Standards For Switchyard PDF
Standards For Switchyard PDF
Standards For Switchyard PDF
IS 335 1993 IS 335 1993 IS 335 1993 IS 335 1993 IS 335 1993 IEC 60296-2003 IS 335 1993 IEC 60296, 2003 IS 335 1993
(r) PCB content (Polychlorinated Bipheyls) (s) Dissolved Gas Analysis (DGA) (t) 2 furfural (Furan Analysis, Test method IEC 61198:1993) (u) Furfural (Aging criteria for oil immersed Power Transformer)
DBPC Phenolic type inhibitor Not detectable 0.1 mg/kg (Max) Not applicable 0.1 mg/kg (Max)
CIGRE DOC. No. 227 Life Management Technique for Power Transformer Page 107 Transformer Diagnostic USBR, june 2003, Page 15
Additional Requirement for inhibited oil Inhibitor content (Antioxidation additive content) DBPC (Ditertiary Butyl Paracersol) DBP (Ditertiary Butly Phenol)
Inhibitor content determination ( Test Mehod:IS 13631) IEC 60296, 2003 Nynas and shell Inhibited oil
1.2
IS 1866 - 2000
IS 1866 - 2000
0.01% by mass
IS 1866 - 2000
35 mN/m 1400C
IS 1866 - 2000
IS 1866 - 2000
(j) Density at 29.50C (Max) (k) Kinematic 0 Viscosity at 27 C (Max) (l) Pour point (Max) (m) Oxidation stability of uninhibited old (i) Neutralization value (Max) (ii) Sludge (Max) Additional requirement for inhibited oil (n) Oxidation Stability of inhibited oil 1.3
Not Essential
IS 1866 - 2000
Not Essential
1.4
Dissolved Gas Analysis (DGA) Typical rates of gas Values in milliliters per day increase for power transformers Hydrogen (H2) <5 Methane (CH4) <2 Ethane (C2H6) <2 Ethylene (C2H4) <2 Acetylene ((C2H2) <0.1 Carbon Monoxide <50 (CO) Carbon dioxide (CO2) <200 Equation to calculate the rate of gas increase as per IEC: 60599 1999 Rate (Y2-Y1)m/{>(d2 d1)} m1/ day Where Y1 = is the reference analysis Y2 = is the last analysis (Y2-Y1) is the increase in micro litre per litre. M = is the mass of oil, in kilograms P = is the mass density, in kilograms per cubic metre. d2 = is the date for Y1 d1 = is the date for Y2 Transformers/ Reactors Ten Delta for bushing 0.007 0 at 20 C Capacitance for -5% to +10% Variation Bushing Contact Resistance 10 Micro Ohm/Connector of Bushing Ten Delta for 0.007 Windings at 200C Ten Delta for 0.005 Windings at 200C (Power factor) Rate of Rise of Tan 0.001 Per year (Max) Delta (Bushing & Winding) Magnetizing current If the excitation current is less than 50 milli amperes test (Excitation (mA), the difference between the two higher currents
IEC 60137
current test)
Winding resistance Transformer and Reactor (Resistance converted to 750C) Voltage Ratio of Transformer (All Taps) Insulation Value (Thumb Rule/ Empirical Formula)
should be less than 10%. If the excitation current more than 50 mA, the difference should be less than 5%. In general, if there is an internal problem, these differences will be greater. Value of supply voltage (230 V AC) in one phase is equal to sum voltage induced in other two phase. When supply voltage in middle limb, voltage induced in outer limbs should equal and roughly half of the supply voltage. %5 difference between phases or from Factory tests.
Min insulation values for one minute resistance measurement for transformers may be determined by using the following formuls: R = CE/ kVA Where R = Insulation resistance, in M C= 1.5 for oil filled transformers at 200C, assuming that the transformers insulating oil is dry, acid free, and sludge free. = 30.0 for un-tanked oil impregnated transformers. E Voltages rating, in V, of one of the single phase windings (ph to ph for delta connected and ph to neutral for wye connected transformers) kVA = Rated capacity of the winding under test ( If the winding under test is three-phase and the three individual windings are being tested as one, the rated capacity of three-phase winding is used. Rated Voltage Class of Min desired IR value at 1 winding minute at 300C (Mega ohm) 11 kV 300 33 kV 400 66 kV & above 500 Polarization index Insulation Condition Less that 1 Dangerous 1.0-1.1 Poor 1.1-1.25 Questionable 1.25- 2.0 Fair 2.0-4.0 Good Above 4.0 Good 1000K Ohms at 2.5/3.5 kV DC for 1 min
CORE INSULATION TEST Min (Between CL and CC +G with tank grounded) Transformer Neutral Resistance Value Turret/ Neutral Resistance Value Vibration level for Reactors Sweep Frequency Response Analysis Test (20 Hz to 2
Below 1 ohm 3% 200 Microns (Peak to Peak) 60 Microns (Average) In general, changes of +/- 3 dB (or more) in following frequency range may indicate following faults: Frequency Range IS 2705
MHz)
Moisture measurement of winding (RVM Measurement) Insulation condition Dry (at commissioning) Normal in operation Wet Extremely wet Degree of polymerization (DP)
Probable Fault 5Hz to 2 KHz Shorted turns, open circuit, residual magnetism or core movement 50 Hz to 20 KHz Bulk movement of windings relative to each other 500 Hz to 2 MHz Deformation within a winding 25 Hz to 10 MHz Problems with winding leads and/ or test lead placement. IEEE Std. 62-1995
% Moisture by dry weight in paper (Wp) 0.5- 1.0% <2% 2-4% >4.5% New insulation 60% to 66% life remaining 30% life remaining 0 life remaining
CIGRE DOC No. 227. Life management Technique for Power Transformer Page 119
6-20% >30% 1,000 DP to 1,400 DP 500 DP 300 DP 200 DP EPRIs Guidelines for the life Extension of Substations, 2002 Update, Chapter 3, Table 7 DP Values for Estimating Remaining paper life.
1.5
CIRCUIT BREAKERS Dew Point of SF6 Gas Dew Point of operating air (A) CB Operating timing (a) Closing time (Max) (b) Trip time (Max) (c) Close/Trip time pole discrepancy at rated operating pressure - Phase to Phase (Max) close open -Break to Break (Max) of same phase (d) CO time (min) (e) Trip delay time for DCRM test (CO operation) Minimum (f) Deviation from standard timings as per GTP of manufactures close open Dew point values as per Annexure II +450C at Atmospheric Pressure 400 kV 150 ms 25 ms 50 ms 3.33 ms 220 kV 150 ms 35 ms 5.0 ms 3.33 ms 132 kV 150 ms 45 ms 5.0 ms 3.33 ms IEC-62271-100 2001 IEC-62271-100 (2001)
IEC-62271-100 (2001)
(C) PIR time - BHEL make - CGL make - ABB mak - NGEF make - M&G make - TELK make Alstom make (HVDC) -ABB make (HVDC) (D) PIR operating time prior to opening of main contacts (ABB, CGL, NGEF make CBs) (E) PIR and main contacts overlap time (BHEL, M&G, ABB (imported make CBs)
ABB CGL BHEL Alstom (Imported) 400 kV 12-16 ms 8-12 ms 8-10 ms 8-12 ms 8-12 ms 8-12 ms 8-12 ms 8-12 ms 5 ms (Min) at rated pressure
IEC-62271-100 (2001)
Manufactures Recommendations.
(F) Tan delta of grading capacitors (G) Rate of rise in Tan dalta
Since temperature correction factor for Tan Delta depends on make, type and also again conditions, the correction factors for different types/ makes are different. Hence no standard temperature error factors can be applied
(H) Capacitance of grading capacitors (I) Contact Resistance of CB (in Micro-Ohm) (J) Contact Resistance of CB terminal connector (K) Evacuation level before SF6 gas filling (L) N2 leakage rate from N2 accumulator (M) IR VALUE 1. Phase Earth 2. Across open contacts 3. Control cables (N) PRESSURE SWITCH SETTINGS - SF6 gas pressure switches
Within 5% of the rated value 400 kV 220 kV 100 132 kV 150 100 NGC, UK Recommendations
1000 M-Ohm (Min) by 5.0/10.0 kV megger 1000 M-Ohm (Min) by 5.0/10.0 kV megger 50 M-Ohm (Min) by 0.5 kV megger.
1.6
- Operating air Within 0.1 Bar of set value pressure switches - Operating oil Within 0.1 Bar of set value pressure switches (O) BDV of oil used for MOCB - At the time of filling 40 kV at 2.5 MM GAP (Min) -During O&M 20 kV at 2.5 MM GAP (Min) CURRENT TRANSFORMERS (A) IR Value 1000 M OHM (Min) -Primary Earth 50 M-OHM (Min) -Secondary Earth 50 M-OHM (Min) -Control Cables Tan delta value 0.007 Rate of rise in Tan 0.001 per year (max) Delta
Manufactures Recommendations by 5.0/10.0 kV Megger by 0.5 kV Megger by 0.5 kV Megger Since temperature correction factor for Tan Delta depends on make, type and also ageing conditions, the correction factors for different types/ makes are different. Hence, no standard temperature error factors can be applied.
(B) Monitoring of Tan delta Upto 0.007 (rise @ 0.001) 0.007 to 0.011 0.011
1.7
3% protection cores 1% metering cores Pressure 0.10 kg/cm2 0.20 kg/cm2 0.30 kg/cm2 0.40 kg/cm2 2 0.50 kg/cm CAPACITIVE VOLTAGE TRANSFORMERS (A) Tan Dalta 0.007 (B) Rate of rise in 0.001 per year (max) Tan Delta
NGC, UK Recommendations IS 2705 - doOil level 10 mm 30 mm 50 mm 70 mm 90 mm Since temperature correction factor for Tan Delta depends on make, type and also ageing conditions, the correction factors for different types/ makes are different. Hence, no standard temperature error factors can be applied.
Measurement Value Measurement Frequency Upto +0.002 - Three yearly +0.002 to +0.003 - Yearly Above +0.003 - alarming
(D) Capacitance (E) Contact resistance of terminal connector. (F) Change in capacitance from pre commissioning value
NGC, UK recommendations
Measurement Value Measurement Frequency Upto 2% - Three yearly 2% to 3 - Yearly Above 6% - alarming (needs replacement) 1000 M-OHM (Min) by 5.0/10.0 kV Megger 50 M-OHM (Min) by 0.5 kV Megger 50 M-OHM (Min) by 0.5 kV Megger
(G) Drift in secondary Voltage (to be measurement in 0.2/0.5 class multimeter) Condition Frequency Measurement Upto 0.5 volts Healthy Six month 0.5 to 0.8 volts To be monitored 03 monthly 0.8 to 1.2 volts Close monitoring monthly 1.2 to 2.0 volts Close monitoring 15 days above +2.0 volts Alarming replacement -0.8 to -4.0 volts Close monitoring 15 days less than -4.0 volts Alarming replacement (H) EMU tank oil parameters BDV (Min) 30 kV (GAP 2.5 MM) Moisture content 35 PPM (Max) Resistivity at 900C 0.1*1012 OHM-CM Acidity 0.5 mg KOH gm (Max) IFT at 270C 0.018 N/M (Min) Tan delta at 900C 1.0 Max Flash Point 1250C (Min) (I) CVT voltage ratio 5% protection cores errors 5% metering cores DISCONNECTING SWITCHES (A) Contact 300 Micro Ohm (Max) resistance (B) Contact 10 Micro-Ohm per connector resistance of terminal connector (C) IR Value - Phase Earth 1000 M-Ohm (Min) by 5.0/10.0 kV megger - Across Open 1000 M-Ohm (Min) by 5.0/10.0 kV megger Contacts - Control cables 50 M-Ohm (Min) by 5.0 kV megger SURGE ARESTER (A) Third Harmonic Upto 30 Micro Ohm Resistive (Upto 150 Micro Ohm) Normal Current (THRC) (150 to 350 Micro-Ohm) to be tested for for all makes insulation test & if value found low Elpro/ Alstom / - to be removed from service. Oblum/ CGL Beyond 350 Micro Ohm (Gapless type) - For new Las - to be removed from service - For Las in Beyond 350 Micro Ohm (Gapless type) services - to be removed from service (B) IR Value 1000 Mega-Ohm (Min)
IS- 1866
1.8
1.9
1.10
MICELLANEOUS (A) Station Earth Resistance (B) Thermovision Scanning - Temp upto 150C (above ambient) - Temp above 0 15-50 C (above ambient) - Temp above 500C (above ambient (C) Therminal Connectors (D) IR Values - All Electrical Motors. - Control Cables - LT Transformer - LT Switchgears
To be immediately attended.
NGC, UK recommendations,
50 M-Ohm (Min) by 0.5 kV megger IS 900 50 M-Ohm (Min) by 0.5 kV megger 100 M-Ohm (Min) by megger 100 M-Ohm (Min) by 0.5 kV megger
1.11
1.12
BATTERIES (A) Terminal connector resistance (B) Specific Gravity DG SET (A) Winding IR value (B) Stator winding resistance
10 Micro-Ohm 20% ANSI/IEEE/450-1987 1200 5GM/L at 270C 50 M-Ohm Within 10% of STD value
BHEL
Remarks
2 3 4 5
-39 C 0 -32 C 0 -35 C 0 -31 C 0 -35 C 0 -26 C 0 -36 C 0 -29 C 0 -27 C 0 -35 C
At the time of commissioning During O&M Critical At the time of commissioning During O&M At the time of commissioning During O&M At the time of commissioning During O&M At the time of commissioning During O&M Critical To be followed for substations having ambient temperature less than 00C