified, voltage value of a 3-phase system corresponds to line to line
voltage.
N2 = 125
b Y
3-phase transformer
3-phase auto transformer
NXY = 200 & NZY = 175
Figure 27.9:
Calculate line to line voltage at which the load receives power. If the load draws 10 A
current, calculate currents (a) in the section XZ & ZY of the autotransformer and (b) line
currents and coil currents of both the sides of the 3-phase, delta-star connected transformer.