Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Profibus Master - Modbus Plus Slave: 512 Bytes (Max 64 Bytes As Modbus Plus Global Data) Ytes, Max

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Profibus Master - Modbus Plus Slave

The Anybus X-gateway copies I/O-data in both directions thus enabling data exchange between the two
networks. Default I/O configuration is 20 bytes Input and 20 bytes Output. Changing default settings is very
simple and is carried out using the RS232 configuration port and a standard terminal interface on a PC,
such as Hyper Terminal for Windows.

The Anybus-M Profibus-DP interface supports connection of up to 125 slaves at baudrates up to 12 Mbit/s.
The Profibus configuration is defined with NetTool-PB, the windows based configuration software for
Profibus from HMS (purchased as a separate accessory).
The Profibus interface module is certified by the Profibus user organization and has proven conformance
and interoperability with leading manufacturers of I/O, drives, instruments etc
Configuration is downloaded to the module via the RS232 configuration port.

The Modbus Plus interface is based on licensed chip-set and software from Modicon Inc. Supporting both
the Global Database and Register mapping to 3x and 4x registers this module implements a versatile
Modbus Plus interface. The Modbus Plus interface module is certified by the Modconnect and has proven
conformance and interoperability with leading PLC´s, HMI´s etc

KEY FEATURES

Profibus configuration: NetTool-PB for Windows

Built on Siemens ASIC ASPC2 Step E with Infineon C165 Microprocessor

Up to 125 slaves can be connected

Profibus configuration through RS232 configuration port

Supports PA baud rate 45.45 kbit/s

Modbus Plus Global Data Base Transaction, Point-to-Point commands, Read holding registers, Preset single register

Modbus Plus Host Firmware Rev. 77

Complete Profibus DP Master according to IEC 61158

TECHNICAL SPECIFICATIONS

Size: 126 mm x 110 mm x 42 mm


Power Supply: 24 VDC (±10%)
Temperature: 0-65°C
Current Consump: max 300 mA
I/O Input: Default 20 bytes, max 512 bytes (max 64 bytes as Modbus Plus Global Data)
I/O Output: Default 20 bytes, max 512 bytes (max 64 bytes as Modbus Plus Global Data)
Mech Rating: IP20/Nema1
Config Method: Windows Hyper Terminal
UL certification: E203225, Listed 67AM, UL-1604 Class 1, Div 2, GP A, B, C, D, Temp Code T4
ATEX certification: ATEX 135419, II 3 G, EEx nL IIC T4, DEMKO 03
Power supply connector: 2-pole 5.08 mm Phoenix pluggable screw connector
Profibus baudrate: 9600 bit/s - 12 Mbit/s
Profibus address: Node address 0-125
Profibus connector: D-sub 9-pin female
Accessory order code: 018330 (NetTool-PB configuration tool for Profibus)
Modbus Plus baudrate: 1 Mbit/s
Modbus Plus address: Node-ID and Source-ID 1-64
ModbusPlus connector: D-sub 9-pin female
Price Group: C
Order Code: AB7809