Chilled Water Fan Coil Units: Supply Air
Chilled Water Fan Coil Units: Supply Air
Chilled Water Fan Coil Units: Supply Air
COOLING CAPACITY SUPPLY AIR WATER PIPE CONN. POWER INPUT DIMENSION
UNIT DESIGNATION MODEL QTY TYPE DRAIN REMARKS
KW HP TR CFM FLOW RATE INLET/OUTLET POWER INPUT VOLT PHASE HERTZ WxDxH
FCU A-4.5kw FP-85XD/B-T 1 CEILING CASSETTE 4.5 1.60 1.28 471 0.21LPS 3/4" 33MM 75W 220 1 60 840x840x190 "GREE-BRAND"
FCU-4KW FP-51WAF-R 12 CEILING CONCEALED 4 1.43 1.14 324 0.19LPS 3/4" 33MM 59W 220 1 50 1011x510x245 "GREE-BRAND"
FCU-7.5kw FP-102WAF-R 4 CEILING CONCEALED 7.5 2.68 2.13 601 0.35LPS 3/4" 33MM 105W 220 1 50 1371x510x245 "GREE-BRAND"
FCU-9.2kw FP-136WAF-R 4 CEILING CONCEALED 9.2 3.29 2.62 854 0.43LPS 3/4" 33MM 151W 220 1 50 1761x510x245 "GREE-BRAND"
CIEF - 88W,650CMH DA-1965,INLINE FAN 1 88W 220 1 50 CFM CUBIC FEET PER MINUTE SAD SUPPLY AIR DIFFUSER
650CMH
FCU FAN COIL UNIT FD FLEXIBLE DUCT
ACCU AIR COOLED CONDENSING UNIT BD BACKDRAFT DAMPER
AHU AIR HANDLING UNIT VD VOLUME DAMPER
CHWR CHILLED WATER RISER CHWP CHILLED WATER PIPE
GENERAL NOTES:
1. ALL MECHANICAL WORKS SHALL BE DONE IN ACCORDANCE WITH THE LATEST REQUIREMENTS OF THE X
'X' DENOTES UNIT, '0' DENOTES UNIT CAPACITY FAN COIL UNIT (CEILING CASSETTE TYPE)
PHILIPPINE BUILDING CODE REGULATIONS. 0
3. ALL EQUIPMENT SHALL BE PROVIDED W/ VIBRATION ISOLATOR. AIR SUPPLY DIFFUSER RETURN AIR GRILL
4. ALL FANS SHALL BE PROVIDED WITH SUITABLE FLEXIBLE CONNECTIONS TO THE INTAKE AND DISCHARGE FLEXIBLE METAL CONNECTOR 'M' DENOTES WIDTH, 'N' DENOTES DEPTH
DUCTWORK. 'O' DENOTES VOLUME FLOW RATE IN CFM
MOTORIZED VALVE
6. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS INDICATING ACTUAL EQUIPMENT DIMENSIONS AND
PROVISIONS FOR THE DUCT PASSAGES THRU WALLS, FLOORS AND ROOFS SHALL BE COORDINATED IN FRESH AIR GRILL
ADVANCE WITH THW INTERIOR DESIGNER/CONTRACTOR. WYE STRAINER
PROFESSIONAL MECHANICAL ENGINEER PROJECT TITLE PROJECT OWNER NOTES SHEET CONTENTS REVISIONS DESIGNED BY : FRUCTUSO GARCIA III SHEET NO.