Transformer Protection
Transformer Protection
TRANSFORMER PROTECTION
FAULTS IN SYSTEM
% OF TOTAL FAULTS
50 10 15 12
TRANSFORMER PROTECTION 2
% OF TOTAL FAULTS
2 3 8
TRANSFORMER PROTECTION
TRANSFORMER TRANSFORMER RATED BETWEEN RATED BELOW 500 KVA AND 500 KVA 5MVA TRANSFORMER RATED ABOVE 5MVA
PROTECTION
DIFFERENTIAL RESTRICTED EARTH FAULT BACKUP OVER CURRENT BACKUP EARTH FAULT
TRANSFORMER PROTECTION
TRANSFORMER PROTECTION
TRANSFOR TRANSFORMER MER RATED RATED BELOW 500 BETWEEN 500 KVA KVA AND 5MVA TRANSFORME R RATED BETWEEN 500 KVA AND 5MVA
PROTECTION
TRANSFORMER PROTECTION
TRANSFORMER PROTECTION
TRANSFOR TRANSFORMER MER RATED RATED BELOW 500 BETWEEN 500 KVA KVA AND 5MVA TRANSFORME R RATED BETWEEN 500 KVA AND 5MVA
PROTECTION
TRANSFORMER PROTECTION
TRANSFORMER PROTECTION
TRANSFORMER PROTECTION
TRANSFORMER PROTECTION
TRANSFORMER COOLING SYSTEM. FAILURE OF INSULATION BETWEEN LAMINATION OF CORE, CORE BOLT INSULATION. BADLY MADE JOINTS AND CONNECTIONS
TRANSFORMER PROTECTION
TRANSFORMER PROTECTION
EXTERNAL FAULTS EXTERNAL OVERLOADS AND SHORT CIRCUITS OVER VOLTAGE REDUCED SYSTEM FREQUENCY. FAULTS IN OLTC FAULTS IN BUSHINGS
TRANSFORMER PROTECTION
10
DIFFERENTIAL PROTECTION
PROTECTS THE TRANSFORMER AGAINST WINDING FAULTS SUCH AS PHASE TO PHASE FAULT AND PHASE TO EARTH FAULT. IT WORKS ON CIRCULATING CURRENT PRINCIPLE.
TRANSFORMER PROTECTION
11
DIFFERENTIAL PROTECTION
I1 I2
i1 RELAY i1 i2
id = i2 - i1 = 0
TRANSFORMER PROTECTION
12
DIFFERENTIAL PROTECTION
7356.8A 11/138KV GT dY1 586.4A
7356.8/1
586.4/1
i1 RELAY 1A 1A
id = i2 - i1 = 0
TRANSFORMER PROTECTION
13
DIFFERENTIAL PROTECTION
I1 I2
i1 RELAY i1 i2
id = i2 - i1 = 0
TRANSFORMER PROTECTION
14
DIFFERENTIAL PROTECTION
I1
i1 RELAY i1
id = i2 - i1 = i1
TRANSFORMER PROTECTION
15
DIFFERENTIAL PROTECTION
I1 I2
i1 RELAY i1 i2
id = i2 + i1
TRANSFORMER PROTECTION
16
DIFFERENTIAL PROTECTION
I1 I2
i1 i1 id R i2
i2 - i1 + i2 - id = 0 - i1 + i2 = id i2 - i1 = id i1 = i2 i2 - i1 = 0
TRANSFORMER PROTECTION
17
DIFFERENTIAL PROTECTION
I1 I2
i1 i1 id R i2
i2 - i1 - i2 - id = 0 - i1 - i2 = id i2 + i1 = -id
TRANSFORMER PROTECTION
18
DIFFERENTIAL PROTECTION
PROBLEMS / DIFFICULTIES, WHILE INCORPORATING DIFFERENTIAL PROTECTION.
DIFFERENT VOLTAGE LEVELS AT PRIMARY AND SECONDARY OF THE TRANSFORMER. POSSIBLE RATIO MISMATCH OF THE CURRENT TRANSFORMERS. 30 PHASE SHIFT IN CASE OF DELTA / STAR TRANSFORMER.
THE AECo LTD
TRANSFORMER PROTECTION 19
8000/5
11/138KV GT dY1
800/1
788A 0
8000/5
11KV/240V ET 11/6.9KV UAT Dd0
4.510A 0
i1 RELAY
4.018A 0
2.32A 0
DIFFERENTIAL PROTECTION
OPERATION OF THE TRANSFORMER AT DIFFERENT TAP POSITION. RELAY MAY NOT BE CONNECTED AT EQUIPOTENTIAL POINT OF THE PILOT WIRES. CT RATIO ERRORS DIFFERENT CT PERFORMANCE AT HIGH FAULT CURRENTS.
INHERENT DIFFERENCE IN THE CT CHARACTERISTIC SATURATION OF CTS CAUSE LARGE RATIO ERRORS IP = K*Is + Im. PRESENCE OF D. C. COMPONENT IN THE FAULT CURRENT.
THE AECo LTD
TRANSFORMER PROTECTION 21
DIFFERENTIAL PROTECTION
TRANSFORMER PROTECTION
22
DC
2nd 3rd 4th
THE AECo LTD
55%
63% 26.8% 5.1%
5th
6th 7th
4.1%
3.7% 2.4%
TRANSFORMER PROTECTION
23
TRANSFORMER PROTECTION
24
DIFFERENTIAL PROTECTION
STATIC RELAYS
DTH 31 / 32 Relay Biased to provide stability during heavy through faults. Second harmonic restraint to present operation by magnetizing inrush current. Fifth harmonic bypass for over excitation condition. An instantaneous high set Element.
TRANSFORMER PROTECTION
25
DIFFERENTIAL PROTECTION
NUMERICAL RELAYS
KBCH (ALSTOM ) MICOM 540 (ALSTOM) RET 316 (ABB)
TRANSFORMER PROTECTION
26
PROVIDES SENSITIVE, INSTANTANEOUS EARTH FAULT PROTECTION WITHIN THE PROTECTED ZONE OF THE TRANSFORMER. OPERATES ON CIRCULATING CURRENT PRINCIPAL.
TRANSFORMER PROTECTION
27
REF PROTECTION
Ir
N
Iy Ib
TRANSFORMER PROTECTION
28
REF PROTECTION
Ir
N
Iy Ib
TRANSFORMER PROTECTION
29
TRANSFORMER PROTECTION
30
A FAULT EXTERNAL TO A TRANSFORMER RESULTS IN OVERLOAD / TEMP. RISE / MECHANICAL FORCES. TRANSFORMER MAY FAIL IF THE FAULT IS NOT CLEARED PROMPTLY.
TRANSFORMER PROTECTION
32
N
IY IB
O/C O/C O/C E/F
Iy
Ib
TRANSFORMER PROTECTION
33
PROVIDED WHERE POWER TRANSFORMERS WITH SECONDARY STAR CONNECTED AND CONNECTED TO TRANSMISSION LINE.
TRANSFORMER PROTECTION
35
TRANSFORMER PROTECTION
36
GTT 11 RELAY IS PROVIDED. SETTING IS DONE AT 1.12 TIMES RATED V/F RATIO WITH TIME DELAY OF 60 SECS
TRANSFORMER PROTECTION
38
BUCHHOLZ PROTECTION
BUCHHOLZ RELAY PROVIDES UNIVERSAL RESPONSE TO ALL TYPES OF FAULTS WITHIN THE TRANSFORMER.
PROVIDES PROTECTION AGAINST TWO TYPES OF FAULTS MINOR / INCIPIENT FAULTS SUCH AS HOT SPOT ON THE CORE DUE TO S/C OF LAMINATION. CORE BOLT INSULATION FAILURE. FAULTY JOINTS. INTER TURN FAULTS OR OTHER WINDING FAULTS INVOLVING LOWER POWER INFEEDS. MAJOR WINDING FAULTS LIKE EARTH FAULTS OR INTERPHASE FAULTS.
TRANSFORMER PROTECTION
39
DY1 CONNECTION
IR IY IB IR Ir IR Ib 30 Ir Ir
Iy Ib
IB
IY
Iy
40
TRANSFORMER PROTECTION
DY11 CONNECTION
IR IY IB IR Ir N Ir Iy Ib IR
Ir
Iy IB IY
30
Ib
41
TRANSFORMER PROTECTION
EXCITATION CURVE
EXCITING VOLTAGE VS
EXCITATION CURRENT Ie
THE AECo LTD
TRANSFORMER PROTECTION 42
i1
i1
i2 I2/2 Id R
I1/2
TRANSFORMER PROTECTION
43
TRANSFORMER PROTECTION
44
THANK YOU
THE AECo LTD
TRANSFORMER PROTECTION 45