Operating Instructions and Installation of ONE2 Heat Pump Hotjet
Operating Instructions and Installation of ONE2 Heat Pump Hotjet
Operating Instructions and Installation of ONE2 Heat Pump Hotjet
pump Hotjet
Hotjet CZ s.r.o. 1 / 29
Operating instructions and installation of heat pumps Hotjet
Contents:
1. USER INSTRUCTIONS ........................................................................................ 2
1.1. General information ..................................................................................................................2
1.1.1.System description ................................................................................................................................................................. 3
1.1.2. Warning ................................................................................................................................................................................4
1.2. Disposal ..................................................................................................................................... 4
1.3. Routine maintenance ............................................................................................................... 4
2. INSTALLATION INSTRUCTIONS ......................................................................... 5
2.1. Handling refrigerant ..................................................................................................................5
2.2. Parts of heat pump .....................................................................................................................7
2.2.1. Construction of heat pump .....................................................................................................................................................7
2.3. Location and connection .........................................................................................................8
2.3.1.Transport and storage ............................................................................................................................................................ 8
2.3.2.Base and pedestal for „ONE2“ ................................................................................................................................................8
2.3.3.Model , base and pedestal „ONE2“ ....................................................................................................................................... 10
2.3.4.Model , base and pedestal „ONE2“ ....................................................................................................................................... 10
2.3.5.Rules for placement of heating valves at outdoor unit “ONE2” .............................................................................................10
2.3.6.Nice and vibration.................................................................................................................................................................. 10
2.3.7.Load-bearing capacity of the structure .................................................................................................................................. 11
2.3.8.Roof installation ..................................................................................................................................................................... 11
2.4. Condensate drain .....................................................................................................................11
2.5. Connection to the heating system ..........................................................................................11
2.6. Connection of the outdoor sensor .........................................................................................12
2.6.1.Connecting conductors of sensors ......................................................................................................................................13
2.7. Antifreeze protection ..............................................................................................................13
3. ELECTRIC INSTALLATION ................................................................................ 14
3.1. Control and electronic instruments ...................................................................................... 14
3.1.1.Three versions of Hotjet „ONE2“ ........................................................................................................................................................................14
3.1.2.Monitoring the power supply phases (3-ph version) ...........................................................................................................................................14
3.1.3.Connection of block remote control (blocking in high-tariff periods) ...................................................................................................................15
Hotjet CZ s.r.o. 2 / 29
Operating instructions and installation of heat pumps Hotjet
Congratulations on your purchase of heat pump Hotjet. Get familiar with these instructions to get the best use and
a long service from the pump.
The heat pump is a compact unit designed for heating water for hot service water and for heating.
The source of heat is the external air, of which heat is transferred to water in an exchanger. The heat pump is a
long service life and a very safe product.
We wish you a trouble-free operation and a lot of thermal comfort.
1.1.1.System description
The Hotjet heat pumps are compact units designed for outdoor and indoor installation. The series Hotjet i units are
intended for indoor installation in an object, and the series Hotjet e units are an alternative for external installation
out of the object. These models take the energy from the air, and that is why it is not necessary to bore holes or to
install ground collectors.
The series Hotjet w are intended for the ground-water or water-water systems. The heat source is a borehole, a
ground collector or a technological or waste heat.
The heat pump is equipped with the Siemens RVS41 or RVS21 or RVS61 regulators. The regulators controls the
running of the actual heat pump, heating of the hot service water, charging of the storage reservoir, controlling the
three-stage bivalent source, directional and heating radiators circuits, swimming pool water heating and many
other parts of the heating and cooling system.
The regulators algorithms are practically identical, and differ only by the number of inputs, therefore the number of
simultaneously connected and regulated subsystems. Each series RSV regulator is extensible by 3 input and 3
output module.
Hotjet CZ s.r.o. 3 / 29
Operating instructions and installation of heat pumps Hotjet
1.1.2. Warning
• The device may be opened only by a person with relevant electrical qualification. Risk of
electric shock.
• ! The power supply circuit of the heat pump must comply with standard ČSN 33 2000 !
• We recommend installation of an 30mA tripping current earth leakage relay (ČSN EN 60335-2-40 ed.) and
a lockable main switch.
• The device must be connected only to properly earthed power supply.
• Before connecting equipment or removing any panel always switch off the power supply and exercise
maximum caution.
• The heat pump is not intended for operation with a frequency converter.
• The heat pump must never be switched on if it is not connected to the heating circuit filled with water.
• The heat pump must never be switched on with the covers removed or when the safety features are out of
operation.
• Arbitrary manipulation with connected heating system, heat pump and electrical power supply is
dangerous and can lead to serious injuries.
• The device service may be performed only by qualified and authorised service personnel.
• Do not tamper with the equipment and do not interfere with its assembly arrangement.
• Do not use any equipment if it has been dropped, or has been mechanically or otherwise damaged.
• Never cover the heat pump, the air inlet and discharge must be always free and open.
• Do not place the outdoor heat pump version inside enclosed premises – it will cool down and its efficiency
will be affected.
• Do not install the heat pump in position, which can be flooded.
• The device should not be installed in close proximity of flammable liquids and fumes.
• Do not store or handle flammable substances neat the equipment.
• Piping and the compressor contain cooling mixture under high pressure, and therefore should not Hotjet
CZ s.r.o. ! ! 4 z 46 Operating instructions and installation of heat pumps Hotjet (3.08/2010/01) be exposed to
high temperatures and the danger of perforation.
• Hot water above 52° C temperature may cause serious burns or death by scalding.
• Never remove or cover any of the markings, labels and warnings placed on the heat pump, as
these should be visible at all times. Replace the damaged ones with new ones.
• The control panel must be out of reach of children.
• Be careful to avoid injuries on sharper edges and projections.
• Implementation of any technical changes on the equipment is possible only with the prior written
consent of HOTJET CZ s.r.o.
1.2. Disposal
Disposal facility to a professional company specialized in the field of refrigeration or contact the manufacturer. The
product contains a filling (refrigerant oil), which must be disposed of properly.
Hotjet CZ s.r.o. 4 / 29
Operating instructions and installation of heat pumps Hotjet
The evaporator should be cleaned at least twice per year and each time when it is visibly fouled. Fouled
evaporator lowers the efficiency of the operation. The external surfaces of the heat pump may be washed with a
sponge and a warm soap water. Do not use bleach, abrasives or solvents, which could damage the surface of the
device. The detergent should not contain acids, soda or chlorides. Make sure that the parts with electrical
installation are protected against ingress of water !!
Check regularly the outdoor unit at below zero temperatures if there isn’t an excessive built up of frost or ice under
the pump. Snowing or strong wind can cause obstruction or snowbound closure of the evaporator inlets. Icing and
snow must be removed.
Filters:
The heating circuit of the pump is fitted with filters, which can be clogged. Check these at last twice a year. Close
the nearest valves before and after the filter and remove the sieve. After installation deaerate the heating system
and fill up the water in the heating circuit.
ATTENTION: The heat pump air-water contains a fan, which can be revolving.
Before maintenance of the evaporator part of the heat pump always disconnect the power supply and wait
until all moving parts of the fan come to standstill!
Warning: The water being discharged from the heat pump could be hot, beware of the danger of scalding.
ATTENTION:
If the heat pump does not start or if it does not heat, consult the situation with your installation company.
The heat pump cover should be removed only by a qualified worker.
The following should be checked by a competent service technician:
Electrical installation:
Check the connection and the condition of the electrical
Heating system:
The functioning of the heating system must be checked prior to the heating season.
2. Installation Instructions
This part of the documentation is intended for qualified installation and service staff as an assistant for proper
installation, operation and maintenance of the heat pump HOTJET. Read it carefully, failure to comply with
instructions may lead to malfunctioning of the heat pump, damage to property, scalding or electrocution injuries.
Hotjet CZ s.r.o. 5 / 29
Operating instructions and installation of heat pumps Hotjet
• Complete safety data sheets according to the refrigerant needs to ask info@hotjet.cz.
SAFETY WARNING
• The most serious adverse effects on human health when using the substance / preparation:
Refrigerant vapors are heavier than air, can cause oxygen displacement.
Rapid evaporation of liquid may cause frostbite.
Hotjet CZ s.r.o. 6 / 29
Operating instructions and installation of heat pumps Hotjet
2.2. Parts of heat pump
2.2.1. Construction of heat pump
14
13
12
11
10
1 2 3 4
5 Compressor 12 Condenser
Hotjet CZ s.r.o. 7 / 29
Operating instructions and installation of heat pumps Hotjet
2.3. Location and connection
2.3.1.Transport and storage
For the transport of heat pump is placed on a pallet. The heat pump should never be stored or installed on the
side. Maximum angle of tilt in any direction is 45 degrees. It is recommended to transport in an upright position.
Carriage on its side would like a written agreement. If transportation is an unavoidable side, it is necessary to
leave the device in an upright position at least 24 hours before starting. Failure to follow these instructions may
result in damage to the heat pump.
After taking heat pump equipment unpack, remove the panel cover and check to avoid damage during shipping.
Identified damage fails
transport companies and ask for their review, a copy of messages you send to HOTJET CZ, s.r.o
"
• The heat pump is equipped with side pedestals comprising adjustable legs to support the evaporator
above ground in elevated position.
• The heat pump can be installed on a solid base, which consists of concrete footing or paving. • The heat
pump horizontal plane is set with the use of the adjustable legs.
• The base material should be filled with material that drains well, e.g. crushed stone, as the
• condensate is discharged along the entire width of the evaporator.
• It is not advisable to place the heat pumps on larger areas – e.g. parking lots, pavements - as these do
not muffle noise well.
Hotjet CZ s.r.o. 8 / 29
Operating instructions and installation of heat pumps Hotjet
Hotjet CZ s.r.o. 9 / 29
Operating instructions and installation of heat pumps Hotjet
2.3.3.Model , base and pedestal „ONE2“
• Check the place of operation of the equipment before its positioning. If possible, place the pump in a
covered place (e.g. a sheltered place, roof overhang, etc.). Exposure of the equipment to unfavourable
climatic conditions may cause its lower efficiency.
• The air heat pump cannot be operated in enclosed spaces without air supply and extraction. In the indoor
unit this problem is solved with the use of special air ducts.
• Place the heat pump on a solid surface, which preferably consists of a concrete base, concrete footing or
paving
• It is not advisable to place the heat pumps on larger areas – e.g. parking lots, pavements - as these do
not muffle noise well.
• Install the heat pump at least 0,3 m above the surface.
• The free space between the heat pump and the surface should be at least 0,2m high to prevent
connection between the heat pump and the surface of the base in instances when ice is created.
Component Position
Drain Valve At the lowest point between HP and the inner part of the installation
Filter The object inside the pipe towards the heat pump
• Do not place outdoor heat pumps near walls of bedrooms, under their windows. Make sure your
neighbours will not be bothered by noise.
• To reduce vibrations of indoor units you can use suitable anti-vibration mountings or a vibration-absorbing
pad. This pad should be a little larger than the bottom part of the heat pump to ensure separation of the
heat pump from the floor.
• We do not recommend you to firmly attach the outdoor base to the building.
• In the case of the indoor units the wear and the possible noise insulating layer should be separated with a
groove up to the impact insulation.
Hotjet CZ s.r.o. 10 / 29
Operating instructions and installation of heat pumps Hotjet
2.3.7.Load-bearing capacity of the structure
• If you install the equipment on a higher floor, in the attic or on the roof, verify the load-bearing capacity of
the building structure.
• Installation on wooden structures should be considered carefully as such structures may transmit
vibrations.
• Façade installation: With regard to a high quantity of condensate suitability of suspension on the facade
should be considered carefully as uncontrolled condensate drain may occur resulting e.g. in soiling of the
wall.
2.3.8.Roof installation
Hotjet CZ s.r.o. 11 / 29
Operating instructions and installation of heat pumps Hotjet
"
•
&
We supply the QAC34 outdoor sensor as an accessory; its installation is not mandatory, but it is
•& MN)&023(E&.02+,*(..)0O,&*E6+.(+H&1EF2.(E+&,NE613&J)&FNE,)+&,6FN&.N2.&J2..)0(),&
F2+&J)&)2,(1P&FN2+H)3&
recommended.5+,/-&/6$7(-8+.$ &
• Wireless outdoor sensor: The standard sensor QAC34 can be converted to a wireless sensor through
the AVS13.399 module. This solution is suitable for situations when QAC34 cannot be interconnected with
"!$KL$<
"!$KL!A
equipped with an AVS71.390 radio transmitter. Due to protection of batteries the transmitter module is
"!$KL$K
& &
"
& &
CAUTION: The outdoor sensor has a different characteristic from the other sensors used by RVS; they cannot be 1-**"./)
CCC
!"#$%&'()*+")
,-**"./)*.-'0&*)*-,
"!$KL$$
!"#"$%&
"
Ourside sensor QAC34
If an extension of sensors is necessary, select a connection conductor (Cu, twisted pair) in accordance with the
table:
The antifreeze protection of the heat pump only works if the heat pump is connected to the power supply
and if the circulation pump of the condenser Q9 is on.
If there is a danger of frequent or prolonged power supply failures, the heating system must be filled with
an antifreeze mixture. This also holds good for installations where a power supply failure cannot be
detected (e.g. huts).
Draining procedure:
• Close the supply valves of heating water from the system to the heat pump.
• Open all the drain valves in the circuit to the heat pump.
When the unit has been filled again, the system must be properly bled before you switch the heat pump on.
Hotjet CZ s.r.o. 13 / 29
Operating instructions and installation of heat pumps Hotjet
3. Electric installation
• You will find electric diagrams in the final part of the documentation.
• The heat pump must be connected by an electrician with the required qualifications.
• We recommend you to install an earth-leakage circuit-breaker with IAN 30 mA (in accordance with Art.
13.2 and 16.2 of ČSN EN 60335-2-40 ed.) in the main switchboard of the building for the heat pump
power supply.
• Caution: If there is an earth-leakage circuit-breaker in the main switchboard of the building, do not install it
in the heat pump or the switchboard of the heat pump.
Basic:
Components of the basic version of HOTJET ONE:
• HOTJET ONE heat pump with a Siemens RVS21 controller and AVS55
• Outdoor temperature sensor
• Siemens QAA75 room thermostat (wired version)
Installation:
In this basic version all the supplementary parts of the heating system must be connected to the RVS21 controller,
which is located in the electric switchboard within the heat pump. The circuit-breaker of the heat pump or possibly
the bivalent source must be installed in the main switchboard of the building.
The HOTJET ONE heat pump has external protection against a wrong sequence of phases or a voltage drop in all
the three phases. Thus, the heat pump is resistant to interchanging of the sequence of phases and subsequent
reverse operation of the compressor and its destruction. As a wrong sequence of phases generally occurs during
the initial installation or subsequent installation only, due to the limited number of inputs of protective elements this
protection is connected in series with the protective element indicating a high pressure. And since the high
pressure error occurs during operation, this function is preferred. For this reason the high pressure monitoring
function is set for the multifunctional EX input in the configuration.
How can you recognize the wrong sequence of phases error if the E10 high pressure error is
indicated?
The heat pump indicates the high pressure error soon after the start.
• In the case of the first start of the heat pump (commissioning) = you have selected a wrong sequence of
phases (switch off the power supply of the pump, interchange the side power supply conductors and
switch on the circuit-breaker of the heat pump power supply again).
• In the case of a subsequent installation in the heat pump or the house switchboard (changing the
sequence of conductors, etc.) repeat the procedure of the previous point.
• The operator of the power supply mains carried out repairs, adaptation, etc. in the place of your
connection and interchanged the sequence of phases.
• If you performed all the above mentioned steps and the high pressure error indication persists, check the
phase protection indicators in the electric switchboard (red indicator on = error; green indicator on =
normal condition). The procedure of disassembly of the heat pump and electric switchboard cover is
described in chapter (). If the green indicator is lit, it is not the case of 3-ph asymmetry, but high pressure
only.
• Indication of the high pressure error shortly after the start of the heat pump can be caused by:
• air in the heating circuit
• low flow (circulation pump with insufficient capacity)
• clogged filter
• closed valves
Hotjet CZ s.r.o. 14 / 29
Operating instructions and installation of heat pumps Hotjet
3.1.3.Connection of block remote control (blocking in high-tariff periods)
In accordance with the diagram you can connect blocking of the heat pump and electric cartridges in periods of
high tariff. To activate the function no other settings are necessary.
The tariff relay can be installed in the production already (on request) or additionally during the installation of the
heat pump.
11 A1
A2
14
N(HDO)
E6:L
(HDO)
FS:2
FA2:2
LP:2
N7
PE7
HP:2
EX4
EX1
EX3
EX2
L
X11 X10
SIEMENS RVS21
!
3.2. Commissioning
Preparation and checks:
§ Precondition for trouble-free commissioning: The heating system is filled with water and
properly bled, the filters are cleaned and ball valves opened. In the case of control of heating circuits
it is absolutely necessary to bleed the floor heating or radiator system as well.
§ Check whether the water inlets and outlets on the heat pump are correctly connected.
§ With the power supply off check whether the evaporator is clean and the fan is not blocked by foreign
objects.
§ Check whether the electric installation has been completed.
Startup:
Hotjet CZ s.r.o. 15 / 29
Operating instructions and installation of heat pumps Hotjet
7. Reset the reduced outdoor temperature (“Consumption diagnostics”, line 8703). In case of a high outdoor
temperature you can simulate the outdoor temperature on line 7150. (It will be automatically reset after 5
hours)
8. Check the messages on lines 8000 - 8010 in the “Equipment status” menu.
9. You can carry out detailed diagnostics of the equipment in the “Source diagnostics” and “Consumption
diagnostics” menu.
10. Use the "rotary knob" to increase the required space temperature, confirm the setting with OK. Or you can
invoke a requirement for heating or cooling via Hx inputs.
§ First, the circulation pumps will be started (at least Q9 - circulation pump of the condenser) and then the
heat pump.
§ At the water outlet from the heat pump the temperature should rise by several degrees within a few tens
of seconds.
Note: The heat pump does not behave e.g. like a gas boiler; during normal operation the
difference between the inlet and outlet temperature is usually about 5°C.
The maximum acceptable difference between the inlet and outlet is 10°C.
In the ideal case < 5°C. A higher temperature difference indicates a problem of the hydraulic
connection and low flow through the condenser of the heat pump, which may be caused by a
too small circulation pump, its setting to a low speed, throttled valves, blocked armored
hoses, clogged filter or air in the heating circuit.
§ The end user can see a limited ser of messages (that can be displayed by repeatedly pressing the INFO
key).
§ Technician -> Status -> lines 8000 to 8010 should be checked (heating circuits, hot service water, heat
pump).
If the bell icon is lit on the display, one or more errors have occurred. After pressing of the INFO key the
description of the error will appear.
After unpacking QAA78 is not set to communicate with your RVS control units and it must be “coupled”. You will
find a detailed description of the procedure in the “Radio” chapter of the “Setting and programming manual” part.
The coupling should be done for each QAA78.
If a connection failure occurs during use, we recommend you to open the rear cover of QAA78 a take the battery
slightly out. After its re-insertion the connection should be established again.
Hotjet CZ s.r.o. 16 / 29
Operating instructions and installation of heat pumps Hotjet
The standard reach of the radio components is 30 m or 2 floors while the distance may differ by the type of
structure of the building.
To accelerate the configuration via QAA78 we recommend you to use the AVS82.495/101 service cable (used to
interconnect QAA78 and RVS) or to carry out configuration via a computer with the use of the OCI700 service
case.
NOTE: Experience shows that the radio connection may be disturbed by mobile phone calls, especially if you are
standing with QAA78 next to RVS. Radio operation of a mobile phone interferes with both the sides, RVS as well
as QAA78. In such a case move QAA78 from RVS to a distance of 5-10m.
The flow switch installed in the heat pump or the heating circuit was not activated. The function, causes and
remedial measures are described in chapter 2.8
The error is caused by air in the heating circuit, low flow (circulation pump with insufficient capacity), clogged filter,
closed valves.
It means that there is low flow in the primary circuits. It is caused by air in the heating circuit, low flow (circulation
pump with insufficient capacity), clogged filter, closed valves.
Connection without an outdoor sensor -> The antifreeze protection of the equipment must be switched off on line
6120 in the configuration.
The antifreeze protection of the heat pump depends on the condition of parameter 6120.
The error may still be displayed for some time after deactivation of the antifreeze protection.
A sensor is connected to the Bx input and its function has not been set in the configuration. Define it on the
“technician” level in the “configuration” menu.
A partial diagram is not completely configured. E.g.: you have a solar system, connect a B6 sensor and define it,
but you have not defined connection of the Q5 solar system circulation pump at one of the Qx multifunctional
outputs. RVS does not know which relay should be actuated and where the circulation pump is "hung".
At an Ex input the function of external blocking of the heat pump is activated, e.g. block remote control.
Hotjet CZ s.r.o. 17 / 29
Operating instructions and installation of heat pumps Hotjet
3.3.9. Error No. "247 Defrosting error" due to a low temperature of water in
the heating circuit and its limitation
The minimum temperature of water in the heating system is limited by the manufacturer for the air-water heat
pump to 12°C. If the heating water temperature at the inlet or outlet drops below this temperature, after 3 attempts
the defrosting will be stopped with error 247 “Defrosting error”. Since defrosting is not carried out properly, frost
usually occurs on the evaporator. Defrosting is a process that is run in certain intervals at outdoor temperatures
below 10°Cm when condensed air humidity gets frozen on the heat pump evaporator.
Note: Error 247 always occurs after several unsuccessful attempts to defrost the evaporator. Another cause may
be a failure to achieve the required temperature on the evaporator within the time period defined as maximum
duration of defrosting.
Compressor
Label:
"
Hotjet CZ s.r.o. 18 / 29
Operating instructions and installation of heat pumps Hotjet
4. Technical data of heat pump
4.1. Technical data of “ONE2”
Characteristics
Noise suppression:
• Use of scroll compressor design eliminates traditional
pistons and valves
• Compressor and cooling circuit multiple spring
suspension
• Solid and compact foundation slab
• Multiple layer noise-proof insulation on covers
• Low speed, 630mm large diameter serrated blades
fan
Advantages :
Storage reservoir (accumulation tank):
• is not required (subject to evaluation)
• Ideal for new objects without internal spaces. • equithermal charging availability
• State-of-the-art technology with a front-end • availability of so-called forced charging, when the
electronics for affordable price. required temperature is reached through charging.
The function’s initiation can be linked to time or
command controlled switching between electricity
Installation position :
tariffs. The advantage is the possibility of heat
“collection” during favourable weather conditions, e.g.
Intended for outdoor installation next to a building during higher air temperatures
structure or on its roof
Hotjet CZ s.r.o. 19 / 29
Operating instructions and installation of heat pumps Hotjet
• integration with a heat pump (hp functions as a
second hot service water)
Bivalent source:
• electrical cartridges support in the flow or in the Swimming pool heating
reservoir Is supported
• External sources support (existing gas, electricity and
other energy driven boilers) Fireplace water heating insert:
• Three or single-stage bivalent control
• the heat pump is switched off when the reservoir is
supplied by the fireplace water heating insert
Heating system :
• Overheated reservoir cool-down function
A fireplace or solid fuel boiler circulating pump can be
• Purely equithermal control (by the external
directly controlled in combination with RVS63,
temperature only) including other functions such as monitoring of
• Control according to space temperature burning intensity to prevent a fire going out.
• Equithermal coupled with space control
• One regulator manages up to two mixing heat circuits Cooling:
and one pump circuit
• Each heating circuits can be controlled fully • cooling support
independently with the use of its own space unit • heating as well as cooling supportin two-pipe and
• The existing ON/OFF switching mode thermostats four- pipe distribution systems
can be used • support of interchangeable cooling and hot service
• Addition of more heating circuits with the use of zone water heating or swimming pool heating
regulators RVS • dew-point check
• Integration with a higher level regulators, e.g. • dehumidifier control
individual rooms temperature control through
separate heating circuits can be achieved Cascade :
• Hot service water heating • The standard regulation supports connecting of up to
• Reservoir heating with an independent boiler 16 heat pumps or other sources is available already
• Storage reservoir heating with the use of floating
at the standard regulation level
boiler • Various type of sources are supported in a cascade
• Internal or external boiler heat exchangers without
(gas, electrical and solid fuel boilers)
internal exchanger or in case of inadequate size • Gas boilers with Siemens regulation can be cascade
• flow heating connected with our heat pumps. On the Czech
• forced heating market this applies to the trade marks Geminox,
• combined with solar heating Brötje, Baxi and Viadrus, equipped with the LMU
• Hot service water heating external source or boiler
units.
electrical heating element adjustment
• function of heat transfer between the storage
Additional functions :
reservoir and the boiler (a typical case when the • Centralised ripple control input (blocking electrical
reservoir heating is supplied by a solid fuel boiler or a heating)
fireplace water heating insert)
• External 0-10V heat requirement input, mode
changeover switching, heat pump start.
Solar system :
• over 50 connecting methods
• definition of 3 take-offs (hot service water, storage
reservoir, swimming pool)
Hotjet CZ s.r.o. 20 / 29
Operating instructions and installation of heat pumps Hotjet
4.1.1. Data sheet
HOTJET HOTJET HOTJET HOTJET HOTJET HOTJET
MODEL
10ONE2 15ONE2 20ONE2 25ONE2 35ONE2 45ONE2
Performance data Topný výkon [kW] / příkon [kW] / Topný faktor [COP]
11,34 / 2,68 / 13,25 / 3,10 / 18,81 / 4,18 / 30,10 / 6,99 / 33,6 / 7,34 /
Heating: A7/W35 1) 40,2 / 9,1 / 4,42
4,23 4,26 4,50 4,30 4,58
11,07 / 3,16 / 15,62 / 4,21 / 25,20 / 6,97 / 28,0 / 7,29 /
Heating: A2/W35 2) 8,71 / 2,61 / 3,33 33,6 / 8,85 / 3,74
3,50 3,71 3,62 3,84
9,34 / 3,20 / 13,01 / 4,21 / 20,64 / 6,95 / 22,83 / 7,23 / 27,35 / 8,87 /
Heating: A-7/W35 6,48 / 2,63 / 2,46 2,91 3,09 2,97 3,16 3,08
14,05 / 4,98 / 18,87 / 6,58 / 29,99 / 10,99 / 33,47 / 11,66 / 40,10 / 14,32 /
Heating: A7/W55 9,88 / 3,69 / 2,68 2,82 2,87 2,73 2,87 2,80
11,41 / 4,83 / 16,15 / 6,53 / 25,73 / 10,90 / 28,67 / 11,47 / 34,35 / 14,08 /
Heating: A2/W55 8,89 / 4,09 / 2,18 2,37 2,47 2,36 2,50 2,44
9,94 / 4,87 / 13,71 / 6,44 / 21,94 / 10,74 / 24,38 / 11,14 / 29,21 / 13,66 /
Heating: A-7/W55 7,34 / 4,08 / 1,80 2,04 2,13 2,04 2,19 2,14
Technical data
Temperature operating
-22°C to 40°C
limits for air [°C]
Temperature limit of
heating system min./max. 20°C to 62°C (to -10°C)
[°C]
Heating and reversing
water communication Outside G 5/4”
pipe
Nominal flow rate on the
heating side of ∆t = 5 °C 1,95 2,34 3,37 5,18 6,1 7,64
[m3 . h-1]
Minimum flow rate on the
heating side of ∆t = 7 °C 1,39 1,67 2,4 3,69 4,36 5,46
[m3 . h-1]
Refrigerant circuit
Hotjet CZ s.r.o. 21 / 29
Operating instructions and installation of heat pumps Hotjet
HOTJET HOTJET HOTJET HOTJET HOTJET HOTJET
MODEL
10ONE2 15ONE2 20ONE2 25ONE2 35ONE2 45ONE2
Technical information,
weight
Width x Depth x Height 1 271 x 500 x 1 1 621 x 600 x 1 1 721 x 700 x 1
[mm] 211 483 680
Weight [kg] 200 205 205 250 X X
Installation site Outdoor
Cabinet Powder coat
Color RAL 7016 (color on demand)
Electrical connection
Hotjet CZ s.r.o. 22 / 29
Operating instructions and installation of heat pumps Hotjet
4.1.2. Characteristic Curves
16 60
14
50
12
40
10
Výkon [kW] (Topný faktor)
20
10
0 0
-25 -20 -15 -10 -5 0 5 10 15 20 25
Teplota vzduchu [°C]
20 60
18
50
16
14
40
12
Výkon [kW] (Topný faktor)
10 30
20
6
4
10
0 0
-25 -20 -15 -10 -5 0 5 10 15 20 25
Teplota vzduchu [°C]
Hotjet CZ s.r.o. 23 / 29
Operating instructions and installation of heat pumps Hotjet
Výkonové křivky HOTJET 20ONE2 - vzduch/voda
25 60
50
20
40
15
Výkon [kW] (Topný faktor)
10
20
5
10
0 0
-25 -20 -15 -10 -5 0 5 10 15 20 25
Teplota vzduchu [°C]
40 60
35
50
30
40
25
Výkon [kW] (Topný faktor)
20 30
15
20
10
10
Hotjet CZ s.r.o. 24 / 29
Operating instructions and installation of heat pumps Hotjet
Výkonové křivky HOTJET 35ONE2 - vzduch/voda
50 60
45
50
40
35
40
30
Výkon [kW] (Topný faktor)
20
20
15
10
10
5
Topný faktor pro aplikace 35°C
60 60
50 50
40 40
Výkon [kW] (Topný faktor)
30 30
20 20
10 10
Hotjet CZ s.r.o. 25 / 29
Operating instructions and installation of heat pumps Hotjet
4.1.3.Dimension Drawing
1 2 3 4 5 6
A A
TČ 45 ONE2
TČ 25 ONE2
B B
700
500
500
600
1482,30
1680
1180
930
C C
Firma:
HOTJET s.r.o. Revize:
Typ dokumentace: Sériová výroba Název výkresu:
Jméno Podpis Datum
Kreslil: Ladislav Pliska 21. 10. 2015 VÝKONOVÁ ŘADA TČ ONE2 5-50KW
D
Kontroloval:
Odstranit otřepy a ostré hrany
Polotovar/Norma: Materiál: Číslo výkresu / Kód:
A4
1 2 Hmotnost: kg Měřítko: 1:20 List: 1/1
Hotjet CZ s.r.o. 26 / 29
Operating instructions and installation of heat pumps Hotjet
4
1483
470
2
5
86
580 290
270
1570 570
1620 6 356
600
1
3
1210
470
5
70
180
467
220
6 243
1216 471
1
1270 500
Hotjet CZ s.r.o. 27 / 29
Operating instructions and installation of heat pumps Hotjet
5. Warranty, Post Warranty Terms and Conditions and
Liability for Defect
• HOTJET CZ s.r.o. (hereinafter only "HOTJET"), shall be liable for the delivery performance in the quantity,
quality and design according to the purchase contract..
• HOTJET shall be liable for defects demonstrated within the warranty period, which is 24 months for the final
consumer - non-entrepreneur, unless agreed upon otherwise. The warranty period for entrepreneurs is 12
months, unless agreed upon otherwise in writing. Existence of the warranty period for HOTJET products is
subject to fulfillment of the terms and conditions set out in this Warranty Certificate.
• The warranty covers defects in material, function and/or workmanship. The warranty is not applicable to defects
caused by incorrect project, incorrect installation, handling, wiring or incorrect operation, improper electrical
fuses and installation, failure to comply with the specified voltage, unprofessional or inadequate interference
and manipulation, modification or dismantling (in case of subsequent installation the preservation of rights
resulting from the warranty is a subject to completion of all protocols relating to the assembly), misuse, natural
disasters, Force Majeure, violent damage and maintenance neglect. The warranty shall expire also should an
unauthorized person interfere into the product. Normal wear and tear of operating fillings is not covered by the
warranty. Operating fillings are not covered by the warranty. The warranty covers only the Goods supplied by
HOTJET. Responsibility for the product selection and use rests entirely with the buyer. The product must be
used in the manner and for the purpose for which it is intended. The installing company provides the warranty
adequate to the warranty period provided for the delivered equipment. If specific warranty conditions are
applicable to certain types of products and services, these shall be specified in the warranty certificate
accompanying the product, whereat the scope and terms of warranty provided to individual product groups may
vary.
• The warranty period commences as of the so-called authorized commissioning of the heat pump. The
authorized commissioning means the process of control activities and the heat pump starting by an authorized
technician certified by HOTJET, however not later than upon expiry of two months from the date of the goods
take over by the buyer. The buyer means HOTJET’s direct business partner to whom the relevant goods are
sold as to the first in the order. The delivery date and the person, to whom the goods were delivered, are always
written and confirmed in the warranty certificate. The period, during which the buyer cannot use the goods due
to a warranty defect, shall not be included into the warranty period.
• The buyer is entitled and obliged to claim visible defects, quantity and completeness of the goods within 3 days
from the goods take over. Any later claims of this nature will be disregarded. Should a defect appear during the
warranty period, the buyer shall inform HOTJET in writing or by e-mail on the defect occurrence, it shall
describe the defect and indicate how its manifested, furthermore, the buyer shall indicate the manufacturing
number, and send the relevant warranty certificate containing the date of sale, invoice number and place of
installation. The parties have agreed that by the aforementioned claim submission it shall be deemed that the
buyer requires a free of charge removal of the defect – by delivery of the material. Based on the defect
description, consultations and possible technical inspections of the equipment, HOTJET shall decide on the
manner of the claim solution or the claim process commencement. HOTJET has the right to require other
documents, e.g. photographs of the installation place, equipment to which the complaint relates, respectively,
from the buyer.
• In case of a justified claim process according to this warranty certificate, HOTJET shall provide the buyer with
repair materials for putting the product into operable condition. The costs associated with repairs shall not be
paid by HOTJET. Parts and materials to which the claim relates shall be send by the buyer to the HOTJET’s
address without any delay.
• If HOTJET, based on an expert’s opinion on the parts received from the buyer in the claim process, determines
that the claim is unjustified, the buyer shall be obliged to pay to HOTJET all costs associated with the claim
process, as well as the handling fee in the amount EUR 150.
• The warranty under this warranty certificate and the HOTJET’s General Terms and Conditions of Contract, is
provided only outside the territories of the Czech Republic and Slovakia. The warranty for other countries of the
world community shall also be applicable to these goods, i.e. to warranty repairs, in case of which the goods
shall be shipped to the HOTJET’s registered office at the buyer's expense and shipped to the buyer after
repairing also at the buyer’s expense.
Hotjet CZ s.r.o. 28 / 29
Operating instructions and installation of heat pumps Hotjet
6. EC declaration of conformity to the heat pump
"
Manufacturer:
HOTJET CZ s.r.o.
Průmyslová 966/21
747 23 Bolatice
Czech Republic
http://www.hotjet.eu
Hereby confirm that the design and construction of the product(s) listed below, in the version(s) placed on
the market by us, conform to the relevant requirements of the applicable EC directives.
This declaration becomes invalidated if any modifications are made to the product(s) without our prior
authorization.
Type: Hotjet 5ASK, Hotjet 8ASK, Hotjet 11ASK, Hotjet 15ASK, Hotjet 18ASK, Hotjet 21ASK / Split lite
Type: Hotjet 10ONE2, Hotjet 15ONE2 , Hotjet 20ONE2, Hotjet 25ONE2 / Split lite Hotjet 35ONE2 Hotjet
45ONE2
Type: Hotjet 8ONE, Hotjet 15ONE, Hotjet 18ONE / Split lite
Type: Hotjet 9w, Hotjet 12w , Hotjet 16w, Hotjet 20w, Hotjet 33w ,Hotjet 50w.
EC Directives:
Applied Standards:
EN 60335-1:2012; EN60335-2-40:2003+A11+A12+A1+corr.+A2:2009+AC:2010 EN55014-1:2006;
EN55014-2:1997+A1:2001
EN61000-3-2:2006; EN61000-3-3:1995+A1:2001+A2:2005 EN378-1:2008+A1:2010; EN378-2:2008+A1:2009;
EN378-3:2008; EN378-4:2008 EN 14511-1:2011; EN14511-2:2011; EN14511-3:2011; EN14511-4:2011
CE mark added :
2015
"
ing. Richard Köhler
Hotjet CZ s.r.o. 29 / 29
Operating instructions and installation of heat pumps Hotjet