Voltage 0-1 mA*, 0-2 mA**, 0-5 mA**, 0-10 mA, 2 or 4 0.2, 0.5, 1.0
0-20 mA, 4-20 mA
0-5 V, 0-10 V
Output cuves
Curve A Curve B Curve F
Linear Linear with live zero Compressed upper region
Mechanical dimensions
75 mm
100 mm 105 mm
AC voltage
Nominal input (Un) 3 x 100 to 415 V L-L (3-phase 3-wire system)
3 x 57.5 to 240V L-N (3-phase 4-wire system)
Measuring range 0 to 130% Un (500 V max.)
Measurement frequency 50/60 Hz (± 5 %)
Burden ≤0.2 VA
Maximum overload voltage 1.3 x Un continuously (500 V max.)
2 x Un for 1 s, with up to 10 repetitions at 10 s intervals
Scale factor 0.8 to 1.5 Un
AC current
Nominal input (In) 1A to 5A
Maximum input current 0 to 150% In
Scale factor 0.6 to 1.5
Burden ≤ 0.2 VA per phase
Maximum overload current 2 x In continuously
20 x In for 1 s, with up to 10 repetitions at 100 s intervals
Active power/reactive power/ apparent power
Nominal input voltage (Un) 3 x 100 to 415 V L-L (3 phase 3 wire system)
3 x 57.5 to 240V L-N (3 phase 4 wire system)
Input voltage range 0-130% Un (up to 500 V)
Nominal input current (In) 1A to 5A
Input current range 0 to 150% In
Measurement frequency 50/60 Hz (± 5%)
Scale factor 0.5 to 1.5 (active power, at unity power factor)
0.3 to 1 (reactive power, at reactive power factor >0.8 or unity)
Un x In primary (apparent power)
Frequency
Nominal input voltage (Un) 3 x 100 to 415 V L-L (3 phase 3 wire system)
3 x 57.5 to 240V L-N (3 phase 4 wire system)
Nominal input current (In) 1A to 5A
Measurement range 45Hz to 55Hz or 55Hz to 65Hz
Accuracy + 0.2%
High auxiliary
Nominal voltage range 80-276 V AC/DC (±10 %)
Frequency 50/60 Hz
Maximum burden ≤11VA, 6 W with two outputs at 750 Ω each
≤12 VA, 7 W with four outputs at 750 Ω each
Low auxiliary
Nominal voltage range 24-80 V DC (±10 %)
Maximum burden ≤6 W with two outputs at 750 Ω each
≤8 W with four outputs at 750 Ω each
DPT300: three phase
Technical specifications
Analogue outputs
Type Current & Voltage (bipolar)
Maximum Load resistance ≤750 Ω for 20 mA, ≥2 kΩ for 10 V (for each output)
Response time 5 cycles measurement (≤100-250 ms)
Ripple <0.4 % peak to peak
Temperature range
Operating temperature -5°C to +55°C
Storage temperature -25°C to +70°C
Usage group 1
Mechanical
Dimension (W x H x D) 100 x 75 x 105 mm
Weight 0.7 kg (approx.)
Material Fire-retardant polycarbonate (PC-FR), UL94 V-0
Mounting DIN (EN 50022)
Connector type Screw terminals
Conductor size for terminals ≤4 mm2
Environmental
Protection class II (double insulation) EN 61010-1
Pollution degree 2
Installation category CAT III for < 300V AC and CAT II for < 600V AC
Protection degree Protection housing: IP 40, terminals: IP 20
Compliance
Standards IEC 60688, IEC 61010-1, IEC 61010-2-30, IEC 61326-1, DIN 50022
Communication ports
Micro USB B-Type For configuration
Can be configured without auxiliary power
RS-485 Modbus RTU enabled (Suitable for integration with SCADA/PLC)
Baud rate 1200-38400 baud
DPT 643-12F
where high auxiliary (6), Output Accuracy
output nos. (4), accuracy class(2) 2: 2 nos. 1: Cl 1.0
4: 4 nos. 2: Cl 0.2
Aux supply 5: Cl 0.5
6: High 7: Accuracy
7: Low as per
configuration