Marakez Fcu Submittal
Marakez Fcu Submittal
Marakez Fcu Submittal
MECHANICAL / 02 0
SUBMITTAL TRANSMITTAL FORM Date: / / 21
TRANSMISSION OF DRAWINGS, DOCUMENTS, MATERIALS, ETC. SUBMITTED FOR CODE
APPROVAL
MAIN CONTRACTOR : Sigma Contractors YOUR INFORMATION
RE: CONTRACT Package No.
ACTION
APPROVED A
APPROVED AS NOTED B
WE ARE SENDING HEREWITH / UNDER SEPARATE COVER, THE DRAWINGS/ NOT APPROVED C
DOCUMENTS / SAMPLES LISTED BELOW. (DELETE AS NECESSARY) FOR INFORMATION D
CODE
QTY DRWS., SPEC. OR ITEM SEQ DESCRIPTION + TYPE
Submittal Action
COPIES
FOR CONTRACTOR
Consultant to enter Action Codes and Remarks, and return to Contractor
REMARKS
CONSULTANT'S COMMENTS
COPIES TO
TYPE : SD:Shop Drawing CA:Calculation SM:Sample MS:Method Statement GT:Guarantee TF:Temporary Facilities
OT:Other CT:Certificates TT:Test Results MK:Mock-up
ROUTING Code to be entered by
FROM
TO Consultant Contractor Contractor
Date Date Date Date Code to be entered by
Signature Signature Signature Signature Consultant
EBAIR CONDITION CO. BRAND NAME AWALGULF AGENT
PROJECT
MARAKEZ
Previous Projects
We are central HVAC Supplier Company established since 2008 as Awal Gulf Factory Distributor in
1 Ismaelia Hospital Fan Coil Units
2 El Safwa Resort Roof Top Package Units
3 Eipico Pharmaceutical Fan Coil Units
4 Maadi Hospital Ducted Concealed Units
5 City Light Mall Fan Coil Units
6 Capital Business Park Fan Coil Units
7 El Galaa Hospital Fan Coil Units
8 Mostfa Kamal Hospital Fan Coil Units
9 Elmenia School Fan Coil Units
10 Hurgada Air Port Fan Coil Units
11 Cairo Festival City Mall Fan Coil Units
12 City Star(15) Shops Fan Coil Units
13 Dr. Diaa Hospital Roof Top Package Units
14 Atos Pharm Factory Air Handing&Fan Coil
15 Catract Aswan Hotel Air Handing&Fan Coil
16 Edrak Bldg Fan Coil Units
17 Serenity Village Hotel Hurgada Fan Coil Units
18 Segma Tech Factory Fan Coil Units
19 Carrefour Sun City Mall Fan Coil Units
20 Sabor Office Arkedia Cassette Type& Decorative FCU
21 De Facto Shop City Stars Cassette Fan Coil Units
22 Admn Bldg ‐ Nabil Emam Cassette Fan Coil Units
23 Villa Elmalawany Central Ducted Split Units
24 Break Defense Minister(10Units 50Ton) Roof Top Package Units
25 Al Afaak Fan Coil Units
26 Private Villa Central Ducted Split Units
27 Engineering Authority Fan Coil Units
28 Camel Bar Hurgada Air Handling Units& Roof Top Package Units
29 Hatchery Plant Factory Air Handling Units
30 Makro Market (3Units 80Ton)Salam Branch Roof Top Package Units
16ST Abdelaziz Eissa Block 35 Ninth region ‐ Nasr City ‐ Cairo ‐ Egypt
Tel. : (+20)2‐2473‐2550
Fax. : (+20)2‐2471‐3965
Email: Info@ebaircindition.com
31 Makro Market (3Units 80Ton) Qalyub Branch Roof Top Package Units
32 Auc library Air Handling&Fan Coil Units
33 Malabo Airport (Nigeria) Air Handling Units
34 Arab mall Ducted Concealed 407c
35 Info Fort factory ‐ 6 October Ducted Concealed 407c
36 Mobinil Call Center ‐ Abour Ducted Concealed 407c
37 Suez petroleum (10Unit 50 Ton) Company Roof Top Package Units
38 Nestile Ice Cream Factory Split Units 407 C
39 Abour Medical Factory Condensing Units
40 Cridet Agricole Bank Central Ducted Split Units
41 Asfour Hospital Fan Coil Units
42 City Light Mall‐Alex Fan Coil Units
43 Lc Shope ‐Obour City Chilled Water Cassette Fcu
44 Chiller Sudan Chiller 80 Ton
45 Cairo Plant Fan Coil Units
46 Chiller Sohag (Atlas Company) Chiller 80 Ton
47 Chiller Asyout (Atlas Company) Chiller 80 Ton
48 Chiller Louxor (Atlas Company) Chiller 80 Ton
49 P&G (CfC) Fan Coil Units
50 B‐Tec 6‐ October Branch Fan Coil Units
51 Metro Poltan School Central Ducted Split Units
52 point Ninety Mall Fan Coil Units
53 point Ninety Mall Cinema Fan Coil Units
54 Abu Ftouah Hospital Air Handling&Fan Coil Units
55 Zayed Hospital Air Handling& Condensing Units
56 Heliopolis School Fan Coil Units
57 E‐ Finance Central Ducted Split Units
58 Talaat Harb Mall Fan Coil Units
59 Tenth Of Ramadan Hospital Air Handling Units
60 Sas Factory Fan Coil Units
16ST Abdelaziz Eissa Block 35 Ninth region ‐ Nasr City ‐ Cairo ‐ Egypt
Tel. : (+20)2‐2473‐2550
Fax. : (+20)2‐2471‐3965
Email: Info@ebaircindition.com
61 Uni Liver Factory Central Ducted Split Units(R407)
62 Mcdonald's (Masr & sudan Branch) Central Ducted Split Units
63 Mcdonald's ( El Horya Branch) Central Ducted Split Units
64 National Bank Aswan Branch Central Ducted Split Units
65 The Egyptian Company For Wholesale Fan Coil Units
66 Ragab's Sons (Giza) Fan Coil Units
67 CIB Bank Abas El Akad Branch Hi Wall Split
68 Wady El Natroon Hospital Fan Coil Units
69 Mena House Hotel Fan Coil Units
70 Vox Cinema Mall Of Egypt Fan Coil Units& Air Handling Units
71 New Giza Hi Wall Split
72 Carrefour City Center Obour Fan Coil Units
73 Etamco factory Fan Coil Units
74 Electricity Station South Helwan Roof Top Package Units
75 Wady Natron Hospital Fan Coil Units
76 Shooting Club Fan Coil Units
77 Henkel Plant Factory Central Ducted Split Units
78 Mansoura Hospital Condensing Units
79 City Center Almaza Roof Top Package& Split Units
80 Snow city –city stars Cassette Decretive fan coil units
81 Helnan Hotel Port Said Fan Coil Units
82 City Center –Maadi Fan Coil Units
83 Maxium Mall New Cairo Fan Coil Units
84 Lapoire Factory Fan Coil Units &Air Handing Unit
85 CFC ‐ Stream 2 Fan Coil Units
86 Al Azhar Library Central Ducted Split Units
87 JUTIN FACTORY Central Ducted Split Units
88 New Capital ‐ Ministries Buildings ‐SIAC Central Ducted Split Units
89 New Capital ‐ Ministries Buildings ‐Giza System Central Ducted Split Units
16ST Abdelaziz Eissa Block 35 Ninth region ‐ Nasr City ‐ Cairo ‐ Egypt
Tel. : (+20)2‐2473‐2550
Fax. : (+20)2‐2471‐3965
Email: Info@ebaircindition.com
90 New Capital ‐ Ministries Buildings ‐ AL Gharably Central Ducted Split Units
91 New Capital ‐ Ministries Buildings ‐ Al Sodaa Central Ducted Split Units
92 New Capital ‐ Ministries Buildings ‐ New Cooler Central Ducted Split Units
93 New Capital ‐ Ministries Buildings ‐ UNITECH Central Ducted Split Units &Fan Coil Units
94 New Capital ‐ Ministries Buildings ‐ Red Sea Central Ducted Split Units
95 New Capital ‐ Ministries Buildings ‐ ROWAD Central Ducted Split Units
96 New Capital ‐ Ministries Buildings ‐ Tallat Mostafa Central Ducted Split Units
97 New Capital ‐ Ministries Buildings ‐Hassan Allam ConCentral Ducted Split Units
98 New Capital ‐ Ministries Buildings ‐Hassan Allam tec Central Ducted Split Units
99 New Capital Mansoura 8 Central Ducted Split Units
16ST Abdelaziz Eissa Block 35 Ninth region ‐ Nasr City ‐ Cairo ‐ Egypt
Tel. : (+20)2‐2473‐2550
Fax. : (+20)2‐2471‐3965
Email: Info@ebaircindition.com
Date 22‐Nov‐21
Our Ref. 21‐688‐FCU‐R0
Project Name: MARAKEZ
Dear Sir,
Reference to the technical specifications of the air‐conditioning system, required for
your project; please find herewith our selection & technical data.
Marshal FAN COIL UNIT INCLUDES THE FOLLOWING:
‐ Eurovent Certified Ceiling Concealed Fan Coil Units.
‐ 3 Speed Fan and Motor Selection at Medium Speed
‐ AHRI Certified 4 Rows (CU Tubes / Al Fins Cooling Coil) For All Units.
‐ Extended Insulated Drain Pan.
‐ Washable Vinyl Chloride Filter
‐ Manual Air Vent.
‐ Insulated return air plenum
C.Capacity Air Flow E.S.P. Q’TY.
Item Model
T.R. CFM PA #
FCU‐01 EDNW18 1.0 450 30.0 9
FCU‐02 EDNW30 1.5 750 30.0 25
FCU‐03 ESNW30 2.0 900 30.0 10
FCU‐04 ESNW36 2.5 1,200 30.0 5
FCU‐05 ESNW42 3.0 1,350 30.0 8
FCU‐06 ESNW60 3.5 1,600 30.0 2
FCU‐07 ESNW60 4.0 1,800 30.0 6
FCU‐08 ESNW72 4.5 2,000 30.0 7
FCU‐09 ESNW72 4.5 2,000 75.0 14
## Selection Based on:
* Ent. Water Temp 44ºF, Water Rise 16ºF
* Ent. Air Temp. (77 DB / 64.4 WB)ºF.
Warrantee:
12 – Months from the date of delivery.
Origin:
Bahrain
16ST Abdelaziz Eissa Block 35 Ninth region - Nasr City - Cairo - Egypt
Tel. : (+20)2-2473-2550
Fax. : (+20)2-2471-3965
Email: Info@ebaircindition.com
EB AIRCONDITION CO. BRAND NAME AWALGULF AGENT
PROJECT
MARAKEZ
PRODUCT TYPE:
ITEM REFERANCE:
FCU‐01
ITEM Model:
EDNW18
Data Sheets
Chilled Water Fan Coil Selection Datasheet
Customer :
Project Details : MARAKEZ
Reference : FCU-01
Location :
Designer :
Qty .: 9
Created Date: 21/11/2021
INPUT
On Coil Dry On Coil Wet Required
External Static Entering water Leaving Water
Air Flow Bulb Bulb Altitude
Pressure Temperature Temperature Capacity
Temperature Temperature
Inch H2O CFM °F °F °F °F Ft Btu/h
0.12 450 77.0 64.4 44 60 0 12000
OUTPUT
Technical Data Unit Data
Fan Data Unit Model : EDNW18 – 4R
Fan Type : Forward Curved Centrifugal Application: (Standard /District Cooling) District Cooling
Size : Inch 6.4 x 8.5 Range: (Low Static / High Static) Low Static
Quantity : 2 Type: Concealed Ceiling Suspended
Cooling Coil Data Casing Details
Coil Face Area : ft^2 1.84 Galvanized Steel.
Coil Tube Diameter : Inch 5/16 G90 Coated.
Tube Type : Gross Grooved Electrostatic deposited Epoxy Powder Paint.
Tube Material : Copper Performance Data
Fin Type: Corrugated Cooling
Fin Material: Aluminum Speed: High Med Low
Fins Per Inch (FPI) / Rows 14 / 4 Total Cooling Capacity Btu/h 12920 12188 11763
Filter Data General Sensible Capacity Btu/h 10321 9689 9325
Return Air Filter Size : Inch 35.1 x 9.1 x 0.3 SHR 0.799 0.795 0.793
Filter Media: Washable Synthetic HDPE mesh
Air Flow Rate : CFM 622 569 543
Efficiency: 90% down to 50 microns External Static Pressure: 0.12 0.12
Inch H2O 0.12
Quantity: 1 Dry Bulb Entering °F 77.0 77.0 77.0
Electrical Data Air Temperature: Leaving °F 57.5 57.2 57.2
Blower Motor : 125 Side 64.4 64.4
W Wet Bulb Entering °F 64.4
Blower Speed : RPM 1350 Temperature: Leaving °F 56.3 55.94 55.94
Blower Motor FLA : A 1 Relative Entering % 50.25 50.25 50.25
Motor Type : AC Motor (PSC) Humidity: Leaving % 92.54 92.49 92.49
Motor Insulation : Class B Entering Water Temp. : °F 44 44 44
Motor IP Rating : IP20 Fluid Leaving Water Temp. : °F 60 60 60
Power Supply Sid Water Flow Rate : GPM 1.63 1.54 1.44
220-240/1/50Hz Water Pressure Drop : Ft h2o 6.04 5.46 5.13
Sound Data at (1.5m) according to JIS B8616-2006 standard Electric Heater (Optional)
Low Speed Sound Level dB (A) 47 Heating Capacity : kW --
Med Speed Sound Level dB (A) 49
High Speed Sound Level dB (A) 51
Version : 1.0.0 Page 1 of 3
Dimensional Drawings
GENERAL
- Eurovent Certified Chilled Water Fan Coil Units.
- Galvanized Steel Casing.
STANDARD - Efficient Heat Exchangers made of Copper and enhanced Aluminum fins.
- Fan Assembly.
- Auto Air vent.
OPTIONAL - 4 pipes system.
CASING
- Galvanized Steel Sheet of 0.8 - 1.2mm thick - Grade G90
STANDARD - Electrostatic deposited Epoxy Powder Paint.
- Passes salts spray test up to 1000 hours.
INSULATION
- Closed cell Elastomer (6mm thickness for high static units).
STANDARD - Density: 48kg/ m³.
- Fire Self-extinguishing type with flame spread index=25 and smoke developed index=50, comply with NFPA 101
OPTIONAL - Plenum insulation for low static units (3mm thickness).
FAN
- Statically and dynamically balanced for quieter and vibration free operation.
- High Quality Aluminum for high static models and plastic for low static.
STANDARD
- Double inlet, double width centrifugal type.
- Forward curved type.
OPTIONAL - Metallic blowers for low static.
COIL
- AHRI 410 certified coils.
- Housed in galvanized steel frames.
STANDARD - Copper tubes mechanically bonded to aluminum fins.
- Manufactured by state-of-the-Art technology equipment.
- Tested to 350 psig.
- District cooling application.
OPTIONAL
- Hydrophilic fins coating.
DRAIN PAN
- Drain pan is made of 0.8mm thick GI.
STANDARD
- 6mm thick insulation.
- Auxiliary drain pan.
OPTIONAL
- Stainless steel drain pan.
FILTER
PROJECT
MARAKEZ
PRODUCT TYPE:
ITEM REFERANCE:
FCU‐02
ITEM Model:
EDNW30
Chilled Water Fan Coil Selection Datasheet
Customer :
Project Details : MARAKEZ
Reference : FCU-02
Location :
Designer :
Qty .: 25
Created Date: 22/11/2021
INPUT
On Coil Dry On Coil Wet Required
External Static Entering water Leaving Water
Air Flow Bulb Bulb Altitude
Pressure Temperature Temperature Capacity
Temperature Temperature
Inch H2O CFM °F °F °F °F Ft Btu/h
0.12 750 77 64.4 44 60 0 18000
OUTPUT
Technical Data Unit Data
Fan Data Unit Model : EDNW30 – 4R
Fan Type : Forward Curved Centrifugal Application: (Standard /District Cooling) District Cooling
Size : Inch 7.9 x 7.9 Range: (Low Static / High Static) Low Static
Quantity : 2 Type: Concealed Ceiling Suspended
Cooling Coil Data Casing Details
Coil Face Area : ft^2 1.84 Galvanized Steel.
Coil Tube Diameter : Inch 5/16 G90 Coated.
Tube Type : Gross Grooved Electrostatic deposited Epoxy Powder Paint.
Tube Material : Copper Performance Data
Fin Type: Corrugated Cooling
Fin Material: Aluminum Speed: High Med Low
Fins Per Inch (FPI) / Rows 14 / 4 Total Cooling Capacity Btu/h 19296 18092 17214
Filter Data General Sensible Capacity Btu/h 14952 13931 13193
Return Air Filter Size : Inch 33.0 x 10.7 x 0.3 SHR 0.775 0.77 0.766
Filter Media: Washable Synthetic HDPE mesh
Air Flow Rate : CFM 920 839 777
Efficiency: 90% down to 50 microns External Static Pressure: 0.12 0.12
Inch H2O 0.12
Quantity: 1 Dry Bulb Entering °F 77 77 77
Electrical Data Air Temperature: Leaving °F 59.2 59 58.6
Blower Motor : W 300 Side Entering °F 64.4 64.4
Wet Bulb 64.4
Blower Speed : RPM 1350 Temperature: Leaving °F 57.92 57.74 57.38
Blower Motor FLA : A 2.6 Relative Entering % 50.25 50.25 50.25
Motor Type : AC Motor (PSC) Humidity: Leaving % 92.58 92.55 92.51
Motor Insulation : Class B Entering Water Temp. : °F 44 44 44
Motor IP Rating : IP20 Fluid Leaving Water Temp. : °F 60 60 60
Power Supply Sid Water Flow Rate : GPM 2.39 2.26 2.12
220-240/1/50Hz Water Pressure Drop : Ft h2o 8.35 7.46 6.84
Sound Data at (1.5m) according to JIS B8616-2006 standard Electric Heater (Optional)
Low Speed Sound Level dB (A) 51 Heating Capacity : kW --
Med Speed Sound Level dB (A) 54
High Speed Sound Level dB (A) 56
Version : 1.0.0 Page 1 of 3
Dimensional Drawings
GENERAL
- Eurovent Certified Chilled Water Fan Coil Units.
- Galvanized Steel Casing.
STANDARD - Efficient Heat Exchangers made of Copper and enhanced Aluminum fins.
- Fan Assembly.
- Auto Air vent.
OPTIONAL - 4 pipes system.
CASING
- Galvanized Steel Sheet of 0.8 - 1.2mm thick - Grade G90
STANDARD - Electrostatic deposited Epoxy Powder Paint.
- Passes salts spray test up to 1000 hours.
INSULATION
- Closed cell Elastomer (6mm thickness for high static units).
STANDARD - Density: 48kg/ m³.
- Fire Self-extinguishing type with flame spread index=25 and smoke developed index=50, comply with NFPA 101
OPTIONAL - Plenum insulation for low static units (3mm thickness).
FAN
- Statically and dynamically balanced for quieter and vibration free operation.
- High Quality Aluminum for high static models and plastic for low static.
STANDARD
- Double inlet, double width centrifugal type.
- Forward curved type.
OPTIONAL - Metallic blowers for low static.
COIL
- AHRI 410 certified coils.
- Housed in galvanized steel frames.
STANDARD - Copper tubes mechanically bonded to aluminum fins.
- Manufactured by state-of-the-Art technology equipment.
- Tested to 350 psig.
- District cooling application.
OPTIONAL
- Hydrophilic fins coating.
DRAIN PAN
- Drain pan is made of 0.8mm thick GI.
STANDARD
- 6mm thick insulation.
- Auxiliary drain pan.
OPTIONAL
- Stainless steel drain pan.
FILTER
PROJECT
MARAKEZ
PRODUCT TYPE:
ITEM REFERANCE:
FCU‐03
ITEM Model:
ESNW30
Chilled Water Fan Coil Selection Datasheet
Customer :
Project Details : MARAKEZ
Reference : FCU-03
Location :
Designer :
Qty .: 10
Created Date: 22/11/2021
INPUT
On Coil Dry On Coil Wet Required
External Static Entering water Leaving Water
Air Flow Bulb Bulb Altitude
Pressure Temperature Temperature Capacity
Temperature Temperature
Inch H2O CFM °F °F °F °F Ft Btu/h
0.12 900 77 64.4 44 60 0 24000
OUTPUT
Technical Data Unit Data
Fan Data Unit Model : ESNW30 – 4R
Fan Type : Forward Curved Centrifugal Application: (Standard /District Cooling) District Cooling
Size : Inch 7.9 x 7.9 Range: (Low Static / High Static) High Static
Quantity : 2 Type: Concealed Ceiling Suspended
Cooling Coil Data Casing Details
Coil Face Area : ft^2 1.84 Galvanized Steel.
Coil Tube Diameter : Inch 5/16 G90 Coated.
Tube Type : Gross Grooved Electrostatic deposited Epoxy Powder Paint.
Tube Material : Copper Performance Data
Fin Type: Corrugated Cooling
Fin Material: Aluminum Speed: High Med Low
Fins Per Inch (FPI) / Rows 14 / 4 Total Cooling Capacity Btu/h 25330 24347 22920
Filter Data General Sensible Capacity Btu/h 18065 17295 16184
Return Air Filter Size : Inch 33.0 x 10.7 x 0.3 SHR 0.713 0.71 0.706
Filter Media: Washable Synthetic HDPE mesh
Air Flow Rate : CFM 987 920 839
Efficiency: 90% down to 50 microns External Static Pressure: 0.12 0.12
Inch H2O 0.12
Quantity: 1 Dry Bulb Entering °F 77 77 77
Electrical Data Air Temperature: Leaving °F 58.7 58.3 57.9
Blower Motor : 300 Side 64.4 64.4
W Wet Bulb Entering °F 64.4
Blower Speed : RPM 1350 Temperature: Leaving °F 57.36 57 56.25
Blower Motor FLA : A 2.6 Relative Entering % 50.25 50.25 50.25
Motor Type : AC Motor (PSC) Humidity: Leaving % 92.40 92.60 90.60
Motor Insulation : Class B Entering Water Temp. : °F 44 44 44
Motor IP Rating : IP20 Fluid Leaving Water Temp. : °F 60 60 60
Power Supply Sid Water Flow Rate : GPM 3.13 3.01 2.88
220-240/1/50Hz Water Pressure Drop : Ft h2o 12.32 11.49 10.33
Sound Data at (1.5m) according to JIS B8616-2006 standard Electric Heater (Optional)
Low Speed Sound Level dB (A) 51 Heating Capacity : kW --
Med Speed Sound Level dB (A) 52
High Speed Sound Level dB (A) 54
Version : 1.0.0 Page 1 of 3
Dimensional Drawings
GENERAL
- Eurovent Certified Chilled Water Fan Coil Units.
- Galvanized Steel Casing.
STANDARD - Efficient Heat Exchangers made of Copper and enhanced Aluminum fins.
- Fan Assembly.
- Auto Air vent.
OPTIONAL - 4 pipes system.
CASING
- Galvanized Steel Sheet of 0.8 - 1.2mm thick - Grade G90
STANDARD - Electrostatic deposited Epoxy Powder Paint.
- Passes salts spray test up to 1000 hours.
INSULATION
- Closed cell Elastomer (6mm thickness for high static units).
STANDARD - Density: 48kg/ m³.
- Fire Self-extinguishing type with flame spread index=25 and smoke developed index=50, comply with NFPA 101
OPTIONAL - Plenum insulation for low static units (3mm thickness).
FAN
- Statically and dynamically balanced for quieter and vibration free operation.
- High Quality Aluminum for high static models and plastic for low static.
STANDARD
- Double inlet, double width centrifugal type.
- Forward curved type.
OPTIONAL - Metallic blowers for low static.
COIL
- AHRI 410 certified coils.
- Housed in galvanized steel frames.
STANDARD - Copper tubes mechanically bonded to aluminum fins.
- Manufactured by state-of-the-Art technology equipment.
- Tested to 350 psig.
- District cooling application.
OPTIONAL
- Hydrophilic fins coating.
DRAIN PAN
- Drain pan is made of 0.8mm thick GI.
STANDARD
- 6mm thick insulation.
- Auxiliary drain pan.
OPTIONAL
- Stainless steel drain pan.
FILTER
PROJECT
MARAKEZ
PRODUCT TYPE:
ITEM REFERANCE:
FCU‐04
ITEM Model:
ESNW36
Chilled Water Fan Coil Selection Datasheet
Customer :
Project Details : MARAKEZ
Reference : FCU-04
Location :
Designer :
Qty .: 5
Created Date: 22/11/2021
INPUT
On Coil Dry On Coil Wet Required
External Static Entering water Leaving Water
Air Flow Bulb Bulb Altitude
Pressure Temperature Temperature Capacity
Temperature Temperature
Inch H2O CFM °F °F °F °F Ft Btu/h
0.12 1200 77 64.4 44 60 0 30000
OUTPUT
Technical Data Unit Data
Fan Data Unit Model : ESNW36 – 4R
Fan Type : Forward Curved Centrifugal Application: (Standard /District Cooling) District Cooling
Size : Inch 8 x 10 Range: (Low Static / High Static) High Static
Quantity : 2 Type: Concealed Ceiling Suspended
Cooling Coil Data Casing Details
Coil Face Area : ft^2 3.26 Galvanized Steel.
Coil Tube Diameter : Inch 3/8 G90 Coated.
Tube Type : Gross Grooved Electrostatic deposited Epoxy Powder Paint.
Tube Material : Copper Performance Data
Fin Type: Corrugated Cooling
Fin Material: Aluminum Speed: High Med Low
Fins Per Inch (FPI) / Rows 14 / 4 Total Cooling Capacity Btu/h 32102 30526 29306
Filter Data General Sensible Capacity Btu/h 24316 23029 22038
Return Air Filter Size : Inch 41.9 x 12.0 x 0.3 SHR 0.757 0.754 0.752
Filter Media: Washable Synthetic HDPE mesh
Air Flow Rate : CFM 1272 1198 1134
Efficiency: 90% down to 50 microns External Static Pressure: 0.12 0.12
Inch H2O 0.12
Quantity: 1 Dry Bulb Entering °F 77 77 77
Electrical Data Air Temperature: Leaving °F 56.7 56.5 56.4
Blower Motor : W 430 Side Entering °F 64.4 64.4
Wet Bulb 64.4
Blower Speed : RPM 1275 Temperature: Leaving °F 55.4 55.22 55.04
Blower Motor FLA : A 2.6 Relative Entering % 50.25 50.25 50.25
Motor Type : AC Motor (PSC) Humidity: Leaving % 91.91 91.88 91.86
Motor Insulation : Class B Entering Water Temp. : °F 44 44 44
Motor IP Rating : IP20 Fluid Leaving Water Temp. : °F 60 60 60
Power Supply Sid Water Flow Rate : GPM 4 3.79 3.65
220-240/1/50Hz Water Pressure Drop : Ft h2o 7.11 6.51 6.06
Sound Data at (1.5m) according to JIS B8616-2006 standard Electric Heater (Optional)
Low Speed Sound Level dB (A) 51 Heating Capacity : kW --
Med Speed Sound Level dB (A) 53
High Speed Sound Level dB (A) 54
Version : 1.0.0 Page 1 of 3
Dimensional Drawings
GENERAL
- Eurovent Certified Chilled Water Fan Coil Units.
- Galvanized Steel Casing.
STANDARD - Efficient Heat Exchangers made of Copper and enhanced Aluminum fins.
- Fan Assembly.
- Auto Air vent.
OPTIONAL - 4 pipes system.
CASING
- Galvanized Steel Sheet of 0.8 - 1.2mm thick - Grade G90
STANDARD - Electrostatic deposited Epoxy Powder Paint.
- Passes salts spray test up to 1000 hours.
INSULATION
- Closed cell Elastomer (6mm thickness for high static units).
STANDARD - Density: 48kg/ m³.
- Fire Self-extinguishing type with flame spread index=25 and smoke developed index=50, comply with NFPA 101
OPTIONAL - Plenum insulation for low static units (3mm thickness).
FAN
- Statically and dynamically balanced for quieter and vibration free operation.
- High Quality Aluminum for high static models and plastic for low static.
STANDARD
- Double inlet, double width centrifugal type.
- Forward curved type.
OPTIONAL - Metallic blowers for low static.
COIL
- AHRI 410 certified coils.
- Housed in galvanized steel frames.
STANDARD - Copper tubes mechanically bonded to aluminum fins.
- Manufactured by state-of-the-Art technology equipment.
- Tested to 350 psig.
- District cooling application.
OPTIONAL
- Hydrophilic fins coating.
DRAIN PAN
- Drain pan is made of 0.8mm thick GI.
STANDARD
- 6mm thick insulation.
- Auxiliary drain pan.
OPTIONAL
- Stainless steel drain pan.
FILTER
PROJECT
MARAKEZ
PRODUCT TYPE:
ITEM REFERANCE:
FCU‐05
ITEM Model:
ESNW42
Chilled Water Fan Coil Selection Datasheet
Customer :
Project Details : MARAKEZ
Reference : FCU-05
Location :
Designer :
Qty .: 8
Created Date: 22/11/2021
INPUT
On Coil Dry On Coil Wet Required
External Static Entering water Leaving Water
Air Flow Bulb Bulb Altitude
Pressure Temperature Temperature Capacity
Temperature Temperature
Inch H2O CFM °F °F °F °F Ft Btu/h
0.12 1350 77 64.4 44 60 0 36000
OUTPUT
Technical Data Unit Data
Fan Data Unit Model : ESNW42 – 4R
Fan Type : Forward Curved Centrifugal Application: (Standard /District Cooling) District Cooling
Size : Inch 8 x 10 Range: (Low Static / High Static) High Static
Quantity : 2 Type: Concealed Ceiling Suspended
Cooling Coil Data Casing Details
Coil Face Area : ft^2 3.7 Galvanized Steel.
Coil Tube Diameter : Inch 3/8 G90 Coated.
Tube Type : Gross Grooved Electrostatic deposited Epoxy Powder Paint.
Tube Material : Copper Performance Data
Fin Type: Corrugated Cooling
Fin Material: Aluminum Speed: High Med Low
Fins Per Inch (FPI) / Rows 14 / 4 Total Cooling Capacity Btu/h 37850 36190 33209
Filter Data General Sensible Capacity Btu/h 28159 26827 24451
Return Air Filter Size : Inch 41.9 x 12.0 x 0.3 SHR 0.744 0.741 0.736
Filter Media: Washable Synthetic HDPE mesh
Air Flow Rate : CFM 1421 1335 1198
Efficiency: 90% down to 50 microns External Static Pressure: 0.12 0.12
Inch H2O 0.12
Quantity: 1 Dry Bulb Entering °F 77 77 77
Electrical Data Air Temperature: Leaving °F 56.5 56.2 56
Blower Motor : W 430 Side Entering °F 64.4 64.4
Wet Bulb 64.4
Blower Speed : RPM 1275 Temperature: Leaving °F 55.22 54.86 54.68
Blower Motor FLA : A 2.6 Relative Entering % 50.25 50.25 50.25
Motor Type : AC Motor (PSC) Humidity: Leaving % 92.06 92.01 91.98
Motor Insulation : Class B Entering Water Temp. : °F 44 44 44
Motor IP Rating : IP20 Fluid Leaving Water Temp. : °F 60 60 60
Power Supply Sid Water Flow Rate : GPM 4.73 4.52 4.15
220-240/1/50Hz Water Pressure Drop : Ft h2o 7.71 7.13 6.14
Sound Data at (1.5m) according to JIS B8616-2006 standard Electric Heater (Optional)
Low Speed Sound Level dB (A) 53 Heating Capacity : kW --
Med Speed Sound Level dB (A) 55
High Speed Sound Level dB (A) 56
Version : 1.0.0 Page 1 of 3
Dimensional Drawings
GENERAL
- Eurovent Certified Chilled Water Fan Coil Units.
- Galvanized Steel Casing.
STANDARD - Efficient Heat Exchangers made of Copper and enhanced Aluminum fins.
- Fan Assembly.
- Auto Air vent.
OPTIONAL - 4 pipes system.
CASING
- Galvanized Steel Sheet of 0.8 - 1.2mm thick - Grade G90
STANDARD - Electrostatic deposited Epoxy Powder Paint.
- Passes salts spray test up to 1000 hours.
INSULATION
- Closed cell Elastomer (6mm thickness for high static units).
STANDARD - Density: 48kg/ m³.
- Fire Self-extinguishing type with flame spread index=25 and smoke developed index=50, comply with NFPA 101
OPTIONAL - Plenum insulation for low static units (3mm thickness).
FAN
- Statically and dynamically balanced for quieter and vibration free operation.
- High Quality Aluminum for high static models and plastic for low static.
STANDARD
- Double inlet, double width centrifugal type.
- Forward curved type.
OPTIONAL - Metallic blowers for low static.
COIL
- AHRI 410 certified coils.
- Housed in galvanized steel frames.
STANDARD - Copper tubes mechanically bonded to aluminum fins.
- Manufactured by state-of-the-Art technology equipment.
- Tested to 350 psig.
- District cooling application.
OPTIONAL
- Hydrophilic fins coating.
DRAIN PAN
- Drain pan is made of 0.8mm thick GI.
STANDARD
- 6mm thick insulation.
- Auxiliary drain pan.
OPTIONAL
- Stainless steel drain pan.
FILTER
PROJECT
MARAKEZ
PRODUCT TYPE:
ITEM REFERANCE:
FCU‐06
ITEM Model:
ESNW60
Chilled Water Fan Coil Selection Datasheet
Customer :
Project Details : MARAKEZ
Reference : FCU-06
Location :
Designer :
Qty .: 2
Created Date: 22/11/2021
INPUT
On Coil Dry On Coil Wet Required
External Static Entering water Leaving Water
Air Flow Bulb Bulb Altitude
Pressure Temperature Temperature Capacity
Temperature Temperature
Inch H2O CFM °F °F °F °F Ft Btu/h
0.12 1600 77 64.4 44 60 0 42000
OUTPUT
Technical Data Unit Data
Fan Data Unit Model : ESNW60 – 4R
Fan Type : Forward Curved Centrifugal Application: (Standard /District Cooling) District Cooling
Size : Inch 8 x 10 Range: (Low Static / High Static) High Static
Quantity : 2 Type: Concealed Ceiling Suspended
Cooling Coil Data Casing Details
Coil Face Area : ft^2 4.81 Galvanized Steel.
Coil Tube Diameter : Inch 3/8 G90 Coated.
Tube Type : Gross Grooved Electrostatic deposited Epoxy Powder Paint.
Tube Material : Copper Performance Data
Fin Type: Corrugated Cooling
Fin Material: Aluminum Speed: High Med Low
Fins Per Inch (FPI) / Rows 14 / 4 Total Cooling Capacity Btu/h 44592 42544 40452
Filter Data General Sensible Capacity Btu/h 33991 32303 30591
Return Air Filter Size : Inch 45.8 x 14.2 x 0.3 SHR 0.762 0.759 0.756
Filter Media: Washable Synthetic HDPE mesh
Air Flow Rate : CFM 1925 1798 1674
Efficiency: 90% down to 50 microns External Static Pressure: 0.12 0.12
Inch H2O 0.12
Quantity: 1 Dry Bulb Entering °F 77 77 77
Electrical Data Air Temperature: Leaving °F 58.3 58.1 57.9
Blower Motor : W 559 Side Entering °F 64.4 64.4
Wet Bulb 64.4
Blower Speed : RPM 1100 Temperature: Leaving °F 57.02 56.84 56.66
Blower Motor FLA : A 5 Relative Entering % 50.25 50.25 50.25
Motor Type : AC Motor (PSC) Humidity: Leaving % 92.46 92.44 92.42
Motor Insulation : Class B Entering Water Temp. : °F 44 44 44
Motor IP Rating : IP20 Fluid Leaving Water Temp. : °F 60 60 60
Power Supply Sid Water Flow Rate : GPM 5.55 5.3 5.07
220-240/1/50Hz Water Pressure Drop : Ft h2o 7.41 6.82 6.25
Sound Data at (1.5m) according to JIS B8616-2006 standard Electric Heater (Optional)
Low Speed Sound Level dB (A) 53 Heating Capacity : kW --
Med Speed Sound Level dB (A) 56
High Speed Sound Level dB (A) 58
Version : 1.0.0 Page 1 of 3
Dimensional Drawings
GENERAL
- Eurovent Certified Chilled Water Fan Coil Units.
- Galvanized Steel Casing.
STANDARD - Efficient Heat Exchangers made of Copper and enhanced Aluminum fins.
- Fan Assembly.
- Auto Air vent.
OPTIONAL - 4 pipes system.
CASING
- Galvanized Steel Sheet of 0.8 - 1.2mm thick - Grade G90
STANDARD - Electrostatic deposited Epoxy Powder Paint.
- Passes salts spray test up to 1000 hours.
INSULATION
- Closed cell Elastomer (6mm thickness for high static units).
STANDARD - Density: 48kg/ m³.
- Fire Self-extinguishing type with flame spread index=25 and smoke developed index=50, comply with NFPA 101
OPTIONAL - Plenum insulation for low static units (3mm thickness).
FAN
- Statically and dynamically balanced for quieter and vibration free operation.
- High Quality Aluminum for high static models and plastic for low static.
STANDARD
- Double inlet, double width centrifugal type.
- Forward curved type.
OPTIONAL - Metallic blowers for low static.
COIL
- AHRI 410 certified coils.
- Housed in galvanized steel frames.
STANDARD - Copper tubes mechanically bonded to aluminum fins.
- Manufactured by state-of-the-Art technology equipment.
- Tested to 350 psig.
- District cooling application.
OPTIONAL
- Hydrophilic fins coating.
DRAIN PAN
- Drain pan is made of 0.8mm thick GI.
STANDARD
- 6mm thick insulation.
- Auxiliary drain pan.
OPTIONAL
- Stainless steel drain pan.
FILTER
PROJECT
MARAKEZ
PRODUCT TYPE:
ITEM REFERANCE:
FCU‐07
ITEM Model:
ESNW60
Chilled Water Fan Coil Selection Datasheet
Customer :
Project Details : MARAKEZ
Reference : FCU-07
Location :
Designer :
Qty .: 6
Created Date: 22/11/2021
INPUT
On Coil Dry On Coil Wet Required
External Static Entering water Leaving Water
Air Flow Bulb Bulb Altitude
Pressure Temperature Temperature Capacity
Temperature Temperature
Inch H2O CFM °F °F °F °F Ft Btu/h
0.12 1800 77.0 64.4 44 60 0 48000
OUTPUT
Technical Data Unit Data
Fan Data Unit Model : ESNW60 – 4R
Fan Type : Forward Curved Centrifugal Application: (Standard /District Cooling) District Cooling
Size : Inch 8 x 10 Range: (Low Static / High Static) High Static
Quantity : 2 Type: Concealed Ceiling Suspended
Cooling Coil Data Casing Details
Coil Face Area : ft^2 4.81 Galvanized Steel.
Coil Tube Diameter : Inch 3/8 G90 Coated.
Tube Type : Gross Grooved Electrostatic deposited Epoxy Powder Paint.
Tube Material : Copper Performance Data
Fin Type: Corrugated Cooling
Fin Material: Aluminum Speed: High Med Low
Fins Per Inch (FPI) / Rows 14 / 4 Total Cooling Capacity Btu/h 50349 48118 45832
Filter Data General Sensible Capacity Btu/h 36551 34793 33005
Return Air Filter Size : Inch 45.8 x 14.2 x 0.3 SHR 0.726 0.723 0.72
Filter Media: Washable Synthetic HDPE mesh
Air Flow Rate : CFM 1925 1798 1674
Efficiency: 90% down to 50 microns External Static Pressure: 0.12 0.12
Inch H2O 0.12
Quantity: 1 Dry Bulb Entering °F 77.0 77.0 77.0
Electrical Data Air Temperature: Leaving °F 57.7 57.5 57.2
Blower Motor : 559 Side 64.4 64.4
W Wet Bulb Entering °F 64.4
Blower Speed : RPM 1100 Temperature: Leaving °F 56.38 56.2 55.84
Blower Motor FLA : A 5 Relative Entering % 50.25 50.25 50.25
Motor Type : AC Motor (PSC) Humidity: Leaving % 92.40 91.10 91.90
Motor Insulation : Class B Entering Water Temp. : °F 44 44 44
Motor IP Rating : IP20 Fluid Leaving Water Temp. : °F 60 60 60
Power Supply Sid Water Flow Rate : GPM 6.28 5.99 5.73
220-240/1/50Hz Water Pressure Drop : Ft h2o 9.14 8.44 7.75
Sound Data at (1.5m) according to JIS B8616-2006 standard Electric Heater (Optional)
Low Speed Sound Level dB (A) 53 Heating Capacity : kW --
Med Speed Sound Level dB (A) 56
High Speed Sound Level dB (A) 58
Version : 1.0.0 Page 1 of 3
Dimensional Drawings
GENERAL
- Eurovent Certified Chilled Water Fan Coil Units.
- Galvanized Steel Casing.
STANDARD - Efficient Heat Exchangers made of Copper and enhanced Aluminum fins.
- Fan Assembly.
- Auto Air vent.
OPTIONAL - 4 pipes system.
CASING
- Galvanized Steel Sheet of 0.8 - 1.2mm thick - Grade G90
STANDARD - Electrostatic deposited Epoxy Powder Paint.
- Passes salts spray test up to 1000 hours.
INSULATION
- Closed cell Elastomer (6mm thickness for high static units).
STANDARD - Density: 48kg/ m³.
- Fire Self-extinguishing type with flame spread index=25 and smoke developed index=50, comply with NFPA 101
OPTIONAL - Plenum insulation for low static units (3mm thickness).
FAN
- Statically and dynamically balanced for quieter and vibration free operation.
- High Quality Aluminum for high static models and plastic for low static.
STANDARD
- Double inlet, double width centrifugal type.
- Forward curved type.
OPTIONAL - Metallic blowers for low static.
COIL
- AHRI 410 certified coils.
- Housed in galvanized steel frames.
STANDARD - Copper tubes mechanically bonded to aluminum fins.
- Manufactured by state-of-the-Art technology equipment.
- Tested to 350 psig.
- District cooling application.
OPTIONAL
- Hydrophilic fins coating.
DRAIN PAN
- Drain pan is made of 0.8mm thick GI.
STANDARD
- 6mm thick insulation.
- Auxiliary drain pan.
OPTIONAL
- Stainless steel drain pan.
FILTER
PROJECT
MARAKEZ
PRODUCT TYPE:
ITEM REFERANCE:
FCU‐08
ITEM Model:
ESNW72
Chilled Water Fan Coil Selection Datasheet
Customer :
Project Details : MARAKEZ
Reference : FCU-08
Location :
Designer :
Qty .: 7
Created Date: 22/11/2021
INPUT
On Coil Dry On Coil Wet Required
External Static Entering water Leaving Water
Air Flow Bulb Bulb Altitude
Pressure Temperature Temperature Capacity
Temperature Temperature
Inch H2O CFM °F °F °F °F Ft Btu/h
0.12 2000 77.0 64.4 44 60 0 54000
OUTPUT
Technical Data Unit Data
Fan Data Unit Model : ESNW72 – 4R
Fan Type : Forward Curved Centrifugal Application: (Standard /District Cooling) District Cooling
Size : Inch 8 x 10 Range: (Low Static / High Static) High Static
Quantity : 2 Type: Concealed Ceiling Suspended
Cooling Coil Data Casing Details
Coil Face Area : ft^2 4.81 Galvanized Steel.
Coil Tube Diameter : Inch 3/8 G90 Coated.
Tube Type : Gross Grooved Electrostatic deposited Epoxy Powder Paint.
Tube Material : Copper Performance Data
Fin Type: Corrugated Cooling
Fin Material: Aluminum Speed: High Med Low
Fins Per Inch (FPI) / Rows 14 / 4 Total Cooling Capacity Btu/h 57223 54856 52564
Filter Data General Sensible Capacity Btu/h 41182 39323 37536
Return Air Filter Size : Inch 45.8 x 14.2 x 0.3 SHR 0.72 0.717 0.714
Filter Media: Washable Synthetic HDPE mesh
Air Flow Rate : CFM 2276 2153 2025
Efficiency: 90% down to 50 microns External Static Pressure: 0.12 0.12
Inch H2O 0.12
Quantity: 1 Dry Bulb Entering °F 77.0 77.0 77.0
Electrical Data Air Temperature: Leaving °F 58.4 58.2 57.8
Blower Motor : 559 Side 64.4 64.4
W Wet Bulb Entering °F 64.4
Blower Speed : RPM 1100 Temperature: Leaving °F 57.1 56.92 56.56
Blower Motor FLA : A 5 Relative Entering % 50.25 50.25 50.25
Motor Type : AC Motor (PSC) Humidity: Leaving % 92.6 92.58 92.90
Motor Insulation : Class B Entering Water Temp. : °F 44 44 44
Motor IP Rating : IP20 Fluid Leaving Water Temp. : °F 60 60 60
Power Supply Sid Water Flow Rate : GPM 7.11 6.87 6.56
220-240/1/50Hz Water Pressure Drop : Ft h2o 10.71 9.94 9.22
Sound Data at (1.5m) according to JIS B8616-2006 standard Electric Heater (Optional)
Low Speed Sound Level dB (A) 55 Heating Capacity : kW --
Med Speed Sound Level dB (A) 59
High Speed Sound Level dB (A) 61
Version : 1.0.0 Page 1 of 3
Dimensional Drawings
GENERAL
- Eurovent Certified Chilled Water Fan Coil Units.
- Galvanized Steel Casing.
STANDARD - Efficient Heat Exchangers made of Copper and enhanced Aluminum fins.
- Fan Assembly.
- Auto Air vent.
OPTIONAL - 4 pipes system.
CASING
- Galvanized Steel Sheet of 0.8 - 1.2mm thick - Grade G90
STANDARD - Electrostatic deposited Epoxy Powder Paint.
- Passes salts spray test up to 1000 hours.
INSULATION
- Closed cell Elastomer (6mm thickness for high static units).
STANDARD - Density: 48kg/ m³.
- Fire Self-extinguishing type with flame spread index=25 and smoke developed index=50, comply with NFPA 101
OPTIONAL - Plenum insulation for low static units (3mm thickness).
FAN
- Statically and dynamically balanced for quieter and vibration free operation.
- High Quality Aluminum for high static models and plastic for low static.
STANDARD
- Double inlet, double width centrifugal type.
- Forward curved type.
OPTIONAL - Metallic blowers for low static.
COIL
- AHRI 410 certified coils.
- Housed in galvanized steel frames.
STANDARD - Copper tubes mechanically bonded to aluminum fins.
- Manufactured by state-of-the-Art technology equipment.
- Tested to 350 psig.
- District cooling application.
OPTIONAL
- Hydrophilic fins coating.
DRAIN PAN
- Drain pan is made of 0.8mm thick GI.
STANDARD
- 6mm thick insulation.
- Auxiliary drain pan.
OPTIONAL
- Stainless steel drain pan.
FILTER
PROJECT
MARAKEZ
PRODUCT TYPE:
ITEM REFERANCE:
FCU‐09
ITEM Model:
ESNW72
Chilled Water Fan Coil Selection Datasheet
Customer :
Project Details : MARAKEZ
Reference : FCU-09
Location :
Designer :
Qty .: 14
Created Date: 22/11/2021
INPUT
On Coil Dry On Coil Wet Required
External Static Entering water Leaving Water
Air Flow Bulb Bulb Altitude
Pressure Temperature Temperature Capacity
Temperature Temperature
Inch H2O CFM °F °F °F °F Ft Btu/h
0.3 2000 77.0 64.4 44 60 0 54000
OUTPUT
Technical Data Unit Data
Fan Data Unit Model : ESNW72 – 4R
Fan Type : Forward Curved Centrifugal Application: (Standard /District Cooling) District Cooling
Size : Inch 8 x 10 Range: (Low Static / High Static) High Static
Quantity : 2 Type: Concealed Ceiling Suspended
Cooling Coil Data Casing Details
Coil Face Area : ft^2 4.81 Galvanized Steel.
Coil Tube Diameter : Inch 3/8 G90 Coated.
Tube Type : Gross Grooved Electrostatic deposited Epoxy Powder Paint.
Tube Material : Copper Performance Data
Fin Type: Corrugated Cooling
Fin Material: Aluminum Speed: High Med Low
Fins Per Inch (FPI) / Rows 14 / 4 Total Cooling Capacity Btu/h 56554 54111 51614
Filter Data General Sensible Capacity Btu/h 39889 38015 36114
Return Air Filter Size : Inch 45.8 x 14.2 x 0.3 SHR 0.705 0.703 0.7
Filter Media: Washable Synthetic HDPE mesh
Air Flow Rate : CFM 2113 2001 1874
Efficiency: 90% down to 50 microns External Static Pressure: 0.3 0.3
Inch H2O 0.3
Quantity: 1 Dry Bulb Entering °F 77.0 77.0 77.0
Electrical Data Air Temperature: Leaving °F 58.1 58 57.8
Blower Motor : 559 Side 64.4 64.4
W Wet Bulb Entering °F 64.4
Blower Speed : RPM 1100 Temperature: Leaving °F 56.92 56.74 56.56
Blower Motor FLA : A 5 Relative Entering % 50.25 50.25 50.25
Motor Type : AC Motor (PSC) Humidity: Leaving % 93.10 92.60 92.90
Motor Insulation : Class B Entering Water Temp. : °F 44 44 44
Motor IP Rating : IP20 Fluid Leaving Water Temp. : °F 60 60 60
Power Supply Sid Water Flow Rate : GPM 7.03 6.78 6.45
220-240/1/50Hz Water Pressure Drop : Ft h2o 10.43 9.65 8.88
Sound Data at (1.5m) according to JIS B8616-2006 standard Electric Heater (Optional)
Low Speed Sound Level dB (A) 55 Heating Capacity : kW --
Med Speed Sound Level dB (A) 59
High Speed Sound Level dB (A) 61
Version : 1.0.0 Page 1 of 3
Dimensional Drawings
GENERAL
- Eurovent Certified Chilled Water Fan Coil Units.
- Galvanized Steel Casing.
STANDARD - Efficient Heat Exchangers made of Copper and enhanced Aluminum fins.
- Fan Assembly.
- Auto Air vent.
OPTIONAL - 4 pipes system.
CASING
- Galvanized Steel Sheet of 0.8 - 1.2mm thick - Grade G90
STANDARD - Electrostatic deposited Epoxy Powder Paint.
- Passes salts spray test up to 1000 hours.
INSULATION
- Closed cell Elastomer (6mm thickness for high static units).
STANDARD - Density: 48kg/ m³.
- Fire Self-extinguishing type with flame spread index=25 and smoke developed index=50, comply with NFPA 101
OPTIONAL - Plenum insulation for low static units (3mm thickness).
FAN
- Statically and dynamically balanced for quieter and vibration free operation.
- High Quality Aluminum for high static models and plastic for low static.
STANDARD
- Double inlet, double width centrifugal type.
- Forward curved type.
OPTIONAL - Metallic blowers for low static.
COIL
- AHRI 410 certified coils.
- Housed in galvanized steel frames.
STANDARD - Copper tubes mechanically bonded to aluminum fins.
- Manufactured by state-of-the-Art technology equipment.
- Tested to 350 psig.
- District cooling application.
OPTIONAL
- Hydrophilic fins coating.
DRAIN PAN
- Drain pan is made of 0.8mm thick GI.
STANDARD
- 6mm thick insulation.
- Auxiliary drain pan.
OPTIONAL
- Stainless steel drain pan.
FILTER
This document is valid at the date of issue - Check the current validity on:
Document valable à la date d’émission - Vérifier la validité en cours sur :
www.eurovent-certification.com
Participant/Titulaire
AWAL GULF MANUFACTURING Co., B.S.C. (c)
Building No:429, Road-108, Block:601 - Sitra Industrial Area
15919 Manama, Bahrain
This certificate is issued by Eurovent Certita Certification Ce certificat est délivré par Eurovent Certita Certification dans
according to the certification rules: les conditions fixées par le référentiel :
ECP FCU - « Fan Coil Units » in force at established ECP FCU – « Ventilo-convecteurs » en vigueur à date
date. d’édition.
Pursuant to the decision notified by Eurovent Certita En vertu de la décision notifiée par Eurovent Certita
Certification, the right to use the mark ECP shall be Certification, le droit d'usage de la marque ECP, est accordé à
granted to the beneficiary company for all products la société qui en est bénéficiaire pour les tous les produits
inside the defined scope according to “certify-all” entrant dans le champ d'application défini selon le principe
principle and in the conditions defined by the “certify-all” et dans les conditions définies par le programme
certification program mentioned. de certification mentionné.
Unless withdrawn or suspended, this certificate remains Sauf retrait ou suspension, ce certificat demeure valide tant
valid as long as the requirements for the certification que les conditions du référentiel du programme de certification
program framework are met. The validity of the sont respectées. La validité du certificat est à vérifier sur le site
certificate is to be verified on www.eurovent- Internet www.eurovent-certification.com
certification.com
CE CERTIFICAT A ÉTÉ EMIS LE 31/10/2019
THIS CERTIFICATE HAS BEEN ISSUED ON 31/10/2019 CE CERTIFICAT EST VALIDE JUSQU’AU 31/08/2020
THIS CERTIFICATE IS VALID UNTIL 31/08/2020
1/2
EUROVENT CERTITA CERTIFICATION SAS au capital de 100 000 € - 48-50 rue de la Victoire 75009 Paris - FRANCE
Tel. : 33 (0)1 75 44 71 71 - 513 133 637 RCS Paris - SIRET 513 133 637 000 35 - TVA FR 59513133637
S06 D06 TEMPLATE_ECP_Certify_All_Rev1.0
CERTIFICATE
N° 11.12.002
Appendix / Annexe
Granted on December 6, 2011 - Date 1ère admission 6 décembre 2011
This document is valid at the date of issue - Check the current validity on:
Document valable à la date d’émission - Vérifier la validité en cours sur :
www.eurovent-certification.com
2/2
EUROVENT CERTITA CERTIFICATION SAS au capital de 100 000 € - 48-50 rue de la Victoire 75009 Paris - FRANCE
Tel. : 33 (0)1 75 44 71 71 - 513 133 637 RCS Paris - SIRET 513 133 637 000 35 - TVA FR 59513133637
S06 D06 TEMPLATE_ECP_Certify_All_Rev1.0
Certificate of Product Ratings
AHRI Certified Reference Number : 203989075 Date : 08-01-2019 Model Status : Active
Header : 0.877;1.125;1.374;1.625;2.125;2.625;3.125;3.622;4.125;5.118;6.125;8.125
Tube Spacing across Coil Face (Stf) X Tube Spacing between Coil Rows (Str) : 25.400 X 22.000
Manufacturing Location : Awal Gulf Manufacturing Co. B.S.C (c) - Manama, Bahrain
Rated as follows in accordance with the latest edition of AHRI Standard 410 Forced-Circulation Air-Cooling and Air-Heating Coils and
subject to rating accuracy by AHRI-sponsored, independent, third party testing:
Software Version : 8
†"Active" Model Status are those that an AHRI Certification Program Participant is currently producing AND selling or offering for sale; OR new models that are being
†
marketed but are not yet being produced.“Production Stopped” Model Status are those that an AHRI Certification Program Participant is no longer producing BUT is still
selling or offering for sale.
Ratings that are accompanied by WAS indicate an involuntary re-rate. The new published rating is shown along with the previous (i.e. WAS) rating.
DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2019 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 132091464124346188
RANGE
TYPE NEMA frame Motor Diameter Construction Rating (HP) No. of Poles
FR 29 42 125 mm Shell 1/30 to 1/3 4.6
FR 39 48 142 mm Shell 1/10 to 1 4,6,8
Superlon Certified
Status
UL 2818 - 2013 Gold Standard for Chemical Emissions for Building Materials, Finishes and Furnishings
Product tested in accordance with UL 2821 test method to show compliance to emission limits on UL 2818. Section 7.1 and 7.2.
UL investigated representative samples of the identified Product(s) to the identified Standard(s) or other requirements in accordance with the agreements and any applicable program service terms in place between UL and the Certificate Holder (collectively
“Agreement”). The Certificate Holder is authorized to use the UL Mark for the identified Product(s) manufactured at the production site(s) covered by the UL Test Report, in accordance with the terms of the Agreement. This Certificate is valid for the identified
dates unless there is non-compliance with the Agreement.
GREENGUARD Gold Certification Criteria for Building Products and Interior Finishes
Maximum Allowable
Criteria CAS Number Predicted Concentration Units
TVOC (A) - 0.22 mg/m³
Formaldehyde 50-00-0 9 (7.3 ppb) µg/m³
Total Aldehydes (B) - 0.043 ppm
4-Phenylcyclohexene 4994-16-5 6.5 µg/m³
Particle Matter less than 10 µm (C) - 20 µg/m³
1-Methyl-2-pyrrolidinone (D) 872-50-4 160 µg/m³
1/2 CREL
Individual VOCs (E) - or -
1/100th TLV
(A) Defined to be the total response of measured VOCs falling within the C6 – C16 range, with responses calibrated to a toluene surrogate. Maximum
allowable predicted TVOC concentrations for GREENGUARD Gold (0.22 mg/m ³) fall in the range of 0.5 mg/m³ or less, as specified in CDPH Standard
Method v1.2.
(B) The sum of all measured normal aldehydes from formaldehyde through nonanal, plus benzaldehyde, individually calibrated to a compound specific
standard. Heptanal through nonanal are measured via TD/GC/MS analysis and the remaining aldehydes are measured using HPLC/UV analysis.
(C) Particle emission requirement only applicable to HVAC Duct Products with exposed surface area in air streams (a forced air test with specific test
method) and for wood finishing (sanding) systems.
(D) Based on the CA Prop 65 Maximum Allowable Dose Level for inhalation of 3,200 ʅg/day and an inhalation rate of 20 m³/day
(E) Allowable levels for chemicals not listed are derived from the lower of 1/2 the California Office of Environmental Health Hazard Assessment (OEHHA)
Chronic Reference Exposure Level (CREL) as required per the CDPH/EHLB/Standard Method v1.2 and BIFMA level credit 7.6.2 and 1/100th of the
Threshold Limit Value (TLV) industrial work place standard (Reference: American Conference of Government Industrial Hygienists, 6500 Glenway,
Building D-7, and Cincinnati, OH 45211-4438).
UL investigated representative samples of the identified Product(s) to the identified Standard(s) or other requirements in accordance with the agreements and any applicable program service terms in place between UL and the Certificate Holder (collectively
“Agreement”). The Certificate Holder is authorized to use the UL Mark for the identified Product(s) manufactured at the production site(s) covered by the UL Test Report, in accordance with the terms of the Agreement. This Certificate is valid for the identified
dates unless there is non-compliance with the Agreement.
105-LB-TEST
Test
Type of Activity Test Name Test Method
Materials/Products
info@eiac.gov.ae
www.eiac.gov.ae
P. O. Box Dubai 67
1 of 1
Office +97143027445 Fax +97143362381
Accreditation Scope
Performance Testing of Electrical Appliances Testing
105-LB-TEST
Awal Gulf Testing Laboratory
Test
Type of Activity Test Name Test Method
Materials/Products
Performance Testing for Unitary Package Air- Energy labeling and SASO 2681
Capacity and Energy conditioners & heat minimum energy
Efficiency of Air pumps, and Central split performance
Conditioners and Heat Air-conditioners & heat requirements for air
Pumps pumps. conditioners and Heat
pumps
info@eiac.gov.ae
www.eiac.gov.ae
P. O. Box Dubai 67
2 of 2
Office +97143027445 Fax +97143362381
Accreditation Scope
Performance Testing of Electrical Appliances Testing
105-LB-TEST
Awal Gulf Testing Laboratory
Test
Type of Activity Test Name Test Method
Materials/Products
Performance Testing for Unitary Package Air- Air Conditioners – SASO 2874
Capacity and Energy conditioners & heat Minimum Energy
Efficiency of Air pumps, and Central split Performance
Conditioners and Heat Air-conditioners & heat Requirements and
Pumps pumps. Testing Requirements
info@eiac.gov.ae
www.eiac.gov.ae
P. O. Box Dubai 67
3 of 3
Office +97143027445 Fax +97143362381
Accreditation Scope
Performance Testing of Electrical Appliances Testing
105-LB-TEST
Awal Gulf Testing Laboratory
Test
Type of Activity Test Name Test Method
Materials/Products
Performance Testing for Energy Efficiency Lable Heating Tests ES 3795 Part 1
Capacity and Energy Requirements For Air
Efficiency of Air Conditioner Part 1: -
Conditioners and Heat Room Air Conditioner
Pumps (Window - Split) with
Fixed Capacity & With
Fixed Speed Compressor
info@eiac.gov.ae
www.eiac.gov.ae
P. O. Box Dubai 67
4 of 4
Office +97143027445 Fax +97143362381
Accreditation Scope
Performance Testing of Electrical Appliances Testing
105-LB-TEST
Awal Gulf Testing Laboratory
Test
Type of Activity Test Name Test Method
Materials/Products
Performance Testing for Energy Efficiency Lable Energy labeling and ES 3795 Part 5
Capacity and Energy Requirements For Air minimum energy
Efficiency of Air Conditioner Part 5: - performance
Conditioners and Heat Fixed Capacity Ducted requirements for air
Pumps Room Air Conditioner conditioners and Heat
With Fixed Speed pumps
Compressor
Accreditation History
3 First issuance under the name of EIAC (Which was formerly 21-11-2018
known as DAC)
info@eiac.gov.ae
www.eiac.gov.ae
P. O. Box Dubai 67
5 of 5
Office +97143027445 Fax +97143362381
MANAGEMENT SYSTEM
CERTIFICATE
Certificate No: Initial certification date: Valid:
109018-2012-AQ-ARE-RvA 05 May 1997 09 December 2020 - 08 December 2023
Amit Bhatia
Management Representative
Lack of fulfilment of conditions as set out in the Certification Agreement may render this Certificate invalid.
ACCREDITED UNIT: DNV GL Business Assurance B.V., Zwolseweg 1, 2994 LB, Barendrecht, Netherlands. TEL:+31(0)102922689.
www.dnvgl.com/assurance
MANAGEMENT SYSTEM
CERTIFICATE
Certificate No: Initial certification date: Valid:
109016-2012-AE-ARE-RvA 08 December 2005 09 December 2020 - 08 December 2023
Amit Bhatia
Management Representative
Lack of fulfilment of conditions as set out in the Certification Agreement may render this Certificate invalid.
ACCREDITED UNIT: DNV GL Business Assurance B.V., Zwolseweg 1, 2994 LB, Barendrecht, Netherlands. TEL:+31(0)102922689.
www.dnvgl.com/assurance
MANAGEMENT SYSTEM
CERTIFICATE
Certificate No: Initial certification date: Valid:
248349-2017-AHSO-ARE-RvA 04 December 2017 05 December 2020 - 04 December 2023
has been found to conform to the Occupational Health and Safety Management