Transformer Protection: Department of Electrical Engineering Institute of Southern Punjab
Transformer Protection: Department of Electrical Engineering Institute of Southern Punjab
Transformer Protection
(1 / 26)
Final Exam Topics
Over Current Protection
Inverse characteristics of over current relay OCR
Inverse definite minimum time relays IDMT
Primary and back up protection
Relay coordination, application of IDMT relays
Direct over current relays D-OCR
Application of D-OCR protection of three phase feeder.
Differential protection
Simple differential protection
Zone of protection of differential relay
Percentage differential relay
Protection of transformer
transformer faults
Differential protection of transformer
Buchaloz relay
Over fluxing
Back up protection schemes for transformer
Generator Protection
Faults in stator and rotor of generator
Protection schemes for stator , rotor faults
Abnormal conditions and their protection
Protection of transmission lines
Draw backs of over current protection
Distance protection
Zones of protection
(2 / 26)
Topics to be covered
Transformer faults
Differential Protection of three- winding transformer
Inrush current and differential protection
Bucholz relays
Over- fluxing in transformer
Earth leakage protection
(3 / 26)
Transformer Protection
Objective
The main objective of transformer protection is to provide the ability
to detect internal transformer faults with high sensitivity, along with
a high degree of immunity to operation on system faults for which
tripping of the transformer is not required.
(4 / 26)
Transformer Protection
Faults
The most common being the winding to core faults because of
weakening of insulation.
Phase faults inside the transformer are rare. However, such faults
may take place outside the transformer, on the transformer terminals
, which fall within the transformer protection zone.
(5 / 26)
Transformer Protection
Transformer Protection
The protection method used for power transformers depends on the
transformer ratings. Transformers are usually categorized according
to their ratings as follows:
Transformers below 5000 KVA (Category I & II) are protected using
Fuses.
Fuses and Medium Voltage (MV) circuit breakers are often used to
protect transformers up to 1000 kVA (distribution transformers for 1
1kV and 33kV).
(6 / 26)
Transformer Protection
For transformers 10 MVA and above (Category III & IV) ,differential
relay are commonly used to protect them.
(7 / 26)
Differential Protection Principle
This system is operates on CDR rule.
Here the electrical quantities entering and leaving the protected
zone or area are compared by current transformers (CTs).
Basic Principle
At normal conditions and for external fault at F, CT1 and CT2
circulate currents at their secondary’s Is1 and Is2 (Is1 =Is2) and no
current flow through the relay (ΔI = Is1 - Is2 = 0), hence the relay
will not operate.
Is1 N1 Is2
Relay
(8 / 26)
Differential Protection Principle
If fault occurs at point F within the protected zone (internal fault) as
shown in Fig, and the fault is fed from both sides, then current
through CT2 will be reversed. Therefore a current ΔI = Is1 + Is2 will f
low in the operating winding of the relay.
This will cause the relay to trip the circuit breaker connected to the
faulty system. Hence the relay trips when
(Is1 + Is2)>0
Is1 N1 Is2
Relay
(9 / 26)
Differential Protection of Transformer
Percentage Biased Current Differential protection
This scheme is employed for the protection of transformer against
internal short circuit.
It provides the best overall protection for internal faults.
It compare the current entering the transformer with the current
leaving the element.
If they are equal, there is no fault inside the zone of protection.
If they are not equal, it means that a fault occurs between two ends.
I1 I2
Relay
(10 / 26)
Differential Protection of Transformer
CB CB
Connections
A a
b
B
CTs on Delta Side of TF CTs on Star Side of TF
should be connected in should be connected in
star Delta
c
C
R
R
Op
R R
Op
R R
Op
(11 / 26)
Differential Protection of Transformer
Phase Shifting in Star-Delta Connected Transformer
The primary and secondary current of the transformer of a
star-delta connection has the phase angle difference of 30 degree.
For this reason, a method that aligns the current phase by differing
from the connection of the CT secondary circuit of both sides is
taken.
(12 / 26)
Differential Protection of Transformer
Turns ratio
(13 / 26)
Seminars
(A)Protective Relays
Fuses introduction
Principle of circuit interruption
Circuit breaker types and characteristics
Ratings of circuit breakers
Group 2
(14 / 26)
Incipient Faults in Transformer
Faults which are not significant in the beginning but which slowly
develop into serious faults are known as incipient faults.
Buchholz relay provides protection against such incipient faults.
Buchhloz Relay
A Buchholz relay is a gas and oil operated device installed in the
pipe between the top of the transformer main tank and the
conservator.
The function of the relay is to detect an abnormal condition within
the tank and send an alarm or trip signal.
(15 / 26)
Buchholz Relay
The Buchholz relay is installed at the pipe between the main unit
and the conservator, and it detects resolved gas by the float
switch when a fault occurs within the transformer.
Principle of operation
A complete loss of oil from the conservator (very low oil level)
(16 / 26)
Buchholz Relay
Construction
Buchholz relay can be used in the transformers having the conservators
only. It is placed in the pipe connecting the conservator and the
transformer tank. It consists of an oil filled chamber. Two hinged floats,
one at the top of the chamber and the other at the bottom of the chamber
which accompanies a mercury switch each is present in the oil filled
chamber. The mercury switch on the upper float is connected to an
external alarm circuit and the mercury switch on the lower is connected to
an external trip circuit.
(17 / 26)
Buchholz Relay
Operation
Fault conditions within a transformer produce gases such as c
arbon monoxide, hydrogen and a range of hydrocarbons.
The oil level will be lowered and the oil in the bucket (B) will tilt
the counter weight C.W., thus switch Hg1 operates alarm circuit
to send an alarm.
(18 / 26)
Phenomenon of over fluxing in transformer
(19 / 26)
Phenomenon of over fluxing in transformer
Further, saturation of the core causes the flux to flow into adjacent
structures, causing high eddy current losses in the core and adjacent
conducting materials.
(20 / 26)