Fireclass Prec en App - 0
Fireclass Prec en App - 0
Fireclass Prec en App - 0
Application Guide
PAGE 1 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
List of Contents
1. LIST OF FIGURES ............................................... 3 11.6.1. CONFIGURE DELAY ZONES .................... 23
2. LIST OF TABLES................................................. 3 11.6.2. 1-2 STAGE DELAY................................. 23
3. INTRODUCTION .................................................. 4 11.6.3. SELECTION OF OUTPUTS TO BE DELAYED 23
4. GENERAL DESCRIPTION ..................................... 4 11.7. SELECTABLE ZONAL OR GENERAL ALARM
4.1. CABINET SPECIFICATIONS .......................... 4 SOUNDER OPERATION.............................. 23
4.1.1. SURFACE PANEL ORDER CODES & 11.8. PULSE NON-ALARM ZONES ...................... 23
DESCRIPTIONS ........................................ 4 11.9. INHIBIT FIRE PROTECTION ON NON-LATCHED
4.1.2. SEMI-FLUSH PANEL ORDER CODES & ZONE ...................................................... 23
DESCRIPTIONS ........................................ 5 11.10. DELAY ALARM SILENCE AND RESET ......... 23
4.1.3. PRECEPT EN FULLY FLUSH PANEL ORDER 11.11. ALARMS ON EVACUATE ONLY................... 23
CODES AND DESCRIPTIONS ..................... 5 11.12. SILENCE BEFORE RESET ......................... 23
4.2. PANEL DESCRIPTION.................................. 6 11.13. SILENT ZONE TEST .................................. 23
4.2.1. C1626 2/4 ZONE MOTHERBOARD ............ 7 11.14. BUZZER DISABLE ..................................... 23
4.2.2. C1627 8/16/32 ZONE MOTHERBOARD ..... 7 11.15. LATCHED FAULTS .................................... 23
4.2.3. C1632 16 ZONE EXPANSION BOARD........ 7 11.16. REPEATER CONFIGURATION..................... 23
4.2.4. C1628 16 ZONE DISPLAY BOARD AND 11.17. OUTPUT RELAY CONFIGURATION ............. 24
C1629 32 ZONE DISPLAY BOARD ............ 7 11.18. EARTH FAULT MONITORING. ..................... 24
4.2.5. C1631 REPEATER INTERFACE BOARD...... 7 12. PANEL REPEATERS ......................................... 24
4.3. PANEL ASSEMBLY ...................................... 8 13. CIRCUIT CONNECTION DETAILS ........................ 24
4.4. PANEL RANGE .......................................... 11 13.1. AUXILIARY SUPPLY .................................. 25
4.5. REPEATER DESCRIPTION ......................... 11 13.2. FIRE ROUTING, FIRE PROTECTION AND
5. FUNCTIONAL SPECIFICATION ............................ 11 FAULT ROUTING OUTPUTS ....................... 25
5.1. PANEL INPUT/OUTPUT LIST ...................... 11 13.3. USE OF AUXILIARY INPUTS ....................... 26
5.2. FEATURES LIST........................................ 12 13.4. SOUNDER CIRCUITS ................................ 26
6. PRECEPT EN C1627 MOTHERBOARD FEATURES 14. ELECTRICAL DESIGN OF DETECTION ZONES ..... 26
....................................................................... 14 14.1. MAXIMUM NUMBER OF DEVICES ON A ZONE
7. PRECEPT EN C1632 16 ZONE EXPANSION BOARD .............................................................. 26
FEATURES ...................................................... 15 15. C1651 CLOCK/TIMER MODULE ........................ 27
8. POWER SUPPLIES ............................................ 15 15.1. CLOCK MODULE FUNCTIONALITY .............. 27
8.1. BATTERY CHARGER ................................. 15 15.1.1. ALARM COUNTER .................................. 27
8.2. VISUAL INDICATIONS................................. 15 15.1.2. DAY/NIGHT DELAY MODE CONTROL ....... 27
ST
8.3. FAULT OUTPUTS ...................................... 16 15.1.3. 1 FIRE ALARM TIME ............................ 27
8.4. BATTERY DISCONNECT ............................ 16 15.2. CLOCK MODULE EDIT FACILITY ................ 27
8.5. 32 ZONE PRECEPT EN POWER SUPPLY 15.2.1. USER CONTROL/EDITING....................... 27
FEATURES & CONNECTIONS ..................... 16 15.2.2. ENGINEER’S EDITING AND CONFIGURATION
9. COMPATIBLE FIELD DEVICES............................ 17 ............................................................ 27
9.1. FIELD DEVICE ORDER CODES & 15.3. C1651 CLOCK MODULE PCB FEATURES.. 28
16. MECHANICAL, ELECTRICAL & ENVIRONMENTAL
DESCRIPTIONS......................................... 17
SPECIFICATION ............................................... 30
10. OVERVIEW OF USER FUNCTIONS ...................... 19
10.1. USER INDICATIONS................................... 19 17. PRECEPT EN INPUT & OUTPUT SPECIFICATION 32
10.2. USER CONTROLS ..................................... 20 18. APPENDIX ....................................................... 34
10.3. SELECTION OF DETECTION ZONES OR 18.1. EN54 OPTIONAL FUNCTIONS WITH
OUTPUTS FOR DISABLEMENT, ENABLEMENT REQUIREMENTS....................................... 34
OR TEST .................................................. 21 18.2. ANCILLARY FUNCTIONS NOT REQUIRED BY
10.4. DISABLEMENT/RE-ENABLEMENT OF EN54 ..................................................... 34
DETECTION ZONES AND OUTPUTS ............ 21 18.3. POWER SUPPLY LOAD CALCULATION ....... 34
10.5. DETECTOR ZONE ONE MAN TEST. ............ 21 18.4. BATTERY STANDBY CAPACITY CALCULATION
10.6. ALARM SOUNDER ONE MAN TEST ............. 21 .............................................................. 35
11. OVERVIEW OF ENGINEERS FUNCTIONS ............. 21 18.5. PANEL CONFIGURATION DESIGN CHART ... 36
11.1. ENGINEER’S CONFIGURATION PROCESS .... 21
11.1.1. ZONE/OUTPUT DELAY CONFIGURATION .. 21
11.1.2. FACTORY DEFAULT CONFIGURATION ...... 22
11.1.3. OTHER CONFIGURABLE FEATURES......... 22
11.2. CONFIGURABLE DETECTION ZONES .......... 22
11.3. DELAY ZONE CONFIGURATION ................... 22
11.4. STANDARD OR INTRINSICALLY SAFE ZONE . 22
11.5. SHORT CIRCUIT FIRE CONFIGURATION ....... 22
11.6. THE DELAY MODE FEATURE ...................... 22
PAGE 2 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
PAGE 3 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
A
The FIRECLASS Precept EN Panel range is fully
compliant with the mandatory requirements and
selected optional requirements of EN54-2 and 4 as
well as the relevant requirements of BSEN5839-
1:2002.
The FIRECLASS Precept EN equipment range:
Panels: 2, 4, 8, 16 and 32 zone versions. C B
Repeater: 2 to 8, 16 and 32 zone versions.
A system comprises of the following: 2/4/8/16 32 8/16 32
One off Precept EN 2, 4, 8, 16 or 32 zone fire zone zone zone zone
detection and alarm panel. panel panel repeater repeater
Top entry
Up to 5 off Repeater Panels [2 to 8, 16 or 32 20mm
zone variants]. 26 32 26 32
knock
outs
Each panel in the range is housed in a single metal
A [mm] 370 441 370 441
enclosure incorporating a door-mounted display
B [mm] 325 400 325 400
board fitted with a polyester overlay providing user
C [mm] 126 131 126 131
controls and indications. User controls are locked &
unlocked via a key-switch. All indications are
implemented using LEDs. The power supply and 4.1.1. Surface Panel Order Codes &
standby batteries are housed within the panel Descriptions
enclosure. Part Number Description
508.032.701 2 Zone Panel
508.032.702 4 Zone Panel
508.032.703 8 Zone Panel
508.032.704 16 Zone Panel
508.032.706 32 Zone Panel
508.032.707 8 Zone Repeater c/w Power Supply
508.032.708 16 Zone Repeater c/w Power Supply
508.032.709 32 Zone Repeater c/w Power Supply
508.032.710 8 Zone Repeater DC Powered
508.032.711 16 Zone Repeater DC Powered
508.032.712 32 Zone Repeater DC Powered
2605070 Clock Module Kit
PAGE 4 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
4.1.2. Semi-flush Panel Order Codes & 4.1.3. Precept EN Fully Flush Panel Order
Descriptions Codes and Descriptions
Part Number Description Part No Description
2603011 2/4/8/16 Zone Semi-flush bezel 2603060 2/4/8/16 Zone Painted bezel
2603012 32 Zone Semi-flush bezel (painted to customer's specification)
2603061 2/4/8/16 Zone Stainless Steel bezel
(brushed or polished)
Figure 2 – Panel Enclosure - semi flush boxes 2603062 2/4/8/16 Zone Brass bezel
y (brushed or polished)
2603065 32 Zone Painted bezel
(painted to customer's specification)
2603066 32 Zone Stainless Steel bezel
(brushed or polished)
z 2603067 32 Zone Brass bezel
z (brushed or polished)
z
z
B
C
2/4/8/16
32 zone 8/16 zone 32 zone
zone
A
panel repeater repeater
panel
x
PAGE 5 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
R0
C1631repeater
1 2 3
CEL C1631
R1
ISSUE 0
R2
interface
[Optional]
Mains
transformer Removable chassis
1
2 DELAY/
4 MINUTES
8
Mains transformer
Batteries Motherboard
Batteries
C1631 repeater
ZONE ZONE ALARM AU interface
CHANG
RESE
X
CLAS
EVAC
CIRCUITS CIRCUITS
E
EVA
OUTPUTS
RST
BUZ
+ 1- + 2- + 3- + 4- + 5- + 6- + 7- + 8-
D.C.
E
N/T
S
DIS
SC
A
B
1 2 3 4
C
SIL
O
.
0
.
.
1 2 3 4 + - + - + - + - 24V
V
TB1 TB2 TB3 TB4 TB5 TB6 TB7 TB8 TB9 TB10 TB12 TB14 TB15 TB16 TB17 TB18 TB19 TB20 TB21
[optional]
O/ C/ C/ O/ C/ O/ N/
+ - +1 - +1 - +1 - +1 - +1 - +1 - +1 - +
P
FAULT - +
P
FIRE - +
P
FIRE -
P
RESEC
9
Removable
T
0 1 2ZONE 3 4 5 6 ROUTING ROUTING PROTECTION
CIRCUITS
EXPANSION
J1
J1
J1 J1 J1
7
J1 J1 J1
6 5 4
2 1 0
7
6
J
I/O
8 7
J J
chassis
J2
0
SW
1 R
Motherboard
EXPANSION
1
0
R J2
CEL C1631
ZONE
2
1 0
ISSUE 0
R
3
2
~ ~
TB23
1
J
DISPLA
J
Y
Mains
1
SW SW
INHIBIT F/P ON 2 SILENCE BEFORE
1
1
DELAYRESET
ON
2 DELA
3
Motherboard
AUTONON-LATCH
CONFIG MINUTE
Y/
L 4 S L
4
ZONES
transformer
1 CONFIG I/S 2
8
5
ZONESM/S
CONFIG ZONAL L
6
ZONES
CONFIG DELAY ALARMS
PULSE NON-ALARM 3
7
ZONES
CONFIG DELAY ZONES
SILENT ZONE L J18
8
O/PS TEST 4 B
2 STAGE BUZZER
9
DELAYON EVAC
ALARMS DISABLE
LATCHED TB11 TB13 L
ORIG
0
1
0
1
ONLY FAULTS FS 5
N1 BATTERY - BAT + THER
1 FUSE T M
Batteries
Batteries
PAGE 6 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
C1631 repeater
ZONE ZONE ALARM AUX INPUTS OUTPUTS REPEATER ZONE CIRCUITS FI
interface
CHAN
+ 17 - + 18 - + 19 - + 20 - + 21 - + 22 - + 23 - + 24 -
ACTI
RES
[optional]
GE
CIRCUITS CIRCUITS
CLA
D1
EVA
VE
ET
OUTPUTS
SS
+ 1- + 2- + 3- + 4- + 5- + 6- + 7- + 8-
D.C.
AC
EV
C.
RS
BU
A
B
SC
1 2 3 4
T.
Z.
N/
DI
S.
O
SI
L.
N
1 2 3 4 + - + - + - + - 24V 0V
TB TB TB TB TB TB TB TB
TB TB TB TB TB TB TB TB TB TB1 TB1 TB1 TB1 TB1 TB1 TB1 TB1 TB2 TB2 1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8 9 0 2 4 5 6 7 8 9 0 1
Removable
O/ C C/ O/ C/ O/ N/ + 25 - + 26 - + 27 - + 28 - + 29 - + 30 - + 31 - + 32 -
+ - +1 - +1 - +1 - +1 - +1 - +1 - +1 - P
+ FAULT /- +
P
FIRE - +
P
FIRE -
P
RESC
9
I/O EXPANSION
0 1 2 ZONE 3 4 5 6 ROUTING ROUTING PROTECTION ET
CIRCUITS
J1
J1
J1 J1 J1
J1 J1 J1
7
6 5 4
2 1 0
7
8 7 6
J J J
J
1
chassis
ZONE EXPANSION J2
0
TO MOTHERBOARD
S
W1 R
1 2 3
0
R J2 J
CEL C1631
ISSUE 0
1
R 0 1
2
Motherboard
17 -32 zone
~ ~
1
J
TB2
expansion
3
DISPL
J
AY
S S
INHIBIT F/P SILENCE BEFORE
board
W1 W2
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
ON NLZ
DELAY ALARM SIL RESET
1
DELAY& RESET
ON DEL
2 MINUT
AUTO
CONFIG NON- AY/
L 4 ES L
LATCH I/S
CONFIG ZONES
1 8 2
ZONESM/S
CONFIG ZONAL J1
L
ZONES
CONFIG DELAY ALARMS
PULSE NON- 8B
3
Mains
ZONES
CONFIG ALARM
SILENT ZONES
ZONE L
2DELAY
STAGEO/PS TEST
BUZZER 4
DELAY DISABLE TB1 TB1 L
ORI ALARMS ON LATCHED
0
1
0
1
FS 1 3 5
GN1 EVAC ONLY FAULTS BATTERY - BA + THE
1 FUSE TT RM
Batteries
Batteries
4.2.1. C1626 2/4 Zone Motherboard all of the site-specific configuration features (DIL
This board is common to the 2 & 4-zone panels. It switch & EEPROM) are accommodated on this
is also used, in a depopulated form, as the board.
motherboard for the range of repeaters. 4.2.3. C1632 16 Zone Expansion Board
It provides terminals for all the field wiring, interface This board provides an additional 16 detection
connectors for the repeater and connections to the zones. It is connected to the C1627 motherboard
display board. The power supply components for via a ribbon cable to provide a total of 32 zones for
the panels and mains powered repeaters are the 32-zone panel.
located on this PCB. The microcontroller (including
Firmware and RAM) and all of the site-specific 4.2.4. C1628 16 Zone Display Board and
configuration features (DIL switch & EEPROM) are C1629 32 Zone Display Board
accommodated on this board. These boards provide visible [LED] user indications
4.2.2. C1627 8/16/32 Zone Motherboard and user buttons. The display board connects to
the motherboard via a ribbon cable.
This board is common to the 8, 16 and 32-zone
panels. It is also used, in a depopulated form, as 4.2.5. C1631 Repeater Interface Board
the motherboard for the range of repeaters. This optional plug-in board provides an RS485
It provides terminals for all the field wiring, interface capability for communication with up to 5 repeaters
connectors for the repeater, zonal expansion and is fitted to the C1627 motherboard via two
connectors and connections to the display board. connectors. One C1631 needs to be fitted to the fire
The power supply components for all panels except alarm panel and one to each repeater.
the 32-zone panel are located on this PCB. The
microcontroller (including Firmware and RAM) and
PAGE 7 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
PAGE 8 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Figure 8 – 8/16 Zone Panel - General Assembly (with optional clock module)
PAGE 9 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Figure 9 – 32 Zone Panel - General Assembly (with optional clock module)
PAGE 10 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
5. Functional Specification
5.1. Panel Input/Output List
Precept EN Panel
Input/Output
2 zone 4 zone 8 zone 16 zone 32 zone
Detection zones 2 4 8 16 32
Remote silence alarm I/P [non monitored] 1 1 1 1 1
Remote reset I/P [non-monitored] 1 1 1 1 1
Remote evacuate I/P [non-monitored] 1 1 1 1 1
Class change I/P [non-monitored] 1 1 1 1 1
Sounder circuits 2 @ 0.5A 4 @ 0.5A 4 @ 1A 4 @ 1A 4 @ 1A
1 1 1
Zonal O/Ps [open collector] 2 4 Optional Optional Optional
Disablement active [open collector] 1 1 1 1 1
Evacuate active [open collector] 1 1 1 1 1
Buzzer active [open collector] 1 1 1 1 1
Monitored Fire Routing O/P 1 1 1 1 1
Monitored Fire Protection O/P 1 1 1 1 1
Monitored Fault Routing O/P 1 1 1 1 1
Volt free reset relay 1 1 1 1 1
Aux DC Supply [fused] 1 @ 0.5A 1 @ 0.5A 1 @ 1A 1 @ 1A 1 @ 1A
2 2 2 2 2
Repeater facility Optional Optional Optional Optional Optional
NOTES:
1
- The 8, 16 & 32 zone panels have zonal outputs for zones 1 to 4 only. Additional outputs can be
added via the output expansion boards. An Output Module communication interface board must be
fitted in the panel if output expansion boards are required..
2
- The use of repeaters requires the addition of a Repeater communication interface board.
PAGE 11 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Switching regulator power High efficiency voltage regulation. Battery charging voltage is
supplies with temperature automatically adjusted between 28.6 and 26.72Vdc over an ambient
o
compensated battery charging temperature range of -10 to +50 C.
Battery disconnect Protects the battery from permanent damage due to over discharge by
automatically disconnecting it when the battery voltage falls to 21Vdc.
Battery Resistance Check Batteries are monitored for high resistance. A fault indication is given if
the resistance exceeds the following values:
1Ω - 2/4-zone panels & repeaters
0.6Ω - 8/16-zone panels
0.35Ω - 32-zone panels
Configurable detection zones Simple and flexible display-based configuration process allowing
detection zones to be configured for any of the following:
o Latching or non-latching Fire indication.
o Delayed or non-delayed Output operation.
o Normal or Intrinsically-Safe zone monitoring.
o Short Circuit = Fault or Short Circuit = Fire
Factory configuration: Latching, non-delay, standard [non-I.S.],
S/C = Fault.
Active fault monitoring on Reduces zone monitoring current and therefore reduces the required
detection zones. [Non- battery capacity.
Intrinsically Safe applications Maintains zone wiring continuity following the removal of a detector,
only] while still providing a fault indication on the panel.
Configurable Fire Routing, Fire Configuration Links on the motherboard allow each Output Relay to be
Protection and Fault Routing individually selected to the EN54 powered/fault-monitored mode or non-
output relays EN54-compliant volt-free changeover contacts.
Factory configuration:-Fully Monitored (EN54 Mode).
Reset Relay A volt-free changeover contact operating for 10 seconds on panel fire
alarm reset.
Auxiliary 24V DC power supply Protected by an electronic fuse. Operation of the fuse is indicated on the
output display. The fuse is reset by pressing the Reset button on the display.
PAGE 12 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Remote inputs Remote Evacuate.
Remote Silence Alarms.
Remote Reset.
One Man Zone Test Each zone can be independently set to the One Man test condition.
Sounders can be configured to either operate briefly to confirm the panel
has detected the test fire or no sounder operation during the test fire.
Other configuration features o Prevent the Fire Protection output operating from a fire condition
on a “Non-Latch” zone.
o Inhibit the silencing and resetting of the panel for 3 minutes
following the occurrence of a fire alarm.
o Set the sounders to operate only when the panel is in the
Evacuate condition.
o Inhibit the resetting of the fire alarm condition until the alarm
sounders have been silenced.
o Disable the internal panel buzzer.
o Select latching fault mode where all fault conditions latch until
the panel is manually reset.
o Restore factory default configuration of zones and outputs to be
delayed.
Repeater panels Support for up to 5 repeater panels via two-wire RS485 serial
communication.
PAGE 13 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Remote Inputs:
Silence Alarms Aux Outputs:
Evacuate DISablement active
Reset Fire EVACuate Active
Routing
Output BUZzer ACTIVE
Fault
Aux DC Supply Routing Fire
24V & 0V Output Protection
Zone Outputs Output
1-4 Alarm Circuits Repeater
[Marked with Active Terminals:
Polarity] A,B, GND
Reset
Zone Relay
Detection Output
Inputs
J6,J7,J8
Fault Routing
Output Connector
configuration J10,J11,J12
Fire Routing Output for C1632,
links Zone
configuration links J14,J15,J16
Expansion
Fire Protection Output Board
configuration links
C1631
J1 Repeater
Display Interface
Connector
Secondary
AC from
transformer
Configuration
mode enabled FS1
LED indicator Battery J18
Fuse Power Supply LED Earth Fault
indicators: Monitoring
Configuration Battery OUTPUT OK Link
switches Terminals Battery/Charger Fault
SW1/1 to Configuration Charger Fault
SW1/10 switches Battery
SW2/1 to Thermistor Mains Fault
SW2/10 Terminals
PAGE 14 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
PAGE 15 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
3) A yellow ‘Charger Fault’ LED (‘Internal Fault’ 8.4. Battery Disconnect
LED on the C1652 PSU board) indicating any
The power supply provides a battery disconnect
of the following:
facility that disconnects the batteries when the
a) A mains fault exists (described below) battery terminal voltage falls below 21.2V ±0.53V.
b) The Switching regulator or charger circuitry This will occur under the following conditions:
is malfunctioning 1) A short circuit across the battery terminals
c) Battery Fuse is blown 2) To prevent deep discharge of the batteries if
4) A yellow ‘Mains Fault’ LED. This indicates that supplying the panel for an abnormally long
the mains voltage has failed or is less than the period of time.
required minimum for correct operation of the The batteries are reconnected when the mains
power supply (80% of the rated voltage). voltage is present and the battery voltage is greater
8.3. Fault Outputs than 18.5V ±0.46V.
All PSU fault conditions are communicated to the 8.5. 32 Zone Precept EN Power
panel motherboard, which will raise a fault Supply Features & Connections
indication on the display and operate the fault
Figure 12 shows the layout of the 32-zone Precept
routing output.
EN panel power supply.
Secondary AC
Supply from
transformer
28V, 0V DC
Power Output
Mains Fault
Output
Common
Fault Output
PAGE 16 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
PAGE 17 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Max. per zone
Manufacturer Part no. Description CEL Part No [See Notes
below]
Apollo 45681-207 Series 60 IS base N/A 10
Hochiki SIH-E CD Range ionisation detector N/A 32
Hochiki DFE-60E CD Range 60 heat detector N/A 32
Hochiki DFE-90E CD Range 90 heat detector N/A 32
Hochiki DCC-1EL CD Range Grade 1 heat detector N/A 32
Hochiki DCC-2EL CD Range Grade 2 heat detector N/A 32
Hochiki DCC-1REL CD Range R1 heat detector N/A 32
Hochiki YFB- Mounting base N/A 32
RL\4H5
Hochiki YBK- CD Range mounting base N/A 32
RL/4H1
Hochiki DFG-E Waterproof Fixed Temp. (60) Heat Detector- No N/A 32
Base Req.
Notes:
The Precept EN panel is designed to monitor 22µF capacitors as end-of-line devices on the zones. If the
zone is configured as an Intrinsically Safe zone then the end-of- line device must be changed to a 10k
resistor. In this case the following limitation must be observed:
The total current drawn by detectors on a zone must not exceed 1.2mA, otherwise the panel may
not detect an open circuit fault on the zone wiring. The standby current drawn by each device will be
given in the manufacturer’s datasheet for the device. To calculate the total number of devices that
may be connected to a zone, add up the individual standby current values for each device and
make sure that the total current does not exceed 1.2mA, including the current drawn by the I.S.
barrier.
If a galvanic isolator (MTL5061) is used on the zone then this device will draw current. Allow at least
0.1mA for the barrier (this could rise to 0.4mA depending on how much current is drawn by the
detectors).
The maximum number of devices per zone must not exceed 32, regardless of standby current.
The values in the above table are for guidance only and will vary for individual detectors. Each zone should
be fully checked for correct fault monitoring during installation & commissioning.
PAGE 18 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
POWER SUPPLY ON
1
FIRE EVACUATE TEST DISPLAY
2
FIRE ROUTING ACTIVE
3
SILENCE/
GENERAL FAULT RESOUND ENABLE 4
ALARMS
POWER SUPPLY FAULT 5
SYSTEM FAULT 6
RESET DISABLE
7
EARTH FAULT
8
FUSE FAILED
SILENCE 9
BUZZER TEST
REPEATER FAULT 10
SOUNDER FAULT/DISABLED 11
DELAY
SOUNDER TEST ON/OFF/ 12
OVERRRIDE
13
FIRE PROTECTION FAULT/DISABLED SELECT
14
FIRE ROUTING FAULT/DISABLED SELECT
ON/OFF 15
FAULT ROUTING FAULT/DISABLED 16
PAGE 19 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
POWER SUPPLY ON
1
FIRE EVACUATE TEST DISPLAY
2
FIRE ROUTING ACTIVE
3
SILENCE/
GENERAL FAULT RESOUND ENABLE 4
ALARMS
POWER SUPPLY FAULT 5
SYSTEM FAULT 6
RESET DISABLE
7
EARTH FAULT
8
FUSE FAILED
SILENCE 9
BUZZER TEST
REPEATER FAULT 10
SOUNDER FAULT/DISABLED 11
DELAY
SOUNDER TEST ON/OFF/ 12
OVERRRIDE
13
FIRE PROTECTION FAULT/DISABLED SELECT
14
FIRE ROUTING FAULT/DISABLED SELECT
ON/OFF 15
FAULT ROUTING FAULT/DISABLED 16
PAGE 20 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
10.3. Selection of Detection Zones or o A fire condition on a zone in Test Mode will not
Outputs for Disablement, operate any of the fire outputs other than any
sounders configured to respond to the zone
Enablement or Test fire.
The panel provides a simple and straightforward o The panel will respond normally to a fire
means for selecting the sounder outputs and/or condition on any zone not selected to the Test
zones which are to be disabled, re-enabled or set to Mode.
the test mode. The Fire Routing output, Fire
Protection output and Fault Routing output can also o Sounders can be configured not to respond to
be individually disabled and enabled. a detector test or to operate for 5 seconds and
then automatically silence.
The zone or output is selected using the Cursor
Select feature. This allows the User to move a o A Zone Test Fire condition will operate the
flashing cursor indication up or down through the sounders in accordance with the panel
yellow fault LEDs associated with the available configuration - i.e. either:
zones and outputs until the required zone or output Zonally - only the sounder group
is highlighted. The yellow LED for the selected associated with the actual detection zone
zone/output flashes in “Cursor” mode, which is being tested, or
easily distinguishable from all other indications. Generally - all sounder groups operate.
With the cursor flashing on the required
o After each test the panel and the device being
zone/output, pressing the Disable button disables
tested is automatically reset allowing the next
the zone/output. Pressing the Enable button re-
device to be tested without needing to return to
enables the zone/output. Pressing the Test button
the panel to silence and reset.
initiates the test condition. [Note: Fire Routing
output, Fire Protection output and Fault Routing o If a fire condition occurs on any zone other
outputs cannot be placed in test condition]. than a zone in test mode, the panel responds
fully to the fire condition as per its normal fire
10.4. Disablement/Re-enablement of response and configuration.
Detection Zones and Outputs
10.6. Alarm Sounder One man Test
Any or all of the zones can be disabled.
The One Man Sounder Test operates all sounders
The panel will not enter the fire alarm condition if a intermittently until the Test mode is manually
fire detection device operates on a disabled zone. cleared. This allows the Engineer to walk the
Similarly, the panel will not enter the fault condition installation and confirm the operation of all
if a fault occurs on a disabled zone. The fire panel sounders. The sounder on/off cycle is 2 seconds on
will respond normally to fire device operations and and 15 seconds off to allow operation to be
wiring faults on all enabled zones. confirmed without being too intrusive for other
The following outputs can also be individually occupants.
disabled & enabled: A genuine fire alarm condition overrides the test
o All Sounder circuits. mode and operates the sounders normally.
o The Fire Routing output. 11. Overview of Engineers
o The Fire Protection output.
Functions
o The Fault Routing output.
This section provides an overview of the functions
A disabled output is prevented from operating
available to the engineer.
under any circumstances.
10.5. Detector Zone One man Test. 11.1. Engineer’s configuration process
Most of the Engineer’s configuration facilities are
When selected to the One Man Test condition,
controlled by DIL switches located on the
devices connected to the zone can be operated for
motherboard accessed by opening the panel door,
test purposes without operating the Fire Routing or
each configuration feature having its own dedicated
Fire Protection outputs. The zone[s] to be set to the
DIL switch.
One Man Test condition are selected using the
Cursor Select feature described in 10.3 above. With 11.1.1. Zone/Output Delay Configuration
the cursor flashing on the required zone, pressing Having selected the DIL switch for configuring the
the Test button initiates the zone test. Pressing the delay zones or the DIL switch for configuring
Enable button or pressing the Test button again delayed outputs, the actual selection of the
clears the test condition and restores normal zones/output is carried out on the panel display
operation to the zone. using the yellow zone [or output] fault/disabled
The features of the One Man Zone Test condition LEDs via the Cursor Select feature. This allows the
are: Engineer to scroll a cursor indication up or down
through the yellow LEDs associated with the
PAGE 21 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
available zones or outputs until the required zone or connected panels cannot be reset from an alarm
output is selected. The yellow LED for the selected condition.
zone/output flashes in “Cursor” mode, which is A fire detector operation on a zone configured to
easily distinguishable from all other indications. the non-latch fire mode initiates the fire alarm
With the cursor flashing on the required condition on the panel, operates the fire alarm
zone/output, pressing the Enable button applies the sounders, the Fire Routing output and zone outputs
configuration to the selected zone. Pressing the as normal. The Fire protection output can be
Disable button clears the configuration, restoring configured to operate or not to operate via DIL
factory setting. switch 1/1. On clearing of the fire input signal on a
When configuring zones, the cursor can only be non-latch zone the panel will clear the alarm
scrolled though zone LEDs. When configuring indication if no other alarms are present.
outputs the cursor is restricted to Fire Routing, Fire 11.3. Delay zone configuration
Protection and Sounder LEDs.
This facility is used along with the other delay
When a zone configuration or the delay outputs
configuration features listed below [see 11.5 below]
configuration feature is initiated, all standing fire
to tailor the Panel Delay operation to the needs of
alarms are reset, all fault/disablement/test
the protected premises. Each zone can be
indications are inhibited and the current
independently configured to Delay Mode. Delay
configuration is indicated on the fault/disabled LEDs
zones would normally be used to monitor automatic
on the display for the appropriate zones or outputs.
fire detectors. A fire condition on a delay zone will
The panel is not able to respond to any fire or fault
indicate the fire alarm audibly and visibly on the
alarm.
panel, operate any non-delayed outputs and start
11.1.2. Factory Default Configuration the time delay function.
The factory default configuration for the zones 11.4. Standard or Intrinsically Safe
and delayed outputs can be restored by selecting
the configuration DIL switches for each of the zone
zone
and output delay configuration features to ON then When configured to the Standard Mode the fire
pressing the Disable switch on the display and and fault trip thresholds for the zone being
finally setting the configuration switches back to the configured are set within the panel software to the
OFF position. normal values and are compatible with a large
11.1.3. Other Configurable Features range of detection devices. This is the factory set
condition.
All other configurable features involve either setting
When configured to the Intrinsically Safe Mode
the appropriate DIL switch to ON or OFF or
removal/replacement of jumpers on the the fire and fault trip thresholds for the zone being
motherboard. configured are adjusted within the panel software to
allow use with I.S barriers. The fault monitoring is
11.2. Configurable Detection Zones configured to the passive mode suitable for use
Display-based Select/Cursor configuration process with end of line resistors only.
allowing each detection zone to be individually Note: Removal of a detector will be reported as
configured to one of the following types: a fault but will not allow the detection of a fire
o Latching or non-latching fire zone. condition on any device connected between the
removed device and the end of line terminator.
o Delay or non-delay zone.
Warning: Use of capacitors on Intrinsically Safe
o Standard or Intrinsically Safe zone.
circuits is dangerous and is not allowed.
o Short circuit gives fire indication.
11.5. Short circuit fire configuration
Factory default: All zones as latching fire, non-
delay, standard [non- intrinsically safe and non Factory default configuration:- short circuit on the
short circuit fire mode]. zone wiring raises a fault warning.
Note: The DIL switch labelled “Configure M.S. When configured to the short circuit fire mode, a
Zones” is used on the Precept EN panel to short circuit across the zone wiring initiates the fire
configure the zones to short circuit fire mode. alarm condition.
Latching fire configuration- This is the normal 11.6. The Delay mode feature
operating configuration and is used when fire This comprises three configurable elements to
detectors and manual call points are connected to allow the panel to be configured to delay the
the zone wiring. operation of three types of outputs in response to a
Non-latching fire configuration - Provided to fire alarm condition triggered by a zone configured
allow users to link panels together via the Fire as a delay zone.
Protection relay and non-latching zone without
causing a system latch-up state, where the
PAGE 22 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
11.6.1. Configure Delay Zones o Zonal sounders for zone in the fire condition
Zones can be configured as delay or non-delay. operate continuously until silenced. All others
Fire detectors would normally be connected to are silent.
delay zones and manual call points to non-delay o Zonal sounders operate continuously - all other
zones. [See 11.3 above]. sounders operate in pulsed mode until
silenced.
11.6.2. 1-2 Stage Delay
The delay can be set up as either a Single or 2- 11.9. Inhibit Fire Protection on Non-
stage delay. Latched Zone
Single stage: 1-10 minutes selectable duration Selects Fire Protection relay to operate or not to
in 1-minute steps. operate for a fire condition on any zone configured
2-stage: Delay 1 = 1-minute fixed delay. Delay to non-latched mode. This feature has been
2 = 0-9 minutes [duration selectable as provided to allow two panels to be linked so that a
described above]. fire condition on one panel triggers a fire on a zone
on the other panel and vice versa without latching
Operation of the Buzzer Silence button before up. The zones used to monitor the signal from the
delay 1 ends will immediately start delay 2, other panel should be configured to non-latching
otherwise all delayed outputs will operate after and the Fire Protection relay should be used to
delay 1 ends. transmit the fire signal.
11.6.3. Selection of outputs to be delayed 11.10. Delay Alarm Silence and Reset
o The Delay Mode can be applied independently
to each or all three of the outputs listed below: Prevents alarms being silenced and panel reset for
a period of 3 minutes after a fire alarm condition
Fire Alarm Routing Output. occurs.
Fire alarm sounders. 11.11. Alarms on Evacuate Only
Fire Protection Output[s]. Selects sounders to operate only when the panel is
No other outputs can be delayed. The factory in the evacuate condition.
default:- No outputs delayed.
11.12. Silence Before Reset
o Operation of a fire detector or manual call point
on any “non-delay” zone overrides the delay Selects type of reset mode:
and immediately operates all delayed outputs. o Reset available when panel is in the [un
o The panel display includes a Delay silenced] fire or fault condition, or
On/Off/Override button allowing the User to o Fire Condition Reset is available only when
enable/disable the delay mode or, if the delay panel is in the Alarm Silenced condition. Fault
is running, to override it, immediately operating reset is available when panel is in the fault
the delayed outputs. condition.
11.7. Selectable Zonal or General 11.13. Silent Zone Test
Alarm Sounder operation Select sounder response in One Man [Detector]
Selects the sounders to: Test Mode:
o General Alarm Mode [all sounders operate for o Normal sounder response [continuous or
any fire condition] or pulsed in line with panel configuration), or
o Zonal Alarm [in conjunction with the Pulse o Silent [no sounder operation].
Non-Alarm Zones switch] 11.14. Buzzer Disable
The standard sounder circuits on the 2 and 4 Enable/disable the internal panel fire/fault buzzer.
zone panels can be used in General or Zonal
modes. On the 8,16 and 32 zone panels, these 11.15. Latched Faults
sounder outputs always operate in the General When enabled, all fault conditions latch until the
mode regardless of the setting on the Reset switch is operated.
general/zonal alarms configuration switch. The A latched zone fault will be cleared if a fire condition
output expansion system [due later] provides occurs on the same zone.
additional sounders circuits for General or
Zonal use on the 8, 16 and 32 zone panels. 11.16. Repeater Configuration
11.8. Pulse Non-Alarm Zones The panel can be configured to communicate with
up to 5 remote indication panels via DIL switch
Selects the type of zonal sounder alarm response selection on Repeater Interface Board.
to a fire when the Zone Alarms feature described
above is selected. The two selectable options are:
PAGE 23 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Aux
Reset N/C
Buz Active
1 2 3 4 5 6 7 8 1 2 3 4
EVAC
GND
RST
DIS
24V
SIL
0V
1 2 3 4 + - + - + - + - + - + - + - + - + - + - + - + - A B
Lower
terminal tier
Upper
terminal tier
+ - + - + - + - + - + - + - + -
O/+
C/+
C/+
24 V
0V
P
C/-
P
O/-
P
O/-
N/O
P
9 10 11 12 13 14 15 16
Zone Circuits Aux Fault Fire Fire Reset
Precept DC Routing Routing Protection
O/- = Normally Open or -ve
2 O/+ = Normally Open or +ve
4 P = Pole
C/+ = Normally Closed or +ve
8 C/- = Normally Closed or -ve
16/32
Grey fill indicates I/O available on selected panel
Upper
terminal tier
+ - + - + - + - + - + - + - + -
25 26 27 28 29 30 31 32
Zone Circuits
PAGE 24 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
13.1. Auxiliary Supply circuit and therefore the total load across both sets
of terminals must not exceed the rated value.
An auxiliary DC supply is available to power
Note: If equipment draws current from the
external field equipment from the panel. This is
auxiliary supply during the mains failed
nominally rated at 27.1V but varies due to
condition, this must be included in the battery
temperature changes and also during mains failed
capacity calculations.
conditions. See section 17 below for details of
maximum load. 13.2. Fire Routing, Fire Protection and
The output is fused using an electronic device and Fault Routing Outputs
fuse activation will be indicated as Fuse Failed on These outputs are factory-set to the fault monitored,
the panel display. The fuse can be reset after powered mode of operation but can be configured
removal of the fault by operating the Reset button at site to volt-free relay outputs [See 11.17 above].
on the display. Connection details for both types of configuration
The auxiliary supply terminals are labelled Aux DC are provided in Figure 15.
0V and 24V. Although two sets of terminals are
provided, they are both protected by the same fuse
C/-
Note: Terminals are dual marked for monitored/powered and volt-free configurations.
For volt-free: O = Open, C = Closed, P = Pole
For monitored/powered: + = Positive, - = Negative
Warning: The volt-free auxiliary relay contacts must not be used to directly switch any voltage that
exceeds 30VDC.
PAGE 25 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Figure 16 – Reset Relay Contact Connection Figure 18 – Alarm Circuit Configuration
details
Alarm +
Panel Wiring Field Wiring
N/O Polarising
3k9 End
diode
of line
[1N4002S]
Volt-Free Changeover resistor
Relay Configuration P Suppression
Output conditions:
diode
For Reset Relay
[1N4002S]
Shown in quiescent
[de-energised] condition. N/C Bell Electronic
sounder
Alarm -
Warning: The volt-free auxiliary relay contacts
must not be used to directly switch any voltage
that exceeds 30VDC.
The voltage drop on each alarm circuit should be
13.3. Use of Auxiliary Inputs calculated to ensure that the minimum voltage at
Auxiliary inputs are provided to allow remote the end of each circuit exceeds the minimum
operation of the following functions: required by each sounding device.
Class Change. The voltage at the end of the circuit is given by:
Remote Evacuate. VAmin = VOmin- (IA x 2 x L x RC)
Remote Silence. VAmin = Minimum Alarm Voltage
Remote Reset. VOmin = Minimum Output Voltage**
To activate an input, 0Vdc should be connected IA = Alarm Current in Amps
across the input circuit via a normally open contact L = Alarm Circuit Length in metres
arranged to close. [See Figure 17] RC = Cable resistance (Ohms per metre)
Figure 17 – Auxiliary I/P Connection Detail ** Min O/P voltages:
Precept EN 32 = 18.4V
Panel Wiring Field Wiring Precept EN 8 and 16 = 19.2V
Sil, Evac, Reset Precept EN 2/4 = 19.2V
or Class External normally open
Change switch or relay contact, The resistance per metre is as follows:
closing to activate I/P 2
1.5mm - 0.015 per metre per core
2
Aux DC 2.5mm - 0.009 per metre per core
0V
14. Electrical Design of Detection
Zones
Note: To prevent unauthorised operation of the To allow the panel to correctly monitor for fault
system, any manually operated auxiliary input conditions, the wiring for each zone must be
must be operated by a key-switch. The key to installed as a continuous pair with no spurs or tees
the switch should be held with the panel’s and be terminated with an end of line device; 22F
access control key. 35V capacitors for standard, non- intrinsically safe
zones, 10k 0.25W for intrinsically safe zones.
13.4. Sounder Circuits Correct polarity must be strictly observed
Precept EN 2-zone panels have 2 sounder circuits throughout.
rated at 0.5 Amps. 4-zone panels have 4, each
rated at 0.5 Amps. The 8, 16 and 32-zone panels
14.1. Maximum Number of Devices on
have 4 sounder circuits each rated at 1 Amp. The a Zone
circuits are reverse-polarity monitored for open and The maximum number of devices supported by a
short circuit faults. To allow monitoring, all devices zone depends on the quiescent current drawn by
must be polarised. To prevent damage to the each device and differs for intrinsically safe and
control panel, bells must also have a suppression non- intrinsically safe zones. The quiescent current
diode fitted as shown in Figure 18. The circuit must will be listed on the device data sheet provided by
be terminated with a 3k9 end of line resistor. the Manufacturers.
For non-intrinsically safe zones, the maximum
current available is 5mA.
PAGE 26 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
For intrinsically safe zones, the maximum current DIL SW OFF - Automatically turns off the delay
available is 0.8mA. mode once a day at a set time [the delay mode
Note: To comply with BSEN 54-2, the maximum first being turned on manually].
number of devices per zone is limited to 32 DIL SW ON - Automatically turn the delay mode
and the maximum number of devices on once a day and off once a day at set times.
connected to a panel is limited to 512. 15.1.3. 1st Fire Alarm Time
Intrinsically Safe Zones This displays the time of the first fire alarm. This
Warning: I.S zone wiring and equipment condition is latched until the panel is reset and is
installation must comply with the installation not updated by any subsequent fire alarms [i.e. fire
guidelines provided with the I.S. fire detection alarms which occur while the first alarm is still
equipment and the I.S. barrier. Any zone on displayed].
which I.S. equipment is to be connected must
be configured as an I.S. zone. [See 11.4
15.2. Clock Module Edit Facility
above]. The Clock Module has a simple edit feature to
allow:
15. C1651 Clock/Timer Module
Set time of day [User accessible].
The LCD clock/Timer module is an optional feature Set daily delay mode on/off times [User
for the Precept EN range of panels, providing the accessible].
Alarm Counter and Day/Night Delay Time features
described elsewhere in this document. Selection of Day/Night delay mode on/off
[Engineer accessible].
A jumper and DIL switch are provided on the clock
module PCB to allow one of the following modes of 15.2.1. User Control/Editing
operation to be set: When the Clock Module is fitted, the User has
i. Day/Night Delay Time access to select the status of the Day/Night Mode -
either ON or OFF and to set the current time. These
ii. Day/Night Delay Time and Alarm Counter.
st
edit features are accessed by operating the Access
iii. Time of 1 fire alarm. key switch, pressing the Select button and using
st
iv. Time of 1 fire alarm and Alarm Counter. the Select ↑ Select ↓ buttons to scroll the cursor
The module is fitted to the rear of the display PCB, indicator through the selectable LEDs until the
inside a break-out window. Two DIL pin headers Clock Module is selected [Clock Module back light
fitted to the rear of the display PCB provide all lit].
electrical connections. The module has a 2-line 8- 15.2.2. Engineer’s Editing and
character alphanumeric backlit LCD. Configuration
The clock module must be used with the “fully Editing: Manual selection of the Day/Night Mode
insertible” display overlay which has a clear window and setting the current time is described in the
through which the LCD can be viewed. A tab on the FIRECLASS Precept EN Installation and
end of the User Instruction insert normally blanks Commissioning Manual.
off the window. This tab must be removed before
Configuration:
the insert is fitted, to expose the window.
Setting the time of day at which the clock module
15.1. Clock Module Functionality automatically turns the delay mode on/off is set
15.1.1. Alarm Counter using the Clock Module menu system as described
in the FIRECLASS Precept EN Installation and
Complying with the requirements of EN54-2 clause
Commissioning Manual. Access to these extra
7.13, recording the number of times the panel
menu pages is protected by a DIL switch on the
enters the fire alarm condition.
rear of the Clock Module PCB.
The current count can be displayed (via Test
A jumper and DIL switch are provided on the clock
Lamps) or reset to zero manually when required.
module PCB to allow one of the following modes of
15.1.2. Day/Night Delay Mode control operation to be set:
This allows the delay mode to be automatically i. Day/Night Delay Time
controlled by the clock module. It can be configured
ii. Day/Night Delay Time and Alarm Counter.
to operate in one of two modes via a DIL switch on
the control panel motherboard (DELAY ON AUTO): iii. First Fire Alarm Time.
iv. First Fire Alarm Time and Alarm counter.
PAGE 27 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
LK1 – Select
operating mode
DIL switch S1 -
Select config mode,
reset/disable counter
PAGE 28 of 37
Typical Zone Wiring Typical Alarm Circuit Wiring Typical Input Circuit Wiring
22uF capacitor end-of-line device for Remote Silence, Evac, Reset &
-observe polarity Class Change,
EQUIPMENT:
+ 1A 2A -
Manual call point
Typical remote
with 680R resistor
0
output wiring
+ -
+ 1 2 -
+ - 2k2 0.5W
resistor
Typical zonal
output wiring Terminal identification
09/03/12
notes:
+ Cl/C = Class Change.
+ -
Connect to B Act = Buzzer Active
Aux DC 24 - RST = Reset
24 V DC V -
+
relay + Repeater Wiring - see
Detector base with Figure 9 - Repeater
Schottky Diode connection diagram
FIRECLASS PREC EN APP
1 2 3 4 1+ 1- 2+ 2- 3+ 3- 4+ 4- 5+ 5- 6+ 6- 7+ 7- 8+ 8- 1+ 1- 2+ 2- 3+ 3- 4+ 4 - 24V 0V Sil Evac RST Cl/C Dis Evac BAct A B GND N/C
Lower terminal tier
PAGE 29 of 37
FIRECLASS PRECEPT EN
Lower terminal tier Zone O/Ps Zone Circuits Alarm Circuits Aux DC Inputs Outputs Repeater RST
Upper terminal tier Zone Circuits Aux DC Fault Routing Fire Routing Fire Protection RST Upper terminal tier
9+ 9 - 10 + 10 - 11 + 11 - 12 + 12 - 13 + 13 - 14 + 14 - 15 + 15 - 16 + 16 - 24V 0V O/+ P C/- C/+ P O/- C/+ P O/- P N/O
Fire Routing, Fault Routing & Fire Protection O/P configuration - Output specification: Fire and Fault Routing output
wiring shown for the
monitored/powered
When configured as monitored/powered outputs: When configured as volt-free changeover relays :
Figure 20 – Typical Panel Connection Diagram
configuration
For Fire Routing and Fire Protection O/Ps:
For Fire Routing and Fire Protection O/Ps: Volt free relay contacts shown in quiescent [de-energised] Relay fitted locally Relay fitted locally
Quiescent: 5 V DC condition. to fault routing to fire routing
Active [fire]: 24 V nom] equipment equipment
For Fault O/P:
For Fault Routing O/P: Volt free relay contacts shown in healthy [energised]
Quiescent: 24 V DC [nom] condition.
Active [fault]: 5 V Field relay spec:
Connections: Coil resistance - 2.6 to 4.5 k Ohms
Connections: Connect to normally open or normally closed contact as Voltage 24 V DC Nom
Observe correct polarity. required.[P= Pole, C= Closed, O = Open] [min 18 V, max 30 V]
[+ = Positive, - = Negative] Applied voltage must not exceed 30 V DC. Fitted with suppression diode as shown.
CHECKED BY: AP
WRITTEN BY: RKP
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
PAGE 30 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Output Voltage
Factory Set
adjustment
Output protection: Electronic current limiting
Common fault
N/A N/A N/A 25mA N/A N/A N/A
output:
Mains failed fault
N/A N/A N/A 25mA N/A N/A N/A
output:
Panel Repeater
Battery Specification
2/4 zone 8 zone 16 zone 32 zone 2-8 zone 16 zone 32 zone
Battery charger output:
[Temperature
compensated float
1.5A 3A 3A 5A 1.5 A 1.5 A 1.5 A
charger]
28.6V 0.1V@-5C
26.5 V0.1V@ +40 C.
Maximum internal
resistance of battery &
charger circuit: 1 0.6 0.6 0.35 1 1 1
(Ri max)
(Ω)
Battery type:
2 off 2 off 2 off 2 off 2 off 2 off 2 off
POWERSONIC
PS1230 PS1270 PS12120 PS12170 PS1230 PS1230 PS1230
[Warning: Replace only [12V 3.4Ah] [12V 7Ah] [12V 12Ah] [12V 17Ah] [12V 3.4Ah] [12V 3.4Ah] [12V 3.4Ah]
with identical battery]
Battery size (mm):
W
Environmental
All Panels
Specification
Operating temperature: -5ºC to 40ºC
Operating humidity: 5% to 95%
PAGE 31 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Ancillary Inputs 2/4 zone Panel 8 zone Panel 16 zone Panel 32 zone Panel
Zonal Fire Outputs for
Open collector, 50mA 30V max input
Zones 1-4
Class Change Input Non- fault monitored. 0 Volt I/P to activate. I/P sensitivity: 0-1k Ohm
Remote Evacuate
Non- fault monitored. 0 Volt I/P to activate. I/P sensitivity: 0-1k Ohm
Input
Remote Silence Input Non- fault monitored. 0 Volt I/P to activate. I/P sensitivity: 0-1k Ohm
Remote Reset Input Non- fault monitored. 0 Volt I/P to activate. I/P sensitivity: 0-1k Ohm
Cable requirements Cable loop resistance <= 1k Ohm
Alarm threshold between 10k Ohm to 70 k Ohm [dependant on circuit] between
Earth Fault I/P
chassis and +ve or -ve line
PAGE 32 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Panel Repeater
Alarm Circuits
2/4 zone 8 zone 16 zone 32 zone 2-8 zone 16 zone 32 zone
Quantity: 2/4 4 4 4 N/A N/A N/A
Maximum Current:
0.5A 1A 1A 1A N/A N/A N/A
per circuit
Output Voltage (battery
20- 28.6V DC
operation):
Output Voltage (mains
28.6- 26.5 V DC
operation):
Fault Monitoring: Reverse polarity for open and short circuit faults
Protection [Self resetting
0.93A 0.93A 1.85A 1.85A N/A
electronic]
Cable requirements: No special requirements. Cable resistance and current load must allow a voltage
at the end-of-line which is above the minimum operating voltage of the sounders.
Panel Repeater
Auxiliary Supply
2/4 zone 8 zone 16 zone 32 zone 2-8 zone 16 zone 32 zone
Maximum Current: 0.5A 1A 1A 1A N/A N/A N/A
Auxiliary supply
20–28.6Vdc N/A N/A N/A
(battery operation):
Auxiliary supply
28.6- 26.5Vdc N/A N/A N/A
(mains operation):
Protection:
0.5 A 1A 1A 1A N/A N/A N/A
[Electronic]
No special requirements. 1A minimum current rating. Minimum voltage at end-of-
Cable requirements:
line must be above sounding device minimum operating voltage.
Panel
Repeater Output
2/4 zone 8 zone 16 zone 32 zone
Number of repeaters: 1 to 5
Maximum repeater
2000m
cable length:
Communication
RS485 serial data 9600baud
protocol:
Protection: Electronic, current limited
Cable Type: Two pair RS485 shielded cable (see below)
PAGE 33 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
PAGE 34 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
18.4. Battery Standby Capacity 10. Substitute the values in to the formula below.
Calculation Cmin = 1.25 x ((Tfault x Ifault) + 2 x (Talarm x Ialarm))/1000Ah
This section describes how to calculate the = ……))/1000Ah
minimum required standby battery capacity for the = 1.25 x (…… +2 x (……)/1000 Ah
control panel. To determine the battery capacity, 1.25 x (……)/1000Ah
perform the following steps:
= 1.25 x ……/1000Ah
1. Look-up the mains failed fault battery current.
Enter this value as Ipanelfault. = ……/1000Ah
2. Look-up the mains failed alarm battery current. = …… Ah
Enter this value as Ipanelalarm.
3. Calculate the maximum load on the alarm
circuits in mA in an alarm condition. Enter this 11. Select the next highest available battery size.
value as Ialarms and enter this figure in the table. Notes:
4. Calculate the load on the auxiliary supply in mA 1. The maximum battery capacities which
in an alarm condition. Enter this value as Iauxfault. can be charged according to BFPSA
5. Calculate the load on the auxiliary supply in mA recommendations are:
in an alarm condition. Enter this value as Maximum
Iauxalarm. Panel
Battery Capacity
6. Calculate the total battery load in fault, Ifault. Precept EN 2 and 4 12Ah
7. Calculate the total battery load in alarm, Ialarm. Precept EN 8 and 16 24Ah
8. Enter the required standby time in hours, T fault. Precept EN 32 40Ah
9. Enter the required time in alarm in hours, Talarm.
2. Any battery which cannot be contained
Ipanelfault = ………mA in the panel enclosure must be located
in an enclosure adjacent to the panel.
3. The Precept EN panels accommodate
Iauxfault = ………mA internally mounted SLA batteries as
listed below:
Ifault = [Ipanelfault + Iauxfault] ………mA
Maximum
Panel
Battery Capacity
Tfault = ………Hrs Precept EN 2 and 4 3Ah
Precept EN 8 7Ah or 12Ah
Ipanelalarm = ………mA Precept EN 16 12Ah
Precept EN 32 17Ah
Ialarms = ………mA
Iauxalarm = ………mA
Ialarm = [Ipanelalarm + Ialarms + ………mA
Iauxalarm]
Talarm = hrs
PAGE 35 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
PAGE 36 of 37
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Table 2 – Zone Configuration Design/Record
Output Configuration
Output
Delay Non-delay
Fire Routing
Fire protection
Alarm Devices
PAGE 37 of 37