CMS Full Guide
CMS Full Guide
CMS Full Guide
User Manual
CMS User Guide
NOJA-559-23
Revision History
21 AM 19-03-19 CMS 3.9 – CMS support for Relay Firmware Version RLM v1.12 or higher,
Updates to SNTP, Added ROCOF, VVS, PMU settings and RC20 support.
(Firmware 1.23).
22 BOS 4-12-19 CMS 3.10 - CMS settings added for Circuit Breaker Fail (CBF) and
Default Ethernet Port Gateway Priority settings. (Firmware 1.24.0.0)
23 EB 28-04-20 VVS, ROCOF added. Multi Master, Directional protection added.
NOJA Power® and OSM® are registered trademarks of NOJA Power Switchgear Pty Ltd. This
document is copyright and is intended for users and distributors of NOJA Power Switchgear product. It
contains information that is the intellectual property of NOJA Power Switchgear and the document, or any
part thereof, should not be copied or reproduced in any form without written permission from NOJA Power
Switchgear.
NOJA Power® and OSM® are registered trademarks of NOJA Power Switchgear and should not be
reproduced or used in any way without written authorisation.
NOJA Power Switchgear applies a policy of ongoing development and reserves the right to change
product without notice. NOJA Power Switchgear does not accept any responsibility for loss or damage
incurred as a result of acting or refraining from action based on information in this User Manual.
Table Of Contents
1 Introduction .................................................................................................................... 5
1.1 Installation ............................................................................................................... 5
1.2 Software Features ................................................................................................... 6
1.3 About CMS.............................................................................................................. 7
2 Main Window and Menus ............................................................................................... 8
2.1 Saving Settings ......................................................................................................13
3 View ..............................................................................................................................14
4 Working with Devices ....................................................................................................18
4.1 Creating New Devices ............................................................................................19
4.2 Device Location......................................................................................................22
4.3 Attachments for Devices ........................................................................................23
4.4 Connection Status ..................................................................................................24
4.5 Importing Devices or Logs ......................................................................................25
4.5.1 Import Device ..................................................................................................25
4.5.2 Import Logs .....................................................................................................29
4.6 Exporting Devices ..................................................................................................32
4.7 Import Offline Settings ............................................................................................33
4.8 Exporting Offline Settings .......................................................................................35
4.9 Copy Device Settings .............................................................................................37
4.10 Compare Settings ..................................................................................................42
4.11 Firmware Update....................................................................................................48
4.12 Print Wizard ...........................................................................................................49
5 Connection Tab .............................................................................................................54
5.1 Online/Offline .........................................................................................................54
5.2 Uploading Settings from the Device .......................................................................55
5.3 Downloading Settings to the Device .......................................................................55
5.4 Settings History ......................................................................................................57
6 Viewing Field Readings .................................................................................................58
6.1 System Status ........................................................................................................58
6.2 Event Log ...............................................................................................................60
6.3 Change Log ...........................................................................................................61
6.4 Close Open Operations Log ...................................................................................62
6.5 Load Profile ............................................................................................................65
6.6 Counters ................................................................................................................66
6.7 Comms Status........................................................................................................66
6.8 Navigation Features for Logs .................................................................................67
6.8.1 Sorting ............................................................................................................68
6.8.2 Grouping .........................................................................................................68
6.8.3 Filter Editor......................................................................................................69
6.8.4 Searching ........................................................................................................71
7 Offline Settings ..............................................................................................................73
7.1 Protection Settings .................................................................................................73
7.1.1 Single Triple Devices.......................................................................................77
7.1.2 Protection Curves............................................................................................78
7.1.3 Curve Selection ...............................................................................................80
7.1.4 Creating a User Defined Curve .......................................................................81
7.1.5 Yn Operation Settings .....................................................................................85
7.1.6 Sectionaliser Mode..........................................................................................86
7.1.7 Frequency and Voltage Protection ..................................................................88
7.1.8 Live Line..........................................................................................................92
NOJA-559-23
9 Control ........................................................................................................................149
9.1 Single Triple .........................................................................................................149
10 Online Operations ....................................................................................................150
10.1 Erase Data ...........................................................................................................150
10.2 Reset ...................................................................................................................151
10.3 Synchronise Date & Time .....................................................................................151
10.4 Device Control & Configuration ............................................................................151
10.5 External Load On/Off............................................................................................152
10.6 I/O Configuration ..................................................................................................152
10.7 Set Life Time Counters.........................................................................................152
10.8 ACO Configuration ...............................................................................................153
10.9 Change Switchgear Type .....................................................................................153
10.10 Test Mode.........................................................................................................154
10.11 COMMS Diagnostic ..........................................................................................154
10.12 Battery Test - Manual .......................................................................................154
10.13 Logic Channel 17-32 Write Protect ...................................................................155
10.14 Change RC Password ......................................................................................155
10.15 DNP3 Security Authentication (DNP3-SA) ........................................................156
10.16 Auto Syncroniser ..............................................................................................156
10.17 Starting a Simulation.........................................................................................158
11 Libraries ...................................................................................................................159
11.1 Creating a New TCC ............................................................................................159
11.2 TCC Library ..........................................................................................................160
11.3 Open a TCC item .................................................................................................161
11.4 Import a TCC file ..................................................................................................162
11.5 Export TCC ..........................................................................................................163
11.6 Standard Curves ..................................................................................................164
11.7 Creating a New TCC group ..................................................................................165
11.8 Simulator Module .................................................................................................165
11.9 Creating a New Simulation ...................................................................................168
11.10 Simulation Library .............................................................................................171
11.11 Open a Simulation ............................................................................................171
11.12 Import a Simulation file .....................................................................................172
11.13 Export a Simulation...........................................................................................174
12 CMS Administration .................................................................................................176
12.1 System Properties ................................................................................................176
12.2 Licences ...............................................................................................................177
12.3 User Management ................................................................................................180
12.3.1 Adding New Users ........................................................................................180
12.3.2 Editing User Settings .....................................................................................182
12.4 Backup Database .................................................................................................183
12.5 Restore a database ..............................................................................................184
12.6 Generate DNP3 Key.............................................................................................185
12.7 Smart Grid Automation .........................................................................................188
NOJA-559-23
Table Of Figures
FIGURE 110: LIVE LINE SETTINGS FOR OC, NPS, EF, SEF ................................................................................................. 92
FIGURE 111: COMMON TAB ........................................................................................................................................ 93
FIGURE 112: HARMONICS SETTINGS.............................................................................................................................. 94
FIGURE 113: SYSTEM SETTINGS .................................................................................................................................... 95
FIGURE 114: SYSTEM SETTINGS- MEASUREMENT ............................................................................................................. 95
FIGURE 115: UPS SETTINGS ........................................................................................................................................ 96
FIGURE 116: BATTERY TEST ......................................................................................................................................... 96
FIGURE 117: REAL TIME CLOCK .................................................................................................................................... 97
FIGURE 118 OPERATOR PANEL - ACTIVE KEY CONFIGURATION 1 ........................................................................................ 97
FIGURE 119: ACTIVE KEY CONFIGURATION ..................................................................................................................... 98
FIGURE 120: ACTIVE KEY CONFIGURATION OPTIONS ........................................................................................................ 98
FIGURE 121: FAST KEY CONFIGURATION LABELS .............................................................................................................. 99
FIGURE 122: SWITCHGEAR CONFIGURATION FOR 3-PHASE DEVICE ..................................................................................... 99
FIGURE 123: PHASE TO PHASE TRIPPING ........................................................................................................................ 99
FIGURE 124: FAULT FLAGS ........................................................................................................................................ 100
FIGURE 125: GPS SETTINGS ...................................................................................................................................... 100
FIGURE 126: SNTP SETTINGS .................................................................................................................................... 101
FIGURE 127: CIRCUIT BREAKER FAIL SETTINGS .............................................................................................................. 101
FIGURE 128: LOAD PROFILE CONFIGURATION ............................................................................................................... 102
FIGURE 129: CO-GENERATION ................................................................................................................................... 103
FIGURE 130: FAULT LOCATOR .................................................................................................................................... 104
FIGURE 131: SWITCHGEAR CALIBRATION...................................................................................................................... 105
FIGURE 132: SWITCHGEAR CALIBRATION - SINGLE TRIPLE................................................................................................ 105
FIGURE 133: DEMONSTRATION BOX SETTINGS – STANDARD ............................................................................................ 106
FIGURE 134: DEMONSTRATION BOX SETTINGS - SINGLE TRIPLE ........................................................................................ 107
FIGURE 135: I/O MODULE CONFIGURATION SCREEN ..................................................................................................... 107
FIGURE 136: LOCAL INPUTS CONFIGURATION ............................................................................................................... 109
FIGURE 137: LOGIC EXPRESSION SCREEN ..................................................................................................................... 110
FIGURE 138: LOGIC EXPRESSION WINDOW................................................................................................................... 110
FIGURE 139 ANALOGUES .......................................................................................................................................... 112
FIGURE 140: DYNAMIC DATA TYPES............................................................................................................................ 113
FIGURE 141 SMART GRID AUTOMATION ...................................................................................................................... 114
FIGURE 142: IMPORTING FBOOT FILE-1........................................................................................................................ 115
FIGURE 143: IMPORTING FBOOT FILE- 2 ....................................................................................................................... 115
FIGURE 144: REMOVING FBOOT FILE ........................................................................................................................... 116
FIGURE 145: ALERTS ................................................................................................................................................ 117
FIGURE 146: SELECTING A NEW ALERT ......................................................................................................................... 118
FIGURE 147: ENABLING A NEW ALERT ......................................................................................................................... 119
FIGURE 148: ENABLING AND CONFIGURING A PROTOCOL................................................................................................. 120
FIGURE 149: DNP3 PROTOCOL SETTINGS .................................................................................................................... 120
FIGURE 150: DNP3-SA CONFIGURATION .................................................................................................................... 121
FIGURE 151: SECURITY STATISTICS PAGE ...................................................................................................................... 122
FIGURE 152: IEC 60870-5-101/104 PROTOCOL SETTINGS ........................................................................................... 122
FIGURE 153: IEC 60870-5-101/104 PROTOCOL SETTINGS ........................................................................................... 123
FIGURE 154: MULTI MASTER CAPABILITIES TO IEC 60870-5 ........................................................................................... 124
FIGURE 155: IEC 61850 – ENABLING MMS AND GOOSE ............................................................................................. 125
FIGURE 156: IMPORTING A *.CID OR *.ICD FILE – 1 ........................................................................................................ 126
FIGURE 157: IMPORTING A *.CID OR *.ICD FILE – 2 ........................................................................................................ 126
FIGURE 158: IMPORTING SCL FILE FOR GOOSE ENGINEERING......................................................................................... 127
FIGURE 159: IEC61850 GOOSE PUBLISHER INFORMATION ........................................................................................... 127
FIGURE 160: GOOSE SUBSCRIPTION WINDOW - MAPPING SUBSCRIBED DATA ................................................................... 128
FIGURE 161: 2179 PROTOCOL SETTINGS ..................................................................................................................... 128
FIGURE 162: FTP SETTINGS....................................................................................................................................... 129
FIGURE 163: PEER TO PEER SETTINGS.......................................................................................................................... 129
FIGURE 164: PMU SETTINGS .................................................................................................................................... 130
FIGURE 165: COMMUNICATIONS PORT SETTINGS – RS232 ............................................................................................. 131
NOJA-559-23
ABBREVIATIONS/ACRONYMS
ABR Auto Backfeed Restoration
ACO Auto Change Over
ACR Automatic Circuit Recloser
AR Auto Reclose
AP Access Point
BC Block Close
CD Carrier Detect
CBF Circuit Breaker Fail
CLP Cold Load Pickup
CMS Control and Management Software
CO Close/Open
CRC Cyclic Redundancy Check
CVT Capacitive Voltage Transformer
CT Current Transformer
CTS Clear to Send
DCD Data Carrier Detect
DCE Data Communication Equipment
DE Directional Element
DFT Disable Fast Trips
DGPS Differential Global Positioning System
DLLB Dead Line/Live Bus
DNP3 Distributed Network Protocol 3
DSA Distribution System Automation
DSP Digital Signal Processing
DSR Data Set Ready
DTR Data Terminal Ready
EMC Electromagnetic Compatibility Performance
EF Earth Fault Element
EFLL Earth Fault Live Line Element
FE Frequency Protection Element
FPGA Field Programmable Gate Array
GOOSE Generic Object Oriented Substation Events
GPS Global Positioning System
HLT Hot Line Tag
HMI Human Machine Interface
HRM Harmonic
HV High Voltage
IDMT Inverse Definite Minimum Time
IEC International Electrotechnical Commission
IEEE Institute of Electrical and Electronics Engineers
I/O Input/Output
IP Internet Protocol
IR Inrush Restraint
ITS Interface Test Set
LCD Liquid Crystal Display
LED Light Emitting Diode
LGVT Last Good Value Trapped
LL Live Line Overcurrent
LLB Live Load Blocking
LLDB Live Line/Dead Bus
LLLB Live Line/Live Bus
LSD Loss of Supply Detection
1
NOJA-559-23
ABBREVIATIONS/ACRONYMS
LSRM Loss of Supply Reclosing Mode
LV Low Voltage
MAIFI Momentary Average Interruption Frequency Index
MCB Miniature Circuit Breaker
MDI Maximum Demand Indication
MMS Manufacturing Message Specification
MNT Maximum Number of Trips
NPS Negative Phase Sequence
NPSLL Negative Phase Sequence Live Line
NVD Neutral Voltage Detection
OC Overcurrent
OCLL Overcurrent Live Line
OF Over Frequency
OSM Outdoor Switch Module
OV Over Voltage
PCB Printed Circuit Board
PDOP Protection Directional Over Power
PDUP Protection Directional Under Power
PPS Pulse per Second
PROT Protection
PSC Protection Status Control
PSM Power Supply Module
RAM Random Access Memory
RC Recloser Controller
REL Relay Module
RI Ring Indicator
RMS Root Mean Squared
ROCOF Rate Of Change Of Frequency
RTC Real Time Clock
RTS Request to Send
RTU Remote Terminal Unit
SAIDI System Average Interruption Duration Index
SAIFI System Average Interruption Frequency Index
SCADA Supervisory Control and Data Acquisition
SEF Sensitive Earth Fault
SEFLL Sensitive Earth Fault Live Line
SGA Smart Grid Automation
SIM (Module) Switchgear Interface Module
SIM (Card) Subscriber Identity Module
SNTP Simple Network Time Protocol
SSID Service Set Identifier
SSM Short Sequence Mode
SST Single Shot Trip
ST Single Triple
SW Switch
TCC Time Current Characteristics
TCP/IP Transmission Control Protocol/Internet Protocol
TD Definite Time
THD Total Harmonic Distortion
TDD Total Demand Distortion
TTA Temporary Time Addition
UDC User Defined Curve
2
NOJA-559-23
ABBREVIATIONS/ACRONYMS
USB Universal Serial Bus
UV Under Voltage
UF Under Frequency
UPS Uninterruptable Power Supply
UTC Coordinated Universal Time
VE Voltage Protection Element
VRC Voltage Reclosing Control
VT Voltage Transformer
VVS Voltage Vector Shift
WiFi Wireless Fidelity (wireless networking)
ZSC Zone Sequence Co-ordination
3
NOJA-559-23
DEFINITION OF TERMS
Item Definition
Fault Reset Time Defines the time after which a pickup is no longer active
before the protection timer resets.
Lockout Lockout is when the device opens and cannot perform any
auto reclosing operation.
Protection Trip A Protection Trip is when the device goes into the open
position when a protection operation is requested.
Sectionaliser Count The device waits for detection of Loss of Supply (LSD) before
increasing the sequence counter. In this instance the fault is
detected and “counted” but the device does not open. Please
refer to OSM User Manual for more details.
Sectionaliser Trip A Sectionaliser trip is when the device waits for detection of
Loss of Supply (LSD) before opening. Please refer to OSM
User Manual for more details.
Sequence Counter/Trip Counter The sequence counter is used to keep a record of the number
of protection operations within the sequence that have
occurred. Please refer to OSM User Manual for more details.
Single Shot A device is in single shot when auto reclosing is disabled for
any reason. Please refer to OSM User Manual for more
details.
Single Shot Mode When in Single Shot mode, if a protection operation occurs,
the device will do one trip to lockout using the Single Shot
Trip (SST) selected configuration.
SST Time When SST Control is enabled, the SST Time applies after
closing the device from a lockout state. While the SST Time
has not expired the device will be in Single Shot Mode. In this
instance the AR Reset time does not apply.
4
NOJA-559-23
1 Introduction
The Control and Management Software (CMS) is a software package that runs on a
Personal Computer (PC) and is used to configure and interrogate the Recloser Control (RC)
cubicle.
Offline mode means that CMS is not connected to the switchgear device. The user is allowed
to do the following types of work:
When working in Online mode the RC must be connected to the PC. The connection can be
a local connection i.e. through a standard USB cable connected to the Operator Panel USB
Port or a remote connection.
▪ read and replace the group of protection settings installed in the device
▪ read the device and protocol status
▪ direct control of the device
▪ adjust the device system settings.
1.1 Installation
If you are upgrading from CMS v2.0 and above, CMS automatically checks for updates when
you are connected to the internet and will update to the latest release of CMS automatically.
Manual Installation/Upgrade
The installation package is a zip file which can be downloaded from the NOJA Power website
www.nojapower.com.au. A username and password will be required to access the download
area. This can be obtained by contacting NOJA Power, or your local NOJA Power distributor.
To start the installation, unzip the file and run the executable (.exe) file.
The following system requirements are necessary for CMS to execute successfully:
5
NOJA-559-23
▪ Windows 8.1
▪ Windows 10.
Warning:
CMS v3.9 and higher only supports device(s) with RLM v1.12 relay firmware or higher. If the
user wants to use a device older than RLM v1.12 relay firmware, then CMS v3.8 or lower
shall be used to connect with older version device(s).
During the upgrade process, CMS checks for any pre-existing devices below RLM v1.12 in
the database. If present, the upgrade process displays a list of those device(s) with an option
to save a copy of each before continuing. CMS will delete the files in the database below
RLM v1.12 when the upgrade is successful.
Any existing devices in the database before upgrade that have a serial number starting with
“059” or “10C” will be greyed out after upgrade because these numbers are only for RC20
devices – which were not supported before CMS 3.9.
Note: If there is no need to retain the old database then you can install the latest version
directly from CMS v1.8 using the latest installation package.
6
NOJA-559-23
To obtain information on the CMS version installed go to “About CMS” from the Help menu
as shown below.
7
NOJA-559-23
Select user name and enter password. User name is not case-sensitive. For example-
“Admin” and “admin” will be considered as the same user.
You must adhere to the following rules when choosing your password:
1) Your password has to be at least 1 character long and the maximum limit is 25
characters.
2) Alphanumeric characters, special characters and spaces are valid.
If this is the first time you are running CMS, you will be asked to confirm your password. You
will also be asked to enter two security answers which can be used to reset the password if
required.
8
NOJA-559-23
Note:
• The initial user to logon to CMS after installation will be granted Administrator access
which will give them full access to CMS and allow them create/modify users.
When the user enters a wrong password or forgets the password, the following steps need to
be followed to reset the password. This is applicable for CMS versions 3.7 and above.
1. On entering a wrong password, the following screen appears. Click on the option
‘Reset Password’.
2. You must answer two security questions which were asked initially when you logged
into CMS for the first time. After answering the two questions, click on the ‘Submit’
button.
9
NOJA-559-23
Once you have logged in the main window appears as shown below.
10
NOJA-559-23
The quick access toolbar is located next to the green menu icon. By default there is a Save
and Open Device Manager icon. Extra icons can be added if required.
Directly below the quick access toolbar is a drop down box that displays which device is
currently selected. It is blank if no devices have been selected.
The ribbon menu bar shows context sensitive icons depending which menu items are
selected.
The main menu is accessed by clicking the green icon in the top left hand corner and is used
to:
▪ Create or Open Devices, Users, Simulation and TCC curves
▪ Save items
▪ Print items
▪ Import and Export files
▪ Configure the CMS Environment.
11
NOJA-559-23
“Options” allows the user to configure the CMS environment such as:
• Startup Screen
• Performance Settings
• Diagnostics Settings.
At the bottom of the screen a Status Bar is displayed which shows the current status of CMS,
devices and displays any warning messages.
An Operator Log can also be displayed (View - > Operator Log) which shows messages
transferred between CMS and any connected devices.
12
NOJA-559-23
To save any changes click on the Save disk icon in the Quick Access toolbar. The disk icon
will be greyed out when changes are saved.
Note: An asterisk * will appear in the bottom tab if there are any changes that need to be saved.
13
NOJA-559-23
3 View
The View menu enables the user to choose how the open windows are displayed and
whether the operator log should be visible or not. It also allows the user to close one or all
windows.
14
NOJA-559-23
Cascading Windows
Click on View -> Cascade Windows.
15
NOJA-559-23
16
NOJA-559-23
17
NOJA-559-23
18
NOJA-559-23
• Enter a Name.
• Select the Switchgear Type (3 Phase1, 3 Phase SEF2, Single Phase or Single Triple3)
The relay serial number can be obtained from the Recloser Controller by turning on the
operator panel, pressing escape to enter the main menu, then scrolling down and selecting
the Identification menu item. The serial number will be displayed in the “Relay” tab.
Notes:
1. OSM 312 reclosers should be created as 3 Phase devices.
2. “3 Phase SEF” is a switchgear model with matched Current Transformers (CTs) providing
0.2A Sensitive Earth Fault (SEF) accuracy.
3. “Single Triple” Switchgear Type is not supported for REL-20 and REL-20-4G devices.
4. The first three numbers of the relay serial number define the relay type e.g.:
• REL-01 01A
• REL-02 031
• REL-15 069
• REL-15-4G 070
• REL-20 059
• REL-20-4G 10C.
Click the “Save” button at the top of the screen to save the new device record.
The User is allowed to create a new device by inserting a minimum of 1 digit in the second
textbox for Relay Serial Number. The maximum number of digits that can be added is 10 in
the second textbox for Relay Serial Number.
The Relay Serial Number cannot be changed after the device is created.
19
NOJA-559-23
Connect the computer to the cubicle using a USB cable plugged into the port on the front
panel.
The device will appear in the “Other Connected Devices” list at the bottom of the screen.
Right click on the device and click “Add as New Device”. Change Name, Description and
Comments as required.
Click the Save button at the top of the screen to save the new device record.
20
NOJA-559-23
21
NOJA-559-23
An address can be entered for the device by clicking on Location in the Device Details
window.
22
NOJA-559-23
23
NOJA-559-23
A PC running CMS can connect to a device locally using a USB cable plugged into the panel
USB port or remotely. For establishing a connection to the RC please refer to section 8.
If a device is connected using a USB cable and the device has already been created, the
Connection Status will change to “Plugged In” as shown below.
Otherwise the device will appear in the “Other Connected Devices” list at the bottom of the
screen. Right click on the device and click “Add as New Device”. Change Name, Description
and Comments as required. The Connection Status will then change to “Plugged In”.
24
NOJA-559-23
Click “Browse” to select the file(s) to import. Select/Deselect files if required. Click “Next”.
When importing device(s), if device(s) have historical settings older than RLM v1.12 relay
firmware but with firmware version RLM v1.12 or higher (due to a firmware upgrade), CMS
25
NOJA-559-23
v3.9 and higher deletes the historical settings from the device(s) database so it can be
successfully imported.
If a device being imported already exists in the database, the following message appears:
For RC-20 and RC-20-4G, if the “Create New Device” option is chosen, Single Triple
Switchgear Type will be greyed out.
The user has the option to overwrite the existing device, skip importing the device or create a
new device. After making a selection click “Continue”.
Note:
• If a device of the same name already exists and the user selects to create a new device, CMS
will only allow the user to enter a relay serial number that is of the same device type as the
device being imported (e.g. REL-01, REL-02, REL_15, REL_15-4G). Refer to section 4.1
Creating New Devices for more details on serial numbers.
26
NOJA-559-23
If the device being imported is from an earlier version of CMS, the originating time zone
needs to be selected as shown below.
A pop up window will display information as the device(s) data is imported and will display a
message when importing is completed.
27
NOJA-559-23
Warning: Do not import devices that were created with a later version of CMS.
Importing device from an earlier or same version of CMS is recommended.
28
NOJA-559-23
Click “Next”.
Note: The folder path should be “:\rc10\logs\RC serial number” as shown below. Do not select any
subdirectories.
29
NOJA-559-23
The user has the option to append to existing log files and settings history or create a new
device and add log files and settings history. After making a selection click “Continue”.
30
NOJA-559-23
A pop-up window will display information as the data imported and will display a message
when importing is completed.
Click Finish.
31
NOJA-559-23
To export a device or a number of devices, click on “Export Device” from the “Device” tab.
Select the devices to export and enter a folder location. You may use browse and/or create
a new folder.
Click “Export”.
32
NOJA-559-23
A pop up window will display information as the device(s) data is exported and will display a
message when exporting is completed.
Please note that .csv and .txt files cannot be imported back into CMS. The following
restrictions apply for importing .xml files back into CMS:
• Can only import .xml files from CMS devices created in the current version of CMS
(i.e. trying to import an .xml file from a device originally created in CMS 3.1 will fail
when importing into CMS 3.2).
• Import/Export of .xml files can only be done via the “Import/Export Offline Settings”
buttons. You cannot import/export .xml files from the Import/Export Device buttons.
• Importing .xml files is only supported from Relay 1.15/CMS 3.1 onwards.
To import .xml file, click on “Import Offline Settings” from the “Device” tab.
Click “Open”.
33
NOJA-559-23
Click “Next”.
Click “Finish”.
34
NOJA-559-23
Please note that .csv and .txt files cannot be imported back into CMS. Some restrictions
apply for importing .xml files back into CMS. Refer to section 4.7 Import Offline Settings.
To export offline settings, click on “Export Offline Settings” from the “Device” tab.
Select the device where you are exporting the offline settings from and click “Next”.
35
NOJA-559-23
Select the settings that you want to export and confirm file path.
36
NOJA-559-23
By clicking on the icon in the bottom right hand corner of the window, as shown below, a user
can change the file location and format including .csv, .xml and .txt
Once the file location and name are confirmed, click “Export”. A message will be displayed
indicating whether the settings were exported successfully.
The “Copy Settings Wizard” is used to copy settings from one device to another or from an
Upload or Download to a device.
37
NOJA-559-23
The following restrictions apply when copying between different switchgear types within REL-10/REL-
15 devices:
Table 4: Restrictions – Copying different switchgear types within REL10 / REL 15 devices
Switchgear
3 Phase 3 Phase SEF Single Triple Single Phase
Type
Except for group1-4
Except for switchgear Except for switchgear
Except for SIM settings, Switchgear
Calibration and SIM Calibration and SIM
calibration, All other Calibration and SIM
3 Phase Calibration, All other Calibration, All other
offline settings are Calibration, All other
offline settings are offline settings are
allowed. offline settings are
allowed*. allowed.
allowed.
Except for group1-4
Except for switchgear Except for switchgear
Except for SIM settings, Switchgear
Calibration and SIM Calibration and SIM
3 Phase calibration, All other Calibration and SIM
Calibration All other Calibration, All other
SEF offline settings are Calibration, All other
offline settings are offline settings are
allowed. offline settings are
allowed*. allowed.
allowed.
Except for group1-4
Except for switchgear Except for switchgear
Except for SIM settings, Switchgear
Calibration and SIM Calibration and SIM
Single calibration, All other Calibration and SIM
Calibration, All other Calibration, All other
Triple offline settings are Calibration, All other
offline settings are offline settings are
allowed. offline settings are
allowed. allowed.
allowed.
Except for group1-4 Except for group1-4 Except for group1-4
settings, Switchgear settings, Switchgear settings, Switchgear Except for SIM
Single Calibration and SIM Calibration and SIM Calibration and SIM calibration, All other
Phase Calibration, All other Calibration, All other Calibration, All other offline settings are
offline settings are offline settings are offline settings are allowed.
allowed. allowed. allowed.
Note:
*When copying “3 Phase SEF” and “3 Phase”, all “3 Phase SEF” new pickup currents data points shall
be copied to their matching “3 Phase” pickup current data points and vice versa.
The following restrictions apply when copying between different switchgear types within REL-20
devices:
Table 5: Restrictions – Copying different switchgear types within REL20 devices
Switchgear Single
3 Phase 3 Phase SEF Single Phase
Type Triple
NA Except for protection
Except for Controller Except for Switchgear (Group1-4 settings and
Calibration, All other Calibration and Controller Curve Selection),
3 Phase offline settings are Calibration, All other offline Controller Calibration,
allowed. settings are allowed*. Switchgear Calibration, All
other offline settings are
allowed.
NA Except for protection
Except for Switchgear
Except for Controller (Group1-4 settings and
Calibration and
Calibration, All other offline Curve Selection),
3 Phase Controller Calibration,
settings are allowed. Controller Calibration,
SEF All other offline settings
Switchgear Calibration, All
are allowed*.
other offline settings are
allowed.
Single NA NA NA NA
Triple
Except for protection NA
Except for protection (Group1-
(Group1-4 settings and
4 settings and Curve Except for Controller
Curve Selection),
Single Selection), Controller Calibration, All other offline
Controller Calibration,
Phase Calibration, Switchgear settings are allowed.
Switchgear Calibration
Calibration All other offline
All other offline settings
settings are allowed.
are allowed.
38
NOJA-559-23
Note:
*When copying “3 Phase SEF” and “3 Phase”, all “3 Phase SEF” new pickup currents data points shall
be copied to their matching “3 Phase” pickup current data points and vice versa.
**SIM and Relay Calibration are displayed under Controller Calibration.
Highlight the Source Device where you are copying settings from and click “Next”.
Note: The source Settings can be settings currently loaded into the device or settings from the
settings history.
39
NOJA-559-23
40
NOJA-559-23
A message indicating that the copy of settings was successful should be displayed when
finished.
41
NOJA-559-23
All uploaded, downloaded and offline settings relating to a particular device can be
compared. Settings can also be compared between different devices.
The following restrictions apply when comparing settings between different switchgear types
within REL-10/REL-15 devices:
Table 6: Restrictions – Comparing different switchgear types within REL10 / REL 15 devices
Switchgear
3 Phase 3 Phase SEF Single Triple Single Phase
Type
Except for protection Except for protection
(Group 1 – 4 settings) (Group 1 – 4 settings)
and Switchgear and Switchgear
Calibration, Only Calibration, Only
Curve Selection, SIM Curve Selection, SIM
3 Phase All Offline settings All Offline settings*
Calibration, System Calibration, System
Settings, I/O, Logic, Settings, I/O, Logic,
COMMS, Protocol COMMS, Protocol
Settings, Power Settings, Power
Quality are allowed. Quality are allowed.
Except for protection Except for protection
(Group 1 – 4 settings) (Group 1 – 4 settings)
and Switchgear and Switchgear
Calibration, Only Calibration, Only
3 Phase Curve Selection, SIM Curve Selection, SIM
All Offline settings* All Offline settings
SEF Calibration, System Calibration, System
Settings, I/O, Logic, Settings, I/O, Logic,
COMMS, Protocol COMMS, Protocol
Settings, Power Settings, Power
Quality are allowed. Quality are allowed.
Except for protection Except for protection Except for protection
(Group 1 – 4 settings) (Group 1 – 4 settings) (Group 1 – 4 settings)
and Switchgear and Switchgear and Switchgear
Calibration, Only Calibration, Only Calibration, Only
Single Curve Selection, SIM Curve Selection, SIM Curve Selection, SIM
All Offline settings
Triple Calibration, System Calibration, System Calibration, System
Settings, I/O, Logic, Settings, I/O, Logic, Settings, I/O, Logic,
COMMS, Protocol COMMS, Protocol COMMS, Protocol
Settings, Power Settings, Power Settings, Power
Quality are allowed. Quality are allowed. Quality are allowed.
Except for protection Except for protection Except for protection
(Group 1 – 4 settings) (Group 1 – 4 settings) (Group 1 – 4 settings)
and Switchgear and Switchgear and Switchgear
Calibration, Only Calibration, Only Calibration, Only
Single Curve Selection, SIM Curve Selection, SIM Curve Selection, SIM
All Offline settings
Phase Calibration, System Calibration, System Calibration, System
Settings, I/O, Logic, Settings, I/O, Logic, Settings, I/O, Logic,
COMMS, Protocol COMMS, Protocol COMMS, Protocol
Settings, Power Settings, Power Settings, Power
Quality are allowed. Quality are allowed. Quality are allowed.
Note:
*When comparing “3 Phase SEF” and “3 Phase”, all “3 Phase SEF” new pickup currents data
points shall be compared with their matching “3 Phase” pickup current data points and vice
versa.
The following restrictions apply when comparing settings between different switchgear types
within REL-20 devices:
42
NOJA-559-23
Note:
*When comparing “3 Phase SEF” and “3 Phase”, all “3 Phase SEF” new pickup currents data
points shall be compared with their matching “3 Phase” pickup current data points and vice
versa.
To compare settings click the “Compare Settings” button. This is located on the “Device” tab.
The Setting Comparison screen will be displayed.
43
NOJA-559-23
44
NOJA-559-23
Select the device you want to compare settings with and click “Next”.
45
NOJA-559-23
The results of the comparison are displayed in a window. A tree view allows you to open any
sub branch to see individual changes.
46
NOJA-559-23
47
NOJA-559-23
The utility simplifies the upgrade process by saving a special version of the UBoot and UKern
files to a USB flash drive which can be used to upgrade the relay. The process is automated
allowing the user to perform the upgrade via the utility following some simple instructions.
Note: For Relay 15 modules please refer to NOJA-793 Firmware Upgrade Procedure to update the
firmware manually.
You will need to be Offline with the device to be able to launch the update utility. Once you
click on the “Firmware Update” button, CMS will display a warning message to ensure you
have a backup of the device settings as the utility will revert the relay to factory defaults.
You must follow the steps provided by the Firmware Upgrade Utility and perform each
operation as instructed. Please DO NOT interrupt the update process at any stage and DO
NOT power off the RC unless instructed.
The table below provides a list of the firmware upgrade utility screens and the actions
required by the user. This is only a guide so please read the instructions carefully when
running the utility.
For more information please refer to NOJA-7487 Firmware Update Utility User Guide.
Detect Relay Connect your PC to the RC cubicle via the USB-L cable. Ensure the RC is
set to Local Mode. Insert the USB Flash drive into a USB port on the relay.
Confirm Upgrade Check each of the confirmation boxes. Please read carefully before
proceeding.
Stage 1 Upgrade No action required. If the UBoot and Ukern files fail to install, you can click
“Retry” to attempt the installation again. If the problem persists, contact
NOJA Power.
Relay Shutdown When prompted, turn Off the AC supply and the battery.
Stage 2 Upgrade When prompted, turn On the AC supply and the battery. After the power
supply is restored, the heartbeat LED will flash during the upgrade
process.
Finalising Upgrade No action required. DO NOT interrupt the upgrade process or power off.
Summary screen Restore RC settings. Review IO and SIM versions and upgrade if
necessary. If you need to update to a latter version of firmware, refer to
NOJA-793 Firmware Upgrade Procedure.
48
NOJA-559-23
Select the type of information you wish to print i.e. “Offline Settings” or “Field Readings”.
Depending on the selection an Offline Settings or Field Readings window will then be
displayed.
Alternatively the user can make a selection from the Settings History list.
49
NOJA-559-23
50
NOJA-559-23
51
NOJA-559-23
When printing a session ensure the “Session To” date and time is greater than the “Session
From” date and time.
52
NOJA-559-23
53
NOJA-559-23
5 Connection Tab
The “Connection” Tab is used to:
▪ Go Online and Go Offline.
▪ Configure communication between the PC and the RC
▪ Upload and Download Settings whilst Online
CMS can connect to a device through the local USB port on the RC or via a remote
connection. Please refer to Section 8 Connecting to a device, for configuring a connection
between CMS and a local or remote device.
5.1 Online/Offline
To go online, the PC running CMS must be connected to the local USB port on the RC or
must be connected via a remote connection.
To go Online click the “Go Online” button from the “Connection” tab.
Note: If the wrong switchgear type is detected or the OSM serial number is incorrect, CMS will not go
online with the device.
54
NOJA-559-23
To upload the settings from a device to CMS ensure that you are Online.
From the “Connection” menu, click “Upload Settings” (alternatively select the “Upload” Tab).
The uploaded settings appear in the settings history table as shown below. A time stamp is
recorded for each upload and download event.
Once the upload is complete, the user can copy the settings to the device. Please refer to
Downloading Settings to the Device.
CMS allows both local and remote download of settings to a device including communication
and protection settings and switchgear coefficients. The only exceptions are the CMS
55
NOJA-559-23
protocol and communication settings and the switchgear serial number. These can only be
downloaded through the local USB port.
To download settings from CMS to a device ensure that you are Online.
From the “Connection” menu, click “Download Settings” (alternatively select the “Download”
Tab). This will bring up a Download Settings window where items to be downloaded can be
selected.
Warning messages may appear if some settings need to be checked prior to starting the
transfer or if some action is required after the transfer for the change to take effect. You will
need to confirm to proceed.
Note: When enabling a protocol you will need to restart the controller after the download for the
protocol to be loaded into memory.
The downloaded settings are recorded in the settings history table below with a timestamp of
the date and time they were downloaded.
56
NOJA-559-23
To view settings history, click on “Settings History” from the “Connection” tab as shown
below.
The list of transfers, each with a time stamp, will be displayed indicating what settings were
uploaded/downloaded.
Note: The Date and Time format is defined in System Settings. Refer to section 7.2.4 Real Time
Clock.
57
NOJA-559-23
The timestamps in the history column indicate the times CMS went online with the device.
Filters can be applied to make searching for specific items in logs easier. Refer to 6.8
Navigation Features for Logs for a description of this feature.
Instantaneous field readings from the device can be viewed in CMS while connected to the
device.
A snapshot of the field readings is recorded each time CMS connects to a particular device.
This history of field readings can be useful as a comparison of how the system and feeder is
performing over time.
Click the “System Status” button from the “Field Readings” Tab.
58
NOJA-559-23
▪ OSM Position
▪ Switchgear Configuration
▪ Local/Remote Mode
▪ Sectionaliser Mode
▪ Protection Status
▪ UPS (Uninterruptible Power Supply) Status
▪ SNTP Status
▪ Malfunctions and Warnings.
Nota: "Inhibit Multi Phase Closes” applies to single triple switchgear only.
The “Measurement” tab displays the items measured by the sensors mounted inside the
OSM tank:
▪ Currents
▪ Voltages
▪ Frequency
▪ Power Readings
▪ Power Factor
▪ Energy Readings
▪ Power Flow Direction.
The “SCADA” tab displays the DNP3 and IEC 61850 status.
The “Identification” tab displays the serial numbers and version numbers for Relay, SIM and
Panel modules inside the RC. It also displays the model number of the Relay and SIM
modules.
The “I/O & Logic Status” tab shows the current state of all physical inputs and outputs, plus
the state of Logic variables. This is particularly useful for commissioning and testing I/O
modules and custom logic expressions. Refer to the Logic and I/O User manual NOJA-5591
for detailed information about these items.
The “ACO Status” tab shows the current status of both reclosers connected together in an
Auto Changeover scheme. ACO is an automation feature available with the RC that connects
59
NOJA-559-23
two adjacent reclosers via a peer to peer communications link and automates switching
between two sources for critical loads. Refer to the ACO User Manual NOJA-594 for detailed
information about this feature.
The “Power Quality Status” tab includes information on data captured for Oscillography,
Harmonics, Interruptions and Sags & Swells.
The event log records every event that occurs inside the RC. Click the “Event Log” button
from the “Field Readings” Tab.
The event log is ordered so the latest event is at the top of the list.
Filters can be applied to make searching for specific items easier. Refer to 6.8 Navigation
Features for Logs for a description of this feature.
Time differences between two events can be checked by highlighting the first item, then
selecting a second event while holding down the CTRL key on the keyboard.
The time difference between the two highlighted events is displayed in the bar at the bottom
of the event log window.
60
NOJA-559-23
The Change Log records changes to settings in the RC. Click the “Change Log” button from
the “Field Readings” Tab.
This log makes it very easy to follow what settings where changed and when the change
occurred.
Time differences between two change events can be checked by highlighting the first item,
then selecting a second event while holding down the CTRL key on the keyboard.
Filters can be applied to make searching for specific items easier. Refer to 6.8 Navigation
Features for Logs for a description of this feature.
61
NOJA-559-23
The Close Open Log records the open and close events that have occurred for any reason.
Click the “Close/Open Log” button from the “Field Readings” Tab.
62
NOJA-559-23
If the trip occurred due to a fault condition, up to 50 cycles of pre-fault history will also have
been recorded. When the fault trip is highlighted, this information will appear in the window
below the event table.
Note: The RC records the pre-fault history for the last 8 protection trips only.
The pre-fault data can be highlighted, then graphed. To do this select the first event, hold
down the CTRL key, and highlight the last event like you would in a spread sheet.
Right click over the selection and choose Chart from Selection from the list.
63
NOJA-559-23
It is also possible to export the data to multiple formats by selecting “Export to File”.
64
NOJA-559-23
The load profile stores measured readings at set regular intervals such as:
▪ Voltages
▪ Current
▪ Power
▪ Power Factor
▪ Frequency
▪ Energy.
Exactly what will be recorded – and at what interval, can be configured. Please refer to
Section 7.2.11 Load Profile Configuration.
To open the Load Profile log, click the “Load Profile” button from the “Field Readings” Tab.
Note: The Load Profile in the RC has a maximum amount of data it can hold, after which it will start
discarding the oldest records. The maximum amount of samples that can be recorded is
dependent on how many items are selected for recording.
65
NOJA-559-23
6.6 Counters
To view the counters, click the “Counters” button on the “Field Readings” Tab.
ROCOF and VVS will be visible under Fault Counters for REL-20 and REL-20-4G devices
only.
Note: For Single Triple switchgear, counters for each phase are displayed for UV, OV and HRM.
The Comms Status screen shows the status of the communications ports available in the
RC. Click the “Comms Status” button from the “Field Readings” Tab.
Bytes received and transmitted record the raw amount of data received and transmitted on
the port. Actual valid protocol packets received and transmitted are recorded in the Counters
screen.
The RS232 Serial Port will also show the status of the individual pins.
The port can be set into a test mode when configured as a Radio connection. When set to
On, the RC will transmit the text “NOJA” out the port.
66
NOJA-559-23
Note:
• DTR=Data Terminal Ready, RTS=Request to Send, DSR=Data Set Ready, CTS=Clear to Send,
CD=Carrier Detect, RI=Ring Indicator
• High indicates that the signal is asserted (logic “1”)
• For more details refer to RC SCADA Interface Description
67
NOJA-559-23
6.8.1 Sorting
The user can sort the data in ascending or descending order of a particular column. Right
click on a column header to display the navigation menu and click “Sort Ascending” or “Sort
Descending”.
6.8.2 Grouping
The user can group data by a particular column. Right click on a column header to display
the navigation menu and click “Group by This Column”. In the example below the Change
log was grouped by the “Source of Change” column.
To ungroup right click on the “Group By” column (“Source of Change” in the example below)
to display the navigation menu and click “Ungroup”.
68
NOJA-559-23
Figure 81 Ungrouping
To create a filter, click on “Edit Filter” from the Field Readings Ribbon Menu Bar.
Alternatively, right click on a column header of a log file to display the navigation menu and
click on “Filter Editor” or click on “Edit Filter” in the bottom left hand corner of the log window.
69
NOJA-559-23
The result can be narrowed further by applying one or more additional filters. Click on the
plus sign to add more filters.
70
NOJA-559-23
Load Filter
By clicking “Load” from the log window or “Load Filter” from the Field Readings Ribbon Menu
Bar the list of saved filters is displayed.
By selecting a filter and then clicking “Apply”, data is uploaded from the device and the filter
is re-applied.
6.8.4 Searching
To search for an item in the list right click on a column header to display the navigation menu
and click “Show Find Panel”. Alternatively press “Ctrl+F”. A search panel area will be
displayed above the column headers as shown below.
71
NOJA-559-23
Type the required search text and press “Enter”. Only those items in the list containing the
required text will be displayed.
Click “Clear” in the find panel area to end the search and return the list back to normal.
72
NOJA-559-23
7 Offline Settings
The RC is configured by modifying the Offline settings as required, then downloading the
new settings to the RC. Please refer to Section 5.3 to download settings to a device.
There are four protection groups available in the RC. They all have the same parameters
available for configuration.
To configure Group Protection settings, click the “Group (1 – 4)” button required.
From the “Auto Reclose” tab you can configure the reclosing sequences associated with
Overcurrent (OC), Negative Phase Sequence (NPS), Earth Fault (EF), Sensitive Earth Fault
(SEF) and Admittance (Yn) protection.
Note: NPS, EF, SEF and Yn do not apply to single phase devices.
Below is a description of the protection elements found on the “Auto Reclose” tab:
73
NOJA-559-23
OC2, NPS2, EF2 Low Set Elements for forward (OC2+, NPS2+, EF2+) and reverse (OC2-, NPS2-,
EF2-) powerflow direction. Used to provide a fast fuse clearing, first operation or
a first stage Time Current Characteristic (TCC) element.
OC3, NPS3, EF3 High set elements for forward (OC3+, NPS3+, EF3+) and reverse (OC3-, NPS3-,
EF3-) powerflow used to minimize exposure to downstream equipment to high
fault currents.
SEF Sensitive Earth Fault protection for forward power flow direction (SEF+) and
reverse power flow direction (SEF-).
I2/I1 Broken Conductor protection using the ratio of negative sequence current over
positive sequence current.
DE OC, DE NPS, DE EF, DE Directional elements provide a means of enabling or disabling directional
SEF protection for each of the OC, NPS, EF and SEF elements. The torque angle set
by the user is used to determine the direction.
When the Directional Element (DE) is enabled for any protection element, the
protection element will only respond to faults in the element’s designated
direction. If DE is not enabled for a particular element then the element will
respond to both forward and reverse overcurrent and operate on the magnitude
of the fault only.
The “Direction Not Detected” setting determines whether the protection element
enabled for directional control will operate if the direction is not detected. By
default this setting is configured to “block” any protection trips. When set to “Trip”
the fastest curve of the elements enabled for directional control will trip once the
fault reaches the pickup value.
The “Dir Change Response” setting determines how the elements, enabled for
directional control, behave when the power flow direction changes while the
protection timer is accumulating:
Lock
When the direction (e.g. positive direction) is detected and a protection element
e.g. OC1+ detects the fault, the protection timer for OC1+ starts to accumulate.
During this time, if the direction of current suddenly changes and exceeds the
pickup current of the opposite element e.g.OC1-, then OC1- will not detect the
fault and the protection timer continues to accumulate for OC1+.
Dynamic
When the direction (e.g. positive direction) is detected and a protection element
e.g. OC1+ detects the fault, the protection timer starts to accumulate for OC1+.
During this time, if the direction of current suddenly changes and exceeds the
pickup current of the opposite element e.g.OC1-, the protection timer resets and
starts to accumulate for OC1-. The OC1+ pickup resets after the fault reset time
if the direction does not return back to the positive direction during the reset time.
74
NOJA-559-23
Advanced Polarised Advanced Polarised Detection can be utilised to determine directionality of high
Detection impedance earth faults detected through EF and SEF elements in isolated and
compensated neutral networks.
When “Advanced Polar Detection” is enabled the user can configure additional
settings to define the boundaries of the operating angle, θ associated with
directional protection. Please refer to the OSM User Manual for more details.
From the “Auto Reclose” tab you can also configure the following settings:
Reset Time Reset Time refers to the period of time subsequent to a close after
which the Auto Reclosing (AR) element is ready to perform its full
sequence.
If the device is closed from a lockout state it will be in Single Shot Mode
until the Reset Time expires (unless SST Control is enabled – see
below).
If the device is closed from a manual source and is not in a lockout state
the device will be in single shot mode until the Reset Time expires.
SST Control, SST Time When SST Control is enabled, if the device is closed from a lockout
state, the device will be in Single Shot Mode until the SST Time expires.
In this instance the Reset time does not apply.
LLB Live Load Blocking prevents close operation from any source ((e.g.
Protection (AR), HMI, CMS, SCADA, IO or Logic) when the voltage on
the nominated load side, as defined by VRC, is within the threshold
range set by the user.
Auto Open
▪ Timer Mode In this mode, the recloser can be set to automatically re-open after a set
period of time and re-enable ABR.
▪ Powerflow Mode In this mode, the recloser will be able to detect reduction and/or change
in power flow direction and open automatically without operator
intervention.
LSRM Loss of Supply Reclosing Mode (LSRM) allows the recloser to trip only
once to Lockout if there is a fault due to loss of supply.
75
NOJA-559-23
Settings Description
ZSC Zone Sequence Co-ordination (ZSC) makes the recloser move its trip
counter forward by one if it detects a downstream protection device has
operated. The counter increments only after all protection elements
have reset.
Sequence Advance Sequence Advance makes the device move its trip counter forward by
one if it detects that an upstream device has operated (a loss of supply
is detected (LSD)). When the number of LSDs reaches the user defined
sequence advance value (1-3), no other sequence advances can occur.
Please note that for single phase devices only the applicable elements can be configured.
76
NOJA-559-23
For Single Triple devices, additional auto reclose settings are available that allow the user to
select the single triple mode of operation for the forward and reverse direction.
77
NOJA-559-23
CMS allows the user to configure three curves for each of the forward and reverse elements.
To display a curve simply click on the desired element in the Auto Reclose Map. A protection
curve screen will be displayed as shown below.
Note: For “3 Phase SEF” switchgear, the range for SEF+, SEF- and SEFLL is 0.2 to 80A and the
resolution is 0.1A.
The protection curve screen allows you to display and configure any of the curves in that
element group by clicking on 1+, 2+, 3+, 1-, 2- and/or 3- on top of the screen or on the side.
By default only the forward power flow curves are displayed.
IF DE is not enabled for a particular element then the element will respond to both forward
and reverse overcurrent. If DE is enabled then all six curves should be configured
appropriately.
You can also display other curves such as the Minimum Curve and Background Curve,
change the scaling and create User Defined Curves.
For example, tick the Minimum Curve box as shown below to display the minimum curve.
78
NOJA-559-23
You can also choose to display a Background Curve. The list of background curves
available comes from curves created via the TCC library. Please refer to 11.2 TCC Library.
79
NOJA-559-23
Each ANSI or IEC Time Current Characteristic can be modified with the aid of the following
operators:
Table 11: ANSI/IEC Time Current Characteristics modifying operators
Operator Definition
Maximum Current Multiplier If maximum current mode is enabled, when current exceeds a
user set maximum, the trip operation timer freezes until
current drops back below that level. This extends the tripping
time to avoid nuisance tripping during operation of
downstream fuses. The maximum current is calculated using
the multiplier applied to the pickup current and is only
applicable to low set elements (OC2+, OC2-, NPS2+, NPS2-,
EF2+ and EF2-).
Minimum Current Multiplier Defines the minimum pickup current. Set as a multiple of the
pickup current.
Definite Minimum Time Defines the minimum time that the device can operate. By
default this is set to 0s. This may be used to define desired
behaviour when an ANSI Inverse Definite Minimum Time
(IDMT) curve intersects a high set curve.
Maximum Tripping Time Defines the maximum time that the device can operate. By
default this is set to 120s.
Additional Time Adds a constant time to the selected TCC curve. By default
this is set to 0s.
Fault Reset Time Defines the time after which a pickup is no longer active
before the protection timer resets.
80
NOJA-559-23
By default, the RC only has the IEC and ANSI Inverse Definite Minimum Time (IDMT) curves
as well as the Definite Time (TD) curve loaded. Up to 10 additional Non-Standard and User
Defined curves can be loaded to the device.
To make additional curves available, click on Offline Settings - > Curve Selection. Tick the
boxes next to the required curves.
Note: These must be downloaded to the RC before they can be selected from the RC
panel.
In addition the user has access to a TCC library where standard curves, with their applicable
settings, for particular zones/areas can be created and maintained (refer to Section 11
Libraries).
A Standard Curve can be converted to a User Defined Curve which has individual time-
current co-coordinates (5 to 32) that can be modified.
To convert a Standard Curve to a User Curve, click on a desired element in the Auto Reclose
Map to display the protection curve screen.
81
NOJA-559-23
Make changes as desired either on the graph or using the table of points displayed.
Once you are satisfied with the changes, click on the curve on the graph and then click on
“Add to Standard Curves.”
82
NOJA-559-23
The following dialog box will then be displayed. Change Name and Description as required.
A message will be displayed indicating that the curve has been successfully saved.
To make the curve available for selection, click on “Curve Selection” in the Offline Settings
ribbon menu.
83
NOJA-559-23
You will need to exit protection settings and go back in for the curves to be displayed in the
drop down list as shown below.
84
NOJA-559-23
85
NOJA-559-23
The Sectionaliser role is to “Count” the number of operations of the upstream recloser under
fault conditions and to open to isolate the downstream fault when a pre-configured number of
“C”s (counts) is reached in the AR map and the upstream recloser is open.
When Sectionalise Mode is Enabled, the “C” (Count) and “S” (Sectionaliser) in the recloser
map will become available:
• “C” (Count) - Sectionaliser Count: When the fault current exceeds the pickup settings
and the protection timer expires, the device will wait for detection of Loss of Supply
(LSD) before increasing the sequence counter in the AR map.
• “S” (Sectionaliser) – Sectionaliser Trip: When the fault current exceeds the pickup
settings and the protection timer expires, the device will wait for detection of Loss of
Supply (LSD) before opening the device.
Note: If the last entry in the Auto Reclose Sequence is “L” (Lockout) then the recloser will not wait
for LSD and will open as soon as the protection timer expires causing a Protection Trip.
When Sectionaliser Mode is Enabled a warning message is displayed asking the user to
review the AR mapping for correct configuration and the user has the option to confirm or
cancel the request.
86
NOJA-559-23
When Sectionaliser Mode is Disabled a warning message is displayed informing the user
that the “C”s and “S”s in the AR map will change to “R”s and “L”s, respectively. The user has
the option to confirm or cancel the request.
Autoreclose Map
If the Autoreclose map is already opened in CMS, when sectionalising is enabled/disabled, it
will need to be closed and re-opened for the following changes to apply:
• When Sectionalise Mode is Enabled, the “C” (Count) and “S” (Sectionaliser) in the
recloser map will become available. All other auto reclose options will still be
available. Standard AR mapping logic applies but in addition, note the following:
o “R” can only precede “L” whereas “C” can precede “S” or “L”.
o “R” and “C” cannot be used in the same AR mapping group for each of the
forward and reverse elements. For example if the sequence R-R-L-L is used for
OC1+ then we cannot use C-S-D-D for OC2+.
o If “R” is used in the forward element group then it is possible to use “C” in the
reverse element group and vice versa. For example if R-R-L-L is used for OC1+
then we can use C-S-D-D for OC2- (if OC1- has a “C” or “S” in the
configuration).
• When Sectionalise Mode is Disabled, “C” in the recloser map will change to “R” and
the “S” in the recloser map will change to “L”. This change applies to all current
based protection elements (OC/NPS/EF/SEF).
87
NOJA-559-23
88
NOJA-559-23
UV3 Responds to phase voltage falling below the Loss of Supply Detection (LSD)
level.
Notes:
• When Auto Close Mode is enabled and the device is opened by UV3, the
recloser will remain opened until voltage is detected above the LSD threshold
on both sides of the recloser for the duration of the configured Auto Close time.
• When “Operation in SST only” is enabled, UV3 will ONLY operate when a UV3
protection operation is requested AND the device is in single shot mode.
UV4 Sag Protects against a voltage sag condition when the voltage drops within a user
defined window for greater than a user defined time (Operation Time).
OV1 Responds to positive sequence voltage rising above a user set level.
OV3 Responds to neutral displacement overvoltage rising above a user set level.
Note: When “Moving Average Mode” is enabled, OV3 values accumulate at each
quarter cycle and are averaged every 100ms. The calculated values of OV3
during the “Moving Average Window” are used instead of the instantaneous
values of OV3. When Moving Average Mode is enabled, an “Inhibit OV3 trip
functionality” is also provided which can be used in conjunction with ground
fault neutralisers and earth fault reduction techniques.
OV4 Responds to negative sequence voltage rising above a user set level.
ROCOF Responds to a rise or dip in the system frequency when it exceeds or falls
below a predetermined value.
Voltage Vector Shift Detects the vector shift in mains voltage and operates when the shift exceeds
the predetermined value.
PDOP Operates when the measured apparent power at the generator exceeds a
threshold
PDUP Operates when the measured apparent power at the generator falls below a
threshold
89
NOJA-559-23
Rate Of Change Of Frequency (ROCOF) protection is used to detect situations of loss of grid
such as islanding or loss of mains and trips the circuit to isolate the distributed generation
plant from the main grid.
ROCOF Settings can be configured from the “Frequency, Voltage and Power” tab for each
Group in Offline Settings.
Voltage Vector Shift (VVS) protection is used to detect sudden changes in the main voltage
angle caused by a change in the output from the generating plant or changes to the demand
connected to the network. It is primarily used to detect when islanding has occurred on an
embedded generation plant and initiates a trip to isolate the circuit from the main grid.
90
NOJA-559-23
VVS Settings can be configured from the “Frequency, Voltage and Power” tab for each
Group in Offline Settings.
Protection Directional Over Power (PDOP) and Protection Direction Under Power (PDUP)
can be configured from the “Frequency, Voltage and Power” tab for each Group in Offline
Settings.
91
NOJA-559-23
Figure 109: Directional Protection – Under Power and Over Power - features
Live Line protection for Overcurrent, Negative Phase Sequence (NPS), Earth Fault (EF) and
Sensitive Earth Fault (SEF) are configured from the “Live Line” tab.
Figure 110: Live Line Settings for OC, NPS, EF, SEF
92
NOJA-559-23
7.1.9 Common
Common settings for Overcurrent (OC), Negative Phase Sequence (NPS), Earth Fault (EF)
and Sensitive Earth Fault (SEF) are configured from the “Common” tab. These include:
• Maximum Number of Trips
• Cold Load Pickup
• Inrush Restraint
• Temporary Time Adder.
93
NOJA-559-23
7.1.10 Harmonics
The RC can measure Total Harmonic Distortion, Total Demand Distortion and Individual
Harmonics for Voltage and Current up to the 15th Harmonic. A total of five (5) individual
harmonics can be selected.
Harmonics Settings can be configured from the “Harmonics” tab for each Group in Offline
Settings.
94
NOJA-559-23
95
NOJA-559-23
▪ USB A, B, C shutdown – sets whether the ports are powered down when the External
Load Time expires. Used to power down communications equipment powered directly
from the USB port.
▪ Mobile Network Time – the length of time the Mobile Network Modem will continue to
run when AC supply is lost to the RC.
▪ Mobile Network Reset Time - the Mobile Network Modem can be turned off and on
again at regular intervals if required
▪ WLAN Time - the length of time the WLAN will continue to run when AC supply is lost
to the RC.
▪ WLAN Reset Time - the WLAN can be turned off and on again at regular intervals if
required.
You will need to set the Battery Test Auto Test to ON and enter a time interval.
Auto Test will initiate a battery test after the first time interval has elapsed. If the system is
restarted the counter for the time interval will be reset.
The battery test will apply a load across the battery for 30 seconds.
Note: The battery test can also be initiated manually at any stage by the user. Please refer to
Section 10 Online Operations.
96
NOJA-559-23
Each push button in an active key configuration can be enable/disabled. Un-ticking the box
for a button will mean no action will occur when the button is pushed on the panel.
97
NOJA-559-23
Note: Delayed Close sets a time delay before a manual Close operation is executed.
The user can change to another active key configuration but must ensure that the labels on
the panel are changed accordingly.
Notes:
98
NOJA-559-23
The following message will appear when changing an active key configuration to ensure the
labels on the panel match the new configuration.
Note: For single triple switchgear, “Phase to Phase Tripping” can be configured when in 1Ph Trip/1Ph
Lockout mode. When “Phase to Phase tripping” is enabled, if a phase to phase fault occurs the
control will trip and lockout all three reclosers when any one phase sequences to lockout.
99
NOJA-559-23
Fault Targets include binary fault targets (fault flags) and fault measured values. Fault
Targets are set when a protection operation has been initiated e.g. Open(OC) is set when
the recloser has opened due to overcurrent protection.
When “Reset Fault Flags on Close” is enabled, fault targets are reset automatically on a
close operation. This is the default setting.
Fault Targets can also be reset manually from the panel via the Reset Menu and the Alerts
page or through SCADA or Logic. Fault Locator Status measurements and “Open” signals
that are not fault targets will not be reset.
When alarms are configured as “Not Latched”, they will reset when the protection element
resets.
When alarms are configured as “Latched”, they will remain active when the protection
element resets. Alarms will reset automatically on a close operation if “Reset Flags on Close”
is enabled and can be manually reset from the panel via the Reset Menu and the Alerts page
or through SCADA or Logic.
Please refer to OSM User manual and relevant protocol document for more details.
The Simple Network Time Protocol (SNTP) can be used to allow the relay to synchronise
date and time with one of the configured servers. The second server will be used when
synchronisation with the first server fails. SNTP synchronisation will only occur while GPS is
disabled or GPS is enabled but not receiving a PPS signal.
100
NOJA-559-23
The Circuit Breaker Fail (CBF) feature is used to detect a failure of the recloser to open. It
does this by checking if current is flowing when it is in an open state, or by detecting an open
operation has failed to occur.
A signal can be generated to trigger a backup trip on an external device if a CBF fail
condition occurs.
CBF Settings can be configured from the “System Settings” tab for each Group in Offline
Settings.
101
NOJA-559-23
▪ Voltages
▪ Current
▪ Power
▪ Power Factor
▪ Frequency
▪ Energy
▪ Harmonics.
It registers up to 10,000 readings and up to 30 items can be selected for each interval record.
To configure the profile, go to the “Offline Settings” tab and click the “System” button.
Tick the boxes next to each item that is required to be logged by the RC.
Note: When the RC reaches 10,000 readings it will start discarding the oldest records.
The System settings will need to be downloaded to the RC for them to take effect.
For REL-20 or REL-20-4G, Line Supply, Peak Power and External Supply Power will be present.
7.2.12 Co-Generation
The synchronisation functionality can be used to connect incoming generators to the grid and
to re-establish a connection between two parts of the network or two islanded systems.
102
NOJA-559-23
• Sync-Check “supervises” the closing of a device and only allows a close when both
sides of the recloser are within the desired limits of frequency, phase angle and
voltage to permit the paralleling of two circuits.
• Auto-Synchronisation can be initiated via Online Operations and it will wait for the
auto-synchroniser conditions to be met prior to requesting a close of the device. If the
conditions are not met within the Auto-sync waiting time then a close will not be
requested. (Refer to section 10.16 Auto Syncroniser).
A user can also configure whether to allow or prevent a manual or automatic close under
various “Live-Dead” conditions.
Note:
• When synchronisation is enabled if the bus voltage or line voltage is less than the live voltage
limit and above the dead voltage limit any manual or automatic close will always be prevented.
• When reconnecting two dead sections during synchronisation, a close is allowed only if it is
configured.
The Fault Locator (21FL) functionality provides impedance based fault location estimation in
a radial distributed system. The 21FL function operates based on the measurements of
current and voltage phasors in the fundamental frequency (50 or 60Hz).
Fault Locator is applicable to OC, EF, SEF, OCLL, EFLL and SEFLL elements.
The following settings need to be configured before enabling fault locator:
103
NOJA-559-23
Length of Line (km) Length of line in forward direction from the relay.
Distance to fault is calculated in two steps. Firstly the fault type is determined then the
distance to fault is calculated based on the detected fault type. When the fault location
calculation is completed the following values are reported via SCADA or Logic:
• M Distance to Fault (km)
• Zf Magnitude of Fault Impedance
• θf Phase Angle of Fault Impedance (degree)
• ZLoop Magnitude of Faulted Loop Impedance
• XLoop Measured Positive Sequence Reactance from the Relay to Fault
Location
• θLoop Phase Angle of Faulted Loop Impedance (degree).
The Switchgear Calibration window has the measurement coefficients for the voltage and
current sensors inside the OSM tank. These are used to calibrate the signals received from
the tank to ensure correct readings within measurement specifications.
OSM# is the serial number of the OSM tank that these coefficients are related to.
104
NOJA-559-23
For Single Triple switchgear, the “Number of Switches” can be selected. If the number of
switches is 3 then the user is able to enter a serial number for each OSM tank. All three
switches use the same coefficients.
105
NOJA-559-23
The OSM serial number can be obtained from the name plate on the switchgear. The serial
number contains 13 characters where the following restrictions apply.
Note: The first three numbers define the switchgear type e.g.:
When the Demonstration Unit is set as Standard, the controller can operate as a single or
three phase device depending on the OSM switchgear type.
From firmware 1.14, if a SIM is not connected, enabling the Demonstration functionality (set
to standard or single triple) allows the unit to be opened and closed without the need to use
an OSM simulator in CMS. If a SIM is present or earlier firmware is used then the unit can
only opened and closed if the OSM Simulator is used in CMS.
106
NOJA-559-23
Two optional I/O modules can be installed as an accessory (I/O 1 and I/O 2).
The I/O screen is used to enable, disable and configure all inputs and outputs.
The I/O modules can be configured as a Remote or Local user. This means the RC must be
in the correct mode before a command can be executed by the I/O module.
The modules must be set to “Enable” to make them operational. This can be done through
Online Operations. Please refer to Section 10.6 I/O Configuration.
Input Settings
The inputs can be assigned to actions. These are selected from the drop down list next to
each input.
The inputs can be set to trigger on the rising edge (Edge Triggered = Yes) or when the input
voltage is level (Edge Triggered = No).
A recognition Time can be set for each input when Edge Triggered = No. This applies a delay
before activating the configured action.
107
NOJA-559-23
Output Settings
The outputs are activated in response to events. This can be an activation of a signal, a
SCADA I/O protocol point activation, or the output of a logic expression.
A recognition Time can be set for each output. This applies a delay before activating the
output relay contacts.
A reset time can be applied for each output. This sets a de-activation delay for the relay
contacts after the activating signal has de-activated.
The outputs can be set to operate as a Pulse (Pulse Enable = On). In this case the output is
activated when the condition is active, stays on for the Pulse Time, then deactivates.
If Pulse Enable is set to Off, the output activates when the signal is active and stays on until
the signal de-activates.
The RC has three digital inputs located on the Relay module (Local Inputs).
The Local Inputs can be Disabled and Enabled as one unit. Each individual input can be
enabled or disabled.
The three Local digital inputs can be assigned to actions. These are selected from the drop
down list next to each input.
The Local Inputs can be configured as a Remote or Local user. This means the RC must be
in the correct mode before a command can be executed by the I/O module.
A recognition Time can be set for each input. This applies a delay before activating the
configured action.
108
NOJA-559-23
7.4 Logic
7.4.1 Expressions
The expressions are evaluated as either true or false. The output result initiates actions,
activates SCADA points or I/O to initiate actions and/or turn on other additional expressions.
32 logic channels or variables are also available as outputs.
Note: Logic Channels 17-32 can be write protected. Please refer to section 10.13.
The expressions employ logic operators such as “or, nor, xor, and, nand, not and ( )” with
other variables such as pickup, open, alarm, closed, status, malfunction or any general
control or indication point.
A logic expression is evaluated on change of state of any of its input signals. Logic is also
evaluated upon download of logic settings from CMS and upon startup of the controller.
The Logic window can be accessed through Offline Settings -> Logic -> Logic Tab.
109
NOJA-559-23
Give the expression a Name – this is used to identify expression state changes in the event
log. Events are only registered if “Log Enable” is set to On.
Note: There is a limit of 7 characters to define the logic channel name. Further restrictions may
apply to languages other than English depending on characters used.
A logic expression window will be opened when you click inside the Expression field.
For example, the logic expression in Figure 138 will close the OSM recloser if it had
previously opened due to a loss of supply (UV3) and voltage has been detected on the ABC
side of the recloser.
110
NOJA-559-23
The expression output is set to Close. Therefore, when the expression is True, it will Close
the recloser.
The “Set When” field is set to “Either” in this example. This will cause the expression state to
reset back to False whenever the expression changes state.
A recognition Time can be set. This introduces a delay between the expression becoming
True or False (depending on the “Set When” condition) and the Expression Output being
activated or deactivated.
The Reset Time adds a delay between a reset condition occurring, and the resetting of the
expression’s output state.
The Expression Output will operate as either a latched output or pulsed output depending on
whether Pulse is enabled.
Please refer to RC Relay IO and Logic User Guide for more details.
User configurable analogues enable the user to add a new scale and offset to existing
measured values such as current, voltage and power.
The configurable analogues are available through the HMI panel, CMS and SCADA
protocols.
In CMS, the Analogues window can be accessed through Offline Settings -> Logic ->
Analogues Tab.
111
NOJA-559-23
Note:
• There is a limit of 8 characters to define the analogue name. Further restrictions may apply to
languages other than English depending on characters used.
• The scaling range is -4.29E-9 to +4.29E9 and the offset range is -4.29E-9 to +4.29E9.
112
NOJA-559-23
To configure DDT points go to Offline Settings - > Logic - > Dynamic Data Type.
• The name for the DDT point can use both upper and lowercase and its maximum
length is 15. Duplicate names are NOT permitted.
• The default type is UI32. Supported data types include: unsigned Integer (UI8),
signed integer (I8), unsigned integer (UI16), signed integer (I16), unsigned integer
(UI32), signed integer (I32) and float (binary32).
113
NOJA-559-23
NOJA Power’s Smart Grid Automation (SGA) enables customers to implement and deploy
distributed control and automation applications on NOJA Power’s Recloser Controller (RC) in
accordance with the IEC 61499 standard. Applications created in SGA are stored in an
“fboot” file and can be downloaded to the RC via CMS.
Please refer to NOJA-5019 Smart Grid Automation User Guide and NOJA-5018 Smart Grid
Automation Implementation for more details.
To launch SGA go to the Administration menu. Refer to section 12 CMS Administration for
more details.
To configure SGA go to Offline Settings - > Logic -> Smart Grid Automation.
Change the Mode to Enable and configure the TCP port number (default is 61499).
Note: The port number ranges from 1025 to 65335. It is the responsibility of the user to ensure that
the specified port number is not used by another service.
114
NOJA-559-23
Click “Finish”.
Once the import has finished go to Connection - > Download Settings to download the
fboot file to the device. Refer to section 5.3 Downloading Settings to the Device.
Note: When an fboot file is downloaded to the device via CMS, it is stored in non-volatile memory.
115
NOJA-559-23
When the SGA settings are downloaded to the device any fboot file installed is removed.
7.4.5 Alerts
Alerts are used to signal to an operator that an event has occurred. If active, the Alerts will
be displayed on the first screen when the HMI panel is turned on.
Alerts can include “Open” fault flags, fault measured values, open signals that are not fault
targets and any logic signal (using variables VAR1 to VAR32).
To configure Alerts:
1. Go to Offline Settings - > Logic - > Alerts.
2. Select “Enable” for the Alerts mode.
3. Select “Enable” for the mode of an individual alert.
4. Save settings.
5. Go Online with the device and download logic settings to the device.
Note:
• “Open” signals that are not fault targets and variables (VAR1 to VAR32) will not reset using
the “Reset Fault Flags on Close”, “Reset Fault Targets” or “Reset Binary Fault Targets”.
• The reset of a variable is dependent on the logic and its associated expression.
• Any non-zero value will result in the Alerts page remaining active.
116
NOJA-559-23
You will notice that a number of “Open” alerts are already listed and can be enabled. To
create a new alert, click in an “Expression” field and select an alert from the “Expression”
form. “Open” fault flags, fault measured values and variables are available for selection.
117
NOJA-559-23
Once you have selected an alert, click “OK”. The name of the alert will appear in the
“Expression” and “Name” fields. You can edit the name if you wish.
Note: There is a limit of 18 characters to define the logic channel name. This applies to all
languages.
Set the mode for the new alert to “Enable” and ensure the Alerts mode is also enabled.
118
NOJA-559-23
Once you have finished ensure you download the Logic settings to the device.
Note: When enabling a protocol, after the download of protocol settings to the device, you will need
to restart the controller for the protocol to be loaded into memory. Please refer to section 5.3
for more details.
Next, the protocol must be assigned to a communications channel by selecting a port and
connection type. The Configure link opens the Comms configuration window for complete
configuration of the chosen port.
The Reset button on the right resets all the protocol settings and points back to their default
factory state.
The Show Enabled box only displays enabled protocol points when ticked.
For REL-20-4G, “LAN 2” port will be visible in the Communication Channel if the protocol has
LAN option available.
119
NOJA-559-23
The tabbed screens are used to configure the chosen communications protocol.
Please refer to the relevant NOJA Power protocol document for more information.
7.5.1 DNP3
120
NOJA-559-23
For more details on DNP3-SA please refer to 12.6 Generate DNP3 Key and section 10.15
DNP3 Security Authentication (DNP3-SA).
Security Statistics for DNP3-SA can be observed through the “Security Statics” tab.
121
NOJA-559-23
122
NOJA-559-23
Please refer to NOJA-5604 IEC60870-5-101 and 104 Protocol Implementation for more
information.
The RC10/15 supports Multi-Master Redundancy Groups and Connections as defined in the
IEC 60870-5-104 Standard. This provides multiple Master stations to connect to the RC
cubicle using two defined methods (Method 1 and Method 2).
For a full description of the settings and options provided for this feature, please refer to the
NOJA-5604-17 IEC60870-5-101 and 104 Protocol Implementation document.
Multi Master capabilities are configured from the “IEC 60870-5-101/104” tab in Protocol
Settings under Offline Settings.
123
NOJA-559-23
124
NOJA-559-23
Tick the functionality you would like to enable and configure the appropriate communication
channel.
Note: Any Ethernet based connection can be selected for IEC 61850 MMS and GOOSE.
125
NOJA-559-23
Click “Browse” and select a file with a *.cid or *.icd extension and click “Open”.
Notes:
• If a CID file is not available, upon download of protection settings, any existing CID files on the
device will be removed.
• A NOJA CID file is supplied with each firmware release.
Once the file is imported go to Connection - > Download Settings to download protocol
settings to the device.
126
NOJA-559-23
Go to the “GOOSE Subscription” tab and click “Browse”. Select an SCL file and click “Open”.
The file may have any of the following extensions: *.icd, *.cid, *.iid or *.scd.
Once a file is selected, the information you can subscribe to, from the other device, will be
displayed.
127
NOJA-559-23
The information will then be displayed in the “GOOSE Subscription” tab in CMS.
You can then map each subscribed data set from the other device to your device as shown
below.
Notes:
• If you wish to do another subscription using the same file, the data attributes that have already
been selected will not appear in the IEC GOOSE Publisher Information window but they will
be there in the GOOSE Subscription window in CMS.
• Once GOOSE Subscription has been configured, the IED name should not be changed.
Please refer to NOJA-5005 IEC 61850 IED Definition and Conformance Statement, NOJA-
5017-00 IEC 61850 RC Logical Nodes Definition and NOJA-5036 IEC 61850 User Guide for
more information.
128
NOJA-559-23
Peer to Peer Settings is for ACO Communications. Please refer to NOJA-594 OSM Auto
Change Over with Recloser Control User Manual for more information.
PMU settings are only applicable to REL-20-4G. The PMU provides synchronized phasor,
frequency and rate of change of frequency estimates from voltage and/or current signals and
a time synchronizing signal.
129
NOJA-559-23
Notes:
1. PMU only supports Ethernet Comms.
2. To transfer PMU data, PMU settings have 12 analogue and 4 digital channels, which are
configured by the user in the CID file. The 12 analogues can be mapped to the User
Configurable Analogues in the Relay and the 4 digitals can be mapped to Logic VARs.
3. Analogues, Digital and all measured phasor values shall only be included in the
synchrophasor messages if enabled by the user in the CID file.
4. For 1 phase device, if the user includes more than one phase in the synchrophasor
messages, then PMU will display the IEEE NaN floating-point value for the non-applicable
voltage and current phase values and will set the ‘Absent Data’ error value in the PMU Stat
field.
Various relay modules are available which provide different port options as shown below:
Table 16: Port options for Relay modules
Communication Ports
Relay RS232 USBA USBB USBC LAN Wi-Fi 4G GPS
REL-01 X X X X
REL-02 X X X X X
REL-15 X X X X X X
REL-15-4GA (Europe/APAC) X X X X X X X
REL-15-4GB (Americas) X X X X X X X
130
NOJA-559-23
Notes:
• To establish a remote connection to the device, once the port is configured, the CMS Protocol
must be assigned to the port and the CMS connection must be configured. Refer to 8.2
Configuring a Remote Connection.
• The RS-232P is the RC Panel communications port. DO NOT change these settings from
default as this will cause the Panel to stop working.
When a connection type is chosen from the drop down box, the appropriate fields are made
available.
The configuration fields available for each port are described in NOJA-565 RC SCADA
Interface Manual and also in the relevant Protocol Implementation document.
The “Reset to Default” button on the right resets all settings back to their default factory state
7.6.1 USB
Please refer to OSM User manual and NOJA-565 SCADA Interface Description for more
details.
131
NOJA-559-23
7.6.2 LAN
LAN settings are not supported in REL-01. For REL-20-4G, “LAN 2” port will also be present.
IPv4 and IPv6 Ethernet addresses are supported.
Please refer to OSM User manual and NOJA 565 SCADA Interface Description for more
details.
132
NOJA-559-23
Figure 168: Ethernet Port Configuration, error message if appropriate relay is not installed
7.6.3 WLAN
WLAN is available for REL-15 and REL15-4G relays. It can be configured as an Access
Point or as a Client. “IPv4” and “IPv6” are supported.
133
NOJA-559-23
When configured as an access point up to four clients can connect to the device. By default
IP addresses are assigned automatically and the wireless network is hidden.
Please refer to OSM User manual and NOJA-565 SCADA Interface Description for more
details.
Note:
• SSID is the name of the Access Point and is configurable. The default is NOJA-#Relay Serial
Number#. If you tick “Hide the Wireless Network”, the SSID will not be broadcast.
• In access point mode, the default value for the Network key (or password) is “12345678”.
• Subnet Mask is not configurable.
• Channel numbers 12 and 13 are not permitted in the US.
134
NOJA-559-23
Note:
• SSID is the name of the Access point you would like to connect to.
A SIM card is required and it has to meet standards specified in the OSM User Manual.
The user has the option to use the SIM card’s network settings or add configuration details
as shown below.
Please refer to OSM User manual and NOJA-565 SCADA Interface Description for more
details.
IPv4 or IPv6 are supported. But both are not supported at the same time.
135
NOJA-559-23
7.6.5 RS232P
This is the serial port for the HMI Panel. It is recommended that the settings are not modified.
The System Default Gateway settings allows the user to set a priority for which default
gateway is used. Also, if a port is inactive, the system can use the next available gateway in
the priority list.
136
NOJA-559-23
137
NOJA-559-23
▪ uses the “Fast Fourier Transform” or FFT algorithm to provide exact values for
the harmonic frequency and its magnitude
▪ captures an oscillogram of the waveform (IEEE COMTRADE format)
▪ captures information for short and long interruptions (IEEE P1159.3 PQDIF
format)
▪ records the number of sags and swells (IEEE P1159.3 PQDIF format).
Data is logged and can be analysed to determine the power quality flowing through the
device using the Power Quality Software (PQS) installed on a PC.
For more details on Power Quality please refer to the OSM user manual.
CMS allows the user to configure Power Quality settings which include: Oscillography,
Harmonics, Interruptions and Sags/Swells.
138
NOJA-559-23
7.7.1 Oscillography
CMS allows the user to configure how the RC captures oscillography data:
For REL-20 and REL-20-4G devices, “Save to USB” and “Save to Internal Memory” will be
greyed out.
7.7.2 Harmonics
The RC controller measures Total Harmonic Distortion (THD), Total Demand Distortion
(TDD), Harmonic Current (HRM_I) and Harmonic Voltage (HRM_V) up to the 15th harmonic.
An independent deadband can be defined for each of these as shown below.
A single timer setting for all deadbands is available such that when the harmonic exceeds the
user set deadband for the user set time period, the value at the end of that time period will be
logged.
139
NOJA-559-23
7.7.3 Interruptions
The long and short duration interruption information collected can be used to calculate
System Average Interruption Duration Index (SAIDI), System Average Interruption
Frequency Index (SAIFI) and Momentary Average Interruption Frequency Index (MAIFI).
The RC allows the user to set a duration to determine the difference between a short and
long interruption, and can log all the information relevant to each of these interruptions
separately. If the duration time is set to zero it will capture all interruptions as Long Duration
Interruptions.
140
NOJA-559-23
Sags
A voltage Sag occurs when one or more of the 3 phase voltages fall below the Sag Normal
Threshold voltage. The Sag ends when all of the 3 phase voltages are equal to or greater
than the Sag Normal Threshold voltage.
Swells
A voltage Swell begins when one of more of the 3 phase voltages is above the Swell Normal
Threshold voltage and ends when all of the 3 phase voltages are equal to or less than the
Swell Normal Threshold voltage.
141
NOJA-559-23
8 Connecting to a device
CMS can connect to the RC directly via the local USB port below the Operator Panel.
Alternatively it can connect to a remote device through serial modems, Ethernet, Wi-Fi or
Mobile Network connections. The local USB connection is not affected and will still work as
normal, but only one CMS session can be connected at a time.
To connect to a local device use a USB Type A to B cable (max length of 3m) to connect to
the panel USB port on the RC. Please note that a USB extension cable with a power supply
may be used.
To configure the communication between CMS and the device, click on “COMMS
Configuration” from the “Connection” tab. The Connection type should be configured as
“USB Direct” as shown below. The protocol used is CMS.
Once the connection type has been configured to USB Direct, go to the Connection toolbar
and click the “Go Online” button.
142
NOJA-559-23
For mobile network connections, the following must be obtained from the
telecommunications provider:
• SIM Card
• Static IP Address
• Access Point Name with username and password.
For Wi-Fi connections you will need IP settings and details for the Wireless Network Key.
If using the USB port, the equipment must be connected through a NOJA Power approved
USB device. NOJA Power supports the following approved USB equipment:
▪ USB RS232 (this allows an additional serial port if the RS232 port is already in use)
▪ USB RS485
▪ USB Ethernet port (connects to routers and other ethernet port equipped devices)
▪ USB Wireless Ethernet (connects to wireless routers)
Any communications equipment with an RS232 port should work through the RS232 Serial
port on the Relay.
To configure the port, click on the “COMMS” button in the “Offline Settings” tab. Select the
port and configure as required.
143
NOJA-559-23
Notes:
• “WLAN” and “Mobile Network” are available in the Relay 15 module.
• For Mobile Network connections the following must be obtained from the telecommunications
provider:
o SIM Card
o Static IP Address
o Access Point Name with username and password.
• For WLAN connections you will need to enter IP settings and details for the Wireless Network
Key. In access point mode, the default value for the Network Key is “12345678”.
• When using serial connections for the CMS protocol it is recommended that a baud rate of
9600 and above is used.
Save changes by clicking the disk icon in the top left hand corner.
Once the port is configured, the CMS Protocol must be assigned to the port. Click the
“Protocol Settings” button from the “Offline Settings” tab, and select the “CMS” tab.
Tick the “Enable Port 2” box, and select the required port from the drop down box.
Save the changed settings by clicking the disk icon in the top left hand corner.
144
NOJA-559-23
Notes:
• Two ports are available for the CMS protocol. Port 1 is used for direct connections to the RC
(using the Panel USB port) and Port 2 is used to communicate remotely to the RC.
• For “LAN”, “WLAN” and “Mobile Network” you will need to enter a TCP port number.
Ensure you have a direct connection to the RC to download the Comms and Protocol
settings to the device. Please refer to Section 8.1 Connecting to a local device and Section
5.3 Downloading Settings to the Device.
After the download of settings, go to Field Readings - > COMMS Status and confirm the
following:
• SSID and AP IP address (WLAN connection)
• IP address (LAN and Mobile Network connection).
If using a Mobile Network connection ensure the SIM card is inserted in the SIM card slot on
the relay. If using a modem or Ethernet connection ensure you have the communication
equipment or cable connected to the relay in the corresponding port.
Change the connection method from USB Direct in the drop down box to Modem or Ethernet.
For an Ethernet connection enter the IP address and TCP Port number configured in Offline
Settings - > COMMS.
145
NOJA-559-23
Note: “Ethernet connection” is used for LAN, WLAN, Mobile Network and USB ports where an
Ethernet device is used.
For a modem connection, select the “Modem Settings” tab and select the Com Port, Baud
Rate and Phone Number to be used by CMS when dialling the remote RC cubicle.
146
NOJA-559-23
Note: When using serial connections for CMS protocol it is recommended that a baud rate of 9600
and above is used.
The “Poll Configuration” tab sets how often CMS will ask for Device Status and Field
Readings changes.
The Device status poll checks the current state of the recloser position and protection
elements. The default setting is normally correct for all connection types.
The Field Readings poll asks for the latest changes to the System Status, Event Log,
Change Log, Close Open Log, Load Profile, Counters and Comms Status logs. If the log files
are large, it can take a while to download them over a slow modem connection. This may
cause Device Status updates to slow down. If this is the case, lengthen the Field Readings
poll time to about 60 seconds.
147
NOJA-559-23
Tick the box if you wish to download the latest Field Readings logs when going Offline.
“Maximum Frame Size” is available for RS232 Direct, USB Direct and Ethernet connections.
Allowable range is 512 – 4096 bytes.
Note:
• Frame size is dependent on limitations of the network and on the equipment used.
• Allow for overheads e.g. if a network transmission frame size of 1024 bytes is required and the
TCP maximum header size is 60 bytes then the CMS maximum frame size = 1024 – 60 = 964
bytes (or less.)
Remember to save the settings by clicking the disk icon in the top left hand corner.
8.2.5 Go Online
If you are using WLAN, you will need to firstly connect to the SSID (Access Point) using the
network name and wireless network key configured in Offline Settings - > COMMS - >
WLAN.
If you are using an external modem or router, ensure the communication equipment is
connected and turned on.
148
NOJA-559-23
9 Control
The “Control” tab will appear when CMS is online. To go online click the “Go Online” button
from the “Connection” tab.
Note: For single phase switchgear NPS, Earth Fault, OV3 and Yn Admittance is greyed out.
For single triple devices additional control options are provided for each phase.
When the switchgear is in “3Ph Trip/3Ph Lockout” or “1 Ph Trip/3Ph Lockout” mode, the open
and close buttons operate in the same way as three phase and single phase reclosers.
When the switchgear type is in “1Ph Trip/1Ph Lockout” mode, a message will be displayed
asking the user to select which phase to open or close, as shown below:
For details on each of the controls please refer to the OSM User Manual.
149
NOJA-559-23
10 Online Operations
The “Online Operations” tab will appear when CMS is online with a device. To go online,
ensure the device is directly connected to the PC and that the connection status for the
device is “Plugged In”.
Select the device and click the “Go Online” button from the Connection tab.
The “Online Operations” tab will allow the user to do a number of things including:
▪ Erase Data
▪ Reset control points and USB hardware
▪ Synchronise Date & Time
▪ Control and Configure the Device
▪ Test the battery
▪ Initiate Auto-synchroniser
▪ Start and Stop a Simulation.
CMS has a Simulator Module which is a licensed feature. Contact NOJA Power Switchgear
to obtain a product licence. For more details, please refer to section 11.8 and NOJA-7123
CMS Simulator User Guide for more details. Simulation Control will only appear once a
license has been obtained.
150
NOJA-559-23
10.2 Reset
The following can be reset while Online:
▪ Restart GPS Hardware1
▪ Reset Logical Block Close
▪ Restart Mobile Network Modem1
▪ Restart Wi-Fi Hardware1
▪ Reset USB Overcurrent2,3.
Note:
1. Only available for relay 15 modules.
2. When an overcurrent draw is detected on a USB port, the relay will stop power to that
port. The device causing the overcurrent will be displayed as a critical parameter in the
event log. Any faulty USB devices should be removed. Power can be restored to the port
using “Reset USB Overcurrent” from the Reset Menu while Online.
3. USB devices include on-board USB Ports A/B/C, Wi-Fi hardware, Mobile Network Modem, GPS
hardware and any external devices on a USB port.
151
NOJA-559-23
Note: “External Load On/Off” can only be operated when in local mode.
Two optional I/O modules can be installed as an accessory (I/O 1 and I/O 2). Once
connected they must be enabled in Online Operations and then configured in Offline Settings
(refer to Section 7.3 Input Output Configuration).
Life time counters calculate and record the total number of Close/Open (CO) Operations and
Contact Wear.
152
NOJA-559-23
The Auto Change Over (ACO) system provides automatic switch over from one supply to
another. It requires two OSM Reclosers and two controllers mounted back to back with a
common load.
Refer to the OSM User manual and document NOJA-594 ACO User Manual for more details.
A new device will appear at the bottom of the screen and can be added to the CMS device
list. The old device can then be deleted from the device list.
Notes:
153
NOJA-559-23
• If a SIM-02 module is present in the RC then the switchgear type will be set to Single Triple
and cannot be modified.
• Please refer to section 7.2.14 Switchgear Calibration for details on OSM Serial number.
To run a battery test on a regular basis go to Offline Settings - > System Settings. For more
details, refer to Section 7.2.3.
154
NOJA-559-23
Note:
• If the battery is not connected, AC not applied, battery is discharging at > 100mA or battery voltage <
12.5V then a “Battery Test Not Performed” will be indicated.
• If a battery test is performed the next test will be blocked for 5 minutes. If an attempt is made to initiate a
battery test during this period then a “Battery Test Not Performed” will also be indicated. The reason
being that the battery test circuit is resting.
• If the Battery Test Circuit is faulty, “Battery Test Circuit Fault” will be indicated.
Click on “Logic CH 17-32 Write Prot” to enable/disable write protection. A message will be
displayed to confirm the operation.
Note: By default the logic channels 17-32 are not write protected
155
NOJA-559-23
Enabling and disabling of DNP3-SA is only be permitted through CMS when connected to
the local USB port and the system is in local mode.
If CMS is connected to the device via a remote connection or the update key is not installed
on the device then this option is greyed out.
156
NOJA-559-23
157
NOJA-559-23
Select a simulation. A message box will be displayed asking the user to confirm executing
the simulation.
Click “Yes” to confirm executing the Simulation. The simulation will start injecting values.
For more details, please refer to section 11.8 and NOJA-7123 CMS Simulator User Guide for
more details.
158
NOJA-559-23
11 Libraries
In the “Libraries” tab you will find:
• Time Current Characteristic (TCC) Library
• Simulation Library
• Standard Curves.
The TCC library allows you to configure settings for particular zones/areas which can then be
easily accessed when configuring protection settings for a device. Please refer to section
11.2 TCC Library.
The Simulator Module is a licensed feature. Please refer to Section 11.8 on how to obtain a
license for this feature. Once the license is obtained the simulation section will be displayed
in the “Libraries” tab.
The list of Standard Curves includes User Standard Curves which are created by the user.
For details on converting a Standard Curve to a User Curve please refer to section 7.1.4
Creating a User Defined Curve.
To create a new TCC, click on “New” from the TCC section in the “Libraries” tab.
Click on the Save disk icon, in the top left hand corner.
159
NOJA-559-23
The TCC library allows you to create and maintain a list of curves with their applicable
settings. These curves can then be used to configure protection settings for a device. This
makes it particularly useful when you want to configure devices with the same settings in a
particular zone/area.
TCC Curves can also be used to display background curves. Please refer to 7.1.2 Protection
Curves.
The curves created in the TCC library can be accessed from Offline Settings.
A TCC library drop down menu is available in each of the forward and reverse powerflow
settings as shown below. From here you can load settings from a TCC.
You can also save the current settings to a new TCC so that it can be easily used elsewhere.
160
NOJA-559-23
To open a TCC item, click on the “Open” button from the TCC section in the “Libraries” tab or
double click on an item from the TCC library list.
161
NOJA-559-23
To import a CMS file, click on “Import” from the TCC section in the “Libraries” tab.
Click “Browse”.
162
NOJA-559-23
If a TCC with the same name already exists you will be asked to skip importing the TCC or
create a new TCC.
A message will be displayed indicating the result of the import.
To export a TCC item click on “Export” from the TCC section in the “Libraries” tab.
Select the TCC item(s) and browse to select the destination folder.
Click the Export button.
163
NOJA-559-23
The list of Standard Curves includes User Standard Curves which are created by the user.
For details on converting a Standard Curve to a User Curve please refer to section 7.1.4
Creating a User Defined Curve.
Standard Curves may be used to configure protection settings for a device via Offline
Settings or to configure a TCC. Refer to section 11.2 TCC Library.
User Standard Curves may only be removed if they are not currently in use by a device or a
TCC curve.
In the example below, the User Defined Curve, “New Standard Curve 1” cannot be removed
as it is used by the device “NOJA Recloser 1” and TCC Curve “OC Curve Zone C Brisbane”.
164
NOJA-559-23
To request a Simulation License, click on “License Details” from The “Administration” tab.
From the System Licence Information screen, click on “Request for new license”, enter
details and click “Send email”.
165
NOJA-559-23
166
NOJA-559-23
When the email with the license file is received, click on “Add new license file”.
Browse for the path to the license file and click “Add license”.
Once the license is added the Simulation section will appear in the “Library” tab as shown
below.
167
NOJA-559-23
To create a new Simulation, click on “New” from the Simulation section in the “Libraries” Tab.
The Residual Current “In” and its angle will be calculated automatically based on the value
and phasing of Ia, Ib, Ic.
Note:
• Make sure you select the correct switchgear type. Use “Single Triple” for single triple devices
and “Standard” for all other devices.
• Make sure to tick the “Use OSM Simulator” communication box to engage the binary OSM
simulator if you don’t have a connection to a recloser tank.
168
NOJA-559-23
• The CMS simulator is used to test analogue signals which have not undergone any
processing. As a result, there are certain features which cannot be tested e.g. powerflow
direction change, phase configuration and power quality data (aside from fundamental
harmonics).
• The CMS simulator does not take into account the configured phase connection and
powerflow direction. Instead the simulator presumes that the phase sequence is ABC and the
power flow is RST to ABC.
Save changes by clicking the disk icon in the top left hand corner.
End conditions are the event that must be achieved before the simulator moves on to the
next step in the sequence. The values specified in that row will continue to be injected until
the condition is met. Timeout condition is a set time and the setting is in milliseconds.
For standard devices, end conditions include Timeout, Open and Close.
For single triple devices, end conditions include: Timeout, All Phases Open, All Phases
Closed, 1 Phase Open, 1 Phase Closed, Any Open, Any Close, Ph A Open, Ph B Open, Ph
C Open, Ph A Close, Ph B Close, Ph C Close.
In the sample simulation below, 40 amps is injected for 10 seconds then the simulator moves
on to the next step where 305 amps is injected until the OSM goes into Open position (or
could use “Phase B Open” for single triple devices). The time taken for the OSM to move to
open and the completion of this step will be dependent on the selected protection settings of
the device.
169
NOJA-559-23
The following simulation could be used to demonstrate the Auto Reclosing functionality on a
standard device where AR is enabled, the AR sequence for OC1+ is set to R-R-L and the
pickup current for OC1+ is set to 300 A.
Note: The “Close” end condition is used in steps 3 and 5. Using “Close” in this instance is more
reliable than using “Timeout” and it works for all reclose times.
Please refer to Section 10 Online Operations for starting and stopping a simulation and to
NOJA-7123 CMS Simulator User Guide for more details.
170
NOJA-559-23
The Simulation library maintains a list of simulations which have been added.
Please refer to Section 10 Online Operations for starting and stopping a simulation and to
Section 11.9 Creating a New Simulation for more details.
To open a Simulation click on the “Open” button from the Simulation section in the “Libraries”
tab or double click on an item from the Simulation library list.
171
NOJA-559-23
Please refer to Section 10 Online Operations for starting and stopping a simulation and to
Section 11.9 Creating a New Simulation for more details.
To import a Simulation file, click on the “Import” button from the Simulation section in the
“Libraries” tab.
Click “Browse”.
172
NOJA-559-23
173
NOJA-559-23
If the Simulation already exists in the Library the following message will appear.
To export a Simulation, click on the “Export” button from the Simulation section in “Libraries”
tab.
174
NOJA-559-23
175
NOJA-559-23
12 CMS Administration
The CMS Administration menus are used to:
• Update System properties
• Manage Users
• Configure DNP3-Security
• Perform Backups and Restores
• Update license details
• Launch Smart Grid Automation.
System Properties allows you to enter system information and shared folder details.
The system information includes system name, description and default system language.
Languages currently supported include English, Spanish and Portuguese.
Use the down arrow to change a language. CMS will need to restart to apply the change.
176
NOJA-559-23
12.2 Licences
CMS has advanced features available such as a power system simulator. Advanced features
require a licence before they are available for use.
To see what licences are installed, click on “License Information” from the “License Details”
page in the “Administration” tab.
177
NOJA-559-23
To request a license, click on “Request for new license”, from the “License Details” page in
the “Administration” tab.
178
NOJA-559-23
When the email with the license file is received save it to a secure location.
Click on “Add new license file” from the “License Details” page in the “Administration” tab.
Browse for the path to the license file and click “Add licence”.
179
NOJA-559-23
CMS provides user management functions that allows a user with “Administrator” access to
add, edit and delete users.
The first user to login after installing CMS will have “Administrator” access.
The “User Manager” window can be accessed from the Administration tab. It displays the
users that have been created and the permissions that they have been granted.
Click the “New” button from the “Administration” ribbon menu to add a new user to CMS.
180
NOJA-559-23
Press the Next button. The wizard will then confirm that the user was created successfully.
181
NOJA-559-23
You can edit the name and indicate if the user is active.
182
NOJA-559-23
To make a backup of the CMS database click on “Backup” from the “Administration” tab.
Click “Browse” to select a path and file name for the backup.
Note: If a backup file with the same name already exits it will be overwritten. It is recommended that
the user creates a new folder for each new backup.
183
NOJA-559-23
CMS will only allow a restore from a database that was created with the same version of
CMS.
Note: Restoring from a backup that was created with an older or newer version of CMS is not
possible.
A message will be displayed indicating that CMS will need to restart to complete the action.
184
NOJA-559-23
The following requirements must be adhered to when creating the DNP3-SA configuration file:
• Permitted characters are A-Z, a-z, 0-9, space, “.”, “-”.
• Config File Version and Update Key version permitted numbers range from 0.0.0 to
255.255.255.
• User Number must be 1 (other numbers may be supported in future releases).
• User Role can be “1” (Operator) or “32768” (Single User).
• Serial number must be a valid RC serial number (13 characters).
• The Update Key must be in hexadecimal format (32 or 64 characters).
• Verification method determines how the RC will find its Update key in the file. If it is set to “0”
the RC will use the update key that matches its serial number in the file. If it is set to”1” it finds
its associated update key by matching the serial number and DNP3 address.
Once the configuration file is created you can use CMS to generate the DNP3 Update Key file.
Browse to select the DNP3-SA configuration file (*.csv) and select output file (*.bax) and location.
Click “Generate”.
185
NOJA-559-23
A message will be displayed indicating that the security key generation was successful.
The DNP3 Update Key can only be uploaded via a USB flash drive connected to the relay.
The file must be in the “\rc10\Updates” folder on the USB flash drive. Please refer to the
OSM User manual for more details.
186
NOJA-559-23
DNP3-SA can then be enabled through Online Operations. Please refer to section 10.15 for
more information.
The status of the DNP3-SA Key Update and DNP3-SA mode is displayed in Field Readings
-> System Status -> System menu.
DNP3-SA parameters can be configured via the DNP3 protocol page. Please refer to section
7.5 Protocol Settings.
187
NOJA-559-23
Click “OK”.
Please refer to NOJA 5010 Smart Grid Automation (SGA) User Guide for detailed
information on SGA.
188