Making light work

DALI LIGHTING
SYSTEMS
Lighting Controls

DLS – DALI Lighting Systems


DLS DALI LIGHTING
SYSTEMS
Addressable lighting control
DLS Connect is a fully featured DALI lighting control system
embedded within a best in class LightSpot HD sensor. Ideal
in modern work spaces with open soffits and areas needing
discrete fittings. It allows a simple implementation of a
powerful DALI addressable system into BEMS system to
create integrated room control systems and enables with
that smart integrated building solutions.

MAKING LIGHT WORK Making light work of Designed to DALI2 MAKING LIGHT WORK
installation and commissioning Standard
OF DALI ADDRESSABILITY OF DALI DLS
Lighting Control System in a sensor
•  • DALI2 brings an additional 64
Ex-Or has been creating award winning lighting control makes DLS simple and quick to install – ideal device addresses to the system Power – the built in Power Supply Unit (PSU)
systems since 1984. Our unrivaled expertise has delivered for exposed soffits where mounting a large provides power to the DALI network, which
• Backwards compatibility with
some of the industry’s most innovative solutions. DALI Lighting controller is unsightly
older DALI systems
is enough for the luminaires, sensors and
Systems (DLS) has been developed to simplify the installation, No additional controller hardware reduces
•  switches.
commissioning and maintenance of DALI addressable lighting. hardware cost and saves time on installation

DLS covering single - and Multi- room systems to fully DALI Addressable simple wiring (just 5
• 
integrated DALI lighting and BEMS integration.Ex-Or has core cable) Reduce wiring errors. Less time
planning wiring lay out and simple installation DLS COMPARISON
redefined DALI addressability.
Soft wiring – Easily make changes to lighting
•  FUNCTION DALI64SYLKPSU DALI64SYLK DALI64 DALINET
without physically re-wiring makes DLS ideal
for multiuse spaces easily reconfigure working
Making light work for spaces 5 core cable for 230V 2 core DALI and 2 core
Wiring 2 core DALI 2 core DALI
comfort and productivity Easy wireless and batteryless switches
• 
and DALI 2 core for Sylk for Sylk

integration over Bluetooth Low Energy help to


• Sophisticated DALI addressable functionality without the typical
save installations cost, increase flexibility and
complexity and high maintenance costs often associated with DALI Luminaires addressable per
ease retrofit 64 N/A
traditional DALI systems system
Easily create sophisticated lighting scenes
• 
• Create comfortable productive spaces by the simple programming
and groups for enhanced working or learning Programming & Commissioning Smart Device and Light Touch APP N/A
and recalling of up to 16 different lighting scenes and groups
environment
• Enable human centric lighting control to match circadian rhythms PSU Power Supply 150mA N/A N/A N/A
Easy configurable automated lighting
• 
when connected to Building Energy Management System (BEMS).
comfort and energy saving functionality Power consumption Network
Colour temperature of white light can be set to any value - from warm N/A 15mA 12mA 4mA
via Light Touch smart App, e.g. Daylight Sensors
white to daylight
harvesting enables further energy savings by
• Convert ‘push to make’ switches into DALI addressable switches reducing light levels as ambient light entering Bluetooth Low Energy Switching Yes Yes Yes No
using the DALI Switch Input Module. Providing up to 4 individual the building
Occupancy Zones 8 8 8 N/A
switch push functions that can be independently programmed to
perform a variety of functions on any of the groups, e.g. OnsSwitch, SBC BEMS Connection PCD7.LRxx-P5 PCD7.LRxx-P5 No No
dim, scene recall, etc

Honeywell Honeywell
2 DALI Lighting Systems DALI Lighting Systems 3
DALI64 DALI64SYLKPSUF
Sensor DALINETF Sensor
DALI64 is a fully featured standalone DALI lighting
control system embedded into a state of the
art LightSpot HD sensor with an advanced lens
DALI Scene Plate
design which provides a wide detection diameter
of 10 metres and with 159 points of detection an
excellent dependable level of occupancy detection
is achieved.

Designed to DALI 2 open protocol, providing 64


DALI luminaire addresses and 64 device addresses Modbus Wall Module Saia PCD7.LRL4-P5

(devices include sensors, switch inputs and scene


plates).
It allows the control of lighting through a range of controls including low
DALI Switch
energy bluetooth switches. Input Modules

DALI64 offers low total cost of ownership with no additional hardware


required and simplified installation. With the intuitive Light Touch
commissioning App many of the complications of traditional DALI
systems are eliminated.

SYSTEM OVERVIEW
INTEGRATED ROOM CONTROL TOGETHER WITH
PCD7.LRXX-P5
Recommendations:

• Not more than maximum of 32 DALI luminaires should be connected


via a standard 5 core cable (3 core mains supply and 2 core for DALI
bus) or a 2 core DALI network cable
• DALI64 allows up to 6 detection zones to be created within the DALI
network DALI64 enables up to 16 scenes and 6 groups to be created
to match user needs.
• DALI64 enables up to 16 scenes and groups to be created to match
user needs.
Note: The maximum of luminaires and devices and groups is depending on the power
consumption and the project system performance needs

Scenes and groups can be controlled using:

• A Mains switch can be connected directly into sensor


• Multiple DALI switch input modules can be added to allow ‘push-to
make’ switches to control the DALI network
• Multiple DALI scene plate can be added to enable simple and
effective selection of scenes
• Multiple Bluetooth wireless switches can be added to control groups
or scenes
DALI64SYLKPSUF DALI64F Sensor DALINETF Sensor
POWER Sensor Bluetooth Switches

• The DALI64SYLKPSU sensor provides 150mA to the DALI network. KEY


If more power would be needed, then it needs to be installed the 5 core cable
Sylk-bus Output from
3 core mains Modbus Output to Fan Coil Unit
DALI64SYLK with an external power supply. The total current within DALI64SYLKPSU Sensor
2 core DALI Bus
the DALI bus must never exceed 250mA.

Honeywell Honeywell
4 DALI Lighting Systems DALI Lighting Systems 5
DALI64 SYLK SYSTEM ARCHITECTURE
The DALI64SYLKPSU can be seamlessly integrate
to SBC BEMS system and Saia PCD Supervisor
with a simple polarity independent 2 wire Wallbus
connection. Saia PCD Supervisor
It allows the control of HVAC and lighting through a common interface.

With a low total cost of ownership due to no additional controller or


gateway hardware, reduced installation and engineering costs, DALI64
makes integration to Saia PCD Supervisor a great opportunity for new IP/Ethernet
installations but also retro fit to the many buildings with PCD7.LRxx-P5
and Saia PCD Supervisor already installed.

PCD1 Plant Controller


A 64 ADDRESS DALI
LIGHTING CONTROL
SYSTEM ENABLES Modbus or S-Bus

SMART INTEGRATED Modbus PCD7.LRxx-P5


BUILDING SOLUTIONS Room Controller

Seamless integration to SBC BEMS system. Allows SyIk-bus


an End User to visualise and control their lighting I/O Module
system through Saia PCD Supervisor. Dali
• Interface to an PCD7.LRxx-P5 room controller with simple 2 wire
DALI64
Wallbus connection

• Share occupancy and light level data with BEMS system


Modbus Wall
• Control of HVAC and lighting over 1 Modbus wall module possible over Module
Modbus interface of the PCD7.LRxx-P5 room controller

• Simple lighting commissioning experience with intuitive App

• Allows creation of maintenance & energy consumption dashboards

• Distributed intelligence provides system redundancy – Lighting works


independently from BEMS and HVAC controller

• Allows System Integrators to integrate sophisticated lighting controls


simply and effectively into BEMS system

Honeywell Honeywell
6 DALI Lighting Systems DALI Lighting Systems 7
SYSTEM CONTROL ADVANTAGES FACILITY COST SAVINGS
Improving Employee productivity and Create real time energy management and maintenance reports
wellbeing or help patients heal faster or • 
Visualisation of energy usage
enhance student learning by utilising
network time schedules to control • 
Luminaire run-time – create preventative maintenance reports
luminaire colour temperature to match • 
Arc power consumption of luminaires
natural circadian rhythm to create
human centric lighting which influence • 
Desired/actual lux levels
various physiological and psychological
processes. This enable benefits in Monitor occupancy data to create room usage reports
different verticals like Offices, Schools, • 
Occupancy data – hours
Healtcare, Hospitality, Retail and
Manufacturing. Staff optimization
• 
Create cleaning rotas based on occupancy - saving time and money
• Select and control lighting scenes
through Saia PCD Supervisor Building space optimization
• Utilise the supervisor to manage light • 
Reporting frequency of space use to maximise room occupancy and
levels, time delays and even change booking
between Absence and Presence mode
• Recall groups and scenes from the head Emergency Test and Reporting
end
• Visualise the status of emergency lighting fittings
• Schedule all of the legally required emergency fitting tests, visualise the
results in the Supervisor and email a test report or alarms

ENGERGY COSTS
SAVING

Combining BEMS/HVAC
and Lighting Controls will
significantly improve the
energy performance of
the building. Integrating
lighting and HVAC control VISUALISATION
together into BEMS For example empirical data can • Visualise lighting and BEMS through
Saia PCD Supervisor
contributes to reaching be used to predict optimum start
Class A energy efficiency and stop times based on historical • Real time occupancy status of
EN15232. occupancy data. building zones
• Current luminaire status, including
lamp failure, in each building zone

Honeywell Honeywell
8 DALI Lighting Systems DALI Lighting Systems 9
DALI64 DALI64
MAKING LIGHT WORK
COLOUR-CODED CONNECTORS

PROGRAMMING WITH EASE


Easy to commission and maintain • Pluggable, colour-coded connectors make it easy to see
what goes where and reduce wiring errors
• Surface mount or flush mount sensors with locking rings
DALI64 has been designed to simplify commissioning.
or spring clips give you complete installation flexibility
We have removed much of the complexity associated
with DALI addressable systems using Light Touch, our • Recall your programmed scenes and groups with our DALI
scene plates or standard switches via DALI input module
free to download and use commissioning App.

DALI64 enables the creation of predictive maintenance


LOCKING RING SPRING CLIP
schedules allowing luminaire replacements to be made
FLUSH MOUNT FLUSH MOUNT
during unoccupied times. Additional Maintenance cost
savings will be realised as Light Touch App eliminates
the costs traditionally associated with luminaire
replacement in DALI systems.

Intuitive programming
Light Touch allows you to connect to the DALI system
over Bluetooth and begin a bus scan. Any luminaire BLUETOOTH® LOW ENERGY SWITCHES DALI 6 BUTTON SCENE PLATES
or DALI device is visually presented in a carousel and
can be dragged and dropped with a simple one finger
Luminaires can be switched on and off, dimmed
action into a user defined map of the space. Once you
and grouped via the touchplate with six individually
have all your lights and devices positioned on your
assignable keys.
building map you can then set up groups and scenes
with minimum fuss. • Capacitive touch – requires less pressure to operate and
Daylight harvesting offers additional energy savings increased durability as there are no moving parts
by automatically regulating the luminaries as the • High-quality appearance with real glass display – easy to clean
ambient light levels change throughout the day. • Power supply via DALI line
Colour temperature can also be configured allowing
• Wireless – instant installation and location flexibility,
circadian rhythms – optimising occupant wellbeing reducing disruption and cost, as there is no need to run
and productivity. switching cables
• Self‑powered innovative patented technology to ‘harvest’
energy means zero maintenance as there are no batteries
to change
• Ultimate flexibility as each switch can control up to 64
luminaires, enabling dimming and scene recall etc DALI SWITCH INPUT MODULE
• Energy savings with additional local control, alongside
the network sensors, users can create an energy efficient DALI switch input modules can
environment be added to convert normal
• Bluetooth® wireless switches - energy harvesting single ‘push-to-make’ switches
and double rocker switches eliminate the need for wiring to DALI switches.
and speed installation time significantly
• Wireless switches can be fixed to surfaces using screws
Scan to discovers On-screen prompts lead you or double sided mounting film
luminaires through configuration

Honeywell Honeywell
10 DALI Lighting Systems DALI Lighting Systems 11
DALI LIGHTING CONTROLS
PRODUCT RANGE
DALI LIGHTING CONTROLLERS WITH BMS CONNECTION AND INTERGRATED POWER SUPPLY ACCESSORIES
PRODUCT NUMBER DESCRIPTION POWER PRODUCT NUMBER DESCRIPTION POWER
DALI2 64 Address Lighting Controller with 150mA Integral Power
DALI64SYLKPSUF Mains
Supply and Sylk Bus for direct BMS connection - Flush Mount 28001987 6 button Scene Plate – On/Off – Up/Down + 3 Scenes 10mA
DALI2 64 Address Lighting Controller with 150mA Integral Power
DALI64SYLKPSUS Mains
Supply and Sylk Bus for direct BMS connection - Surface Mount
28001989 6 button Scene Plate – On/Off + 6 Scenes 10mA

DALI LIGHTING CONTROLLERS WITH BMS CONNECTION


DALI Switch input module - enables 4 switch inputs per
PRODUCT NUMBER DESCRIPTION POWER DLS4IM 4mA
module
DALI2 64 Address Lighting Controller with Sylk Bus for direct BMS
DALI64SYLKF 15mA
connection (need external power supply) - Flush Mount
00030366 Bluetooth wireless switch 1 gang N/A
DALI2 64 Address Lighting Controller with Sylk Bus for direct BMS
DALI64SYLKS 15mA
connection (need external power supply) - Surface Mount
00030666 Bluetooth wireless switch 2 gang N/A

DALI LIGHTING CONTROLLERS FOR GROUP EXTENSION


10 metre DALI / QuickLink lead - connects DALI64
PRODUCT NUMBER DESCRIPTION POWER LSHDQBL2210 N/A
sensors simply

DALI64F DALI2 64 Address Lighting Controller Bus Powered - Flush Mount 12mA
Remote Infrared Hand-held unit c/w Wall Bracket -
QCUB light level adjustment for 1 group and recall six lighting N/A
DALI2 64 Address Lighting Controller Bus Powered - scenes to change
DALI64S 12mA
Surface Mount
Light Touch
Free commissioning App optimised for 9” tablet N/A
by Honeywell
DALI NETWORK SENSORS FOR DETECTION-ZONE EXTENSION
PRODUCT NUMBER DESCRIPTION POWER

DALINETF DALI2 Network Sensor Bus Powered - Flush Mount 4mA

DALINETS DALI2 Network Sensor Bus Powered - Surface Mount 4mA

Honeywell Honeywell
12 DALI Lighting Systems DALI Lighting Systems 13
Saia-Burgess Controls AG
Bahnhofstrasse 18 3280 Murten, Switzerland
Telephone headquarters +41 26 580 30 00
Telephone SBC Support +41 26 580 31 00
Fax +41 26 580 34 99

Email Support: support@saia-pcd.com


Support site: www.sbc-support.com
SBC site: www.saia-pcd.com

International offices & SBC sales subsidiaries:


www.saia-pcd.com/contact

Honeywell May 2021


www.saia-pcd.com © 2021 Honeywell International Inc.