Hyosung MV GIS

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Model

ProS ProE ProC ProCC ProG ProU


Series Series Series Series Series Series
Item

Rated voltage kV 24 25.8 25.8 36 25.8 36 38 25.8 36


Rated short-circuit breaking current kA 25 25 25 31.5 31.5 / 40 40
630 A ●
1250 A ● ● ● ● ● ● ● ● ●
2000 A ● ● ● ● ● ● ● ● ●
2500 A ● ● ● ● ● ●
3150 A ● ● ●
4000 A ● ●
Rated power frequency withstand kV/60s 50 70 70 70 70 / 95 70
Rated lighting impulse withstand kV 125 150 150 150 150 / 200 170
Frequency Hz 50/60 50/60 50/60 50/60 50/60 50/60
Internal arc withstand current sec 1 1 1 1 1 1
Standard enclose IP level IP4X IP4X IP4X IP4X IP4X IP4X
Optional enclose IP level IP41,42 IP41,42 IP41,42 IP41,42 IP41,42 IP41,42
Insulation Gas SF6 Dry air SF6 SF6 SF6 SF6
Width mm 650 600 550 600 600 / 700 600 700 700 / 800 700 / 800
2350 / 2600
Height mm 2350 2600 2350 2000 2350 2350 2700 2700
/ 2700
Depth mm 1500 2200 1200 1250 2000 / 2100 1800 1800 2300 2300
1) Enclosure & Compartments

A. LV COMPARTMENT DOOR
D. ARC DUCT WITH PRESSURE RELIEF
- DIGITAL PROTECTION RELAY
D
(PROJECT SPECIFIC)
- DOOR HANDEL (OPTION – PADLOCK) E
- CONTROL SWITCHES/ LAMPS
- LOCK-OUT RELAY/ TEST TERMINALS A E. MAIN BUS BAR COMPARTMENT
- MAIN NAME PLATE/ DEVICE LABEL - MAIN BUS BAR
- GAS DITECTOR F - INSULATION BUSHING(ALUMINUM OXIDE
(Aℓ2O3) INSULATION MATERIAL)
B. LOW VOLTAGE COMPARTMENT - CONNECTION BUS BAR

- CONTROL DUCT & CONTROL WIRING


- AUXILIARY RELAYS G F. 3 Position ED/S COMPARTMENT
- MINIATURE / MOLDED CASE
CIRCUIT BREAKERS - 3-POSITION EARTHING SWITCH &
- CT shorting terminals DISCONNECT SWITCH
- THERMOSTAT/ POWER SOCKET B C - MOTOR DRIVEN /MANUAL TYPE

C. CIRCUIT BREAKER COMPARTMENT H G. CABLE COMPARTMENT


- MOTOR DRIVEN/MANUAL TYPE
- CURRENT TRANSFORMER
(MOTOER DRIVEN / PMA TYPE)
- ZERO SEQUENCE CURRENT TRANSFORMER
- VACUUM CIRCUIT BREAKER
- EPOXY INSULATOR
(VCB, FIXED TYPE)
- PRIMARY BUSHING
G. INSULATION MATERIAL

- SF6(99.9%)
- DRY AIR( O2 : 20 %, N2 : 80%)
3. General Characteristics for MV GIS
2) Lay out
3. General Characteristics for MV GIS
3) Arc-Resistance Structure & Enclosure
ARC Proof Test Criteria (1~5) As per IEC 62271-200

IAC (Internal arc classified) - AFLR  Doors must remain closed and no opening of the cover panels
Duration must occur

- 31.5kA : 1 s  No hazardous parts to be ejected


- 40kA : 1 s  No holes in the external housing in any parts accessible to
personnel
Accessibility
 Vertically and horizontally arranged fabric indicators must not
A: Type (restricted to authorized personnel only) incinerate
F: for Front side  All earthing connections must remain effective
L: for Lateral side
R: for Rear side
3. General Characteristics for MV GIS
4) Application examples & Maintenance
Install in Mobile Container Substation
3. General Characteristics for MV GIS
6) Benefits & Special Features

BENEFITS FEATURES

 high insulation characteristics using Aluminum Oxide(Aℓ2O3) for 170kV GIS insulation
SAFETY
material.
 Internal arc tested design up to 40kA, 1s

 We have proven our GIS technology with thousands of installations worldwide of GIS
HIGH QUALITY ranging from 24kV to 800KV
 Hyosung is only producing 36kV 4000A 40kA GIS in the world.

INCREASED  Use of metallic, earthed shutters and partitions(LSC2B according to IEC 62271-200)
PRODUCTIVITY  Use of maintenance-free vacuum circuit-breakers

EASY
 Interchangeability (Electrical & Mechanical) with similar type of breakers
OPERATION &
 Fully type tested as per IEC standard for reliable operations
RELIABILITY
CUSTOMIZED  Customized production for Customer requirements