ffiryr§-:?rygl Customer
Plant:
BAPCO Rev. 0
SERVICE ACTIVITY
REPORT
From 0110312020 to 06/03/2020
2
I
0 Dec. 07, 2006 issue
HEV. Date Description Prepared Checked Approved
Job. N. 261 908054 Date 06103t2020
f;annnn ffcna
re§ Customer BAPCO PS3 Rev. n
Plant:
HTH25MWiFO/PA Sr.Nr QCP233O1 B
SERVICE ACTIVITY REPORT
QCP23301B
I
H
Y
'.tA
Inspection door burned & operation of repair, door should be changed with a new one
Job. N, 261 908054 Date 06t03t2020
THICKNESS CONTROL
Thickness control show value into admissible range, heater pipe thick is in good condition.
LEAK:
Diathermic Oil Leakage from coil Drain, should remove insolation & repair
Job. N. 261 908054 Date 06t03t2020
i:,m I
.l
Leak on Heat exchanger, crude oil side leah on diathelmic oil side
Job. N. 261908054 i oat" 06t0312020
FLEXBLE HOSE
High pressure Flexible hose should be replaced
ffi tan*un ffi;srt*trnengim
N
sERVtcE RcnvrrY
) Check, test and calibrate all protection and control devises where applicable
Fire Emergency stop of customer side was Not connected to Terminal, cable are
not present in the cabinet.
visual Level ofExpansion Tank not according ( real level show in pic was at 40%)
ONE of visual level should be replaced
BMS
BMS
@,1":. BMS on heater 233018 was damage , replace with
spare part on site
a new one, need to restore the
UV SENSORCONNECTION
UV sensor connection was modified fiom original drawing, was use a VFC from Kl22 to close
contact on BMS
instead the vFC of FIREYE uv sensor, fireye contact eneigise K122 relay.
TRACE HEATER
The Trace heater on crude oil Line are not working actually, NEED To BE REPLACED
ASAP.
Customer request is improve an upgrade in order to permii starting with diesel oil,
swap to crude oil and betbre stop
heater swap again to diesel in automatic, to flush the tine.
Job. N. 261 908054 Date 06t03t2020
SETTINCS OF FIEATER:
I
I
r-l,l r rl l,llli
lIti llxt,tlil
lrl _0 0
Job. N. 261 908054 Date 06103t2020
§annnn ffir:n* §nergia
ffi§ I
Gustomer BAPCO PS3 Rev. 0
Plant:
HTH2SMW/FO/PA Sr.Nr QCP23301 B
SERVICE ACTIVITY ìT
SAFETY CHECK
tllell:ilcl
i F:L{ar6g ,
rTzLa&$'8.
t,. '-.,/
.ì. '--
;i§il;t-i r,
.{Ulr,lr "',.,Jì I'\-,-',rJ
l:,jrllitlt .t,;:!
I :rr uti"4' i.; 1'>§r'r/1!,
. -Ld**Li:-ri ,
x!; tt i i, rr , tr, iJ ,'/
il
::ì
;!,L'fi)t
-ll-'l\wllr'j
l
iJtì§r!J;vJ
r'ì .»c (,. rr'
"i3: tvti
OXYGEN PROBE
Oxygen probe on QCP2330lB not working, in stand by condition show 0.0% of 02 ,should be replaced
witha new one.
Check Damper movement , remove internal impediment due for a construction of negative sample of DPT
combustion air, check movement & cleaning damper . Movement part was grease from customer.
Check- Also motor of oil purnp & Fan was grease from customer regularly.
10
Job. N. 261 908054 Date 06t03t2020
Functional Check.
IGNITION SEQTIENCE
During ignition sequence pilot time is not enough to ensure all the time correct working of boiler, often we had a
shutdown for lack of flame in main valve position.
Customer usually is use to by-pass the UV sensor signal ( really dangerous)
To fix situation properly we increase pilot time on I(130 up to maximum ( 30 sec). Solve it.
During Ignition sequence find problem with pilot valves, was neaessary
replace pilot line with new line initially designated to eCp2330lA .
The pilot valves also ifenergized didn't open, so it's necessary provide to
ship spare part ( 2 new pilot valves) and replace it.
On site at the moment there is NO spare for pilot valve available.
cleaning UV sensor lens , cleaning burner nozzle & flushing line with diesel oil.
IGNITION SEQUENCE
Ignition sequence become difficult with crude oil maintain a correct pressure drop due a problem on feedline not
,
traced( not working). so customer usually start with diesel oil then change to crude oil.
This operation is doing manually, sometimes they forgot diesel valve opin and fill the tank with return
of crude oil
(there isn't a check valve) so customer want to upgrade to an automatiCswitch from diesel into
crude oil.
11
Job. N. 261 908054 Date 06t03t2020
REGULATION VALVE
Due to a problem with main flame ( was unstable) after cleaning crude oi1 line it was necessary reset & calibrate
FV005B (crude oil regulation valve ) and PDV009B ( atomizing air regulation valve).
Customer requires is to replace with new one all this valve on this heaters inciuding TV007B.
This heaters had for a long time problem due a valve regulation '
ry%-
k
REGT]LATION CHECK
Control modulation set with Heater in production, customer switch OFF Heater A for next service, so movement
between different point ofcombustion curve is subject to the consumption from the plant.
t2
Job. N. 261 908054 Date 06t03t2020
) Conclusion
Main problem on this site is a relaxing manage in heaters maintenance, flame stability'problem is
almost appears two months ago, pipe tracer was broken from 6 months, BMS was damage( and heater
stop) from January 2020.
Seems that persomel didn't take care of problem & don't explain about historical of problem,
So we have notice of all problem after 2 days ofinvestigation .
In order to guarantee efficiency & safety condition for heater ALL SPARE PARTS IN THE LIST
SHOULD BE REPLACE .
Especially Crude oil pipe line need a strong upgrade: trace heater, nozzle,crude oil 3 way
valve(BV0O4B) & crude oil regulation valve should be replace.
MANDATORY
. OXIGENPROBE
. PILOT VALVE (NR2)
. 3 WAY VALVE TCV 008B at EXCHANGER E-23001B
13
Job. N. 261 908054 Date 06to3t2020
. BURNERREFRACTORY
. REFRACTORYDOOR
. BMS ( HONEYWELL 7850 Or new type in case on cabinet upgrade)
. COMBUSTION AIR GAUGE
. VISUAL LEVEL OF EXPANSION TANK ( COLIMA)
. RUPTURE DISK FORDIATHERMIC OIPLANT.
. SPARE NOZZLE FOR CRUDE OIL
. CRUDE OIL PIPE HEATER TRACING ( available on site)
. FLEXIBLE HOSE FOR CRUDE OIL BURNER LINE.
. PSV FOR CRUDE OIL LINE
. PSV FOR DIATHERMIC OIL LINE
. CRUDEOILPRESSUREGAUGE
. FV005B ( crude oil regulation valve)
. PDV009B ( atomizing air regulation valve)
. crude oil 3 way valve(BV004B)
. TV007B ( crude oil heating skid valve)
SUGGESTED
. PLC SIEMENS S73OO , CPU315-2DP . SPARE PARTS MAYBE NOT YET AVAILABLE
. ELECTRICALPANELUPGRADE(HMD
. FUEL SYSTEM UPGRADE FOR WORKING IN AUTOMATIC MODE IN ORDER TO
SWITCH FROM HFO TO DIESEL & VICE VERSA.
Gliente/Customer.
14
Job. N. 261908054 Doc. N.
Plant:
HTH 25MW/FO/PA NF QCP23401B
SERVICE ACTIVITY
REPORT
From 08/03/2020 to 11/03/2020
2
1
0 Dec. 07, 2006 issue
Rev. Date Description Prepared Checked Approved
Job. N. 261908054 Date
cable connection to UV SENSOR TE cable connection CRUDE OIL VALVE cable connection
Cleaning & prepare combustion chamber pipe for tickness control, all pipe present a consistent dust on surface.
Recommended to organize an a hydro jet cleaning next stop.
LEAK:
TV008 diathermic oil regulation valve inlet at all heat exchanger leakages or damage . SHOULD BE REPLACE Nr
3 valve.
PICTURE 1 - Crude oil line flange on HEAT EXCHANGER present a massive leakage, should replace gasket
PICTURE 2- HIGH PRESSURE FLEXIBLE HOSE burner side was damage and old, SHOUL BE REPLACE.
for safety reason.
PICTURE 3- Manual valve inlet line of diathermic oil pump leakage and disconnect the wheel. Should be checked
or replace.
Job. N. 261908054 Date
Check, test and calibrate all protection and control devises where applicable
SETTINGS OF HEATER:
Job. N. 261908054 Date
SAFETY CHECK
All new safety device installed was tested, was not possible test in working condition all safety
because diathermic oil pump working for booth heater and had to share the oil flow.
One boiler should be in running mode always for production.
ATTACHED SAFETY TEST DOC
OXYGEN PROBE
Oxygen probe on QCP23401B not working, in stand by condition show 0.0% of O2 should be replaced with a
new one.
Functional Check.
IGNITION SEQUENCE
During ignition sequence pilot time is not enough to ensure all the time correct working of boiler, often we had a
shutdown for lack of flame in main valve position.
To fix situation properly we increase pilot time on K130 up to maximum ( 40 sec). Solve
Crude oil pressure in main line should be @ 10 bar to ensure a correct working of discharge valve and regulation
valve.
Job. N. 261908054 Date
REGULATION CHECK
Control modulation set with Heater in production, customer switch OFF Heater A .
COMBUSTION REGULATION
Crude oil Air damper % DP atomiz air Atomiz Crude O2 CO2 CO O2 % CO2 CO
valve % pressure oil line % % mg/m3 % mg/m3
press. NEW NEW @3%O2 @3%O2
NEW OLD OLD OLD
OLD NEW OLD NEW % bar bar bar
Light 16,0 34,5 6,0 6,0 24,5 1,8 8,0
off
P1 18,0 39,0 7,0 7,0 45%-1,2 2,6 8,0 11,9 6,8 170
P2 22,0 44,0 8,0 8,0 45%-1,2 2,6 8,0 14,3 5,3 683
P3 31,0 47,0 10,5 10,5 44%-1,0 2,6 8,0 12,1 6,7 169
P4 36,0 49,0 12,0 12,0 44%-1,0 2,5 8,0 11,4 7,2 60
P5 40,0 51,0 15,0 14,0 2,8 8,0 12,3 6,6 154
P6 45,0 53,0 18,0 18,0 8,0 10,8 7,5 22
P7 50,0 55,0 22,0 22,0 8,0 10,7 7,7 26
P8 55,0 57,0 26,0 24,0 56%-1,0 3,8 8,0 6,8 10,7 53
P9 60,0 60,0 30,0 30,0 58%-1,0 3,9 8,0 8,7 9,1 38
P10 66,5 66,5 36,5 36,5 58%-0,4 4,6 8,0 8,3 9,5 30
P11 69,0 69,0 41,0 41,0 58%-0,4 4,6 8,0
P12 74,0 74,0 45,0 45,0
P13 78,0 78,0 50,0 50,0 WAS NOT POSSIBLE TEST OVER P11 COMBUSTION DUE TO A LOW CONSUMPTION
P14 80,0 80,0 55,0 55,0 FROM THE PLANT, SO CRUDE OIL TEMP REACH IN 2 min THE MAXIMUM TRIP
TEMPERATURE OF 80°C.
P15 82,0 82,0 60,0 60,0
CONCLUSION
In order to guarantee efficiency & safety condition for heater ALL SPARE PARTS IN THE LIST
SHOULD BE REPLACE .
Especially Crude oil pipe line need a strong maintenance: replace nozzle , crude oil pump replace gasket
( at least) , crude oil 3 way valve(BV004B) atomizing regulation valve & crude oil regulation valve
should be replace .
Crude oil main line supply should be fix , customer find water in crude oil sample from crude oil pump.
In this heater was find big problem in burner & combustion regulation, due to a low pressure on main crude
oil line ( 8 bar) the consequence was that, to increase a little combustion value ( in order to reduce CO
value) was necessary increment opening crude oil valve position up to 20% ( from 22% to 34,5% in light
off position)in all combustion point until point 7 . customer organize to re-calibrate atomizing regulation
valve & crude oil regulation valve.
Job. N. 261908054 Doc. N.
Plant:
HTH 25MW/FO/PA NF QCP23301A
SERVICE ACTIVITY
REPORT
From 13/03/2020 to 16/03/2020
2
1
0 issue
Rev. Date Description Prepared Checked Approved
Job. N. 261908054 Date
Wiring Cable
Wiring cable on Boiler side was damage for time, sun & environmental condition, all external protection
is done. Cleaning of UV sensor lens & Burner Nozzle
Job. N. 261908054 Date
Cleaning & prepare combustion chamber pipe for thickness control, all pipe presents a consistent dust on
surface. Recommended to organize a hydro jet cleaning next stop.
Circulation pump
Job. N. 261908054 Date
OXYGEN PROBE
Oxygen probe on QCP23301A not working, in stand by condition show 0.0% of O2 should be replaced with a
new setup.
Main oil storage tank electric heater damage and No oil filtration. Need duplex filter for good circulation.
Job. N. 261908054 Date
6. Check, test and calibrate all protection and control devises where applicable
Setting of Heater
Job. N. 261908054 Date
SAFETY CHECK
All new safety device installed was tested, was not possible test in working condition all safety
because diathermic oil pump working for booth heater and had to share the oil flow.
One boiler should be in running mode always for production.
ATTACHED SAFETY TEST DOC
Job. N. 261908054 Date
IGNITION SEQUENCE
During ignition sequence pilot time is not enough to ensure all the time correct working of boiler, often we had a
shutdown for lack of flame in main valve position.
To fix situation properly we increase pilot time on K130 up to maximum (30 sec).
valve.
Job. N. 261908054 Date
REGULATION CHECK
COMBUSTION REGULATION
CONCLUSION
In order to guarantee efficiency & safety condition for heater ALL SPARE PARTS IN THE LIST
SHOULD BE REPLACE.
Especially Crude oil pipe line need maintenance: Replace nozzle,
Crude oil pump Tag# P 23302 (A & B) should replace. (Booster pumps) pumps B seal leakage.
Crude oil 3-way valve (BV004B) atomizing regulation valve & crude oil regulation valve should be
replaced.
Both thermal oil pumps condition not good should be replace ASAP.
Circulation pump Tag # P23301 A not running because of motor defected customer remarks
Circulation pump Tag # P23301 B pump running on load, found leakage in gland area.
Job. N. 261908054 Date
QCP23301A MANDATORY
OXIGEN PROBE
PILOT VALVE (NR 2)
REFRACTORY DOOR
COMBUSTION AIR GAUGES
RUPTURE DISK FOR DIATHERMIC OIL PLANT.
SPARE NOZZLE FOR CRUDE OIL
FLEXIBLE HOSE FOR CRUDE OIL BURNER LINE.
PSV FOR CRUDE OIL LINE
PSV FOR DIATHERMIC OIL LINE
REGULATION VALVE FOR CRUDE OIL FV005B
REGULATION VALVE ATOMIZING
CRUDE OIL PRESSURE GAUGES.
CRUDE OIL PUMP FOR BOTH HEATERS.
TV007 CRUDE OIL HEATER CONTROL VALVE.
BURNER CONTROLL UNIT HONYWELL
UV SENSOR
PILOT IGNATION TRANSFORMER.
D.P TRANSMITTER (oil& air)
SUGGESTED
PLC siemens S7300 , CPU 315-2DP . Spare parts maybe not yet available
electrical panel upgrade (HMI)
burner refractory
Fuel system upgrade for working in automatic mode in order to switch from Crude oil to
diesel & vice versa.