Basics of EMI and EMC
Basics of EMI and EMC
Basics of EMI and EMC
Earthing, equipotential bonding and earthing are a major part of all new buildings and
facilities. These have a great influence on the EMC of the system and the mitigation of EMI
wherever applicable.
As the number of electronic devices increases, every building owner is required to abide by
all applicable EMC regulations and laws. In regards to telecommunications equipment and
cabling systems, there is often an uncertainty about what to do and to find the correct way
for a proper installation.
This guide is intended to give some basic explanation of these issues as they relate to
cabling systems. In general EMC is a vast subject and there are various books and literature
available.
This guide briefly highlights the parts covering earthing, equipotential bonding and electrical
power distribution. But all parts are important in regards to EMC and are valid for shielded
and unshielded cabling systems.
There is often a misunderstanding between the requirements for earthing and equipotential
bonding for both shielded and unshielded systems.
This misunderstanding is often the problem in practise. It is often assumed that this is the
responsibility of the electrical installer or the architect and not the responsibility of the data
cabling installer. But in fact it is a responsibility shared by all parties. In regards to EMC it is
the responsibility of the consultant and or architect to ensure the installed systems are
compliant.
EMC is more and more important and therefore its relevance is crucial to understand.
Therefore European standards continue to emphasis this importance.
With 10 Gigabit Ethernet most of the existing rules have to be reconsidered. The future is
shielded and EMC is the key issue.
2
Earthing and equipotential bonding
EMI and EMC are heavily dependant on sounding earthing and equipotential bonding
principles. The main functions of earthing are Safety and EMI mitigation. The primary
function of earthing is to:
Save the life of humans and animals in case of any electrical fault.
This can be achieved by installing a low impedance connection to the protective conductor.
At the other end of this conductor there is a connection to an electrode in the ground.
The main connection to ground is called the protective earth (PE) and is recognised by the
typical green/yellow insulation colour.
A second function is to have a defined path for surges in the power system, lightning and
emissions from outside sources like radar station, broadcast stations etc. It is fundamental to
understand, that only a proper earthing system can prevent harm from the issues referred to
above. The intention of European standard EN 50310 is to provide the optimum earthing and
equipotential bonding conditions for buildings. Even though the focus of this discussion is for
buildings with communication technology installation, the standard shall be applied for at
least all new buildings and if possible for existing buildings.
All office and company buildings today have a communication technology installation, and
even more so residential buildings. Many problems can result from an improper earthing
system. In practice screening, earthing and equipotential bonding will be combined. To make
it clear:
The latest edition of EN 50310 and EN 50174-2 state clear that these efforts are
applicable to any IT system!
Fig 2: Termination earthing system to steel armour for Mesehd bonding concept (Obo Bettermann)
Functional earthing: A functional earth connection serves a purpose other than providing
protection against electrical shock. In contrast to a protective earth connection, a functional
earth connection may carry a current during the normal operation of a device. Functional
earth connections may be required by devices such as surge suppression and
electromagnetic-compatibility filters, some types of antennas and various measurement
instruments. Generally the protective earth is also used as a functional earth though this
requires care in some situations.
Note: A good functional earthing system is necessary for safety reasons! A cabling
system requires a well designed earthing system to perform properly.
This is applicable for both unshielded and shielded systems! Even when a fibre optic
cabling system is installed a fully functional earthing system is mandatory (earthing
of metal enclosures)!
4
Equipotential bonding
This refers to the need to connect all metalwork or conducting parts within an electrical panel
or on a machine to the protective earth. Equipotential bonding has a safety and an EMC
aspect. This is also the case in a house or commercial building, where ideally all metallic
components are connected to the equipotential bonding network. These include:
• All metal conduits within the building, e.g. water and gas conduits
• All metal parts of the building or the construction
o steel girder
o Metal Facade
o Steel in cement
• Metal cabinets for data or power distribution
• Raised floors with metal uprights
• Metal cable conduit
5
All connections will terminate at
the main equipotential bonding
terminal.
Note:
• PE Power system
• PE Telecom system
• Upright Pins of raised
floors
Fig 5: Main bonding terminal
• Metallic cable trays
• All parts of a cabinet
6
Facts:
• Earthing and equipotential bonding is a must for safety and EMC reasons
• A TN-S system is mandatory for all buildings with IT!
• TN-S shall be installed and is recognised by most electrical standards
• The equipotential system (equipotential bonding) has to be part of the EMC design
• All metal parts have to be included
• A meshed equipotential bonding system is better then a star equipotential bonding
system
For residential buildings and small buildings serviced directly by the power authority, 4-
conductor power cables will enter the buildings.
Note: TN-S is preferred in EN 50310 and meanwhile the default system in accordance
to most local electrical wiring regulations!
In some countries (e.g. Australia and New Zealand, the TN-C-S earthing system is
used.
7
Installation of IT cabling systems
As any building today contains IT equipment, electrical and other standards reflect this in
their content.
This means that all rules and recommendations in regards to EMC and safety apply to any
kind of IT system. From a practical point of view, the most common equipment includes
racks and metal panels, metal path ways, raised floors with metal frames.
In regards to safety and EMC all equipment needs a defined path to EB (equipotential
bonding).
In the cabinet all patch panels must have very good electrical connection (zero dc
resistance) to the cabinet. This cabinet shall be connected to the equipotential bonding
system. All bonded panels have to
be terminated to the terminal bar
(Fig 85). The insulation colour of
the earthing conductor shall be
green/yellow as used for the PE.
8
Shielded systems
New products provide automatically excellent earth
connection to the panel. The “closed” principle is
done by design. Once the cable is terminated the
jack has just to be clicked into the panel, and that’s
all.
Old technology products have UTP jacks where
the installer has to “build” the shield around it.
By installing the shield to each jack the installer atomically fulfils the requirement of
EN 50310:
“Cable screens shall be bonded directly to racks, cabinets or where required to the
dedicated SRPP at least at each end. Circumferential (i. e. 360 °) connections are most
effective.”
Note: The only additional effort is the shield termination to the jack. This takes about
10 seconds for the integrated shielded technology designed products. The
connection to the EB system of the shielded link
is done by the panel. As stated earlier, earthing
and equipotential bonding have to be done for all
IT systems!
The total channel shall contain shielded products only. The screen shall be terminated on
both sides. This is done by terminating the screen at both sides with the connecting
hardware, in our example the jacks. In case of modern die cast jacks this is done
automatically. Old fashion products need an extra connection which causes difficulties.
This complete channel shall be terminated to the equipotential bonding system. This is done
by the panel, as this has to be terminated to the equipotential system (SRPP).
In the case of die cast jacks (integrated shielded technology) the cable link includes a
connection at the fixing points in the panel, (see picture above).
9
Outlets do not have to be bonded. To improve the overall EMC performance the link is
connected at the device side to the PE of the power system. All Switches, NIC’s and
Notebooks have shielded RJ 45 ports. Those ports are connected to the PE of the power
side in the device.
In this configuration the shielded system provides additional EMC performance and support
the idea of a meshed concept.
Cable routing
With higher data rates and more electronic devices installed, cabling installation and routing
have to be done in the proper way. Much of this useful information can be found in EN
50174-1/-2.
The main issue for IT systems is the sparation from power cables, as they are mostly
commonly installed in one cable tray system.
Today EN 50174-2 contains the following table:
non-metallic divider
As shown above, metal dividers or cable screens help to reduce the separation. This is the
best way, otherwise large separations would be required. There is no other way. Best
example is a screened power and IT cable, where therequired separation distance is 0 mm!
Note: If the cable conduit is metallic, it has to be bonded properly!
10
The fairy tales
Although the physical environment is clear, some parties propagate misleading statements
and confusion. The following pages explain basic of physics and follow existing standards
and EMC rules.
Fairy tale No. 1
If a shielded system is used, the screen is propagating EMI, is dangerous and an earth
loop is creating problems.
• PE of electrical system
• Metallic parts of the building
• Metallic service conduits (e.g. water
conduits)
• All metal-enclosed IT devices
o Cabinet
o Panels
o Screen of IT cabling system Fig 12: Euipotential bonding
Conclusion
• No loop
• No antenna effect
There can’t be any loop as everything is at zero 0 potential. This is again the main intention
of equipotential bonding.
To propagate EMI any kind, electrical energy must be present. This can only be done, if a
conductor is carrying some kind of electrical energy. The screen of a cabling system is
terminated to to the equipotential bonding network, which, under normal conditions carries
no current and has 0V potential to earth.
Therefore the screen is unable to propagate any EMI.
11
Fairy tale No. 2
The Symmetry (Twist) is the only way to provide good EMC conditions.
To explain this we have to come back to the basics. Modern data transmission is called
symmetrical data transmission. All copper systems (UTP and STP) have the same design.
Each system contains 4 pairs which are twisted.
The degree of symmetry of a pair defines the ability of a cabling system to provide a level of
EMC. This is called coupling attenuation.
Note: Coupling attenuation is applicable to both, shielded and unshielded systems
and is part of the global cabling standard IS 11801 /EN 50173
This parameter is an indicator the quality of a cabling system is to mitigate any EMI.
There are two ways to fulfil this.
• Twisting
• Shielding
In pactice each cable is a victim of electromagnetic waves and disturbing signals from other
cables, mostly power cables.
Now the facts:
UTP STP
(Symmetry, Balanced (Symmetry, Balanced Pair,
Pair) Screen)
EMC Mitigation mechanism Twist Rate Twist Rate + EM Screen
The Pair Twist is just one component of the EMI mitigation method. The complete solution to
EMI mitigation is Pair Twist and a shield. This results in 100% more coupling attenuation
and explains why all systems with PimF cable have no issues with ANEXT. The Twist Rate
of a UTP cable is higher than that of an FTP or PimF cable. This results in higher TCL. But
this is just 50% of the total. Shielded cables have a shield, therefore the Twist Rate is
different and both have to taken into consideration.
12
Fig 13: The real EMC situation
13
Quick comparison:
UTP STP
Conclusion
The efforts and cost for a well designed eathing and bonding system is independent of the
kind of media that is installed. This is recognised by EN 50310 and EN 50174-2.
The illusion to save money or avoid trouble by installation of fibre optic cables or UTP cables
is an old fairy tale. All standards state this clearly in their publications. Fibre connections
shall be installed between buildings. This is applicable for large installations and plants.
With respect to 10 Gigabit Ethernet, the combination of a shielded system and a well
designed EB system provides maximum EMC performance of the building. The ANEXT and
background noise issues emphasise this.
Consultants in particular should take care of these issues during the planning phase.
14
Facts:
• Earthing and equipotential bonding are a must for safety and EMC reasons
• They are applicable without exception for any IT system
• The cable screen has to be terminated on both sides with the connecting
hardware
• The whole channel has to be bonded at least once to the EB system (Panel)
• Outlets do not have to be bonded
• The total effort for earthing and bonding is the same for all cabling systems
With 10 Gigabit over copper cabling, shielded systems show the advantage of a shield by
completely meeting the 100 m channel ANEXT performance requirement by a margin of
about 20 dB.
The overall future parameter will be Coupling Attenuation for cabling systems and their EMC
performance. While STP systems with PimF cables have about 90dB of coupling
attenuation, UTP systems have only 45 dB. In any case, for both technologies a well
designed Earthing and Bonding system is mandatory. There is no reason anymore not to
join the shielded world.
15
AMP NETCONNECT Regional Headquarters:
North America Latin America Europe Mid East & Africa Asia Pacific
Harrisburg, PA, USA Buenos Aires, Argentina Kessel-Lo, Belgium Cergy-Pontoise, France Hong Kong, China Sydney, Australia
Ph: +1-800-553-0938 Ph: +54-11-4733-2200 Ph: +32-16-35-1011 Ph: +33-1-3420-2122 Ph: +852-2735-1628 Ph: +61-2-9407-2600
Fx: +1-717-986-7406 Fx: +54-11-4733-2282 Fx: +32-16-35-2188 Fx: +33-1-3420-2268 Fx: +852-2735-1625 Fx: +61-2-9407-2519
16 04/07 © 2007 – Tyco Electronics AMP Deutschland GmbH – All rights reserved
TYCO, AMP and NETCONNECT are trademarks. http://www.ampnetconnect.com/EMEA