Zero Export DG PV Power Management

Download as pdf or txt
Download as pdf or txt
You are on page 1of 42

ZERO EXPORT & POWER MANAGEMENT

CLASSIFICATION | INTERNAL 1
What is Zero Export & Power Management?
It simply means
“NO POWER EXPORT TO GRID”

Solar energy supplies the local load instead of the public utility by monitoring /
limiting the voltage and current as per the load requirement.
Zero Export device will monitor & then accordingly Inverter can generate the same
unit or less unit than the load.
Requirement-
• In India where net metering is required, sometimes local DISCOM provide the
facility in 6-8 months. Due to uni-directional meter available on site, it pays a
lot of cost to the client because of extra un-used units generated on site.
Therefore, clients prefer to go with zero export device.
CLASSIFICATION | INTERNAL 2
HAVELLS – YOUR TRUSTED & RELIABLE SOLAR PARTNER

 Right System Design Zero Export Solutions for Enviro GTi Inverters

ELECTRICAL DESIGN
R Y

B
Zero Export & DG-PV Management

 Zero Export Device required for ZERO EXPORT DEVICE FOR ANTI REVERSE POWER CONTROLLER (ARPC) FOR
1-Ø INVERTERS 3-Ø INVERTERS
restricting export to Grid where no
Net Metering is available

 DG-PV Synchronising Control Panel


is required to ensure no push back
of power to DG Set

Zero Export CT/ ARPC is always installed between LT Panel & Net Meter/ Transformer

CLASSIFICATION | INTERNAL
HAVELLS – YOUR TRUSTED & RELIABLE SOLAR PARTNER

 Right System Design DG-PV Synchronising Panel for Grid Tie Inverters
ELECTRICAL DESIGN

• To Run the Solar Plant in


synchronization with DG
Set when Grid is not
available
Slave Controller Panel Master Controller Panel
• To restrict “Push Back” of
Solar PV to DG under low
load conditions
• Ensure Solar Power share
to Load does not exceed
30% of DG rated output
under low load conditions
• The DG PV management
system can also be
expanded for enabling
Zero export to Grid in
larger PV Plants
Schematics of DG-PV Sync
System
CLASSIFICATION | INTERNAL
Inputs required from End customer/Dealer/System
Integrators for Zero Export-

• System configuration of the Plant (Solar DC Capacity).


• Incoming cable size from Net Meter/Transformer to customer’s LT panel.
• Existing CT rating and its ratio .
• Connected Load of the site.
• Distance from Inverter to meter.
• Electrical SLD of Plant.

CLASSIFICATION | INTERNAL 5
Zero Export Device for Single Phase
In Havells GTi Single Phase Inverters, zero export facility is in-built, Current Transformer
(CT) is to be installed externally.
Single Phase Inverter range is given below-
Model-
• Enviro GTi1100NG
• Enviro GTi2200NG
• Enviro GTi3000NG
• Enviro GTi5000D

CLASSIFICATION | INTERNAL 6
What is Current Transformer?
A Current Transformer (CT) is a type of transformer that is
used to reduce or multiply an alternating current (AC). It
produces a current in its secondary which is proportional to
the current in its primary.
Uses-Current transformers are the current-sensing units of
the power system and are used at generating stations,
electrical substations, and in industrial and commercial
electric power distribution.
Applications-
Measuring current metering, protections, Controls, Isolations,
etc.

CLASSIFICATION | INTERNAL 7
Zero Export Device for Single Phase
• The standard CT which comes with zero
export device is Split Type of 150Amp, 16
mm dia only.
• Zero Export Device in-built into Single Phase
Inverter can take maximum 150Amp current
only.
• In Single Phase system, we can go for zero
export for connected load upto 5KW &
cable from LT Panel to net meter dia should
be less than 16mm.
• We have to connect CT with Inverter
through Ethernet cable to enable zero
export of the system.

CLASSIFICATION | INTERNAL 8
Cable Size in Single Phase System
• Current Transformer is placed in cable from LT Panel to Net Meter.
• Generally cable in single phase system from LT Panel to Net Meter
is of 2CX4sqmm/6sqmm XLPE Un-armoured.
• From table we can observe that upto 2C X 16sqmm, overall dia is
14mm, so we can use Havells Std. Current Transformer 150Amp,
2C XLPE Un-armoured cable
16mm dia.
• NOTE- It is recommended to advise Installer to check cable size
on site as in many sites cable tapings are there which increase
cable dia and results in failure of CT fittings.

CLASSIFICATION | INTERNAL 9
Zero Export Device for Single Phase

Current Transformer Current Transformer connection with Ethernet cable

CLASSIFICATION | INTERNAL 10
Zero Export Device for Single Phase

CLASSIFICATION | INTERNAL 11
Anti-Reverse Power Controller for Three Phase

Operation Principle:
• ARPC will detect grid voltage on R,Y,B input and current on
CT, the CT are connected before the local load input.
• The ARPC can calculate the reverse power by voltage and
current.
• In case local load power is less than solar inverter power,
then there will be reverse power detected on ARPC. ARPC
will give the command to the string inverter by relay output
to inverter IN1, IN2, IN3, IN4.
• The IN1, IN2, IN3, IN4 on/off status determines the inverter
output power, in this way, inverter will decrease its power
till there is no reverse power on ARPC (zero export.)

CLASSIFICATION | INTERNAL 12
Anti-Reverse Power Controller for Three Phase

• In Three Phase System, we have to install Zero


Export Device which is called Anti-Reverse
Power Controller with Current Transformer per
phase.
• We can use ARPC with connected load provided
per phase current rating should be upto
150Amp & cable dia of R, Y, B per phase
conductor should less than 16mm provided
there is no DG on site.
• We will supply our Std. CT of 150Amp current
rating 3 nos total.
ARPC have four nos of inputs.

CLASSIFICATION | INTERNAL 13
Anti-Reverse Power Controller for Three Phase
• Pls Note- ARPC in 3 phase can be installed maximum upto 100KW. If DC Capacity is
more than 100KW then customer needs customized ARPC which can support secondary
current 5Amp.

• Second option is customer can use regular Std. ARPC with CT ratio 1000:1 as ARPC
supports current transformer ratio (secondary)- 0-1A.

• In this case Havells will suggest Current Transformer rating to Installer to buy from the
market as per the customer’s sanctioned load.

• Pls Note- For customized Zero Export Device may take 6-8 weeks to deliver.

CLASSIFICATION | INTERNAL 14
Cable Size in Three Phase System
• Generally cable in three phase system from LT Panel to Net
Meter/Transformer is of 3.5C / 4C XLPE armoured. 3.5C XLPE
• From table we can observe that upto 3.5C X 150sqmm, armoured cable
overall dia is 44mm, so we can use Havells Std. Current
Transformer.
• (44/3.5= 12.5mm) Therefore, we can use three nos of CT, one
CT per phase.
• NOTE- It is recommended to advise Installer to check cable
size on site as in many sites cable tapings are there which
increase cable dia and results in failure of CT fittings.

CLASSIFICATION | INTERNAL 15
Equipment required & Scope in Three Phase

Anti-Reverse Power Controller (ARPC)- Std Split Type Current Transformer-Havells


Havells scope. scope, Customized CT- Installer’s scope.

CLASSIFICATION | INTERNAL 16
Equipment required & Scope in Three Phase

From ARPC to R,Y,B • From ARPC to CT-


Phase-Voltage cable, CT Cable, twisted
Cable section 2-4 Sq shield Ethernet
mm- Installer’s Cable – Installer’s
scope. scope.
• From ARPC to
Inverter- Load
limiting cable,
twisted shield
Ethernet Cable –
Installer’s scope.

CLASSIFICATION | INTERNAL 17
Case Study

CLASSIFICATION | INTERNAL 18
Case Study

Pls Note- ARPC is always installed between LT Panel & Net Meter/ Transformer
CLASSIFICATION | INTERNAL 19
Case Study

ARPC to R,Y,B phase for voltage reference-


4sqmm copper cable

CLASSIFICATION | INTERNAL 20
Case Study

ARPC to CT- Ethernet cable for current signal.

CLASSIFICATION | INTERNAL 21
Case Study

Inverter to ARPC Cable – Ethernet cable

CLASSIFICATION | INTERNAL 22
Case Study

CLASSIFICATION | INTERNAL 23
Case Study

If there are multiple Inverter, then we have to loop ARPC & all Inverters with Ethernet cable.

CLASSIFICATION | INTERNAL 24
Case Study

CLASSIFICATION | INTERNAL 25
DGPV POWER MANAGEMENT

CLASSIFICATION | INTERNAL 26
WHY WE REQUIRE DG PV SOLUTION?
• To Run the Solar Plant in synchronization with DG when Grid is not available to restrict the back feed ( Push back )
of solar Power to Genset and to maintain the DG on 30 % load.
EXAMPLE : A factory having Connected Load = 600 KW
Solar Plant Capacity = 500 KW
DG Rating – 600 KVA
CASE 1 : Suppose the Running Load is 400 KW and solar Generation is of 300 KW and DG is operational .
30 % load to be maintained on DG i. e 30 % of 600 KVA = 180 KVA= 144KW (approx. 150kW)
Load shared Solar Plant : 400- 150 = 250 KW
AS the extra Energy Produced by Solar 300- 250 KWp = 50 KW
To restrict the back feed ( Solar Pushback) to DG ,the DG PV management system is required to protect the DG set.

The moto is to save the fuel and Money.


• Zero export and DG control can be done at same time with use of controllers if required.

CLASSIFICATION | INTERNAL
INITIAL INFORMATION BEFORE SELECTING THE SOLUTION
S.NO Parameters/points to be checked Comments

1 Solar power plant capacity(DC)


2 Inverter Make
3 Inverter Model Number
4 Number of Inverters
5 Total No of ACDB
6 Communication cable length (Inv to Inv)
7 Communication cable length (last Inv to
Controller)
8 Number of DG
9 If more than one DG: DG -DG
Synchronization is available on site?

CLASSIFICATION | INTERNAL
S.NO Parameters/points to be checked Comments

10 If DG-DG synchronization is there: DG


Synchronization Solution/Product/Controller
available on site.
11 If DG not Synchronize: is multiple DG running at the
same time.
12 All DG capacity
14 All DG make and mfg. year
15 DG C.T availability
16 Can We use existing C.T of customer for our meter?

17 Potential free contacts at DG and Grid Input breaker


(if no, need to install 230V relay with NO NC contacts)

18 Please provide SLD if SLD not there please provide


hand Sketch SLD.
19 If DG not Synchronize: is multiple DG running at the
same time.

CLASSIFICATION | INTERNAL
DG PV Controllers
1.Controllers are used to control the power by sensing the Load from Grid Or DG and correlated to the Power
being generated by solar PV plant to ensure that there is no back feed of power to the grid or DG as the case
may be.

2. Controllers having the LCD display on it which shows the various parameters .

A) Solar Generation for each ACDB

B) Load on DG

C) Load on Grid

D) Alarm if any fault

CLASSIFICATION | INTERNAL
DG PV Solutions- Available

1. Single Step Control with Single DG (up to 100 KWp)

2. Single Step Control with two DG (Up to 100 KWp)

3. Linear Control solution with Multiple DG -16 nos Maximum

CLASSIFICATION | INTERNAL
DG PV SOLUTION With
Single Step Control with Single DG

CLASSIFICATION | INTERNAL
CLASSIFICATION | INTERNAL
Zero Export Solution & linear Control with multiple DG

CLASSIFICATION | INTERNAL
LINEAR ZERO EXPORT & POWER MANAGEMENT

CLASSIFICATION | INTERNAL
CASE STUDY – GHILOTH PROJECT

1. It is distributed system consisting of total no of 6 ACDBS and


differently located at various location with some distance

2.The distance between ACDB’S and UTILITY Plant is 950 meters.


To establish a communication due to higher distance optical fibre
used with the help of Converter to convert the light signals into
electrical signals.

3.Utility plant ahs 3 nos of DG of 1500 KVA and each DG to


maintained at 30 % of the rated capacity.

4. There is two transformers and we have to maintain the Zero


export for both the transformers at same time.

5. Control cables are used to get the signal at each breakers of


Transformers , DG and ACDB’s.

CLASSIFICATION | INTERNAL
DG PV System installation was done at Havells Plant of Lloyd AC
unit at Ghiloth Rajasthan .

The System Comprises of


 11 Controllers
 2x 3150 KVA Transformer
 3x1500 KVA DG
 1.9 MW Solar Plant

The solar Panels are located at factory roof and inverters are
placed at production area on a elevated platform at 6 locations.

CLASSIFICATION | INTERNAL
6 nos of ACDB are located were located
at Production area. Each ACDB is having a
controller to sense the voltage and current
which can be monitored at hybrid Panel
Display.

CLASSIFICATION | INTERNAL
The DG PV main controller shows all the Parameters and real time
power generation showing solar is connected with 5 nos of power
sources .
( 2 nos of transformers and 3 DG )
All sources generating power as per plant demand and feeding to a
single bus

CLASSIFICATION | INTERNAL
BLOCK DIAGRAM

CLASSIFICATION | INTERNAL
Pls contact if any Zero Export/APRC/DGPV
Management related query-