Zero Export DG PV Power Management
Zero Export DG PV Power Management
Zero Export DG PV Power Management
CLASSIFICATION | INTERNAL 1
What is Zero Export & Power Management?
It simply means
“NO POWER EXPORT TO GRID”
Solar energy supplies the local load instead of the public utility by monitoring /
limiting the voltage and current as per the load requirement.
Zero Export device will monitor & then accordingly Inverter can generate the same
unit or less unit than the load.
Requirement-
• In India where net metering is required, sometimes local DISCOM provide the
facility in 6-8 months. Due to uni-directional meter available on site, it pays a
lot of cost to the client because of extra un-used units generated on site.
Therefore, clients prefer to go with zero export device.
CLASSIFICATION | INTERNAL 2
HAVELLS – YOUR TRUSTED & RELIABLE SOLAR PARTNER
Right System Design Zero Export Solutions for Enviro GTi Inverters
ELECTRICAL DESIGN
R Y
B
Zero Export & DG-PV Management
Zero Export Device required for ZERO EXPORT DEVICE FOR ANTI REVERSE POWER CONTROLLER (ARPC) FOR
1-Ø INVERTERS 3-Ø INVERTERS
restricting export to Grid where no
Net Metering is available
Zero Export CT/ ARPC is always installed between LT Panel & Net Meter/ Transformer
CLASSIFICATION | INTERNAL
HAVELLS – YOUR TRUSTED & RELIABLE SOLAR PARTNER
Right System Design DG-PV Synchronising Panel for Grid Tie Inverters
ELECTRICAL DESIGN
CLASSIFICATION | INTERNAL 5
Zero Export Device for Single Phase
In Havells GTi Single Phase Inverters, zero export facility is in-built, Current Transformer
(CT) is to be installed externally.
Single Phase Inverter range is given below-
Model-
• Enviro GTi1100NG
• Enviro GTi2200NG
• Enviro GTi3000NG
• Enviro GTi5000D
CLASSIFICATION | INTERNAL 6
What is Current Transformer?
A Current Transformer (CT) is a type of transformer that is
used to reduce or multiply an alternating current (AC). It
produces a current in its secondary which is proportional to
the current in its primary.
Uses-Current transformers are the current-sensing units of
the power system and are used at generating stations,
electrical substations, and in industrial and commercial
electric power distribution.
Applications-
Measuring current metering, protections, Controls, Isolations,
etc.
CLASSIFICATION | INTERNAL 7
Zero Export Device for Single Phase
• The standard CT which comes with zero
export device is Split Type of 150Amp, 16
mm dia only.
• Zero Export Device in-built into Single Phase
Inverter can take maximum 150Amp current
only.
• In Single Phase system, we can go for zero
export for connected load upto 5KW &
cable from LT Panel to net meter dia should
be less than 16mm.
• We have to connect CT with Inverter
through Ethernet cable to enable zero
export of the system.
CLASSIFICATION | INTERNAL 8
Cable Size in Single Phase System
• Current Transformer is placed in cable from LT Panel to Net Meter.
• Generally cable in single phase system from LT Panel to Net Meter
is of 2CX4sqmm/6sqmm XLPE Un-armoured.
• From table we can observe that upto 2C X 16sqmm, overall dia is
14mm, so we can use Havells Std. Current Transformer 150Amp,
2C XLPE Un-armoured cable
16mm dia.
• NOTE- It is recommended to advise Installer to check cable size
on site as in many sites cable tapings are there which increase
cable dia and results in failure of CT fittings.
CLASSIFICATION | INTERNAL 9
Zero Export Device for Single Phase
CLASSIFICATION | INTERNAL 10
Zero Export Device for Single Phase
CLASSIFICATION | INTERNAL 11
Anti-Reverse Power Controller for Three Phase
Operation Principle:
• ARPC will detect grid voltage on R,Y,B input and current on
CT, the CT are connected before the local load input.
• The ARPC can calculate the reverse power by voltage and
current.
• In case local load power is less than solar inverter power,
then there will be reverse power detected on ARPC. ARPC
will give the command to the string inverter by relay output
to inverter IN1, IN2, IN3, IN4.
• The IN1, IN2, IN3, IN4 on/off status determines the inverter
output power, in this way, inverter will decrease its power
till there is no reverse power on ARPC (zero export.)
CLASSIFICATION | INTERNAL 12
Anti-Reverse Power Controller for Three Phase
CLASSIFICATION | INTERNAL 13
Anti-Reverse Power Controller for Three Phase
• Pls Note- ARPC in 3 phase can be installed maximum upto 100KW. If DC Capacity is
more than 100KW then customer needs customized ARPC which can support secondary
current 5Amp.
• Second option is customer can use regular Std. ARPC with CT ratio 1000:1 as ARPC
supports current transformer ratio (secondary)- 0-1A.
• In this case Havells will suggest Current Transformer rating to Installer to buy from the
market as per the customer’s sanctioned load.
• Pls Note- For customized Zero Export Device may take 6-8 weeks to deliver.
CLASSIFICATION | INTERNAL 14
Cable Size in Three Phase System
• Generally cable in three phase system from LT Panel to Net
Meter/Transformer is of 3.5C / 4C XLPE armoured. 3.5C XLPE
• From table we can observe that upto 3.5C X 150sqmm, armoured cable
overall dia is 44mm, so we can use Havells Std. Current
Transformer.
• (44/3.5= 12.5mm) Therefore, we can use three nos of CT, one
CT per phase.
• NOTE- It is recommended to advise Installer to check cable
size on site as in many sites cable tapings are there which
increase cable dia and results in failure of CT fittings.
CLASSIFICATION | INTERNAL 15
Equipment required & Scope in Three Phase
CLASSIFICATION | INTERNAL 16
Equipment required & Scope in Three Phase
CLASSIFICATION | INTERNAL 17
Case Study
CLASSIFICATION | INTERNAL 18
Case Study
Pls Note- ARPC is always installed between LT Panel & Net Meter/ Transformer
CLASSIFICATION | INTERNAL 19
Case Study
CLASSIFICATION | INTERNAL 20
Case Study
CLASSIFICATION | INTERNAL 21
Case Study
CLASSIFICATION | INTERNAL 22
Case Study
CLASSIFICATION | INTERNAL 23
Case Study
If there are multiple Inverter, then we have to loop ARPC & all Inverters with Ethernet cable.
CLASSIFICATION | INTERNAL 24
Case Study
CLASSIFICATION | INTERNAL 25
DGPV POWER MANAGEMENT
CLASSIFICATION | INTERNAL 26
WHY WE REQUIRE DG PV SOLUTION?
• To Run the Solar Plant in synchronization with DG when Grid is not available to restrict the back feed ( Push back )
of solar Power to Genset and to maintain the DG on 30 % load.
EXAMPLE : A factory having Connected Load = 600 KW
Solar Plant Capacity = 500 KW
DG Rating – 600 KVA
CASE 1 : Suppose the Running Load is 400 KW and solar Generation is of 300 KW and DG is operational .
30 % load to be maintained on DG i. e 30 % of 600 KVA = 180 KVA= 144KW (approx. 150kW)
Load shared Solar Plant : 400- 150 = 250 KW
AS the extra Energy Produced by Solar 300- 250 KWp = 50 KW
To restrict the back feed ( Solar Pushback) to DG ,the DG PV management system is required to protect the DG set.
CLASSIFICATION | INTERNAL
INITIAL INFORMATION BEFORE SELECTING THE SOLUTION
S.NO Parameters/points to be checked Comments
CLASSIFICATION | INTERNAL
S.NO Parameters/points to be checked Comments
CLASSIFICATION | INTERNAL
DG PV Controllers
1.Controllers are used to control the power by sensing the Load from Grid Or DG and correlated to the Power
being generated by solar PV plant to ensure that there is no back feed of power to the grid or DG as the case
may be.
2. Controllers having the LCD display on it which shows the various parameters .
B) Load on DG
C) Load on Grid
CLASSIFICATION | INTERNAL
DG PV Solutions- Available
CLASSIFICATION | INTERNAL
DG PV SOLUTION With
Single Step Control with Single DG
CLASSIFICATION | INTERNAL
CLASSIFICATION | INTERNAL
Zero Export Solution & linear Control with multiple DG
CLASSIFICATION | INTERNAL
LINEAR ZERO EXPORT & POWER MANAGEMENT
CLASSIFICATION | INTERNAL
CASE STUDY – GHILOTH PROJECT
CLASSIFICATION | INTERNAL
DG PV System installation was done at Havells Plant of Lloyd AC
unit at Ghiloth Rajasthan .
The solar Panels are located at factory roof and inverters are
placed at production area on a elevated platform at 6 locations.
CLASSIFICATION | INTERNAL
6 nos of ACDB are located were located
at Production area. Each ACDB is having a
controller to sense the voltage and current
which can be monitored at hybrid Panel
Display.
CLASSIFICATION | INTERNAL
The DG PV main controller shows all the Parameters and real time
power generation showing solar is connected with 5 nos of power
sources .
( 2 nos of transformers and 3 DG )
All sources generating power as per plant demand and feeding to a
single bus
CLASSIFICATION | INTERNAL
BLOCK DIAGRAM
CLASSIFICATION | INTERNAL
Pls contact if any Zero Export/APRC/DGPV
Management related query-
• Uttkarsha – Uttkarsha.shrivas@Havells.com
• Vikash- vikash3.kumar@havells.com
• Manish- manish2.singh@Havells.com
• Rakesh- rakesh.Neithilath@Havells.com
• Manas- manas.Sachan@Havells.com
• Pradeep- Pradeep.menon@Havells.com
CLASSIFICATION | INTERNAL 41
CLASSIFICATION | INTERNAL 42