480V, 1600A, 42KAIC, 3Ø, 3W, 60HZ, TIN PLATED


Ø1 0.25 X 3" (2) BAR PER PHASE

PROVISIONS Ø2 PROVISIONS
A FOR FUTURE FOR FUTURE A
EXTENSION Ø3 EXTENSION
TO
TRANSFORMER
(BUS DUCT)
272
11 0-1600A
IQ250 1 2
AØ BØ CØ AM
SB1 (C0) (C01)
1 IA
X1 HI LO
1CT X2
B (3) CT'S 2 IB B
1600:5A X1 HI LO
1/ø X2
3 IC 11 12 13 14
36
X1 HI LO
X2
4 21 22 23 24
SB5 AS
1 219
L1 VA
FROM TRANSFORMER 1
L2 VB
2
3 L3 VC
C TB1-2 C
ES51G 156 ES27/59 157 VR

268
60 0-480\V
168 180 86 167
LINE PT 1 2
VM
FU1/2A 480:120VAC FU2/1.6A (V1) (V2)
TB1-A V1 V11

1 2 H1 X1 1 2 TB1-1
H2 X2
D TB1-B 11 12 13 14 D
V2

3 4 TB1-2
H1 X1 21 22 23 24
TB1-C V3 H2 X2 V13

5 6 5 6 TB1-3 VS
10 215

SB2 787
1 IAW1
Z01 Z02
2 IBW1
E E
FROM UPSTREAM Z03 Z04
BREAKER 3 ICW1
MAIN CUSTOMER SUPPLIED
BREAKER 520LSIG Z05 Z06
1600A 4

SB3
X2 1 IAW2
F 2CT X1 F
(3) CT'S Z07 Z08
1600:5A X2 2 IBW2
1/ø X1
Z09 Z10
37 X2 3 ICW2
C50 X1
Z11 Z12
4

5
CROSS REFERENCE
6 REFERENCE
G No.
G
SB4 Powell Electrical Systems, Inc.
1 IN 8550 Mosley Road
E09 E10 Houston, Texas 77075-1180
FROM TRANSFORMER Powered by Safety Tel:713.944.6900 Fax:713.947.4453
2
P.O. No. 4403495099
CUSTOMER NAME, PROJECT NAME & LOCATION

PROVISIONS PROVISIONS LYONDELLBASEL


#6-350MCM LUG 1/4" X 2" GND BUS
FOR FUTURE FOR FUTURE LB EDISON CATALYST EXPANSION
EXTENSION EXTENSION EDISON, NEW JERSEY
H DRAWING DESCRIPTION RATING, EQUIPMENT TYPE & I.D H
CONTROL SCHEME 480V, 3PH, 3W, 60HZ, 42KAIC, 1600A
TERMINAL BLOCK IN EQUIPMENT FOR POWELL CONNECTIONS. SHORTING BLOCK IN EQUIPMENT FOR POWELL CONNECTIONS. REVISION DESCRIPTION SIZE 1&2 FVNR LOW VOLTAGE MOTOR CONTROL
TERMINAL BLOCK IN EQUIPMENT FOR CUSTOMER CONNECTIONS SHORTING BLOCK IN EQUIPMENT FOR CUSTOMER CONNECTIONS STARTER 480V MCC
TERMINAL BLOCK IN UNIT 14RM RELAY CABINET. Confidential information. Not to be REV. BY REV. DATE REV. NO DRAWN BY DATE DRAWN DWG. No.
# ITEM NUMBER ON BILL OF MATERIAL. used in any way detrimental to Powell 00 ANTHONY.RUSSO 30-JAN-2019 2319680800201
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

A A
VERTICAL BUS
Ø1 Ø2 Ø3

Ø1 Ø2 Ø3

MCCB
B B

L1 L2 L3

LOAD

C C

D D

E E

F F

CROSS REFERENCE

REFERENCE
G No.
G

Powell Electrical Systems, Inc.


8550 Mosley Road
Houston, Texas 77075-1180
Powered by Safety Tel:713.944.6900 Fax:713.947.4453

P.O. No. 4403495099


CUSTOMER NAME, PROJECT NAME & LOCATION
LYONDELLBASEL
LB EDISON CATALYST EXPANSION
EDISON, NEW JERSEY
H DRAWING DESCRIPTION RATING, EQUIPMENT TYPE & I.D H
FEEDER WIRING 480V, 3PH, 3W, 60HZ, 42KAIC, 1600A
TERMINAL BLOCK IN EQUIPMENT FOR POWELL CONNECTIONS. REVISION DESCRIPTION DIAGRAM LOW VOLTAGE MOTOR CONTROL
TERMINAL BLOCK IN EQUIPMENT FOR CUSTOMER CONNECTIONS 480V MCC
TERMINAL BLOCK IN UNIT 13RM RELAY CABINET. Confidential information. Not to be REV. BY REV. DATE REV. NO DRAWN BY DATE DRAWN DWG. No.
# ITEM NUMBER ON BILL OF MATERIAL. used in any way detrimental to Powell 00 ANTHONY.RUSSO 30-JAN-2019 2319680800310
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

CLOSE COMAND
TRIP COMAND

BKR STATUS
THIS DWG.

THIS DWG.

THIS DWG.

THIS DWG.
RLY PWR
TBAC-1
A A

TRIP COIL MONITOR

TRIP CKT HEALTHY

BREAKER STATUS
REMOTE TRIP
BREAKER CLOSE

BREAKER CLOSE
SPRING CHARGE
REMOTE CLOSE

BREAKER OPEN

RELAY POWER
RELAY TRIP 86
RELAY TRIP

51G TRIP
A01 A02 A03 A04 A05 A06 A08 A07 A09 A10 A11 A12

86 TRIP
165 171 165 171 165 172
GND +/H -/N OUT101 OUT102 OUT103 IN101 IN102
FU3/15A TB1-7 FU4/15A TB1-15 FU5/5A
1 2 1 2 1 2 SLOT A

10 PART# 07871X1A1A0XA5850200
B X1(+) X1(+) X1(+) X1(+) X1(+) 11 XX 14 B
ES IRP PORT 3
BIL GIL RIL AIL WIL 86
X2(-) X2(-) X2(-) X2(-) X2(-) 14 51G TRIP XX 16
105 101 102 103 104

TB1-21 IRIG-B
PORT 2

B01+
B02-
787 787
TX RX
A05 A03 C01 A10 C09 A01
OUT102 OUT101 OUT301 IN101 IN301 PWR 787
A06 A04 C02 A11 C10 A02 PORT 1
TB1-10 FRONT
265
TCM TB1-16 TB1-19
XX 1 SLOT B
C IRP C
CLOSE XX
K

DWG 2319680800**
TO ANNUNCIATOR
TB1-11 TB1-13 TB1-14 TB1-14
787 R1 R2
120VAC SUPPLY

TRIP 86 RELAY

BLOCK START
C03
FROM UPS PNL OUT302 G
12

THIS DWG

THIS DWG

THIS DWG
C04
CKT. #*, 231968-01 F A01 ES A01

86 TRIP
86 86 ES TB1-35 TB1-36
DWG# 2319680100*** 2 3 C
18 A02 51G A02 27/59
11 B
156 157
86
D 13 D
TB1-17
C01 C02 C03 C04 C05 C06 C07 C08 C09 C10 C11 C12 C13 C14 C15 C16
11 OUT301 OUT302 OUT303 OUT304 IN301 IN302 IN303 IN304
TB1-9
86
13
SLOT C
B8 B12 A16 B15 B22 B10 B20

52 52 52
SC LS
INTERLOCK

b b a
ZONE

52
a
SR LS SR
E E
M

SLOT D
B9 B13 B14 B23 B11 B21

IN
E09 Z10
TB1-8 TB1-18 TB1-20
CURRENT INPUT
SEE THREE LINE DIAGRAM
2319680800201 SLOT E
TBAC-2
F F
IAW1 IBW1 ICW1 1AW2 IBW2 1CW2
Z01 Z02 Z03 Z04 Z05 Z06 Z07 Z08 Z09 Z10 Z11 Z12 SLOT Z
UNDERVOLTAGE OVERVOLTAGE
ALARM TO ALARM TO
SEE DWG 2319680800***

ANNUNCIATOR ANNUNCIATOR
CURRENT INPUTS
TO ANNUNCIATOR

SEE 2319680800*** SEE 2319680800*** SEE THREE LINE DIAGRAM


2319680800201
GIL STOPPED
BKR STATUS
THIS DWG.

THIS DWG.

POSITION
THIS DWG.

THIS DWG.

THIS DWG.

THIS DWG.

DECK

RESET
TB1-23 TB1-25 TB1-31 TB1-33 CONTACTS TRIP CROSS REFERENCE
TB1-27 TB1-29
11 13 REFERENCE
G No.
G
12 18
15 21 15
B20 B22 B24 B26 17 Powell Electrical Systems, Inc.
11 12 15 14 21 22 25 24 16 14
52 52 52 52 8550 Mosley Road
a b a b 86 86 86 86 86 86 86 86 ES27/59 ES27/59 21 23 Houston, Texas 77075-1180
13 18 17 16 23 28 27 26 18 16 24 22 22 28 Powered by Safety Tel:713.944.6900 Fax:713.947.4453
B21 B23 B25 B27 25 27
26 24 M MOTOR FOR SPRING CHARGING
P.O. No. 4403495099
31 33 CUSTOMER NAME, PROJECT NAME & LOCATION
TB1-28 TB1-30 32 38 SH
TB1-24 TB1-26 TB1-32 TB1-34 35 37 TR SHUNT TRIP LYONDELLBASEL
36 34 TERMINAL BLOCK IN POWELL EQUIPMENT LB EDISON CATALYST EXPANSION
a NORMALLY OPEN CONTACT FOR CUSTOMER CONNECTIONS.
86 LOCKOUT RELAY EDISON, NEW JERSEY
CAT. #7603D 240 b NORMALLY CLOSED CONTACT TERMINAL BLOCK IN POWELL EQUIPMENT
H 86 LOCK OUT RELAY DRAWING DESCRIPTION RATING, EQUIPMENT TYPE & I.D H
FOR POWELL CONNECTIONS.
MAIN 480V, 3PH, 3W, 60HZ, 42KAIC, 1600A
TERMINAL BLOCK IN EQUIPMENT FOR POWELL CONNECTIONS. REVISION DESCRIPTION BREAKER LOW VOLTAGE MOTOR CONTROL
TERMINAL BLOCK IN EQUIPMENT FOR CUSTOMER CONNECTIONS 480V MCC
TERMINAL BLOCK IN UNIT 13RM RELAY CABINET. Confidential information. Not to be REV. BY REV. DATE REV. NO DRAWN BY DATE DRAWN DWG. No.
# ITEM NUMBER ON BILL OF MATERIAL. used in any way detrimental to Powell 00 ANTHONY.RUSSO 30-JAN-2019 2319680800401