Cold Formed Track Design
Cold Formed Track Design
$5.00
Summary: When cold-formed steel studs are used on exterior walls between spandrel beams or floor slabs to
create the exterior envelope of the building, a deflection track is often required at the top of the wall to allow for
the roof or floor above to deflect without transferring axial load to the studs. This Technical Note explores two
methods for deflection track usage.
Disclaimer: Designs cited herein are not intended to preclude the use of other materials, assemblies, structures or
designs when these other designs and materials demonstrate equivalent performance for the intended use; CFSEI
documents are not intended to exclude the use and implementation of any other design or construction technique.
INTRODUCTION
When cold-formed steel studs are used on exterior close to the end of the member to restrain the stud from
walls between spandrel beams or floor slabs to create lateral movement and twisting under lateral loading.
the exterior envelope of the building, a deflection track 2. Deflection track is constructed with two
is often required at the top of the wall to allow for the tracks, the upper “over” track is an oversized track with
roof or floor above to deflect without transferring long legs, and the lower track is a standard track with
axial load to the studs. Proprietary products such as legs long enough, typically 1” longer than the over track
slotted track or deflection clips may be used. Follow to allow clearance for the screw heads. The lower track
m a n u f a c t u r e ’s p u b l i s h e d d e s i g n v a l u e s a n d is fastened to the studs with low profile screws or other
installation recommendations when using these suitable connectors at each flange and a gap is left
products. However the following two methods are between the lower and upper track. The tracks are not
covered in this tech note: attached to each other. Bracing is not required for the
1. Deflection track is constructed with a studs because the lower track is attached to each flange
single, long leg track, a gap is left between the wall and braces the stud against rotation.
stud and the track web, and a row of bracing is placed
FIGURE 1
FIGURE 2 FIGURE 4
2. Issue of overhang of the structure - Limit the outward 4. Reinforcing blocking at jamb locations - Use stud
and upward deflection to 1/8" for serviceability and blocks to stiffen the deflection track, see Figure 5. in
prevent stud from disengaging. Design the fasteners to this case both track legs are resisting the load provided
the structure for direct shear from the stud reaction and the screws can transfer the load to the other leg. If
for indirect tension due to the eccentricity of the load and enough screws are used the capacity may be doubled
the pivot point of the track. See figure 3. as compared to deflection track without reinforcement.
overhang
FIGURE 5
FIGURE 3
FI
FIGURE 7
FIGURE 8 FIGURE 9
Studs with a deflection track are generally subjected to lateral or wind loads only. In order to prevent any transfer of
axial load between the structure and the stud, a gap is placed between the web of the deflection track and the top of
the stud. This gap must allow for construction tolerances, material tolerances, in addition it must provide for upward
and downward movement of the structure. Upward movement may occur when the structure experiences uplift
pressure, especially in the roof, or from unbalanced loading of the floor. Studs are attached to structural elements
which are subjected to live load deflection, typically limited to L/360. For a 30 foot span the vertical movement of the
beam could be as much as 1 inch if full design live load is applied. EOR typically provides the required gap in the
construction documents.
Calculation of required gap:
Floor Beam Span: 20 ft
Live Load Deflection Limit: L/360
Max. Live Load Deflection: (20 ft x 12 in/ft) / 360 = 0.67 in
Required Gap: 0.67 in
FIGURE 10
w dt t 2 Fy (Eq. B2.3-1)
Pndt =
4e
Where:
t = track thickness
Fut= track yield strength
e = design gap for deflection
Ω = 2.8 for ASD
Φ = 0.55 for LRFD
Fut = 0.45 for LSD
Note: For the double slip track, wdt is taken as the stud spacing, and the plate bending formula is used.
fb = M / S ⇒ M = fb · S ⇒ 0.6 · Fy · wdt · t2 / 6
Where:
Fy = 33,000 psi Pall = 0.6 · (33,000 psi)(16”)(0.0451”)2/6(0.5”)
e = 0.5 inch
t = 0.0451inch
½” Gap ¾” Gap
Stud Spacing = 12 in Stud Spacing = 16 in
ksi 43mil 54mil 68mil ksi 43mil 54mil 68mil
33 144 213 287 33 123 158 210
50 218 323 435 50 187 240 318
½” Gap 1” Gap
Stud Spacing = 16 in Stud Spacing = 12 in
ksi 43mil 54mil 68mil ksi 43mil 54mil 68mil
33 163 213 287 33 72 113 169
50 247 323 435 50 109 172 256
½” Gap 1” Gap
Stud Spacing = 24 in Stud Spacing = 16 in
ksi 43mil 54mil 68mil ksi 43mil 54mil 68mil
33 163 213 287 33 96 129 169
50 247 323 435 50 145 195 256
¾” Gap 1” Gap
Stud Spacing = 12 in Stud Spacing = 24 in
ksi 43mil 54mil 68mil ksi 43mil 54mil 68mil
33 96 151 210 33 102 129 169
50 145 229 318 50 154 195 256
References
1. North American Standard for Cold-Formed Steel Framing - Wall Stud Design, AISI S211-07, American Iron and Steel Institute,
Washington, DC, 2007.
This “Technical Note on Cold-Formed Steel Construction” is published by the Cold-Formed Steel Engineers Institute (“CFSEI”). The
information provided in this publication shall not constitute any representation or warranty, express or implied, on the part of CFSEI
or any individual that the information is suitable for any general or specific purpose, and should not be used without consulting with a
qualified engineer, architect, or building designer. ANY INDIVIDUAL OR ENTITY MAKING USE OF THE INFORMATION
PROVIDED IN THIS PUBLICATION ASSUMES ALL RISKS AND LIABILITIES ARISING OR RESULTING FROM SUCH
USE. CFSEI believes that the information contained within this publication is in conformance with prevailing engineering standards of
practice. However, none of the information provided in this publication is intended to represent any official position of the CFSEI or
to exclude the use and implementation of any other design or construction technique.