Dorot 68-De - El - MR
Dorot 68-De - El - MR
Dorot 68-De - El - MR
MODEL 68 DE\EL-MR
DE\EL-MR
Electrically Actuated, Manual Reset
Deluge Valve 2/2 Solenoid
• High pressure (PN25/375psi), high flow • Low lifelong maintenance costs due to
deluge systems straightforward design
• Automatic or local manual emergency • Applicable for fresh or brackish water,
actuation seawater & foam
• Out of box fully assembled & tested valves
• Hazardous, flammable & explosion • Factory trimmed for vertical or horizontal
classified area fire suppression installations without modification
• Superior design featuring exceptionally • Extensive valve & trim materials selection
low pressure losses at high flow rates and corrosion protection coating
TYPICAL APPLICATIONS
w w w. c o n t r o l va l v e s . c o m
FIRE PROTECTION DELUGE
MODEL 68 DE\EL-MR
OPERATION
The basic control valve [1] used in this deluge system is a direct sealing elastomeric diaphragm,
hydraulically operated control valve engineered specifically for fire protection systems. The system
includes a 2/2-way N.C. solenoid [9] as the interface between the fire alarm control panel - monitoring
heat, smoke or flames - and the deluge valve.
In the stand by position, the deluge valve is held closed by the upstream water pressure, trapped in
the valve’s control chamber. The water pressure enters the control chamber through the priming Line
Ball Valve [2], a Y-Type Strainer [3], a Check Valve [4] and a DMR (Manual Reset Latching Device) [5].
Under fire conditions, a fire alarm control panel (F&G panel) energizes the 2/2-way N.C. Solenoid (or
de-energizes the coil of a continuously energized ED 100% normally open solenoid for SIL 3-4 rated
systems). Water is drained from the deluge valve’s control chamber through the 2/2-way N.C. Solenoid.
The deluge valve opens instantly and allows water to flow into the pipeline and through the open
sprinklers over the protected area.
Manual emergency actuation is enabled by opening the Emergency Manual Activation Valve [6]. The
deluge valve opens instantly and allows water to flow into the pipeline and through the open sprinklers
over the protected area.
When the valve trips open, the DMR isolates the control chamber from the upstream pressure source.
Reconnecting the upstream pressure to enable the deluge valve to close can only be achieved by
pressing the DMR’s knob.
Resetting, maintenance and periodic testing instructions must be followed as described in detail in the
2 applicable OCV IOM (Installation, Operation & Maintenance) Manual.
w w w. c o n t r o l va l v e s . c o m
FIRE PROTECTION DELUGE
MODEL 68 DE\EL-MR
TYPICAL MATERIALS
w w w. c o n t r o l va l v e s . c o m
FIRE PROTECTION DELUGE
MODEL 68 DE\EL-MR
Valve 2” (50) 2.5” (65) 3” (80) 4” (100) 6” (150) 8” (200) 10” (250)
inch mm inch mm inch mm inch mm inch mm inch mm inch mm
A 9 /8
5
243 9 3/16 233 12 3/16 310 14 356 17 3/16 436 20 7/8 530 25 635
AG (1) 9 5/8 243 10 253 13 3/16 336 15 380 17 5/16 440 21 7/8 556 N/A
B 6 5/8 168 7 3/8 185 7 7/8 200 9 3/8 238 12 1/8 306 14 3/16 360 16 7/8 430
C 4 13/16 122 4 13/16 122 6 1/8 155 6 154 7 11/16 198 9 3/8 238 11 5/16 287
D 5 11/16 145 5 11/16 145 5 /16 145
11
5 /16 145
11
6 5/16 160 7 /8
7
200 9 13/16 249
E 9 11/16 247 9 11/16 247 12 3/8 313 12 3/8 309 15 3/8 392 16 5/16 412 17 1/8 435
F 10 3/8 262 10 3/8 262 10 3/8 262 10 3/8 262 10 3/8 262 10 3/8 265 12 1/2 317
* Approximate dimensions
(1) Grooved model length
w w w. c o n t r o l va l v e s . c o m
FIRE PROTECTION DELUGE
MODEL 68 DE\EL-MR
TYPICAL INSTALLATION
2 3
1
5 Heat/Smoke/Other Detectors
w w w. c o n t r o l va l v e s . c o m
FIRE PROTECTION DELUGE
MODEL 68 DE\EL-MR
TECHNICAL DATA
ENGINEERING SPECIFICATIONS
The deluge valve shall be hydraulically operated, direct elastomeric diaphragm-seal, single chamber
weir type. The valve shall consist of three major components: the body, the cover and the diaphragm
assembly. The diaphragm assembly shall be the only moving part. The diaphragm forms a sealed
control chamber in the upper portion of the valve, separating operating pressure from line pressure.
Packing glands, stuffing boxes and dynamic O-ring seals are not permitted and there shall not be shafts,
discs, bearings or pistons operating the valve. No hourglass shaped disc retainers shall be permitted,
and no V-type, U-type or other slotted type disc guides shall be used. The valve shall contain a nylon
reinforced rubber diaphragm, elastic & resilient through its entire surface without vulcanized radial
seals and/or reinforcements. The diaphragm assembly shall not be guided by any shafts or bearings
and shall not be in close contact with other valve parts except for its sealing surface. The deluge
valve shall be fully trimmed, hydrostatically and operationally tested at the factory. Maintenance,
disassembly and reassembly of all the valve’s components shall be made possible on-site and in-line,
without the need to remove the valve from the line. Main valve body and bonnet standard material
shall be Ductile Iron or Cast Steel. Main valve body and bonnet surfaces shall include a fire red epoxy
coating. Other materials and coatings available upon request. The deluge valve shall be a Model 68
DE\EL-MR, UL Listed under VLFT category, as manufactured by OCV Fluid Solutions, Tulsa, OK, USA.
OCV companies worldwide reserve the right to make changes without notice including product specification and con-
figuration, content, description(s), dimensions etc. The information herein is subject to change without notice. OCV
shall not be held liable for any errors. All rights reserved. © Copyright by OCV.
w w w. c o n t r o l va l v e s . c o m