Service Manual: VLT HVAC Basic Drive FC 101
Service Manual: VLT HVAC Basic Drive FC 101
Service Manual: VLT HVAC Basic Drive FC 101
Service Manual
VLT® HVAC Basic Drive FC 101
Contents VLT® HVAC Basic Drive Service Manual
Contents
1 Introduction 6
1.1 Purpose 6
1.2 Product Overview 6
1.3 Safety 6
1.4 Electrostatic Discharge (ESD) 6
1.5 Tools Required 9
1.6 Electrical Installation in General 10
1.7 Exploded Views – H Frame Size 11
1.8 Exploded Views - I Frame Size 14
1.9 Ratings Tables 17
1.9.1 Short Circuit and Over-current Trips 17
1.9.2 DC Voltage Levels 17
4 Troubleshooting 31
4.1 Troubleshooting Tips 31
4.2 Exterior Fault Troubleshooting 31
4.3 Fault Symptom Troubleshooting 31
6 Test Procedures 46
6.1 Non-repairable Units 46
6.2 Introduction 48
6.3 Static Test Procedures 48
6.3.1 Pre-requisite 48
6.3.2 Rectifier Circuit Test 49
6.3.3 Inverter Section Tests 49
6.3.4 Intermediate Section Tests 50
6.3.5 Location of UDC Terminals 50
6.4 Dynamic Test Procedures 52
6.4.1 No Display Test (Display is Optional) 53
6.4.2 Input Voltage Test 53
9 Block Diagrams 96
9.1.1 H6 Frame Size 96
9.1.2 I6 Frame Size 97
9.1.3 H7, H8, I7, I8 Frame Size 98
9.1.4 H9 Frame Size 99
9.1.5 H10 Frame Size 100
Index 101
1 1 1 Introduction
CAUTION
Frequency converters contain dangerous voltages when 1.4 Electrostatic Discharge (ESD)
connected to mains. Only a trained technician should carry
out the service. See also warnings in 2.1 Introduction.
CAUTION
When performing service, use proper Electrostatic
CAUTION Discharge (ESD) procedures to prevent damage to sensitive
components.
For dynamic test procedures, main input power is required
and all devices and power supplies connected to mains are
energized at rated voltage. Take extreme caution when Many electronic components within the frequency
conducting tests in a powered frequency converter. converter are sensitive to static electricity. Voltages so low
Contact with powered components could result in that they cannot be felt, seen, or heard can reduce the life,
electrical shock and personal injury. affect performance, or completely destroy sensitive
electronic components.
• Analog voltmeter
• Oscilloscope
Table 1.6
Table 1.7
130BC341.10
13 14
12
11
10
9
7 15
3
4
2
6
5
16
17
1 18
Table 1.9
1 1 17 18
130BC342.10
14 16
15
12 19
13
11
9 10 20
8
7
3 5 22
21
6
4
2
23
24
Table 1.10
1 1
130BC214.11
19
18
20
17
16
15
14
21
13
12
11
22
10
7
6
5
2
3
1
4
Table 1.11
1 1
1.8 Exploded Views - I Frame Size
130BC046.11
10
7 9
8
5
6
4
2 3
13
14 12
15
11
16
Table 1.12
1 1
130BC215.11
16
15
14
13
12
17
11
10
9 18
8
19
7
20
6 21
5
4
3
22
2
1
23
24
25
Table 1.13
1 1
130BC216.11
11
10
6 7 8
2 4 5
3 12
1
14
13
18
16 15
17
19
1 LCP 11 DC coil
2 Front cover 12 Rectifier modules
3 Cradle 13 IGBTs
4 LCP gasket 14 Capacitors
5 Control card 15 Heatsink fan assembly
6 Control card mounting plate 16 Fan
7 Support bracket 17 Cable mounting plate
8 RFI filter 18 Relay/transducer card with mounting plate
9 Power Card 19 Cable entry
10 Power card mounting plate
Table 1.14
The frequency converter is protected against short circuits inverter turns off the IGBTs individually when the short
with current measurement in each of the three motor circuit current exceeds the permitted value (Alarm 16 Trip
phases or in the DC link. A short circuit between two Lock).
output phases causes an over current in the inverter. The
1.9.2 DC Voltage Levels
control cable is run between frequency converters, and not 14-28 Production Settings and 14-29 Service Code, are the
between frequency converters and other devices. relevant service parameters.
Parameters for configuring the input and output using Parameter settings are displayed by pressing [Main Menu] 2 2
NPN and PNP. on the LCP.
These parameters cannot be changed while the motor is Use the navigation keys [▲], [▼], [►] and [◄] to scroll
running. through parameters.
2.3.2 Output Signals See the FC 101 Quick Guide, MG18A for detailed
information on accessing and displaying parameters, and
The frequency converter also produces output signals that for descriptions and procedures for service information
are carried either through the RS-485 serial bus or terminal available in parameter group 6-** Analog In/Out.
42. Output terminal 42 operates in the same manner as
the inputs. The terminal can be programmed for either a
variable analog signal in mA or a digital signal (0 or 1) in
2.5 Control Terminals
24 V DC. In addition, a pulse reference can be provided on Control terminals must be programmed. Each terminal has
terminals 27 and 29. Output analog signals generally specific functions and a numbered parameter associated
indicate the frequency, current, torque, and so on, to an with it, see Table 2.2. The setting selected in the parameter
external controller or system. Digital outputs can be enables the function of the terminal.
control signals used to open or close a damper, or send a
start or stop command to auxiliary equipment.
It is important to confirm that the control terminal is
programmed for the correct function.
Additional terminals are Form C relay outputs on terminals
01, 02, and 03, and terminals 04, 05, and 06.
Parameter settings are displayed by pressing [Main Menu].
130BB626.10
L1 U
2 2
L2 V
3 Phase
power L3 W
input
PE PE
Motor
UDC-
Not present on all power sizes
UDC+
0-10Vdc- 54 (A IN) 04
0/4-20 mA
55 (COM A IN/OUT) relay1
42 0/4-20mA A OUT / DIG OUT 03
240V AC 3A
45 0/4-20mA A OUT / DIG OUT 02
Bus ter. 01
12 (+24V OUT) ON=Terminated
ON
1 2
OFF=Unterminated
18 (DIGI IN)
24V (NPN)
OV (PNP)
19 (DIGI IN)
24V (NPN)
20 (COM D IN) OV (PNP)
Bus ter.
27 (DIGI IN)
24V (NPN) RS-485 (N PS-485) 69
OV (PNP) RS-485
29 (DIGI IN) Interface
24V (NPN) (P RS-485) 68
OV (PNP) Do not connect shield to
(Com RS-485 ) 61 61 on 116,117 and 118 unites
(PNP)-Source
(NPN)-Sink
Correct earthing Control cables and cables for serial communication must be fitted with cable
clamps at both ends to ensure the best possible electrical connection.
Incorrect earthing Do not use twisted cable ends (pigtails) since they increase screen
impedance at high frequencies.
Earth potential protection When the earth potential between the frequency converter and the
PLC or other interface device is different, electrical noise may occur that can disturb the entire
system. This can be resolved by fitting an equalizing cable next to the control cable. Minimum
cable cross section is 8 AWG.
50/60 Hz earth loops When using very long control cables, 50/60 Hz earth loops may occur
that can disturb the entire system. This can be resolved by connecting one end of the screen
with a 100 nF capacitor and keeping the lead short.
Serial communication control cables Low frequency noise currents between frequency
converters can be eliminated by connecting one end of the screened cable to frequency
converter terminal 61. This terminal connects to earth through an internal RC link. It is
recommended to use twisted-pair cables to reduce the differential mode interference between
conductors.
130BC343.10
Control Card Power
3. Power Section
Another part of the logic section is the removable LCP or
In 3.3 Sequence of Operation, these three sections are display mounted on the front of the frequency converter.
covered in greater detail while describing how power and The LCP provides the interface between the internal digital
control signals move throughout the frequency converter. logic and the operator.
3.2.1 Logic section All programmable parameter settings can be uploaded into
the EEPROM of the LCP. This function helps in maintaining
The control card includes most of the logic section (see a back-up frequency converter profile and parameter set.
Illustration 3.2). The primary logic element of the control Its download function can be used in programming other
card is a microprocessor, which supervises and controls all frequency converters or restoring a program to a repaired
functions of frequency converter operation. In addition, a unit. The LCP is removable during operation to prevent
separate PROM contains the parameters to provide the undesired program changes. With the addition of a remote
user with programmable options. These parameters are mounting kit, the LCP can be mounted in a remote
programmed to enable the frequency converter to meet location.
specific application requirements. This data is stored in an
EEPROM providing security during power-down and also Control terminals, with programmable functions, are
allows the flexibility to change the operational character- provided for input commands such as run, stop, forward,
istics of the frequency converter. reverse and speed reference. Additional output terminals
are provided to supply signals to run peripheral devices or
for monitoring and reporting status.
The control card logic 7 V DC, 6 V DC, and 3.3 V DC operating voltage. SMPS
powers the logic and interface circuitry. SMPS is supplied
• communicates via serial link with outside devices by the DC bus voltage. The secondary SMPS provides
such as personal computers or Programmable power to the logic circuitry with main input disconnected.
Logic Controllers (PLC). It can keep units with communication options live on a
network when the frequency converter is not powered
3 3 • provides two voltage supplies for use from the
control terminals.
from the mains.
24 V DC is used for switching functions such as start, stop, Circuitry for controlling speed of the cooling fans is also
and forward/reverse. The 24 V DC supply also supplies 200 provided on the power card.
mA of power, which can partly be used to power external
encoders or other devices. A 10 V DC supply rated at 17
mA is also available for use with speed reference circuitry.
3.2.3 Power Section
130BC330.10
• serial communications Rectifier Intermediate
(SCR/Diodes) circuit
Inverter
section (IGBTs)
• additional relays
The logic to power interface isolates the high voltage Illustration 3.2 Typical Power Section
components of the power section from the low voltage
signals of the logic section. The interface consists of two
sections.
3.3 Sequence of Operation
• Power Card
3.3.1 Rectifier Section
• Gate Driver
The control card handles much of the fault processing for Depending on size of the frequency converters, the
output short circuit and ground fault conditions. The rectifier section is built on either six or three diodes and
power card provides conditioning of these signals. Scaling three thyristors.
of current feedback and voltage feedback is accomplished
on the interface sections before processing by the control Inrush current in units with a normal 6-diode rectifier is
card. limited with a simple PTC and relay circuit.
The power card contains a Switch Mode Power Supply Phase controlling the thyristors (active inrush control)
(SMPS). The SMPS provides the unit with 24 V DC, 16 V DC, limits the inrush current in units with diodes and thyristors.
The low voltage power supplies are activated when the DC ripple voltage is present on the DC bus, the actual DC
bus reaches approximately 50 V DC less than the alarm value is closer to V ACx1.38 under unloaded conditions
voltage low for the DC bus (see rating tables in and may drop to V ACx1.32 while running under load. For
1 Introduction). After a short delay, an inrush enable signal example, a frequency converter connected to a nominal
is sent from the control card to the power card SCR gating 460 V line, while sitting idle, the DC bus voltage is approxi-
circuit. The SCRs are automatically gated when forward mately 635 V DC (460x1.38).
biased, as a result acting similar to an uncontrolled 3 3
rectifier. As long as power is applied to the frequency converter,
this voltage is present in the intermediate circuit and the
When the DC bus capacitors are fully charged, the voltage inverter circuit. It is also fed to the Switch Mode Power
on the DC bus is equal to the peak voltage of the input AC Supply (SMPS) on the power card and is used for
line. Theoretically, this can be calculated by multiplying the generating all other low voltage supplies.
AC line value by 1.414 (V ACx1.414). However, since AC
130BC134.10
Brake not connected to terminal on FC 101
AC / DC BR DC /AC
RFI (variations)
Inrush
L1 A
U
MAINS
Motor
L2 x3 RFI _ RL 2 x3 A V
L3 A W
o
C
RFI _ RL 1
BR BR INV Temp.
FB GD GD conv.
GD
Supply
RL 1
uC+ RL 1
Tmp_ VGDS
P_BRF
7 xGD
RL 2
SMPS EEP RL 2
RFI _RL 1
RFI _ RL 2 VGD +/- 15 /UDC -/-5
Inrush
Control Card UINV_P SAFE _ FB
VCX (GX ) 5V
Tmp _VGDS
D-I /O
UINV_N VCC
A-I /O VCC (GND) 5V
Isol. RS 485 FAN 1 Int.
FFB 1 fans
VDD (GND) 24V
Imax2 comp.
VGD +/- 15 /UDC -/-5 Level
Shift
LCP ACP MCP
Display
CAN
”Internal Communication”
control
panel ”Internal supply bus”
130BC135.10
Thyristor x3 AC / DC Brake not connected to terminal on FC 101
BR DC /AC
RFI (variations)
A
U
Motor
L1
3 3
x3
V
MAINS
A
L2 W
A
L3 o
C
uC+ RL 1
Tmp_VGDS
P _BRF
7 xGD
EEP RL 2
RL 2
RFI _ RL 1
RFI _ RL 2 VDD (GND ) 24V
Inrush
SMPS SAFE _ FB
Control Card UINV_P
Tmp _ VGDS
D-I/O
UINV_N
VCX (GX) 5V VCC
Int.
A-I/O fans
FAN
Isol. RS 485
VCC (GND) 5V FFB
Illustration 3.4 Example of H7, H8, I7, I8 Power and Control Section
3.3.2 Intermediate Section capacitor. It also provides a current path for discharging
the capacitors once power has been removed from the
Following the rectifier section, voltage passes to the frequency converter.
intermediate section. An LC filter circuit consisting of the
DC bus inductor and the DC bus capacitor bank smooths Also located in the intermediate section is the High
the rectified voltage. Frequency (HF) filter film capacitors. These capacitors
reduce the common mode noise caused by switching into
The DC bus inductor provides series impedance to stray capacitors to earth in cable and motor.
changing current. This impedance aids the filtering process
while reducing harmonic distortion to the input AC current In some units, RFI relay 2 can be opened to minimize
waveform normally inherent in rectifier circuits. voltage charge up.
The DC capacitor bank assembly consists of up to six If DC-link increases above a certain level specified in EE-
capacitors arranged in series/parallel configuration. A prom for each unit, RFI relay 2 opens automatically.
bleeder circuit maintains equal voltage drops across each
130BC335.10
Brake not connected to terminal on FC 101
3 3
AC / DC BR DC /AC
RFI (variations)
Inrush
L1 A
U
MAINS
Motor
L2 x3 RFI _ RL 2 x3 A V
L3 A W
o
C
RFI _ RL 1
BR BR INV Temp.
FB GD GD conv.
GD
Supply
RL 1
uC+ RL 1
Tmp_ VGDS
P_BRF
7 xGD
RL 2
SMPS EEP RL 2
RFI _RL 1
RFI _ RL 2 VGD +/- 15 /UDC -/-5
Inrush
Control Card UINV_P SAFE _ FB
VCX (GX ) 5V
Tmp _VGDS
D-I /O
UINV_N VCC
A-I /O VCC (GND) 5V
Isol. RS 485 FAN 1 Int.
FFB 1 fans
VDD (GND) 24V
Imax2 comp.
VGD +/- 15 /UDC -/-5 Level
Shift
LCP ACP MCP
Display
CAN
”Internal Communication”
control
panel ”Internal supply bus”
130BC336.10
Thyristor x3 AC / DC Brake not connected to terminal on FC 101
BR DC /AC
RFI (variations)
A
U
Motor
L1 x3
V
MAINS
A
L2 W
A
L3 o
C
uC+ RL 1
Tmp_VGDS
P _BRF
7 xGD
EEP RL 2
RL 2
RFI _ RL 1
RFI _ RL 2 VDD (GND ) 24V
Inrush
SMPS SAFE _ FB
Control Card UINV_P
Tmp _ VGDS
D-I/O
UINV_N
VCX (GX) 5V VCC
Int.
A-I/O fans
FAN
Isol. RS 485
VCC (GND) 5V FFB
3.3.3 Inverter Section Hall effect current sensors monitor the output current and
deliver proportional signals to the power card where they
In the inverter section (see Illustration 3.8), gate signals are are buffered and delivered to the control card. The control
delivered from the control card, through the power card to card logic uses these current signals to determine proper
the gates of the IGBTs. The series connection of each set of waveform compensations based on load conditions. They
IGBTs is delivered to the output, first passing through the further serve to detect over current conditions, including
3 3 current sensors. earth faults and phase-to-phase shorts on the output.
Once a run command and speed reference are present, the During normal operation, the power card and control card
IGBTs begin switching to create the output waveform, as are monitoring various functions within the frequency
shown in Illustration 3.8. Looking at the phase-to-phase converter. The current sensors provide current feedback
voltage waveform with an oscilloscope shows that the information. The DC bus voltage and mains voltage are
Pulse Width Modulation (PWM) principal creates a series of monitored as well as the voltage delivered to the motor. A
pulses which vary in width. Basically, the pulses are thermal sensor mounted inside the sixpack IGBT module
narrower as zero crossing is approached and wider the provides heatsink temp feedback for the inverter. This
farther from zero crossing. The pulse duration of applied applies to unit up to and including H6 and I6 frame sizes.
DC voltage controls the width. Although the voltage For H7-H8 and I7-I8 frame sizes, the inverter consists of 3
waveform is a consistent amplitude, the inductance within dual IGBT modules and the thermal sensor is mounted
the motor windings serve to average the voltage delivered separately on the heatsink.
and so. As the pulse width of the waveform varies, the
average voltage seen by the motor varies as well. This then
130BX136.10
equates to the resultant current waveform which takes on
the sine wave shape expected in an AC system. The pulse
rate determines the waveform frequency waveform. By
employing a sophisticated control scheme, the frequency
converter can deliver a current waveform that nearly
replicates a true AC sine wave.
Illustration 3.7 Output Voltage and Current Waveforms
This waveform, as generated by the Danfoss VVCplus PWM
principle at the control card, provides optimal performance
and minimal losses in the motor.
130BC337.10
Brake not connected to terminal on FC 101
3 3
AC / DC BR DC /AC
RFI (variations)
Inrush
L1 A
U
MAINS
Motor
L2 x3 RFI _ RL 2 x3 A V
L3 A W
o
C
RFI _ RL 1
BR BR INV Temp.
FB GD GD conv.
GD
Supply
RL 1
uC+ RL 1
Tmp_ VGDS
P_BRF
7 xGD
RL 2
SMPS EEP RL 2
RFI _RL 1
RFI _ RL 2 VGD +/- 15 /UDC -/-5
Inrush
Control Card UINV_P SAFE _ FB
VCX (GX ) 5V
Tmp _VGDS
D-I /O
UINV_N VCC
A-I /O VCC (GND) 5V
Isol. RS 485 FAN 1 Int.
FFB 1 fans
VDD (GND) 24V
Imax2 comp.
VGD +/- 15 /UDC -/-5 Level
Shift
LCP ACP MCP
Display
CAN
”Internal Communication”
control
panel ”Internal supply bus”
130BC338.10
Thyristor x3 AC / DC Brake not connected to terminal on FC 101
BR DC /AC
RFI (variations)
A
U
Motor
L1 x3
V
MAINS
A
L2 W
A
L3 o
C
uC+ RL 1
Tmp_VGDS
P _BRF
7 xGD
EEP RL 2
RL 2
RFI _ RL 1
RFI _ RL 2 VDD (GND ) 24V
Inrush
SMPS SAFE _ FB
Control Card UINV_P
Tmp _ VGDS
D-I/O
UINV_N
VCX (GX) 5V VCC
Int.
A-I/O fans
FAN
Isol. RS 485
VCC (GND) 5V FFB
IP20 IP20
Enclosure H6 H7 H8 Enclosure H9 H10 H6 H7 H8
Voltage T2 T2 T2 T2 T2 T2 Voltage T6 T6 T6 T6 T6 T6 T6 T6 T6 T6 T6 T6
3 3 Power Rating
(kW)
15 18. 5 22 30 37 45
Power
Rating 2.2 3.0 5.5 7.5 11 15 22 30 45 55 75 90
FAN start (kW)
45 45 45 45 45 45
temperature °C FAN start
FAN max speed tempera- 35 35 35 35 45 45 45 45 40 40 40 40
60 60 60 60 60 60
temperature °C ture °C
FAN stop FAN max
36 36 36 36 36 36
temperature °C speed
55 55 55 55 60 60 60 60 55 55 55 55
tempera-
Table 3.1 Fan Speed Control, IP20, H6-H8, T2 ture °C
FAN stop
IP20 tempera- 31 31 31 31 36 41 41 41 30 30 30 30
Enclosure H6 H7 H8 ture °C
Voltage T4 T4 T4 T4 T4 T4
Power Rating Table 3.4 Fan Speed Control, IP20, H9-H10 and H6-H8, T6
30 37 45 55 75 90
(kW)
FAN start
45 45 45 40 40 40
temperature °C
FAN max speed
60 60 60 55 55 55
temperature °C
FAN stop
41 41 41 30 30 30
temperature °C
IP54
Enclosure I6 I7 I8
Voltage T4 T4 T4 T4 T4 T4 T4
Power Rating
22 30 37 45 55 75 90
(kW)
FAN start
45 45 45 40 40 40 40
temperature °C
FAN max speed
60 60 60 55 55 55 55
temperature °C
FAN stop
35 35 35 30 30 30 30
temperature °C
4 Troubleshooting
CAUTION
4.1 Troubleshooting Tips Never assume that a motor is wired properly after a service
of the frequency converter. There is a risk of overlooking
Before repairing a frequency converter, read and
for example, loose connections, improper programming, or
understand the following instructions.
added equipment.
4 4
1. Note all warnings concerning voltages present in
It is best to develop a detailed approach, beginning with a
the frequency converter. Always verify the
physical inspection of the system. See Table 4.1 for items
presence of AC input voltage and DC bus voltage
to examine.
before working on the unit. Some points in the
frequency converter are referenced to the
negative DC bus. They are at bus potential even 4.3 Fault Symptom Troubleshooting
though it may appear on diagrams to be a
neutral reference. This troubleshooting section is divided into sections based
on the symptom being experienced. To start, Table 4.1,
CAUTION provides a visual inspection check list. Often, wrong instal-
Voltage can be present for as long as 20 minutes on lation or wiring of the frequency converter cause the
frequency converters after removing power from the unit. problem. The check list provides guidance through various
See the label on the front of the frequency converter door items to inspect during any frequency converter service
and Table 1.1 for the specific discharge time. process.
2. Never apply power to a unit that is suspected of
being faulty. Many faulty components within the Next, symptoms are approached as the technician most
frequency converter can damage other commonly discovers them: reading an unrecognized
components when power is applied. Always frequency converter display, problems with motor
perform the procedure for testing the unit after operation, or a warning or alarm displayed by the
repair as described in 4.7 After Repair Tests. frequency converter. Remember, the frequency converter
processor monitors inputs and outputs as well as internal
3. Never attempt to defeat any fault protection
frequency converter functions. Thus, an alarm or warning
circuitry within the frequency converter, as this
does not necessarily indicate a problem within the
results in unnecessary component damage and
frequency converter itself.
can cause personal injury.
4. Always use factory approved replacement parts. Each incident has further descriptions on how to
The frequency converter is designed to operate troubleshoot that particular symptom. When necessary,
within certain specifications. Incorrect parts can further referrals are made to other parts of the manual for
affect tolerances and result in further damage to additional procedures. 5 Frequency Converter and Motor
the unit. Applications presents detailed discussions on areas of
5. Read the instruction manual. A thorough frequency converter and system troubleshooting that an
understanding of the unit is the best approach. If experienced repair technician must understand for
ever in doubt, consult the factory or authorized effective analysis.
repair center for assistance.
Finally, a list of tests, 4.7 After Repair Tests is provided.
Always perform these tests under the following conditions:
4.2 Exterior Fault Troubleshooting
There may be slight differences in servicing a frequency • Starting a frequency converter for the first time.
converter that has been operational for some extended
time compared to a new installation. When using proper
• Approaching a frequency converter that is
suspected of being faulty.
troubleshooting procedures, make no assumptions.
• After a repair to the frequency converter.
4 4 input power side of frequency converter or output side to motor. Examine operation and condition of
these items as possible causes for operational faults. Check function and installation of pressure sensors
or encoders (etc.) used for feedback to frequency converter.
Cable routing Avoid routing motor wiring, AC line wiring, and signal wiring in parallel. If parallel routing is
unavoidable, try to maintain a separation of 150–200 mm (6-8 inches) between the cables or separate
them with a grounded conductive partition. Avoid routing cables through free air.
Control wiring Check for broken or damaged wires and connections. Check the voltage source of the signals. Though
not always necessary depending on the installation conditions, the use of shielded cable or a twisted
pair is recommended. Ensure the shield is terminated correctly.
Frequency converter cooling Check operational status of all cooling fans. Check door filters on NEMA 12 (IP54) units. Check for
blockage or constrained air passages. Verify bottom gland plate is installed.
Frequency converter display Warnings, alarms, frequency converter status, fault history and many other important items are available
through the display on the local control panel of frequency converter.
Frequency converter interior Frequency converter interior must be free of dirt, metal chips, moisture, and corrosion. Check for burnt
or damaged power components or carbon deposits that were the result of a catastrophic component
failure. Check for cracks or breaks in the housings of power semiconductors, or pieces of broken
component housings loose inside the unit.
EMC considerations Check for proper installation with regard to electromagnetic capability. Refer to the frequency converter
instruction manual and this chapter for further details.
Environmental conditions Under specific conditions these units can be operated within a maximum ambient of 50°C (122°F).
Humidity levels must be less than 95% non-condensing. Check for harmful airborne contaminates such
as sulfur based compounds.
Grounding The frequency converter requires a dedicated ground wire from its chassis to the building ground. It is
also suggested that the motor be grounded to the frequency converter chassis as well. The use of
conduit or mounting of the frequency converter to a metal surface is not considered a suitable ground.
Check for good ground connections that are tight and free of oxidation.
Input power wiring Check for loose connections. Check for proper fusing. Check for blown fuses.
Motor Check nameplate ratings of motor. Ensure that motor ratings coincide with frequency converters. Ensure
frequency converter's motor parameters (1–20 to 1–25) are set according to motor ratings.
Output to motor wiring Check for loose connections. Check for switching components in output circuit. Check for faulty contacts
in switch gear.
Programming Ensure frequency converter parameter settings are correct according to motor, application, and I/O
configuration.
Proper clearance These frequency converters require top and bottom clearance adequate to ensure proper air flow for
cooling in accordance with the frequency converter size. frequency converters with exposed heat sinks
out the back of the frequency converter must be mounted on a flat solid surface.
Vibration Though somewhat subjective look for an unusual amount of vibration that the frequency converter may
be subjected to. The frequency converter should be mounted solidly or the use of shock mounts
employed.
If the display stays lit, the problem is in the control wiring Unit ready
(external to the frequency converter). Check all control Terminal 27 is low (no signal).
wiring for shorts or incorrect connections. Ensure that terminal 27 is logic “1”. Refer to the Input
Terminal Signal Test.
If the display continues to cut out, follow the procedure Run OK, 0 Hz
for 4.5.1 No Display as though the display was not lit at all. This message indicates that a run command has been
given to the frequency converter but the reference (speed
command) is zero or missing.
4 4 fieldbus.
A correct control word must be transmitted to the
of Motor Supply Voltage Test.
frequency converter over the communication bus. Motor draws high current but cannot start
STOP Possible open winding in motor or open connection to
One of the digital input terminals 16, 17, 27, 29, 32, or 33 motor.
is programmed for “Stop Inverse” and the corresponding Perform 6.4.6 Output Imbalance of Motor Supply Voltage Test
terminal is low (logic “0”). to ensure that frequency converter is providing correct
Ensure that the above parameters are programmed output (see Motor Runs Rough above).
correctly and that any digital input programmed for “Stop Check motor for open windings. Check all motor wiring
Inverse” is high (logic “1”). connections.
Display Indication that the unit is functioning, but there is Run an AMA to check the motor for open windings and
no output. unbalanced resistance. Inspect all motor wiring
Check that parameter 620 is not set to “Run With Inverter connections.
Disabled”.
If the unit is equipped with external 24 V DC option, check 4.6 Warnings and Alarms
that the main power is applied to the frequency converter.
When the frequency converter fault circuitry detects a fault
NOTE condition, or a pending fault, a warning, or alarm is issued.
In this case, the display alternately flashes Warning 8. A flashing display on the LCP indicates an alarm or
warning condition and the associated number code on line
4.5.6 Incorrect Motor Operation 2. Sometimes a warning precedes an alarm. defines
whether a warning precedes an alarm and whether the
Occasionally, a fault can occur where the motor continues frequency converter suspends operations (trips).
to run, but not in the correct manner. The symptoms and
causes may vary considerably. Many of the possible 4.6.1 Alarms
problems are listed below by symptom along with
recommended procedures for determining their causes. An alarm causes the frequency converter to trip (suspend
operation). The frequency converter has three trip
Wrong speed/unit does not respond to command conditions which are displayed on line 1:
Possible incorrect reference (speed command).
Ensure that the unit is programmed correctly according to TRIP (AUTO RESTART): The frequency converter is
the reference signal being used, and that all reference programmed to restart automatically after the fault is
limits are set correctly as well. Perform 6.4.7 Input Terminal removed. The number of automatic reset attempts can be
Signal Tests to check for faulty reference signals. continuous or limited to a programmed number of
attempts. If the selected number of automatic reset
Motor speed unstable
attempts is exceeded, the trip condition changes to TRIP
Possible incorrect parameter settings, faulty current
(RESET).
feedback circuit, loss of motor (output) phase.
Check settings of all motor parameters, including all motor
TRIP (RESET): Requires resetting of the frequency converter
compensation settings (Slip Compensation, Load Compen-
before operation after a fault is cleared. The frequency
sation, etc.). For Closed Loop operation, check PID settings.
converter can be reset manually by pressing [Reset], a
Perform 6.4.7 Input Terminal Signal Tests to check for faulty
digital input, or a serial bus command. For FC 101
reference signals. Perform Output Phase Imbalance Test to
frequency converters, the stop and reset are the same key.
check for loss of motor phase.
If [Stop/Reset] is used to reset the frequency converter,
Motor runs rough [Start] must be pressed to initiate a run command in either
Possible over magnetization (incorrect motor settings), or local or remote.
an IGBT misfiring.
TRIPLOCK (DISC> MAINS): Requires that the main AC input A warning indicates a condition that may require attention
power to the frequency converter must be disconnected or a trend that may eventually require attention. A
long enough for the display to go blank. The fault warning remains active until the cause is no longer
condition must be removed and power reapplied. present. Under some circumstances, motor operation may
Following power up, the fault indication changes to TRIP continue.
(RESET) and allow for manual, digital, or serial bus reset.
A trip is the action when an alarm has appeared. The trip
Line 2 displays alarm and the associated number while line removes power to the motor. It can be reset after the
3 identifies the alarm in plain language. condition has been cleared by pressing [Reset], or through
a digital input (parameter group 5-1* Digital Inputs). The 4 4
NOTE event that caused an alarm cannot damage the frequency
converter or cause a dangerous condition. Alarms must be
When exchanging the unit which requires fire mode
reset to restart operation once their cause has been
activation, carefully check that the Fire Mode parameters
rectified.
• 24-00 FM Function
4 4 47
48
Control Voltage Fault
VDD1 Supply Low
(X)
(X)
(X)
(X)
50 AMA Calibration Failed (X)
51 AMA check Unom and Inom (X)
52 AMA low Inom (X)
53 AMA motor too big (X)
54 AMA motor too small (X)
55 AMA Parameter out of (X)
range
56 AMA interrupted by user (X)
57 AMA timeout (X)
58 AMA internal fault (X) (X)
59 Current limit (X)
60 External Interlock (X)
66 Heat sink Temperature Low (X)
69 Pwr Card Temperature (X) (X) (X)
79 Illegal PS config (X) (X)
80 Drive Initialized to Default (X)
Value
87 Auto DC Braking (X)
95 Broken Belt (X) (X) 22–6*
201 Fire Mode (X)
202 Fire M Limits Exceeded (X)
250 New spare parts (X) (X)
251 New Type Code (X) (X)
(X) Dependent on parameter. A trip is the action when an WARNING/ALARM 2, Live zero error
alarm has appeared. The trip coasts the motor and can be This warning or alarm only appears if programmed by the
reset by pressing [Reset] or make a reset by a digital input user in 6-01 Live Zero Timeout Function. The signal on one
(parameter group 5-1* Digital Inputs [1]). The original event of the analog inputs is less than 50% of the minimum
that caused an alarm cannot damage the frequency value programmed for that input. Broken wiring or faulty
converter or cause dangerous conditions. A trip lock is an device sending the signal can cause this condition.
action when an alarm occurs, which can damage the Troubleshooting
frequency converter or connected parts. A trip lock Check connections on all the analog input
situation can only be reset by a power cycling. terminals. Control card terminals 53 and 54 for
signals, terminal 55 common. MCB 101 terminals
Warning Yellow 11 and 12 for signals, terminal 10 common. MCB
Alarm Flashing red 109 terminals 1, 3, 5 for signals, terminals 2, 4, 6
common).
Table 4.3 LED Indication
Check that the frequency converter programming
The alarm words, warning words and extended status and switch settings match the analog signal type.
words can be read out via serial bus or optional fieldbus Perform Input Terminal Signal Test.
for diagnosis.
WARNING/ALARM 4, Mains phase loss when the motor runs with more than 100% overload for
A phase is missing on the supply side, or the mains too long.
voltage imbalance is too high. This message also appears Troubleshooting
for a fault in the input rectifier on the frequency converter. Check for motor overheating.
Options are programmed at 14-12 Function at Mains
Imbalance. Check if the motor is mechanically overloaded
ALARM 14, Earth (ground) fault ALARM 32, Motor phase W missing
There is current from the output phases to earth, either in Motor phase W between the frequency converter and the
the cable between the frequency converter and the motor motor is missing.
or in the motor itself. Remove power from the frequency converter and check
Troubleshooting: motor phase W.
Remove power to the frequency converter and ALARM 38, Internal fault
repair the earth fault. When an internal fault occurs, a code number defined in
Check for earth faults in the motor by measuring Table 4.4 is displayed.
4 4 the resistance to ground of the motor leads and
the motor with a megohmmeter.
Troubleshooting
Cycle power
ALARM 16, Short circuit
Check that the option is properly installed
There is short-circuiting in the motor or motor wiring.
Check for loose or missing wiring
Remove power to the frequency converter and repair the
short circuit. It may be necessary to contact your Danfoss supplier or
service department. Note the code number for further
WARNING/ALARM 17, Control word timeout
troubleshooting directions.
There is no communication to the frequency converter.
The warning is only active when 8-04 Control Word Timeout No. Text
Function is NOT set to OFF. 0 Serial port cannot be initialised. Contact your
If 8-04 Control Word Timeout Function is set to Stop and Danfoss supplier or Danfoss Service Department.
Trip, a warning appears and the frequency converter ramps 256-258 Power EEPROM data is defective or too old
down until it trips, while giving an alarm. 8-03 Control 512-519 Internal fault. Contact your Danfoss supplier or
Timeout Time could possibly be increased. Danfoss Service Department.
Troubleshooting: 783 Parameter value outside of min/max limits
Check connections on the serial communication 1024-1284 Internal fault. Contact your Danfoss supplier or the
cable. Danfoss Service Department.
Increase 8-03 Control Word Timeout Time 1299 Option SW in slot A is too old
1300 Option SW in slot B is too old
Check the operation of the communication
1302 Option SW in slot C1 is too old
equipment.
1315 Option SW in slot A is not supported (not allowed)
Verify a proper installation based on EMC 1316 Option SW in slot B is not supported (not allowed)
requirements. 1318 Option SW in slot C1 is not supported (not
WARNING 24, External fan fault allowed)
The fan warning function is an extra protective function 1379-2819 Internal fault. Contact your Danfoss supplier or
that checks if the fan is running/mounted. The fan warning Danfoss Service Department.
can be disabled in 14-53 Fan Monitor ([0] Disabled). 2820 LCP stack overflow
Troubleshooting Troubleshooting:
Turn off the frequency converter and remove the
The heatsink temperature measured as 0 °C could indicate
earth fault.
that the temperature sensor is defective, thus causing the
Measure the resistance to ground of the motor fan speed to increase to the maximum. If the sensor wire
leads and the motor with a megohmmeter to between the IGBT and the gate drive card is disconnected,
check for earth fault in the motor. this warning is produced. Also, check the IGBT thermal
WARNING 47, 24 V supply low sensor.
The 24 V DC is measured on the control card. The external ALARM 79, Illegal power section configuration
24 V DC backup power supply may be overloaded,
otherwise contact the Danfoss supplier.
The scaling card is the incorrect part number or not
installed. Also MK102 connector on the power card could
4 4
WARNING 48, 1.8 V supply low not be installed.
The 1.8 V DC supply used on the control card is outside of ALARM 80, Drive initialised to default value
allowable limits. The power supply is measured on the Parameter settings are initialised to default settings after a
control card. Check for a defective control card. If an manual reset. Reset the unit to clear the alarm.
option card is present, check for an overvoltage condition.
ALARM 95, Broken belt
ALARM 51, AMA check Unom and Inom Torque is below the torque level set for no load, indicating
The settings for motor voltage, motor current, and motor a broken belt. 22-60 Broken Belt Function is set for alarm.
power are wrong. Check the settings in parameters 1-20 to Troubleshoot the system and reset the frequency converter
1-25. after the fault has been cleared.
ALARM 52, AMA low Inom WARNING 200, Fire mode
The motor current is too low. Check the setting in This warning indicates the frequency converter is operating
4-18 Current Limit. in fire mode. The warning clears when fire mode is
ALARM 53, AMA motor too big removed. See the fire mode data in the alarm log.
The motor is too big for the AMA to operate. WARNING 202, Fire mode limits exceeded
ALARM 54, AMA motor too small While operating in fire mode one or more alarm conditions
The motor is too small for the AMA to operate. have been ignored which would normally trip the unit.
Operating in this condition voids unit warranty. Cycle
ALARM 55, AMA parameter out of range power to the unit to remove the warning. See the fire
The parameter values of the motor are outside of the mode data in the alarm log.
acceptable range. AMA does not run.
WARNING 250, New spare part
56 ALARM, AMA interrupted by user The power card or switch mode power supply has been
The user has interrupted the AMA. exchanged. The frequency converter type code must be
ALARM 57, AMA internal fault restored in the EEPROM. Select the correct type code in
Try to restart AMA again. Repeated restarts can over heat 14-23 Typecode Setting according to the label on the unit.
the motor. Remember to select ‘Save to EEPROM’ to complete.
ALARM 58, Internal fault WARNING 251, New typecode
Contact your Danfoss supplier. The frequency converter has a new type code.
WARNING 59, Current limit
The current is higher than the value in 4-18 Current Limit. 4.7 After Repair Tests
Ensure that Motor data in parameters 1-20 to 1-25 are set
correctly. Possibly increase the current limit. Be sure that Following any repair to a frequency converter or testing of
the system can operate safely at a higher limit. a frequency converter suspected of being faulty, the
following procedure must be followed. Following the
WARNING 60, External interlock
procedure will ensure that all circuitry in the frequency
A digital input signal is indicating a fault condition external
converter is functioning properly before putting the unit
to the frequency converter. An external interlock has
into operation.
commanded the frequency converter to trip. Clear the
external fault condition. To resume normal operation,
apply 24 V DC to the terminal programmed for external 1. Perform visual inspection procedures as described
interlock. Reset the frequency converter. in Table 4.1.
WARNING 66, Heatsink temperature low 2. Perform static test procedures to ensure that
This warning is based on the temperature sensor in the frequency converter is safe to start.
IGBT module. 3. Disconnect motor leads from output terminals (U,
V, W) of frequency converter.
As stated, the AMA function must be set 1-30 Stator The FC 101 has an AC brake which increases magnetisation
Resistance (Rs) and 1-35 Main Reactance (Xh). The values for current to increase loss in motor and reduce DC-link
these parameters can either be supplied by the motor voltage. If the DC-link voltage exceeds a certain voltage,
manufacturer, or contain factory default values. the overvoltage control increases the frequency.
When the input voltage becomes unbalanced or a phase This data can also be read in parameter group 16-6* Inputs
disappears completely, the ripple voltage increases. This and Outputs.
situation causes the frequency converter to trip and issue
Alarm 4, Mains Phase Loss. In addition to missing phase If there is no correct indication, check if the signal is
voltage, a line disturbance or imbalance can cause an present at the input terminals of the frequency converter.
increased bus ripple. Line disturbances can be caused by Use a voltmeter or oscilloscope in accordance with
line notching, defective transformers, or other loads that 6.4.7 Input Terminal Signal Tests.
can affect the form factor of the AC waveform. Mains
imbalances which exceed 3% cause sufficient DC bus
If the signal is present at the terminal, the control card is
ripple to initiate a trip.
defective and must be replaced. If the signal is not
present, the problem is external to the frequency
Output disturbances can have the same effect of increased
5 5 ripple voltage on the DC bus. A missing or lower than
converter. The circuitry providing the signal along with its
associated wiring must then be checked.
normal output voltage on one phase can cause increased
ripple on the DC bus. When a mains imbalance trip occurs,
it is necessary to check both the input and output voltage
5.1.4 Programming Problems
of the frequency converter.
Difficulty with frequency converter operation can be a
result of improper programming of the frequency
Severe imbalance of supply voltage or phase loss can
converter parameters. Three areas where programming
easily be detected with a voltmeter. View line disturbances
errors can affect frequency converter and motor operation
through an oscilloscope. Conduct tests for input imbalance
are motor settings, references and limits, and I/O configu-
of supply voltage, input waveform, and output imbalance
ration. See 2.3 Frequency Converter Inputs and Outputs.
of supply voltage as described in 4 Troubleshooting.
• Start Command: to execute. Any references or limits set incorrectly result in less than
• Reference or Speed Command: to identify the acceptable frequency converter performance. For instance,
speed of execution. if maximum reference is set too low, the motor is unable
to reach full speed. These parameters must be set
The frequency converters are designed to accept various
according to the requirements of the particular installation.
signals. First determine which of these signals the
References are set in parameter group 3-0* Reference Limits.
frequency converter is receiving
5.1.5 Motor/Load Problems frequency converter display. With the motor disconnected,
the current should be zero. A frequency converter with a
Problems with the motor, motor wiring, or mechanical load defective current sensor indicates some current flow. An
on the motor can develop in a number of ways. The motor indication of a fraction of one amp is tolerable. However,
or motor wiring can develop a phase-to-phase or phase-to- that value should be considerably less than one amp. If the
earth short resulting in an alarm indication. Checks must display shows more than one amp of current, there is a
be made to determine whether the problem is in the defective current sensor. All three current sensors in
motor wiring or the motor itself. FC 101 units are mounted on one circuit board (either
power card, SMPS card, or current transducer card). The
A motor with unbalanced, or unsymmetrical, impedances repair procedure is to replace all three current sensors at
on all three phases can result in uneven or rough the same time.
5 5
operation, or unbalanced output currents. For
measurements, use a clamp-on style ammeter to 5.2.2 Signal and Power Wiring
determine whether the current is balanced on the three Considerations for Electromagnetic
output phases. See 6.4.6 Output Imbalance of Motor Supply Compatibility
Voltage Test.
This section provides an overview of general signal and
Usually a current limit warning indicates an incorrect power wiring considerations when addressing the Electro-
mechanical load. If possible, disconnect the motor from magnetic Compatibility (EMC) concerns for typical
the load to determine if the load is incorrect. commercial and industrial equipment. Only certain high-
frequency phenomena (such as RF emissions, RF immunity)
Quite often, the indications of motor problems are similar are discussed. Low-frequency phenomena (such as
to those of a defect in the frequency converter itself. To harmonics, mains voltage imbalance, notching) are not
determine whether the problem is internal or external to covered.
the frequency converter, disconnect the motor from the
frequency converter output terminals. Perform 6.4.6 Output NOTE
Imbalance of Motor Supply Voltage Test procedure on all Special installations or compliance to the European CE
three phases with an analog voltmeter. If the three voltage EMC directives require strict adherence to relevant
measurements are balanced, the frequency converter is standards and are not discussed here.
functioning correctly. Hence, the problem is external to the
frequency converter. 5.2.3 Effect of EMI
If the voltage measurements are not balanced, the While electromagnetic interference (EMI) related distur-
frequency converter is malfunctioning. This typically means bances to frequency converter operation are uncommon,
that one or more output IGBTs are not switching on and the following detrimental EMI effects may be seen:
off correctly. This can be a result of a defective IGBT or
gate signal.
• Motor speed fluctuations
• Telephone interference
The simplest method of determining whether a current
sensor is defective is to disconnect the motor from the
• Computer network data loss
frequency converter. Then observe the current in the • Digital control system faults
5.2.4 Sources of EMI frequency, and variable voltage PWM waveform. This high
rate of voltage change [dU/dt] is the primary source of the
Modern frequency converters (see Illustration 5.1) utilize frequency converter generated EMI.
IGBTs to provide an efficient and cost effective means to
create the Pulse Width Modulated (PWM) output waveform The high rate of voltage change caused by the IGBT
necessary for accurate motor control. These devices rapidly switching creates high frequency EMI.
switch the fixed DC bus voltage creating a variable
130BX137.10
Rectifier DC Bus Inverter
Filter reactor
5 5 AC Line Motor
IGBT
Filter capacitor
Sine wave
PWM waveform
Illustration 5.1 Frequency Converter Functionality Diagram
130BC154.10
4
1 3
130BC344.10
2 4
1 3
5 5
5
6
6
9 7
8
7
Illustration 5.2 Earth Currents
Illustration 5.3 Signal Conductor Currents
CAUTION NOTE
Stray capacitance between the motor conductors, Unprotected or poorly routed signal conductors located
equipment earth, and other nearby conductors results in close to or in parallel to motor and mains conductors are
induced high frequency currents. susceptible to EMI.
High earth circuit impedance at high frequencies results in Signal conductors are especially vulnerable when they are
an instantaneous voltage at points reputed to be at earth run in parallel to the power conductors for any distance.
potential. This voltage can appear throughout a system as EMI coupled into these conductors can affect either the
a common mode signal that can interfere with control frequency converter or the interconnected control device.
signals. See Illustration 5.4.
Theoretically, these currents return to the DC bus via the While these currents tend to travel back to the frequency
earth circuit and a high frequency (HF) bypass network converter, imperfections in the system cause some current
to flow in undesirable paths, thus exposing other locations be terminated in a manner that is appropriate for the
to the EMI. connected equipment. Avoid terminating the screen
through a pigtail connection as it increases the high
frequency impedance and spoils the effectiveness of the
2
130BC345.10
screen.
4
1 3
A simple alternative is to twist the existing single
conductors to provide a balanced capacitive and inductive
coupling. This operation cancels differential mode
interference. While not as effective as true twisted-pair
cable, it can be implemented in the field using the
5
6 materials on hand.
Motor cable selection
Motor conductors have the greatest influence on the EMI
5 5
Illustration 5.4 Alternate Signal Conductor Currents characteristics of the system. These conductors must
receive the highest attention whenever EMI is a problem.
Single conductor wires provide the least protection from
NOTE EMI emissions. Often, if these conductors are routed
High frequency currents can be coupled into the mains separately from the signal and mains wiring, then no
supplying the frequency converter when the mains further consideration is needed. If the conductors are
conductors are located close to the motor cables. routed close to other susceptible conductors, or if the
system is suspected to cause EMI problems, consider
5.2.6 Preventive Measures alternate motor wiring methods.
Installing screened power cable is the most effective
EMI-related problems are more effectively alleviated during means to alleviate EMI problems. The cable screen forces
the design and installation phases rather than after the the noise current to flow directly back to the frequency
system is in service. Many of the listed steps can be converter before it gets back into the power network or
implemented at a relatively low cost compared to the cost takes other undesirable high frequency paths. Unlike most
of identifying and fixing the problem later. signal wiring, the screening on the motor cable must be
terminated at both ends.
Earthing If a screened motor cable is not available, then three-phase
Earth the frequency converter and motor solidly to the conductors along with earth in a conduit provides some
equipment frame. A good high frequency connection is degree of protection. This technique is not as effective as
necessary to allow the high frequency currents to return to screened cable due to the unavoidable contact of the
the frequency converter rather than to travel through the conduit with various points within the equipment.
power network. The earth connection is ineffective if it has
Serial communications cable selection
high impedance to high frequency currents. Therefore it
There are various serial communication interfaces and
must be as short and direct as practical. Flat-braided cable
protocols in the market. Each of these interfaces
has lower high-frequency impedance than round cable.
recommends one or more specific types of twisted-pair,
Simply mounting the frequency converter or motor onto a
screened twisted-pair, or proprietary cables. Refer to the
painted surface does create an effective earth connection.
manufacturer’s documentation when selecting these
In addition, running a separate earth conductor directly
cables. Similar recommendations apply to serial communi-
between the frequency converter and the running motor is
cation cables as to other signal cables. Using twisted-pair
recommended.
cables and routing them away from power conductors is
Cable routing encouraged. While screened cable provides additional EMI
Avoid routing motor wiring, mains wiring, and signal protection, the screen capacitance may reduce the
wiring in parallel. If parallel routing is unavoidable, try to maximum allowable cable length at high data rates.
maintain a separation of 200 mm (6–8 inches) between the
cables or separate them with an earthed conductive
partition. Avoid routing cables through free air.
Signal cable selection
Single conductor 600 V rated wires provide the least
protection from EMI. Twisted-pair and screened twist-pair
cables are available which are designed to minimize the
effects of EMI. While unscreened twisted-pair cables are
often adequate, screened twisted-pair cables provide
another degree of protection. The signal cable screen must
6 Test Procedures
130BC299.10
6.1 Non-repairable Units
H1-H5 and I2-I4 are non-repairable units and should not be
repaired. The information about Line/Motor/UDC+-
terminals is useful to verify what went wrong with these
1
frequency converters, for statistics and WIIS purposes, but
8
also to avoid replacing a frequency converter that is
actually not defective. 7
6 6 130BB634.10 3
1
4
MAINS
2
4
Motor Illustration 6.2 I2 Frame
IP54 380-480 V, 0.75-4.0 kW
U V W
-DC+DC
2
1 RS-485
2 Line in
3 3 Earth
4 Wire clamps
5 Motor
6 UDC
7 Relays
8 I/O
Illustration 6.1 H1-H5 Frame
Table 6.2
IP20 200-240 V, 0.25-11 kW and IP20 380-480 V, 0.37-22 kW
1 Line
2 Earth
3 Motor
4 Relays
Table 6.1
130BC201.10
130BD011.10
6 6
1 RS-485
2 Line in
1 RS-485
3 Earth
2 Line in
4 Wire clamps
3 Earth
5 Motor
4 Wire clamps
6 UDC
5 Motor
7 Relays
6 UDC
8 I/O
7 Relays
8 I/O Table 6.4
Table 6.3
Pay close attention to the polarity of the meter leads to The inverter section is primarily made up of the IGBTs used
ensure the identification of any faulty component, in case for switching the DC bus voltage to create the output to
an incorrect reading appears. the motor. The frequency converter also has clamping
capacitors between +UDC and -UDC on the IGBT.
Described next is the procedure to conduct the static test
on the rectifier.
CAUTION
Disconnect motor leads when testing inverter section. With
NOTE leads connected, a short circuit in one phase reads in all
In H6 units the +/-UDC terminals are not readily accessible. phases, making isolation difficult.
Find terminals K601 (+) and K611 (-) between the DC
capacitors.
Before starting tests, ensure that meter is set to diode
In H7-H8 units the +/-UDC terminals are directly accessible
scale.
on MK900 on the power card.
In I7-I8 units the +/-UDC terminals are accessible on MK900
6 6
on the power card or on MK3 on the current sensor board. Inverter test part I
For further details, see 6.3.5 Location of UDC Terminals 1. Connect the positive (+) meter lead to the (+)
before measuring) positive DC bus terminal.
2. Connect the negative (–) meter lead to terminals
Rectifier test part I U, V, and W in sequence.
1. Connect the negative terminal of the multimeter Each reading must show infinity. The meter starts at a low
lead to the positive DC Bus. value and slowly climbs toward infinity due to capacitance
2. Connect the positive terminal of the multimeter within the frequency converter being charged by the
lead to the input terminal L1, L2, L3 in turn. The meter.
multimeter indicates Rectifier open.
Rectifier test part II Inverter test part II
3. Reverse the meter leads. That is, connect the 1. Reverse the meter leads by connecting the
positive terminal of the multimeter lead to the negative (–) meter lead to the positive (+) DC bus
positive DC Bus. terminal.
4. Connect the negative terminal of the multimeter 2. Connect the positive (+) meter lead to U, V, and
lead to the input terminal L1, L2, L3 in turn. The W in sequence. Each reading should show a
multimeter indicates Diode open. diode drop.
6. Connect the negative terminal of the multimeter 2. Connect the negative (–) meter lead to terminals
lead to the input terminal L1, L2, L3 in turn. The U, V, and W in sequence. Each reading should
multimeter indicates a diode drop of 0.4 V~0.6 V show a diode drop.
(depending on the power size) on the three Inverter test part IV
terminals. 1. Reverse the meter leads by connecting the
Rectifier test part IV negative (–) meter lead to the negative (-) DC bus
7. Reverse the meter leads. That is, connect the terminal.
negative terminal of the multimeter lead to the 2. Connect the positive (+) meter lead to U, V, and
negative DC Bus. W in sequence.
8. Connect the positive terminal of the multimeter Each reading should show infinity. The meter starts at a
lead to the input terminal L1, L2, L3 in turn. The low value and slowly climb toward infinity due to
multimeter indicates Diode open. capacitance within the frequency converter being charged
by the meter.
NOTE H6
This test is applicable for H7, H8, I7, and I8 units only. Remove the IP20 front cover, then remove the capacitor
vibration support. The terminals K601 (+UDC) and K611
(-UDC) are located between the 4 capacitors on the circuit
The intermediate section of the frequency converter is
board. Remove the metal cover to access these terminals.
made up of the DC bus capacitors, the DC coils, and the
balance circuit for the capacitors.
130BC352.10
1. Test for short circuits with the ohmmeter set on
Rx100 scale or, for a digital meter, select diode.
2. Measure across the positive (+) DC terminal and
the negative (–) DC terminal. Observe the meter
polarity.
6 6 3. The meter starts out with low ohms and then
move towards infinity as the meter charges the
capacitors.
4. Reverse meter leads.
5. The meter pegs at zero while the meter
discharges the capacitors. The meter then begins
moving slowly toward two diode drops as the
meter charges the capacitors in the reverse
Illustration 6.5 UDC Terminals Location on H6 Frequency
direction. Although the test does not ensure that
Converter
the capacitors are fully functional, it ensures that
no short circuits exist in the intermediate circuit.
Incorrect reading
A short circuit could be caused by a short in the inrush
130BC353.10
circuit, rectifier or inverter section. Be sure that the tests
for these circuits have already been performed successfully.
A failure in one of these sections could be read in the
intermediate section since they are all routed via the DC
bus.
The only other likely cause would be a defective capacitor
within the capacitor bank.
There is not an effective test of the capacitor bank when it
is fully assembled. If suspecting a failure within the
capacitor bank, replace the entire bank. Replace the
capacitor bank in accordance with the disassembly
procedures.
130BC356.10
130BC354.10
Illustration 6.9 +/- UDC Terminals
6 6
H9
The UDC terminals are available on connectors at the
bottom of the frequency converter. Static measurements
can be done directly from here.
Illustration 6.7 The UDC Terminals on the Circuit Board
130BC351.10
H7 and H8
Remove the IP20 front cover to access the terminals
directly on the power card MK900.
130BC355.10
W V U
L3 L2 L1 DC+ DC-
H10
130BC358.10
Remove the front terminal cover to access the connectors.
The UDC terminals are located inside the frequency
converter.
130BC351.10
W V U
130BC359.10
Illustration 6.11 UDC Terminals Location on H10 Frequency
Converter
I7 and I8
Remove the IP54 front cover to access the +/- UDC
terminals, either on the power card MK900 or on MK3 on
the current sensor board.
130BC356.10
WARNING
Never disconnect the input cabling to the frequency
converter with power applied due to danger of severe
injury or death.
CAUTION
Take all the necessary safety precautions for system start-
up before applying power to the frequency converter.
Incorrect reading
The reading must be within ±1.5%.
CAUTION
6.4.1 No Display Test (Display is Optional) Open (blown) input fuses or tripped circuit breakers
usually indicate a more serious problem. Before replacing
A frequency converter with no display in the LCP can be fuses or resetting breakers, perform static tests.
the result of several causes. First, verify that there is no
display. A single character in the display or a dot in the An incorrect reading here requires further investigation of
upper corner of the display indicates a communication the main supply. Typical items to check would be:
error. Check that all option cards are properly installed.
When this condition occurs, the green power-on LED is
• Open (blown) input fuses or tripped circuit
illuminated. breakers
not lit, proceed with the following tests. • Problems with the power distribution system
If the Input Voltage Test was successful check for voltage to
First test for proper input voltage. the control card.
6.4.2 Input Voltage Test 6.4.3 Basic Control Card Voltage Test
1. Apply power to frequency converter. 1. Measure the control voltage at terminal 12 with
2. Use the DVM to measure the input mains voltage respect to terminal 20. The meter must read
between the frequency converter input terminals 21-27 V DC.
in sequence: An incorrect reading here could indicate that a fault in the
L1 to L2 customer connections loads down the supply. Disconnect
control wiring and repeat the test. If this test is successful, 6. Reapply power to the frequency converter and
then continue. Remember to check the customer place it in run.
connections. If still unsuccessful, change the control card. 7. Repeat the current measurements.
If the imbalance of supply voltage moves with swapping
2. Measure the 10 V DC control voltage at terminal
the leads, the mains supply is suspect. Otherwise, it may
50 with respect to terminal 55. The meter must
indicate a problem with the gating of the rectifiers.
read between 9.2 and 11.2 V DC.
An incorrect reading here could indicate that a fault in the
6.4.5 Input Waveform Test
customer connections loads down the supply. Disconnect
control wiring and repeat the test. If this test is successful,
Testing the current waveform on the input of the
then continue. Remember to check the customer
frequency converter can assist in troubleshooting mains
connections. If still unsuccessful, change the control card.
phase loss conditions or suspected problems with the SCR/
diode modules. Phase loss caused by the mains supply can
Replace the LCP with a known good one. If the problem be easily detected. In addition, the SCR/diode modules
6 6 persists, replace the control card in accordance with the
disassembly procedures.
control the rectifier section. If one of the SCR/diode
modules become defective or the gate signal to the SCR
lost, the frequency converter responds the same as loss of
6.4.4 Input Imbalance of Supply Voltage one of the phases.
Test
The following measurements require an oscilloscope with
Theoretically, the current drawn on all three input phases voltage and current probes.
must be equal. Some imbalance may be seen, however,
due to variations in the phase to phase input voltage, and
Under normal operating conditions, the waveform of a
single phase loads within the frequency converter.
single phase of input AC voltage to the frequency
converter appears as in Illustration 6.15.
A current measurement of each phase reveals the
balanced condition of the line. To obtain an accurate Input A
130BX142.10
reading, the frequency converter must run at its rated
load, or at a load of not less than 40%.
1. Perform the input voltage test before checking
the current, in accordance with procedure.
Voltage imbalances automatically result in a
corresponding current imbalance.
2. Apply power to the frequency converter and 0.0 ms 5 ms/Div.
one of other two phases. Illustration 6.16 AC Input Current Waveform with Diode Bridge
With a phase loss, the current waveform of the remaining 1. Using a voltmeter, measure AC output voltage at
phases would take on the appearance shown in frequency converter motor terminals 96 (U), 97
Illustration 6.17. (V), and 98 (W). Measure phase-to-phase checking
U to V, then U to W, and then V to W.
Input B
130BX144.10
All three readings must be within 8 V AC of each other.
The actual value of the voltage depends on the speed at
which the frequency converter is running. The volts/hertz
ratio is relatively linear (except in VT mode) so at 60 Hz the
voltage should be approximately equal to the mains
voltage applied. At 30 Hz, it is about half of that, and so
on, for any other speed selected. The exact voltage
reading is less important than balance between phases.
0.0 ms 5 ms/Div.
130BC108.11
1
130BC113.11
4 1
7 7
3
1 LCP
2 Cradle 1 Fan cover plate
1. Remove the 4 screws on the DC coil cover to 1. Remove the 6 screws on coil mounting plate.
access the DC coils.
2. Remove the coil mounting plate.
2. Remove the 4 screws to loosen the cables from
3. Loosen the 4 screws from the DC Link card.
the DC Link card.
4. Press one of the barbs to loosen the link card.
3. Remove the 6 screws on the DC coils (3 screws
on each coil). 5. Unplug the 10-pin ribbon cable and the filter
cable.
4. Remove the coils.
6. Remove the DC Link card.
Reinstall in the reverse order.
Reinstall in the reverse order. Join the mounting snaps.
130BC109.11
1
130BC110.11
1
7 7
2
2
1 DC coil cover
2 DC coils 1 Coil mounting plate
2 Capacitor bank metal cover
Table 7.3 3 DC link card
Table 7.4
4. Remove the 3 screws from U V W cables. 3. Remove the 3 small screws (T10) from the power
card.
5. Press the barbs on the side of the filter.
NOTE
6. Remove the RFI filter.
If it is difficult to get out the screws, use a magnet.
Reinstall in the reverse order. 4. Remove the 6 remaining screws (T20).
5. Lift the power card and slide it out of the frame.
130BC111.11
1 Reinstall in the reverse order.
NOTE
If it is difficult to remove the power card, it is helpful to
130BC112.11
1
1 Power card
1 RFI filter 2 Power card mounting plate
2 EMC shield
Table 7.6
Table 7.5
130BC108.11
1
7.4 H7 Frame Size Disassembly and
Assembly Instructions
2
7.4.1 Control Card and Control Card
Mounting Plate
1 LCP
2 Cradle
3 Control card
4 Control card mounting plate
Table 7.7
1. Remove the LCP ribbon cable from the power 1. Remove the 2 screws (T20) from the filter shield.
card.
2. Remove the shield.
2. Unplug all other cables from the power card,
3. Remove the 4 screws (T20) from the power card
including the 3 gate cables at the bottom of the
mounting plate.
card.
4. Remove the power card mounting plate.
3. Remove the 3 screws (T20) from the mounting
plate. 5. Unplug all cables from the inrush card.
4. Remove the power card by pushing in the 6 6. Remove the 6 screws (T20) from the inrush card.
retaining clips. 7. Remove the inrush card.
NOTE Reinstall in the reverse order.
Use a screwdriver if the retaining clips are hard to reach.
5. Slide the power card out and remove it.
130BC346.10
1
Reinstall in the reverse order.
7 7
130BC125.11
1 Power card
Table 7.9
Table 7.8
1. Remove the red/black cables from the filter cable. 1. Unplug cables on the relay transducer card.
2. Remove the protective foil. 2. Loosen the right cable connector using a hex 5
3. Remove the 3 filter cables screws using a hex 8 key.
key. 3. Open the plastic clamp to remove the cables
4. Remove the 2 screws (T20) from the EMC shield. from the connector.
5. Remove the EMC shield. 4. Remove the 2 screws (T20) from the holding
bracket.
6. Remove the 8 screws (T20) on the filter cable
cover. 5. Remove the holding bracket.
7. Loosen the left cable connector using a hex 5 key 6. Remove the 3 cable screws (T20).
7. Remove the 3 screws on relay card (T20).
8. Remove the entire filter assembly.
8. Remove the Relay card by pushing in the
Reinstall in the reverse order.
retaining clips on the standoffs. Use a screwdriver
if necessary.
7 7
130BC126.11
1
9. Remove the mounting plate.
2
Reinstall in the reverse order.
130BC127.11
1
1 RFI filter
2 Screws Illustration 7.11 Relay or Transducer Card
3 EMC shield
Table 7.10
1 Relay transducer card
2 Relay card mounting plate
Table 7.11
130BC131.11
1. Loosen and remove the 2 cables (T20).
2. Remove the 6 screws (T20) from the shield.
3. Remove metal shield and plastic cover.
4
4. Remove the 2 screws (T20) from each of the
rectifier modules. 3
5. Remove the 3 rectifier modules. 2
7.4.7 IGBT
CAUTION 3
4
Bus bar
Capacitor
The IGBTs and the heatsink have thermal paste on them.
Be careful not to touch the paste directly as it is Table 7.12
poisonous.
11. Remove the thermal paste from the IGBT.
12. Clean the heatsink.
Reinstall in the reverse order. Join the mounting snaps.
1. Remove the 4 screws (T20) from the fan cover 1. Remove the 4 screws (T20) from the DC coil
plate. cover plate.
2. Press the fan cover plate outwards using a 2. Remove the 4 screws (T20) from the heatsink.
screwdriver.
3. Remove the heatsink.
3. Remove the fans and the fan cover plate.
4. Remove 4 screws (T20) from each of the 2 DC
Reinstall in the reverse order. Coils.
5. Remove the coils.
130BC132.11
Reinstall in the reverse order.
130BC133.12
1 1
2
7 7
3
Illustration 7.13 Heatsink Fan Assembly
1 Fan cover
2 Fan assembly
Table 7.13
Table 7.14
1 Foil
2 Bottom plate
3 Capacitor bank
Table 7.15
130BC108.11
1
1. Remove 2 screws (T20) from the EMC shield.
2. Remove cables from EMC shield.
2
3. Remove the EMC shield.
4. Remove the LCP ribbon cable from the power
3 card.
5. Unplug all other cables from the power card.
6. Remove the 3 screws (T20) from the mounting
plate.
4 7. Remove the power card by pushing in the 6
retaining clips.
NOTE
Use a screwdriver if the retaining clips are hard to reach.
8. Slide the power card out and remove it.
Reinstall in the reverse order. 7 7
130BC125.11
1
1 LCP
2 Cradle
3 Control card
4 Control card mounting plate
Table 7.16
1 Power card
Table 7.17
130BC346.10
1
7 7 8.
9.
Remove the plastic cover.
Remove the 2 screws (T20) on each of the
rectifier modules
2 10. Remove the thermal paste paper.
11. Clean up any excessive thermal paste.
Reinstall in the reverse order. Join the mounting snaps.
3
1 EMC shield
2 Power card mounting plate
3 Inrush card
Table 7.18
130BC128.11
1
4
5. Remove the entire filter assembly.
Reinstall in the reverse order.
130BC126.11
1
2
3 7 7
Table 7.20
5. Remove the 3 screws (T30) on the relay card. 2. Remove the cable retaining guide.
6. Remove the 2 10-pin ribbon cables. 3. Remove the 4 screws (T20) from the cable
connector plate.
7. Remove the 3 screws (T20) from the relay card.
4. Remove the cable connector plate.
8. Press the 3 retaining clips.
5. Remove the 2 cable screws (T20)
9. Remove the relay card.
6. Remove the 2 screws (T30) in each of the 2
10. Remove the relay card mounting plate. capacitors.
7 7 Reinstall in the reverse order. 7. Remove the capacitors.
8. Remove the 2 screws (T30) from the bus bar.
130BC127.11
1
9. Remove the 4 screws (T20) holding the
capacitors.
10. Remove the bus bar.
2
11. Remove the gate cables from the IGBTs.
12. Remove the 4 screws from each IGBT.
13. Remove the thermal paper.
14. Remove the thermal paste from the IGBTs and
the heatsink.
Reinstall in the reverse order. Join the mounting snaps.
Table 7.21
130BC131.11
1. Remove the 4 screws (T20) from the fan cover
plate.
2. Press the fan cover plate outwards using a
4 screwdriver.
3. Remove the fans and the fan cover plate.
3
Reinstall in the reverse order.
2
130BC132.11
2
1
7 7
1. Remove the 4 screws (T20) from the DC coil 1. Remove the foil.
cover plate. 2. Remove the 4 screws from the bottom plate.
2. Remove the 4 screws (T20) from the heatsink. 3. Remove the bottom plate.
3. Remove the heatsink. 4. Remove the 4 screws from the capacitor bank
4. Remove 4 screws (T20) from each of the 2 DC assembly.
Coils. 5. Remove the assembly.
5. Remove the coils. 6. Turn the assembly upside-down.
Reinstall in the reverse order. 7. Remove the 2 hex nuts with a hex 19 key.
8. Remove the 2 capacitors.
130BC133.12
1 Reinstall in the reverse order.
2
130BC348.10
7 7
3
Table 7.24
1 Foil
2 Bottom plate
3 Capacitor bank
Table 7.25
130BC103.11
removed by hand.
2. Remove 3 screws (T10) securing the control card
mounting plate to the control assembly support
bracket.
3. Carefully lift out the control card.
Reinstall in the reverse order. 130BC101.11
7 7
1
3
Illustration 7.27 Power Card Cover
Table 7.27
1 LCP
2 Control card mounting plate
3 Control card
Table 7.26
1. Remove the 4 screws (T10) for the DC coil cables. 1. Remove the 7 mounting screws from top surface.
2. Remove the 5 screws (T10) for the heatsink. 2. Press and loosen the 3 barbs at the bottom.
3. Remove the 4 IGBT screws (T25). 3. Unplug the DC coil cables.
4. Unplug fan cable connector. 4. Remove the heatsink.
The power card and the heatsink have thermal paste on Reinstall in the reverse order.
them. Wear protective gloves as the paste is poisonous.
5. Lift out the power card.
130BC105.11
6. Remove the capacitor bank gasket.
Reinstall in the reverse order.
130BC104.11
7 7 1
Table 7.29
1 Power card
130BC106.11
Table 7.28
1 DC coil
Table 7.30
130BC107.11
7 7
1
1 Heatsink fan
2 Fan mounting plate
Table 7.31
130BC059.11
1
130BC064.11
7. Remove 2 screws (T20) from the mounting plate.
Reinstall in the reverse order.
130BC060.11 2
8 8
2
1
1 Fan cover
Illustration 8.2 Cable Mounting Plate 2 Fan assembly
Table 8.3
1 EMC shield
2 Cable mounting plate
Table 8.2
1. Remove the 3 black plastic covers. 1. Remove the 2 screws from the snubber capacitor
2. Unplug and remove the fan. on the bus bar unit.
4. Remove the 2 screws (T20) at MK101. 3. Use a Hex 8 key to remove 2 screws from the bus
bar unit.
5. Remove the 3 screws (T20) at K103A, K104A, and
K105A. 4. Remove the 6 small screws (T10).
6. Remove the 4 screws (T20) and from the SMPS 5. Remove the remaining 9 screws (T20).
card. 6. Unplug cables.
7. Lift off the SMPS card. 7. Lift out the bus bar unit.
Reinstall in the reverse order. Reinstall in the reverse order.
1
130BC061.11
130BC062.11
1
8 8
1 SMPS card
Table 8.4
1 Fan
2 Bus bar unit
Table 8.5
130BC065.11
130BC063.11
1
Illustration 8.7 8 8
Illustration 8.6 Power Card
1 DC coil
1 Power card
Table 8.7
Table 8.6
130BC066.11
1. Remove 2 screws (T20) from the 2 cover plates.
1
2. Remove the LCP cradle.
3. Remove 3 screws (T10) from the control card.
4. Remove the control card.
5. Remove 2 screws (T20) from the bracket next to
the control card mounting plate.
6. Remove 4 screws (T20) to remove the control
card mounting plate.
7. Unplug the LCP ribbon cable.
8. Remove the control card mounting plate.
8 8 Illustration 8.8
Reinstall in the reverse order.
1 RFI filter
Table 8.8
130BC059.11
1
3
4. Remove the power card.
4 Reinstall in the reverse order.
5
130BC070.11
1
8 8
Illustration 8.10
Illustration 8.9 Control Card Mounting Plate
1 Power card
1 LCP and cradle
2 Control card and mounting plate Table 8.10
3 EMC shield
Table 8.9
1. Remove 4 screws (T20) from the power card 1. Unplug all cables.
mounting plate.
2. Remove 6 screws (T20) from the inrush card.
2. Remove the power card mounting plate with the
3. Remove the inrush card.
fan attached.
Reinstall in the reverse order.
Reinstall in the reverse order.
130BC072.11
1
130BC071.11
1
8 8
Illustration 8.12
Illustration 8.11
1 Inrush card
1 Power card mounting plate
Table 8.12
Table 8.11
1. Unplug and remove the red/black cable. 1. Unplug the 3 filter cables from the thyristors
2. Remove the black plastic cover. using a hex 8 key.
3. Remove 8 screws (T20) from the support bracket. 2. Loosen the 3 cables from the cable connector
using a hex 5 key.
4. Remove the bus bar assembly.
3. Remove 3 screws (T20) from the support bracket.
Reinstall in the reverse order.
4. Remove support bracket.
5. Remove 4 screws (T20) from the RFI Filter.
130BC073.11
1
6. Remove the entire assembly.
Reinstall in the reverse order.
130BC076.11
1
8 8
Illustration 8.13
1 Bus bar
1 RFI filter
Table 8.14
1. Remove the 3 clamps on each side of the 2 cable 1. Remove 2 screws (T20) on the fan bracket.
connectors. 2. Remove 2 screws (T20) from the fan.
2. Remove the cable connector with no cables 3. Remove the fan.
attached.
Reinstall in the reverse order.
3. Remove 3 screws (T20) from the support bracket.
4. Loosen the 3 cables from the relay transducer 1
130BC077.10
card.
5. Remove the cable connector with cables and
retaining guide attached.
6. Unplug all other cables from the relay transducer
card.
7. Remove the 3 screws (T20)
8. Remove the relay transducer card.
Reinstall in the reverse order.
8 8
130BC075.11
Illustration 8.16
1 Fan
Table 8.16
Illustration 8.15
Table 8.15
1. Remove the black plastic cover. 1. Remove 2 screws (T20) from the 2 snubbers.
2. Remove 4 screws (T20) on the cover plate. 2. Remove the snubbers.
3. Remove the terminal plate. 3. Loosen and remove cables from bus bar assembly
Reinstall in the reverse order. and DC coil.
4. Remove 6 screws (T20) from the bus bar
assembly.
130BC078.11
1 5. Remove the bus bar assembly.
Reinstall in the reverse order.
130BC080.11
1
8 8
Illustration 8.17
1 Terminal plate
Table 8.18
1. Remove gate cables from IGBTs. 1. Remove 4 screws (T20) from each of the
2. Remove 2 screws (T20) from the heatsink fan capacitors.
assembly. 2. Remove the capacitors.
3. Push the fan cable down through the gasket. Reinstall in the reverse order.
4. Carefully press the gasket down with a
130BC081.11
screwdriver.
1
5. Remove the fan assembly.
Reinstall in the reverse order.
130BC350.10
2
1
1 Capacitors
Table 8.19
1. Remove 5 screws (T20) on the potted coil. 1. Remove 2 screws (T20) from each of the 3 IGBTs.
2. Remove the DC coil.
CAUTION
Reinstall in the reverse order. The IGBTs and the heatsink have thermal paste on them.
Wear protective gloves as the paste is poisonous.
2. Remove all IGBTs.
130BC082.11
1
Reinstall in the reverse order.
130BC083.11
2
1
Table 8.21
1 IGBT
Table 8.22
8.3.15 Thyristor
8.4 I8 Frame Size Disassembly and
1. Remove 2 screws (T20) from each of the 3
thyristors.
Assembly Procedure
130BC074.11
1
1 Thyristor
Table 8.23
130BC059.11
1
3
4. Remove the power card.
4 Reinstall in the reverse order.
5
130BC070.11
1
8 8
Illustration 8.25
Illustration 8.24 Control Card Mounting Plate
1 Power card
1 LCP and cradle
2 Control card and mounting plate Table 8.25
3 EMC shield
Table 8.24
1. Remove 4 screws (T20) from the power card 1. Unplug all cables.
mounting plate.
2. Remove 6 screws (T20) from the inrush card.
2. Remove the power card mounting plate with the
3. Remove the inrush card.
fan attached.
Reinstall in the reverse order.
Reinstall in the reverse order.
130BC072.11
1
130BC071.11
1
8 8
Illustration 8.27
Illustration 8.26
1 Inrush card
1 Power card mounting plate
Table 8.27
Table 8.26
1. Unplug and remove the red/black cable. 1. Unplug the 3 filter cables from the thyristors
2. Remove the black plastic cover. using a hex 8 key.
3. Remove 6 screws (T20) and 2 screws (T30) from 2. Loosen the 3 cables from the cable connector
the support bracket. using a hex 5 key.
4. Remove the bus bar assembly. 3. Remove 3 screws (T20) from the support bracket.
130BC073.11
1
Reinstall in the reverse order.
130BC076.11
1
8 8
Illustration 8.28
1 Bus bar
Illustration 8.29
Table 8.28
1 RFI filter
Table 8.29
1. Remove 2 screws (T20) from each of the 2 cable 1. Remove 4 screws (T20) on the cover plate.
connectors.
2. Remove the complete terminal plate including
2. Remove the cable connector. cable connector.
3. Remove 3 screws (T20) from the support bracket. Reinstall in the reverse order.
4. Loosen the 3 cables (T30) from the relay
transducer card.
130BC078.11
1
5. Unplug all other cables from the relay transducer
card.
6. Remove the 3 screws (T20).
7. Remove the relay transducer card.
Reinstall in the reverse order. 130BC075.11
8 8 Illustration 8.31
1 Terminal plate
Table 8.31
Table 8.30
1. Remove 2 screws (T30) from each of the 2 1. Remove 4 screws (T20) from the heatsink fan
snubbers. assembly.
2. Remove the snubbers. 2. Push the cables down through the gaskets.
3. Loosen and remove the 2 cables from bus bar 3. Carefully press the gaskets down with a
assembly and DC coil. screwdriver.
4. Remove 2 screws (T30). 4. Remove the fan assembly.
5. Remove 8 screws (T20) on top of the bus bar Reinstall in the reverse order.
assembly.
6. Remove the bus bar assembly.
130BC094.11
Reinstall in the reverse order.
1
130BC080.11
2
8 8
Illustration 8.33 Heatsink Fan Assembly
Table 8.32
1. Remove 4 screws (T20) from each of the 1. Remove 5 screws (T20) on the potted coil.
capacitors.
2. Remove the DC coil.
2. Remove the capacitors.
Reinstall in the reverse order.
Reinstall in the reverse order.
130BC082.11
1
130BC081.11
1
1 Bus bar
1 Capacitors 2 DC coil
1. Remove 4 screws (T20) from each of the 3 IGBTs. 1. Remove 2 screws (T20) from each of the 3
thyristors.
CAUTION
The UGBTs and the heatsink have thermal paste on them. CAUTION
Wear protective gloves as the paste is poisonous. The thyristors and the heatsink have thermal paste on
2. Remove all IGBTs. them. Wear protective gloves as the paste is poisonous.
2. Remove the thyristors.
Reinstall in the reverse order.
Reinstall in the reverse order.
130BC083.11
1
130BC074.11
1
8 8
1 IGBT
1 Thyristor
Table 8.36
Table 8.37
9 Block Diagrams
130BC339.10
Brake not connected to terminal on FC 101
AC / DC BR DC /AC
RFI (variations)
Inrush
L1 A
U
MAINS
Motor
L2 x3 RFI _ RL 2 x3 A V
L3 A W
o
C
RFI _ RL 1
BR BR INV Temp.
FB GD GD conv.
GD
Supply
RL 1
uC+ RL 1
Tmp_ VGDS
P_BRF
7 xGD
RL 2
SMPS EEP RL 2
RFI _RL 1
RFI _ RL 2 VGD +/- 15 /UDC -/-5
Inrush
Control Card UINV_P SAFE _ FB
VCX (GX ) 5V
Tmp _VGDS
D-I /O
9 9
UINV_N VCC
A-I /O VCC (GND) 5V
Isol. RS 485 FAN 1 Int.
FFB 1 fans
VDD (GND) 24V
Imax2 comp.
VGD +/- 15 /UDC -/-5 Level
Shift
LCP ACP MCP
Display
CAN
”Internal Communication”
control
panel ”Internal supply bus”
Illustration 9.1
RFI (variations)
Inrush A
L1 U
x3 RFI _ RL 2 x3 A
L2 V
Motor
MAINS
L3 W
o A
C
RFI _ RL 1
BR BR INV Temp.
FB GD GD conv.
GD
Supply
RL 1
uC+ RL 1
RL 2
EEP P_ BRF
7 xGD
SMPS
RL 2
RFI _ RL 1
Tmp _ VGDS
SAFE _ FB
UINV_ P VCX (GX ) 5V
Illustration 9.2
97
9 9
9 9
98
Thyristor x3 AC /DC Brake not connected to terminal on FC 101
Block Diagrams
BR DC /AC
130BC340.10
RFI (variations)
A
U
L1 x3 A V
Motor
L2 W
o A
MAINS
L3 C
9.1.3 H7, H8, I7, I8 Frame Size
RL 1
uC+ RL 1
RL 2
EEP
7 xGD
RFI _ RL 1 P _BRF
Tmp _VGDS
RL 2
RFI _ RL 2 VDD (GND ) 24V
Inrush
SMPS SAFE _ FB
Control Card UINV_ P
Tmp _ VGDS
VLT® HVAC Basic Drive Service Manual
UINV_N VCC
Int.
D-I/O VCX (GX) 5V
Illustration 9.3
Block Diagrams
130BC136.10
AC/DC BR DC /AC
RFI (variations)
Inrush
9.1.4 H9 Frame Size
A
L1 U
x3 RFI _ RL 2 x3 A
L2 V
Motor
MAINS
L3 A W
o
C
RFI _ RL 1
BR BR INV Temp.
FB GD GD conv.
GD
Supply
RL 1
uC+ RL 1
EEP RL 2
P _BRF
7 xGD
SMPS
RL 2
RFI _ RL 1
Tmp_VGDS
RFI _ RL 2
VGD+/- 15/UDC-/-5
Inrush
Control Card UINV _ P SAFE _ FB
VLT® HVAC Basic Drive Service Manual
VCX (GX ) 5V
Tmp_VGDS
Illustration 9.4
99
9 9
9 9
100
Block Diagrams
A
L1 U
x3 RFI _ RL 2 x3 A
L2 V
Motor
MAINS
L3 A W
o
C
RFI _ RL 1
BR BR INV Temp.
FB GD GD conv.
GD
Supply
RL 1
RL 1
uC+
RL 2
EEP P_ BRF
7 xGD
SMPS
RL 2
RFI _ RL 1
Tmp _ VGDS
Illustration 9.5
Index VLT® HVAC Basic Drive Service Manual
Index
H
Heatsink........ 11, 12, 13, 28, 58, 64, 65, 70, 72, 74, 75, 77, 86, 93,
A 95
AMA........................................................................ 34, 36, 37, 39, 41, 42
Analog
Inputs................................................................................................... 36 I
Output........................................................................................... 19, 42 IGBT...................................... 12, 13, 16, 24, 28, 34, 41, 43, 44, 49, 53
Signal............................................................................... 19, 20, 36, 56 Impedance.................................................................. 22, 26, 43, 44, 45
Signals.................................................................................................. 18
Input
Cabling................................................................................................. 52
C Signal............................................................................... 18, 20, 39, 42
Cable Cross Section............................................................................. 22 Terminals............................................................................................. 36
Gating Circuit......................................................................................... 25
R
Reference Signal................................................................................... 34
S
SCR...................................................................................................... 25, 54
Serial Bus...................................................................... 18, 19, 33, 34, 36
Short Circuit................................................................ 17, 38, 48, 49, 50
Signal Conductor.................................................................................. 44
Status
Line........................................................................................................ 18
Messages...................................................................................... 18, 33
Switch................................................................................................ 24, 32
Switching Function.............................................................................. 24
T
Thermal Sensor............................................................................... 28, 43
Thyristor................................................................................................... 24
Torque Limit.................................................................................... 41, 43
Trip
Condition............................................................................................ 34
Lock................................................................................................ 35, 36
V
Voltage
Imbalance............................................................................. 37, 43, 55
Waveform.................................................................................... 28, 55
W
Waveform............................................... 23, 26, 28, 41, 42, 44, 54, 55
*MG90X202*