Busbar Protection
Busbar Protection
SOMPOL C.
Busbar Protection
Bus arrangement 1. Radial bus 2. Main and transfer 3. Double breaker double bus 4. Ring bus 5. Breaker and a half
Busbar Protection
Busbar Protection
Main Bus
Disconnect Switch Circuit Breaker
Circuit
Radial bus
Busbar Protection
Lowest cost Small land area required Easy to expand Simple to operate Simple protective relay
Busbar Protection
Low reliability Low flexibility of operation for maintenance Bus fault and failure of breaker requires substation be removed from service
Busbar Protection
Main Bus
Disconnect Switch
Circuit Breaker
N.O.
N.O.
N.O.
Transfer Switch
Transfer Bus
Circuits
Circuits
Busbar Protection
Small land area required Easy to expand Increased flexibility of operation over radial bus Any breaker can be removed from service without an outage
Busbar Protection
Increased cost over radial bus Increased complexity of operation over radial bus Increased complexity of protection over radial bus Low reliability
Busbar Protection
Circuits
Bus No. 1
Disconnect Switch
Circuit Breaker
Circuit Breaker
Circuits
Bus No. 2
Busbar Protection
Very high reliability Very flexibility operation Any breaker can be removed from service without an outage
Busbar Protection
High cost Large land area required Complex protective relaying and control
Busbar Protection
Load
Line Disconnect Switch
Source
Disconnect Switch
Circuit Breaker
Source
Ring bus
Load
Busbar Protection
High reliability Flexibility operation Low cost Any breaker can be removed from service without outage Expandable to breaker and a half configuration
Busbar Protection
Complex protective relaying and control Failed breaker during fault caused outage of one additional circuit
Busbar Protection
Circuits
Disconnect Switch
Circuit Breaker
Circuits
Busbar Protection
Very high reliability Very flexibility operation Any breaker can be removed from service without an outage
Busbar Protection
5. Breaker and a half Disadvantages
Large land area required High cost Complex protective relaying and control
Busbar Protection
Approximate per unit cost Reliability
Radial Main and transfer Ring bus Breaker and a half Double breaker double bus
5 4 3 2 1
Busbar Protection
Radial bus
Busbar Protection
Busbar Protection
Busbar Protection
Practice 0
- What kind of bus arrangement in single line diagram 1 and 2 ? - Where is the zone of protection of 87B1 and 87B2 ?
Busbar Protection
Criteria of Bus Differential relay (87B) Check the difference current between the current flow in and out of the protected bus ( vector summation at relay = 0 )
Busbar Protection
1. Every bay must use same class and CT ratio 2. Suitable for non switching substation 3. Easy to expand 4. Easy to use
Because of fault current at bus bar is very high, so some CT may saturate and make 87B misoperation on external fault..
saturate
Voltage = 0 at 87B
CT saturation
- Equivalent circuit ( saturate ) Ip/n Is Rct
Im
saturate
Ip/n
Is
Rct
Lm
Rct
E
If
Lm = 0 Im =
Rct
87B
Voltage > 0 at 87B
Ex Calculation of 87B
- CT ratio 2000/5 ( N ) - Rct = 1.2
Data - 3 phase fault current at bus = 25000 A ( If - 3phase ) - 1 phase fault current at bus = 23600 A ( If - 1phase )
- RL = 1.5 ( lead resistance between relay and CT ) - Relay setting range ; 175, 225, 275, 325 v - Vk = 800 v
Setting of 87B ( Vs )
Vs1 >= ( If / N )* ( Rct + 2RL ) ; 1phase fault Vs3 >= ( If / N )* ( Rct + RL ) ; 3 phase fault Vs1 = 249.6 v Vs3 = 169.8 v So set Vs = 325 v; ( Vk >= 2Vs )
Practice 1
- From single line diagram 2, if - 3phase fault =17000 A - 1phase fault = 13000 A What is the setting of Vs ?
Busbar Protection
1. Can use difference CT ratio for each bay 2. Suitable for switching substation 3. Not easy to expand
Function of bus differential Trip all circuit breakers that connected to the fault bus via 86B ( bus differential lockout relay ) and interlock all circuit breakers also.
Busbar Protection
Practice 2
From single line diagram 2 - Which circuit breaker should be tripped if 87B1 operated? - What is the operating time of 87B?
Zr = Vr / Ir
ZS
Ir
Z line
Vs
Vr
Zr
Z load
Operating condition :
Z = R + jX
R = P cos X = P sin
Z = R + jX P P
2 + X2 = R
-1 X/R = tan
Z = R + jX
Z1=R1+jX1
Z2=R2+jX2
2 1
Load area
R-X diagram
Plain impedance
Mho
R
Offset mho
Z1C
Ex Calculation of 21
Data - Base voltage =115 kV - Base MVA = 100 MVA - CT ratio = 800/5 - PT ratio 115/115 kV/V - Conductor type : 477 MCM AAC 590 A
Data - Length of line AB = 70 km, line BC = 30 km, line BD = 50 km - Impedance data : AB : z1= z2 = 9.7 + j29.1 p , z0 = 25.4 + j101 p BC : z1= z2 = 5.8 + j16.9 p BD : z1= z2 = 8 + j25 p C A
21
Multiply by 0.16, so AB : z1= z2 = 1.55 + j4.65 s , z0 = 4 + j16.1 s = 4.91 71.5 s BC : z1= z2 = 0.92 + j2.7 s BD : z1= z2 = 1.28 + j4 s Setting Zone 1 = 85% line AB = 4.17 71.5 s Zone2 = 120% line AB = 5 71.5 s , 0.5 sec Zone3 = 100% line AB + 120% line AB = 9.17 71.5 s ,1 sec
jX
71.5
A
Kn = ( z0 z1 ) / 3z1
= 2.51 + j11.51 = 11.78 77.6 4.67 + j13.97 14.73 71.5 = 0.799 6.15
Practice 3
From single line diagram 2 - Which circuit breaker should be tripped if 21 line 1 operated ( both primary and back up )? - Which circuit breaker should be reclosed? - Where is the zone of protection of 21?
Tele Protection
Teleprotection scheme
1. Permissive underreach transfer trip ( PUTT ) 2. Permissive overreach transfer trip ( POTT )
Benefit of teleprotection
- clear fault 100% line as fast as zone 1 - on more over trip - also initiate recloser as zone 1
( only trip by high speed zone ) - Single or multi shots - Single or three poles - Dead time and reclaim time should be set properly - Helpful for temporary fault
Dead time
Synchrocheck relay ( 25 )
- Supervise recloser relay befor close circuit breaker by check voltage level, frequency, and phase angle at both sides of circuit breaker ( sync. Function , BH-LH or LL-LB) - Only check voltage level for charge line function ( voltage check Function, BH-LD or DL-LB )
Back up Protection
Back up Protection
In protection system, each equipment should have 2 sets of protective relay. One set we call primary protection and the another is call back up protection.
Example :
Back up Protection
Transformer Primary 87K, self protection, Back up 51T, BF Feeder Primary 51/51G, Back up 51T, BF
Transmission line Primary zone1, Back up zone2, zone3 and others distance relay ( 115 kV ), BF Primary protection primary, Back up protection back up and others distance relay ( 230 kV ) , BF
Back up Protection
Bus bar Primary 87B, Back up zone2, zone3 of others distance relay at remote end substation ( 115 kV ), BF
Back up Protection
Back up Protection
Principle of Breaker failure
Measure the duration of fault current from the instance at which any relay operates to trip circuit breaker. If current is still flowing after preselected time delay, it is considered that the circuit breaker has failed to trip.
Back up Protection
Principle of Breaker failure
Normally breaker failure timer should less than zone 2 timer of distance relay at remote end substation to limit the tripping area only in substation that breaker fail.
Back up Protection
Element of Breaker failure
1. Main protection operate 2. Current detector operate ( 50BF) 3. Breaker fail timer operate ( 62BF) 4. On this function by cut off switch ( BFCO)
Back up Protection
Function of Breaker failure
When breaker fail to trip, the tripping and interlocking of all other circuit breakers connected to the failed circuit breaker will be initiated. Another lockout relay, 86BF, is required.
Practice 4
From single line diagram 2 - If circuit breaker 80722 fail to trip, which circuit breakers should be tripped? From single line diagram 1 - If circuit breaker 7052 fail to trip, which circuit breakers should be tripped?
Question ?
The end