Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

C Aluminium terminal pad

a b c

100
D
D E D >1600A D 1600A
20
200 100 60
Pitch circle Mechanical terminal loads

Insulator height
F1 F1

80
Bottom fitting Top fitting
4xM16

200
127 F1 F1
F1 F1
F1 F1
2-Earthing terminals Series arrangement
diagonal on the frame of poles

a b c

100
60
60 280 P 3150 P 3150
M16x30 depth

Rated voltage (kV) 145


Rated current (A) 1600 2500 3150 4000
Weight of disconnector (kg) 140 145 150 150
without insulator & drive(1 Pole)
Operating mechanisms are to be
mounted at pole a, b, c optionally.
Minimum failing load of insulator (kN) 4 6
Mechanical terminal load
F1 static terminal load (kN) 1.2 1.5
Isolating distance

F1 static+dynamic (kN) 3.1 4.7


Mounting Dimensions Weight of insulator(approx.) (kg) 63 70
PREPARED.
A NEW DRG.

Rated Current Terminal pad A B C D E


DIN 14 50 -
1600A 2070 280
NEMA 14.3 44.4 -
DIN 14 50 50
1 Operating mechanism of 2500A 2120 330
NEMA 14.3 44.4 55.6
Disconnector DIN 14 50 50
3150A 2170 380
NEMA 14.3 44.4 55.6
FOR TENDER PURPOSE ONLY 4000A
DIN
2170 380
14 50 50
NEMA 14.3 44.4 55.6
All dimension are in mm
General Arrangement SDF145
A 2013/01/11 Three pole Horizontal Centre Break
Disconnector without earth switch. 1HYD990321-010