Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Trane Mie

Download as pdf or txt
Download as pdf or txt
You are on page 1of 56

Split System Heat Pumps

Split System Heat Pumps


TWA075A-TWA200B
Air Handlers
TWE050A-TWE200B
50 Hz

November 2003 SSP-PRC002-EN


Introduction

Split System Heat Pump Units . . .


Designed With Your Needs In Mind.

The Trane reputation for quality and Designing the Details Filters
reliability in air conditioning continues Careful attention was given to designing The TWE050A, 075A, 100A and 100B air
with the Odyssey™ family of light the details — from control wiring to the handlers are supplied with 1" (25.4 mm)
commercial split systems. Trane paid access panels. Odyssey units feature throwaway filters as standard.The filter
attention to your needs to make sure you time-saving colored and numbered racks were designed to easily convert for
get a system that will meet your job wiring and removable panels which installation of 2" (50.8 mm) filters. The
requirements every time...and at a allow complete access to all major TWE155B and 200B air handlers have 2"
competitive price. components and controls. All outdoor (50.8 mm) filters as standard.
CoupleTrane’s reputation for quality and units feature external high and low
reliability in split system air conditioners pressure switches for easy diagnosing UL Listed and ARI Certified
with efficiency, flexibility and installation and servicing of the unit. Service valves
ease...and you have systems that will with gauge ports are provided on all Trane meets or exceeds all nationally
give you “SimplyThe Best Value.’’ units. recognized agency safety and design
standards. Each condensing unit is UL
designed, approved and labeled in
Manufacturing Control Standardized Cabinets accordance to UL Standards: UL 1995 for
Trane’s exclusive control over the design In addition, all cabinets have been central cooling air conditioners,
and manufacturing of all major standardized. When you are servicing an refrigeration and air conditioning
components is unique in the industry. outdoor unit or an air handler, all condensing and compressor units. Each
This approach assures us total control components are in the same location air handler is designed, approved and
over both the quality and reliability of from unit to unit. labeled in accordance to UL 465 and UL
these components. And allows us to 1995 standard for heat pumps. Each unit
custom match components to deliver the is certified in accordance with ARI
best in split system performance. Standard 210/240 or 340/360.

©American Standard Inc. 2001 SSP-PRC002-EN


Contents

Introduction 2
Features and Benefits 4
Application Considerations 6
Selection Procedure 7
Model Number Description 8
General Data 9
Performance Data 12
Cool and Heat Performance 12
Fan Performance 24
Electric Power 31
Connection and Wiring 33
Dimension and Weights 39
Mechanical Specifications 52

SSP-PRC002-EN 3
Features and
Benefits

Condensing Units Options Trane split systems have been specified Air Handlers Offer More
in thousands of applications and you’ll Flexibility
TheTWA075A and 100A single
find Odyssey will win you even more
compressor models feature single jobs with its small manageable cabinet.
refrigeration circuitry, lowering job Flexibility is a key to meeting changing
This light, compact design will save time market requirements. Odyssey split
installation costs by requiring only one
and money for rigging and installation. sytems offer not only heat pumps but
set of refrigerant lines.These units are And the compactness will permitTrane’s
ideal for the low cost, new construction also convertible air handlers.The air
unit to replace almost any unit — handlers can be installed either vertically
jobs as well as renovation and
effortlessly. in a mechanical room or horizontally
replacement buildings.
Low Ambient Cooling Operation above a ceiling. And it doesn’t require
In addition, Odyssey includesTWA155B any removal of panels to make either
and 200B dual compressor units to give Each heat pump unit can operate to 50°F airflow application work.These air
true stand-by protection; if one (10°C) as standard in the cooling mode. handlers have a double sloped
compressor fails, the second will An accessory Head Pressure Control condensate drain pan that allows for
automatically start-up. Also, the first gives you the capability to operate to 0°F either airflow configuration. And the
compressor can be serviced without (-18°C). All heat pumps offer these drain pan can easily be removed for
shutting down the unit since the accessories: cleaning. All the air handlers feature
refrigerant circuits are independent. • Head Pressure Control factory installed belt drive and ball
• Coil Guard Kits bearing evaporator fans with adjustable
Dual compressors are not just for • Isolators both Rubber-in-Shear and sheaves for maximum airflow
protection, they also save energy costs. SpringType performance. In fact, the standard motor
Most buildings are designed for the peak • Anti-Short-Cycle Kit on theTWA100A air handler will deliver
load requirements yet the building • Time Delay Relay 3325 cfm (5649 m3/hr) at 1.4" (349 Pa)
usually operates at less than peak load. ESP. Plus oversized motors are available
During light load conditions, only one for higher static applications.
compressor functions to maintain the
space comfort thus reducing the need
for energy.

4 SSP-PRC002-EN
Features and
Benefits

Odyssey air handler versatility is further Odyssey Lowers Installation


increased by a complete line of
accessories designed to match and
Costs
install smoothly: Your installation costs are reduced with
• Discharge Plenum and Grille Odyssey. Both outdoor units and air
• Return Grille handlers are factory packaged and
• Subbase assembled so jobsite installation is quick
• Electric Heaters and easy.You get a complete unit with
• High Static Evaporator Motor all the components, controls and the
• Isolators both Rubber-in-Shear internal wiring factory ready for a
and SpringType smooth jobsite start-up.
• A Full Line ofThermostats
• OutdoorThermostat Unlike some competitive models the
following components are factory-
installed inTrane air handlers:
• Single Point Power Entry
• Blower wheel and housing
• Evaporator motor with sheaves
andpulleys
• Low VoltageTerminal Board
• Transformer
• Contactor
• Fan relay
• DX Coil with complete refrigeration
circuitry
• Expansion Valve and Check Valves

There’s no need to install components


and put together the air handler on the
job.This provides you with less labor
cost and fewer chances for installation
errors which cause callbacks. All this
means saving you money both in
replacement and new construction
applications.

Odyssey — A Complete Split


System
Odyssey delivers the flexibility to select
a complete system that meets your
particular job requirements. Air
handlers are designed, tested, and
rated with outdoor units to let you
select the proper match between
capacity and load. Heat pumps can also
be matched withTrane built-up air
handlers. Also, these matched systems
can be quickly engineered for specific
applications usingTrane’s computerized
selection and load programs.

SSP-PRC002-EN 5
Application
Considerations

Application of this product should be Low Ambient Cooling


within the catalogued airflow and As manufactured, these units can
performance considerations. operate to 50°F (10°C) in the cooling
mode of operation. An accessory head
Clearance Requirements pressure control will allow operation to
0° F (-17.8°C) outdoor ambient. When
The recommended clearances identified
using these units with control systems
with unit dimensions should be
maintained to assure adequate such as bypass changeover Variable Air
Volume, make sure you consider the
serviceability, maximum capacity and
requirement for a head pressure control
peak operating efficiency. Actual
clearances which appear inadequate to allow low ambient cooling.
should be reviewed with the localTrane
Representative.

180° Blower Rotation


TheTWE050, 075 and 100 air handler
blower section can be rotated 180° to
change the discharge pattern.This
modification must be done in the field
and requires an addition of kit. See unit
installer's guide.
Typical Horizontal Air Handler Application Typical Vertical Air Handler Application

Typical Split System Application

6 SSP-PRC002-EN
Selection
Procedure

Cooling Capacity Table PD-9 indicates the mechanical


Step 1 — Calculate the building’s total Note:The Evaporator Fan Performance heating portion of the heat pump will
and sensible cooling loads at design Table has included the effect of a 1 in. provide 49.1 MBh (14.4 kW) for the
conditions. (250 Pa) filter already.Therefore, the winter design conditions.
Step 2 — Size the equipment usingTable actualTotal Static Pressure is 1.10 - 0.10 = Step 3 — Because 49.1 MBh (14.4 kW) is
PD-1. Match the cooling loads at design 1.00 in. (275 - 25 = 250 Pa). less than the building’s required heating
conditions. With 2500 cfm (4247 m3/h) and 1.00 capacity, a supplementary heater must
Example:The following are the building inches (250 Pa),Table PD-15 shows a 1.07 be selected. 110 - 49.1 = 60.9 MBh (32.2 -
cooling requirements bhp (0.8 kW). 14.4 = 17.8 kW) minimum heater
a Note:The formula below the table can be capacity.
Electrical Characteristics: 380-415/50/3 used to calculate Fan Motor Heat, FromTable PD-25, the 24.22 kW heater
b Constant x Motor Power = has a capacity of 82,670 Btu. FromTable
Summer Design Conditions: Entering Fan Motor Heat ED-5, the 24.22 kW heater at 400V
Evaporator Coil: 80 DB/67 WB 3.5 x bhp = MBh indicates the heater model number is
(27 DB/19 WB°C) 3.5 x 1.07 = 3.75 MBh BAYHTRL435A.This heater will be
Outdoor Ambient: 95°F (35° C) 1.375 x (kW) = kW adequate to cover the residual heat
c 1.375 x 0.8 = 1.1 kW capacity needed for the application.
Total Cooling Load: 75 MBh (22kW) Air Delivery Selection
d NetTotal Cooling Capacity
= 85.1 MBh – 3.75 = 81.35 MBh External static pressure drop through the
Sensible Cooling Load: 53 MBh air distribution system has been
(15.5 kW) = 24.9 kW - 1.1 = 23.8 kW
Net Sensible Cooling Capacity calculated to be 0.77 inches (192.5 Pa) of
e water gauge. FromTable PD-24 static
Airflow: 2500 cfm (4247 m3/h) = 60.8 MBh – 3.75 = 57.05 MBh
= 17.8 MBh - 1.1 = 16.7 kW pressure drop through the electric heater
External Static Pressure: 0.77 in. wg is 0.12 inches (30 Pa) of water (0.77 + 0.12
(193 Pa) Heating Capacity = .89 in.) (192.5 + 30 = 222.5 Pa). Enter
Table PD-1 shows that aTWA075A Step 1 — Calculate the building heating Table PD-15 forTWE090A4 at 2500 cfm
matched with aTWE075A has a gross load using theTrane calculation form or (4247 m3/h) and .90 in. (225 Pa) static
cooling capacity of 85.1 MBh (24.9 kW) any other standard accepted method. pressure.The standard motor at 790 rpm
and 60.8 MBh (17.8 kW) sensible capacity Step 2 — Size the equipment usingTable will give the desired airflow.
at 95 DB (35°C) ambient and 2500 cfm PD-9 to match the heating loads at
(4247 m3/h) and 80 DB/67 WB (27 DB/19 design conditions.The following are
WB) air entering the evaporator. building heating requirements:
To find the net cooling capacities, fan a
motor heat must be subtracted. Total Heating Load: 110 MBh (32.2 kW)
Determine the total unit static pressure: b
Outdoor Ambient (Winter): 17°F
External Static 0.77 in (193 Pa) (-8.3°C) DB
Standard Filter 0.10 in (25 Pa) c
Supplementary Electric Heat Indoor ReturnTemperature: 70°F
0.23 in (57 Pa) (21.1°C) DB
Total Static Pressure 1.10 in (275 Pa) d
Airflow: 2500 cfm (4247 m3/h)

SSP-PRC002-EN 7
Model
Number
Description

Split System Heat Pump Model Nomenclature

T W A 0 7 5 A D 0 0 D A
1 2 3 4 5 6 7 8 9 10 11 12

Digits 1, 2, 3 - Product Type Digit 8 - Electrical Characteristics

TWA = Split System Heat Pump D = 380-415/3/50

Digits 4, 5, 6 - Nominal Gross Cooling Capacity Digits 9, 10 - Factory - Installed Options


(MBh) 00 = No Options
0S = Black Epoxy Coated Coil
075 = 75
100 = 100 Digit 11- Minor Design Sequence
155 = 155
200 = 200 D = Fourth

Digit 12- Service Digit


Digit 7- Major Development Sequence
A = First
A = Single Compressor
B = Dual Compressor

Air Handler Model Nomenclature

T W E 0 5 0 A D 0 0 C A
1 2 3 4 5 6 7 8 9 10 11 12

Digits 1, 2, 3 - Product Type Digit 8 - Electrical Characteristics

TWE = Cooling Convertible D = 380-415/3/50


Digit 9, 10 - Factory - Installed Options
Digits 4, 5, 6 - Nominal Gross Cooling 00 = No Options
Capacity (MBh)
Digit 11- Minor Design Sequence
050 = 50
075 = 75 C = Third
100 = 100
Digit 12- Service Digit
155 = 155
200 = 200 A = First
Digit 7- Refrigerant Circuit
A = Single
B = Dual

8 SSP-PRC002-EN
General
Data (Heat Pumps)

Table GD-1 — General Data — Heat Pumps


TWA075A TWA100A
Cooling Performance1
Gross Cooling Capacity, Btu (kW)
Matched Air Handler, Btu (kW) 85,000 (24.89) 112,000 (32.79)
Heat Pump Only2, Btu (kW) 85,000 (24.89) 112,000 (32.79)
ARI Net Cooling Capacity3 83,000 (24.30) 108,000 (31.62)
System Power kW 7.91 10.27
Heat Pump Only Power kW 7.12 9.32
Heating Performance
ARI Heating with Matched Air Handler
HighTemperature Capacity, Btu (kW) 81,000 (23.72) 110,000 (32.21)
LowTemperature Capacity, Btu (kW) 49,000 (14.35) 71,000 (20.79)
Compressor
Number 1 1
Type 3D®Scroll 3D®Scroll
No. Motors 1 1
Motor HP (kW) 6.25 (4.7) 8.33 (6.21)
Motor RPM 2875 2875
ARI Sound Rating (Bels)4 8.8 8.8
System Data5
No. Refrigerant Circuits 1 1
Suction Line, in. (mm) OD 1.375 (34.9) 1.375 (34.9)
Liquid Line, in. (mm) OD 0.500 (12.7) 0.500 (12.7)
Outdoor Coil —Type Plate Fin Plate Fin
Tube Size, in. (mm) OD 0.375 (9.5) 0.375 (9.5)
Face Area, sq. ft (m2) 19.2 (1.78) 29.5 (2.74)
Rows 2 2
Fins Per Inch 18 18
Outdoor FanType Propeller Propeller
No. Used 1 1
Diameter, in. (mm) 26.00 (660.4) 28.00 (711)
DriveType Direct Direct
No. Speeds 1 1
CFM6, (m3/h) 4900 (8325.1) 6700 (11383.30)
No. Motors 1 1
Motor HP (kW) 0.33 (.25) 0.75 (.56)
Motor RPM 925 925
R-22 Refrigerant Charge, lb7 (kg) 18.0 (8.16) 31.5 (14.29)
Notes:
1. Cooling Performance is rated at 95°F (35°C) ambient, 80°F (26.7°C) entering dry bulb, 67°F (19.4°C) entering wet
bulb and nominal cfm listed. ARI rating cfm is 350 cfm/ton for this product. Gross capacity does not include the
effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for
operation to ±20% of nominal cfm. Rated accordance with ARI Standard 340/360-00.
2. Condensing Unit Only Gross Cooling Capacity rated at 45°F (7.2°C) saturated suction temperature and at 95°F
(35°C) ambient.
3. ARI Net Cooling Capacity is calculated with matched blower coil and 25 ft (7.2 m) of 1.375, 0.500 OD interconnect-
ing tubing. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. Integrated
Part Load Value is based on ARI Standard 340/360-00. Units are rated at 80°F (26.7°C) ambient, 80°F (26.7°C) entering dry
bulb, and 67°F (19.4°C) entering wet bulb at ARI rated cfm.
4. ARI Sound Rating is rated in accordance with ARI Standard 270 or 370.
5. System Data based on maximum linear length 80 ft (26.7 m). Maximum lift: suction 60 ft (18.3 m) liquid 60 ft (18.3
m). For greater lengths, refer to refrigerant piping applications manual.
6. Outdoor Fan cfm is rated with standard air-dry coil outdoor.
7. Refrigerant (operating) charge is for condensing unit (all circuits) with matching blower coils and 25 ft (7.6 m) of
interconnecting refrigerant lines.

SSP-PRC002-EN 9
General
Data (Heat Pumps)

Table GD-2 General Data — Heat Pumps


TWA155B TWA200B
Cooling Performance1
Gross Cooling Capacity, Btu (kW)
Matched Air Handler, Btu (kW) 167,000 (48.9) 218,000 (63.83)
Condensing Unit Only2, Btu (kW) 167,000 (48.9) 218,000 (63.83)
ARI Net Cooling Capacity3 162,000 (47.43) 211,000 (61.78)
System Power kW 15.67 21.51
Condensing Unit Power kW 13.91 19.1
Heating Performance
ARI Heating with Matched Air Handler
HighTemperature Capacity, Btu (kW) 166,000 (48.6) 214,000 (62.66)
LowTemperature Capacity, Btu (kW) 101,000 (29.57) 139,000 (40.70)
Compressor
Number 2 2
Type 3D®Scroll 3D®Scroll
No. Motors 2 2
Motor HP 6.25 (4.7) 8.33 (6.21)
Motor RPM, (kW) 2875 2875
ARI Sound Rating (Bels)4 8.8 8.8
System Data5
No. Refrigerant Circuits 2 2
Suction Line, in. (mm) OD 1.375 (34.9) 1.375 (34.9)
Liquid Line, in. (mm) OD 0.500 (12.7) 0.500 (12.7)
Outdoor Coil —Type Plate Fin Plate Fin
Tube Size, in. (mm) OD 0.375 (9.5) 0.375 (9.5)
Face Area, sq. ft (m2) 38.4 (3.57) 48 (4.46)
Rows 2 2
Fins Per Inch 18 18
Outdoor FanType Propeller Propeller
No. Used 2 2
Diameter, in. (mm) 26.00 (660.4) 28.00 (711)
DriveType Direct Direct
No. Speeds 1 1
CFM6, (m3/h) 9800 (16650.2) 13400 (22766.60)
No. Motors 2 2
Motor HP (kW) 0.33 (.25) 0.75 (.56)
Motor RPM 925 925
R-22 Refrigerant Charge, lb7 (kg) 36.0 (16.33) 48.5 (22.0)
Notes:
1. Cooling Performance is rated at 95°F (35°C) ambient, 80°F (26.7°C) entering dry bulb, 67°F (19.4°C) entering wet
bulb and nominal cfm listed. ARI rating cfm is 350 cfm/ton for this product. Gross capacity does not include the
effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for
operation to ±20% of nominal cfm. Rated accordance with ARI Standard 340/360-00.
2. Condensing Unit Only Gross Cooling Capacity rated at 45°F (7.6°C) saturated suction temperature and at 95°F
(35°C) ambient.
3. ARI Net Cooling Capacity is calculated with matched blower coil and 25 ft (7.6 m) of 1.375, 0.500 OD interconnect-
ing tubing. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. Integrated
Part Load Value is based on ARI Standard 340/360-00. Units are rated at 80°F (26.7°C) ambient, 80°F (26.7°C) entering dry
bulb, and 67°F (19.4°C) entering wet bulb at ARI rated cfm.
4. ARI Sound Rating is rated in accordance with ARI Standard 270 or 370.
5. System Data based on maximum linear length 80 ft (26.7 m)Maximum lift: suction 60 ft (18.3 m) liquid 60 ft (18.3
m) For greater lengths, refer to refrigerant piping applications manual.
6. Outdoor Fan cfm is rated with standard air-dry coil outdoor.
7. Refrigerant (operating) charge is for condensing unit (all circuits) with matching blower coils and 25 ft (7.6 m) of
interconnecting refrigerant lines.

10 SSP-PRC002-EN
General
Data (Air Handlers)

Table GD-3 — General Data — Air Handlers


TWE050A TWE075A TWE100A TWE100B
System Data1
No. Refrigerant Circuits 1 1 1 2
Suction Line, in. (mm) OD 1.120 (28.4) 1.380 (35.0) 1.380 (35.0) 1.380 (35.0)
Liquid Line, in. (mm) OD 0.38 (9.7) 0.50 (12.7) 0.50 (12.7) 0.50 (12.7)
Indoor Coil — Type Plate Fin Plate Fin Plate Fin Plate Fin
Tube Size, in. (mm) OD 0.375 (9.5) 0.375 (9.5) 0.375 (9.5) 0.375 (9.5)
Face Area, sq. ft (m2) 5.00 (.47) 8.07 (.75) 11.18 (1.0) 11.18 (1.0)
Rows 3 3 4 4
Fins Per Inch 12 12 12 12
Refrigerant Control Expansion Valve Expansion Valve Expansion Valve Expansion Valve
Drain Connection No. 4 4 4 4
Drain Connection Size, in. (mm) 0.75 (19.0) 0.75 (19.0) 0.75 (19.0) 0.75 (19.0)
Drain Connection Type PVC PVC PVC PVC
Indoor Fan Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used 1 1 1 1
Diameter, in. (mm) 12.0 (304.8) 15.0 (381) 15.0 (381) 15.0 (381)
Width, in. (mm) 12.0 (304.8) 15.0 (381) 15.0 (381) 15.0 (381)
DriveType Belt Belt Belt Belt
No. Speeds 1 1 1 1
CFM, (m3/h) 1670 (2837) 2500 (4247) 3325 (5649) 3325 (5649)
No. Motors 1 1 1 1
Motor HP (kW)
— Standard/Oversized 0.75/1.0 (.55/.74) 1.0/1.5 (.74/1.11) 1.5/2.0 (1.11/1.49) 1.5/2.0 (1.11/1.49)
Motor RPM (Standard) 1425 1425 1425 1425
Motor Frame Size (Standard) 56 56 56 56
Filters — Type Throwaway Throwaway Throwaway Throwaway
Furnished Yes Yes Yes Yes
No. 1/1 3 4 4
Recommended Size, in. (mm) 16x20x1/20x20x1 16x25x1 16x25x1 16x25x1
(406.4x508x25.4/ (406.4/635/25.4) (406.4/635/25.4) (406.4/635/25.4)
4/508x508x25.4)

Table GD-3 — General Data — Continued


TWE155B TWE200B
System Data
No. Refrigerant Circuits 2 2
Suction Line, in. (mm) OD 1.38 (35.0) 1.38 (35.0)
Liquid Line, in. (mm) OD 0.500 (12.7) 0.500 (12.7)
Indoor Coil — Type Plate Fin Plate Fin
Tube Size, in. (mm) OD 0.375 (9.5) 0.375 (9.5)
Face Area, sq. ft (m2) 16.33 (1.52) 21.63 (2.01)
Rows 3 3
Fins Per Inch 12 12
Refrigerant Control Expansion Valve Expansion Valve
Drain Connection No. 4 4
Drain Connection Size, in. (mm) 1.000 (25.4) 1.000 (25.4)
Drain Connection Type PVC PVC
Indoor Fan Type FC Centrifugal FC Centrifugal
No. Used 2 2
Diameter, in. (mm) 15.0 (381) 15.0 (381)
Width, in. (mm) 15.0 (381) 15.0 (381)
DriveType Belt Belt
No. Speeds 1 1
CFM, (m3/h) 5000 (8494) 6650 (11297)
No. Motors 1 1
Motor HP (kW)
— Standard/Oversized 2.0/3.0 (1.49/2.24) 3.0/5.0 (2.24/3.72)
Motor RPM (Standard) 1425 1425
Motor Frame Size (Standard) 145T 184T
Filters — Type Throwaway Throwaway
Furnished Yes Yes
No. 8 4/4
Recommended Size, in. (mm) 15x20x2 16x20x2/16x25x2
(381x508x50.8) (406.4x508x50.8/406.4x635x50.8)
Notes:
1. ARI certified with various condensing units per ARI Standard 210/240 or 340/360-00 certification program. Refer to
Performance Data section in this catalog.
SSP-PRC002-EN 11
Performance
Data (System)

Table PD-1 — Gross Cooling Capacities (MBh) TWA075A Heat Pump with TWE075A Air Handler (I-P)
Ambient Temperature (°F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (°F)
Bulb 61 67 73 61 67 73 61 67 73 61 67 73
CFM (°F) Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.
2250 75 78.1 61.6 86.4 51.4 95.4 35.1 75.4 60.3 83.4 50.1 91.9 33.9 72.3 58.8 79.9 48.7 88.0 32.5 68.7 57.0 75.9 47.1 83.7 31.0
80 78.4 71.9 86.6 59.4 95.4 46.0 75.9 70.6 83.6 58.1 92.0 44.7 72.8 69.1 80.1 56.6 88.1 43.2 69.4 67.4 76.0 54.8 83.7 41.6
85 80.2 80.2 86.7 69.6 95.5 56.5 78.0 78.0 83.7 68.2 92.1 55.2 75.4 75.4 80.2 66.7 88.2 53.8 72.3 72.3 76.3 64.9 83.9 52.2
90 84.3 84.3 87.1 79.9 95.6 67.0 82.0 82.0 84.2 78.6 92.2 65.7 79.3 79.3 80.9 77.0 88.3 64.1 76.1 76.1 77.1 75.4 84.0 62.4
2500 75 79.6 64.6 88.1 50.6 96.9 35.8 76.9 63.2 84.9 49.3 93.4 34.6 73.6 61.6 81.3 47.8 89.3 33.2 69.9 59.8 77.2 46.1 84.8 31.6
80 80.2 75.9 88.2 62.1 97.0 47.5 77.6 74.5 85.1 60.8 93.4 46.2 74.5 73.0 81.4 59.1 89.4 44.7 70.7 70.6 77.3 57.3 85.0 43.1
85 82.9 82.9 88.3 73.2 97.1 59.0 80.6 80.6 85.2 71.8 93.6 57.7 77.8 77.8 81.6 70.2 89.6 56.3 74.6 74.6 77.6 68.5 85.2 54.7
90 87.2 87.2 89.0 84.5 97.1 70.3 84.7 84.7 86.1 83.2 93.7 68.9 81.8 81.8 82.6 81.7 89.7 67.4 78.6 78.6 78.6 78.6 85.3 65.7
2750 75 81.0 67.3 89.4 52.3 98.2 36.5 78.1 65.9 86.1 51.0 94.6 35.1 74.8 64.3 82.4 49.5 90.4 33.7 71.0 62.5 78.2 47.8 85.8 32.0
80 81.8 79.7 89.4 64.6 98.3 48.9 79.1 78.3 86.2 63.2 94.7 47.6 75.7 75.7 82.5 61.6 90.5 46.2 72.5 72.5 78.3 59.8 86.0 44.6
85 85.3 85.3 89.7 76.6 98.4 61.4 82.8 82.8 86.5 75.3 94.8 60.1 79.9 79.9 82.9 73.7 90.7 58.6 76.6 76.6 78.8 71.9 86.2 57.0
90 89.7 89.7 90.8 89.1 98.5 73.5 87.1 87.1 87.8 87.7 94.9 72.1 84.1 84.1 84.2 84.2 90.9 70.6 80.6 80.6 80.7 80.7 86.4 68.9
3000 75 82.1 70.0 90.5 54.0 99.3 36.9 79.2 68.6 87.2 52.6 95.6 35.6 75.8 67.0 83.3 51.1 91.3 34.1 71.9 65.1 79.1 49.4 86.6 32.5
80 82.8 82.8 90.6 67.0 99.4 50.3 80.4 80.4 87.3 65.6 95.7 49.0 77.5 77.5 83.5 64.0 91.5 47.5 74.1 74.1 79.2 62.2 86.9 45.9
85 87.4 87.4 90.9 80.0 99.5 63.7 84.8 84.8 87.7 78.6 95.9 62.4 81.7 81.7 84.0 77.0 91.6 60.7 78.3 78.3 79.9 75.2 87.0 59.0
90 91.9 91.9 92.0 92.0 99.7 76.6 89.2 89.2 89.3 89.3 96.0 75.2 86.0 86.0 86.1 86.1 91.8 73.6 82.5 82.5 82.6 82.6 87.3 71.9
Note: All temperatures are in degrees Fahrenheit. Airflow is in cfm.

Table PD-1— Gross Cooling Capacities (kW) TWA075A Heat Pump with TWE075A Air Handler (SI)
AmbientTemperature (°C)
29.4 35.0 40.6 46.1
Enter.
Dry Entering Wet Bulb (°C)
Bulb 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
3
m /h (°C) Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.
3823 24 22.9 18.0 25.3 15.0 27.9 10.3 22.1 17.7 24.4 14.7 26.9 9.9 21.2 17.2 23.4 14.3 25.8 9.5 20.1 16.7 22.2 13.8 24.5 9.1
27 23.0 21.1 25.4 17.4 27.9 13.5 22.2 20.7 24.5 17.0 26.9 13.1 21.3 20.2 23.4 16.6 25.8 12.7 20.3 19.7 22.3 16.0 24.5 12.2
29 23.5 23.5 25.4 20.4 28.0 16.5 22.8 22.8 24.5 20.0 27.0 16.2 22.1 22.1 23.5 19.5 25.8 15.7 21.2 21.2 22.3 19.0 24.6 15.3
32 24.7 24.7 25.5 23.4 28.0 19.6 24.0 24.0 24.7 23.0 27.0 19.3 23.2 23.2 23.7 22.6 25.9 18.8 22.3 22.3 22.6 22.1 24.6 18.3
4248 24 23.3 18.9 25.8 14.8 28.4 10.5 22.5 18.5 24.9 14.4 27.3 10.1 21.6 18.0 23.8 14.0 26.2 9.7 20.5 17.5 22.6 13.5 24.8 9.2
27 23.5 22.2 25.8 18.2 28.4 13.9 22.7 21.8 24.9 17.8 27.4 13.5 21.8 21.4 23.8 17.3 26.2 13.1 20.7 20.7 22.6 16.8 24.9 12.6
29 24.3 24.3 25.9 21.4 28.4 17.3 23.6 23.6 25.0 21.0 27.4 16.9 22.8 22.8 23.9 20.6 26.2 16.5 21.8 21.8 22.7 20.0 24.9 16.0
32 25.5 25.5 26.1 24.8 28.4 20.6 24.8 24.8 25.2 24.4 27.4 20.2 24.0 24.0 24.2 23.9 26.3 19.7 23.0 23.0 23.0 23.0 25.0 19.2
4672 24 23.7 19.7 26.2 15.3 28.8 10.7 22.9 19.3 25.2 14.9 27.7 10.3 21.9 18.8 24.1 14.5 26.5 9.9 20.8 18.3 22.9 14.0 25.1 9.4
27 24.0 23.3 26.2 18.9 28.8 14.3 23.2 22.9 25.3 18.5 27.7 13.9 22.2 22.2 24.2 18.0 26.5 13.5 21.2 21.2 22.9 17.5 25.2 13.0
29 25.0 25.0 26.3 22.4 28.8 18.0 24.3 24.3 25.3 22.0 27.8 17.6 23.4 23.4 24.3 21.6 26.6 17.2 22.4 22.4 23.1 21.1 25.2 16.7
32 26.3 26.3 26.6 26.1 28.8 21.5 25.5 25.5 25.7 25.7 27.8 21.1 24.6 24.6 24.6 24.6 26.6 20.7 23.6 23.6 23.6 23.6 25.3 20.2
5097 24 24.0 20.5 26.5 15.8 29.1 10.8 23.2 20.1 25.5 15.4 28.0 10.4 22.2 19.6 24.4 15.0 26.7 10.0 21.1 19.1 23.1 14.5 25.4 9.5
27 24.3 24.3 26.5 19.6 29.1 14.7 23.5 23.5 25.6 19.2 28.0 14.4 22.7 22.7 24.5 18.7 26.8 13.9 21.7 21.7 23.2 18.2 25.4 13.4
29 25.6 25.6 26.6 23.4 29.1 18.7 24.8 24.8 25.7 23.0 28.1 18.3 23.9 23.9 24.6 22.5 26.8 17.8 22.9 22.9 23.4 22.0 25.5 17.3
32 26.9 26.9 26.9 26.9 29.2 22.4 26.1 26.1 26.1 26.1 28.1 22.0 25.2 25.2 25.2 25.2 26.9 21.6 24.2 24.2 24.2 24.2 25.6 21.1
Note: All temperatures are in degrees Celsius. Airflow is in liters per second.

12 SSP-PRC002-EN
Performance
Data (System)

Table PD-2 — Gross Cooling Capacities (MBh) TWA100A Heat Pump with TWE100A Air Handler (I-P)
AmbientTemperature (°F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (°F)
Bulb 61 67 73 61 67 73 61 67 73 61 67 73
CFM (°F) Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.
3000 75 103.1 81.2 113.7 68.1 125.2 46.1 99.3 79.2 109.5 66.4 120.5 44.4 95.2 77.2 105.1 64.6 115.7 42.7 91.0 75.1 100.5 62.7 110.6 41.0
80 103.4 94.5 113.9 77.5 125.1 59.9 99.7 92.6 109.7 75.6 120.5 58.2 95.8 90.6 105.3 73.7 115.7 56.3 91.7 88.5 100.7 71.8 110.6 54.4
85 105.4 105.4 113.9 90.8 125.2 73.3 102.2 102.2 109.7 88.8 120.6 71.5 98.9 98.9 105.4 86.8 115.8 69.7 95.3 95.3 100.8 84.8 110.8 67.8
90 110.6 110.6 114.3 103.9 125.3 86.6 107.3 107.3 110.2 102.0 120.7 84.8 103.8 103.8 106.0 100.1 115.9 83.0 100.2 100.2 101.6 98.1 110.9 81.1
3325 75 105.0 84.7 115.8 66.1 127.2 46.9 101.1 82.8 111.4 64.3 122.4 45.3 96.9 80.7 106.9 62.4 117.4 43.5 92.5 78.5 102.2 60.4 112.2 41.6
80 105.6 99.3 115.9 80.8 127.1 61.8 101.8 97.4 111.6 78.9 122.4 60.0 97.8 95.3 107.0 77.0 117.4 58.1 93.7 93.3 102.3 75.1 112.2 56.2
85 108.7 108.7 115.9 95.1 127.2 76.3 105.4 105.4 111.6 93.2 122.5 74.5 101.9 101.9 107.1 91.1 117.5 72.6 98.2 98.2 102.5 89.1 112.4 70.7
90 114.1 114.1 116.6 109.5 127.3 90.7 110.6 110.6 112.5 107.6 122.6 88.9 107.0 107.0 108.2 105.6 117.7 87.1 103.2 103.2 103.8 103.7 112.4 84.9
3650 75 106.6 88.1 117.4 68.2 128.8 47.8 102.6 86.1 113.0 66.3 123.9 46.0 98.3 84.0 108.3 64.4 118.8 44.1 93.9 81.9 103.5 62.4 113.4 42.2
80 107.6 103.9 117.6 84.0 128.8 63.5 103.7 102.0 113.1 82.1 123.9 61.7 99.1 99.1 108.5 80.2 118.8 59.8 95.4 95.4 103.6 77.9 113.5 57.9
85 111.6 111.6 117.6 99.3 128.9 79.1 108.1 108.1 113.2 97.3 124.1 77.3 104.5 104.5 108.7 95.3 119.0 75.5 100.6 100.6 104.0 93.2 113.7 73.5
90 117.1 117.1 118.7 114.9 129.0 94.7 113.5 113.5 114.5 113.0 124.2 92.9 109.8 109.8 109.7 109.7 119.0 90.7 105.8 105.8 105.7 105.7 113.8 88.6
3975 75 108.1 91.4 118.9 70.1 130.2 48.3 103.9 89.3 114.3 68.3 125.2 46.5 99.6 87.2 109.6 66.3 120.0 44.7 95.1 85.1 104.6 64.3 114.5 42.8
80 109.4 108.4 119.0 87.0 130.3 65.2 105.0 105.0 114.4 84.9 125.3 63.3 101.3 101.3 109.7 82.9 120.1 61.5 97.5 97.5 104.7 80.8 114.7 59.5
85 114.2 114.2 119.1 103.3 130.4 81.9 110.6 110.6 114.7 101.3 125.4 80.1 106.8 106.8 110.1 99.3 120.2 78.2 102.8 102.8 105.3 97.2 114.8 76.2
90 119.9 119.9 120.7 120.2 130.4 98.3 116.2 116.2 116.1 116.1 125.4 96.3 112.2 112.2 112.2 112.2 120.3 94.3 108.1 108.1 108.1 108.1 114.9 92.3
Note: All temperatures are in degrees Fahrenheit. Airflow is in cfm.

Table PD-2 — Gross Cooling Capacities (kW) TWA100A Heat Pump with TWE100A Air Handler (SI)
Ambient Temperature (°C)
29.4 35.0 40.6 46.1
Enter.
Dry Entering Wet Bulb (°C)
Bulb 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
3
m /h (°C) Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.
5097 24 30.2 23.8 33.3 19.9 36.6 13.5 29.1 23.2 32.1 19.4 35.3 13.0 27.9 22.6 30.8 18.9 33.9 12.5 26.6 22.0 29.4 18.4 32.4 12.0
27 30.3 27.7 33.3 22.7 36.6 17.5 29.2 27.1 32.1 22.1 35.3 17.0 28.0 26.5 30.8 21.6 33.9 16.5 26.9 25.9 29.5 21.0 32.4 15.9
29 30.9 30.9 33.3 26.6 36.7 21.5 29.9 29.9 32.1 26.0 35.3 20.9 28.9 28.9 30.8 25.4 33.9 20.4 27.9 27.9 29.5 24.8 32.4 19.8
32 32.4 32.4 33.5 30.4 36.7 25.4 31.4 31.4 32.3 29.9 35.3 24.8 30.4 30.4 31.0 29.3 33.9 24.3 29.3 29.3 29.8 28.7 32.5 23.7
5649 24 30.7 24.8 33.9 19.4 37.2 13.7 29.6 24.2 32.6 18.8 35.8 13.3 28.4 23.6 31.3 18.3 34.4 12.8 27.1 23.0 29.9 17.7 32.8 12.2
27 30.9 29.1 33.9 23.7 37.2 18.1 29.8 28.5 32.7 23.1 35.8 17.6 28.6 27.9 31.3 22.6 34.4 17.0 27.4 27.3 30.0 22.0 32.9 16.5
29 31.8 31.8 33.9 27.8 37.3 22.3 30.9 30.9 32.7 27.3 35.9 21.8 29.8 29.8 31.4 26.7 34.4 21.3 28.7 28.7 30.0 26.1 32.9 20.7
32 33.4 33.4 34.1 32.1 37.3 26.6 32.4 32.4 32.9 31.5 35.9 26.0 31.3 31.3 31.7 30.9 34.4 25.5 30.2 30.2 30.4 30.3 32.9 24.8
6201 24 31.2 25.8 34.4 20.0 37.7 14.0 30.0 25.2 33.1 19.4 36.3 13.5 28.8 24.6 31.7 18.9 34.8 12.9 27.5 24.0 30.3 18.3 33.2 12.4
27 31.5 30.4 34.4 24.6 37.7 18.6 30.4 29.9 33.1 24.0 36.3 18.1 29.0 29.0 31.8 23.5 34.8 17.5 27.9 27.9 30.3 22.8 33.2 17.0
29 32.7 32.7 34.4 29.1 37.8 23.2 31.7 31.7 33.2 28.5 36.3 22.6 30.6 30.6 31.8 27.9 34.8 22.1 29.5 29.5 30.4 27.3 33.3 21.5
32 34.3 34.3 34.8 33.7 37.8 27.7 33.2 33.2 33.5 33.1 36.4 27.2 32.1 32.1 32.1 32.1 34.8 26.5 31.0 31.0 31.0 31.0 33.3 25.9
6754 24 31.6 26.7 34.8 20.5 38.1 14.2 30.4 26.2 33.5 20.0 36.7 13.6 29.2 25.5 32.1 19.4 35.1 13.1 27.8 24.9 30.6 18.8 33.5 12.5
27 32.0 31.7 34.8 25.5 38.1 19.1 30.8 30.8 33.5 24.9 36.7 18.5 29.7 29.7 32.1 24.3 35.2 18.0 28.5 28.5 30.7 23.7 33.6 17.4
29 33.4 33.4 34.9 30.2 38.2 24.0 32.4 32.4 33.6 29.7 36.7 23.4 31.3 31.3 32.2 29.1 35.2 22.9 30.1 30.1 30.8 28.5 33.6 22.3
32 35.1 35.1 35.3 35.2 38.2 28.8 34.0 34.0 34.0 34.0 36.7 28.2 32.9 32.9 32.8 32.8 35.2 27.6 31.7 31.7 31.6 31.6 33.6 27.0
Note: All temperatures are in degrees Celsius. Airflow is in liters per second.

SSP-PRC002-EN 13
Performance
Data (System)

Table PD-3 — Gross Cooling Capacities (MBh) TWA155B Heat Pump with TWE155B Air Handler (I-P)
AmbientTemperature (°F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (°F)
Bulb 61 67 73 61 67 73 61 67 73 61 67 73
CFM (°F) Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.
4500 75 153.9 122.2 170.3 101.7 187.8 69.2 148.7 119.6 164.4 99.3 181.0 66.9 142.5 116.5 157.4 96.5 173.3 64.2 135.4 113.0 149.5 93.3 164.6 61.2
80 154.6 142.7 170.6 117.7 187.8 90.9 149.6 140.2 164.7 115.2 181.1 88.4 143.6 137.2 157.6 111.9 173.4 85.5 136.8 133.8 149.8 108.5 164.9 82.4
85 158.5 158.5 170.8 138.0 188.1 112.0 154.2 154.2 165.0 135.4 181.4 109.5 149.0 149.0 158.1 132.3 173.8 106.7 143.0 143.0 150.3 128.9 165.3 103.5
90 166.7 166.7 171.7 158.7 188.2 132.8 162.1 162.1 166.0 156.1 181.6 130.1 156.7 156.7 159.3 153.1 174.0 127.1 150.5 150.5 152.0 149.8 165.5 123.8
5000 75 157.0 128.0 173.4 100.2 190.8 70.5 151.6 125.3 167.3 97.7 183.8 68.1 145.1 122.2 160.0 94.7 175.8 65.4 137.8 118.6 152.0 91.4 166.9 62.2
80 158.1 150.6 173.5 122.9 190.9 94.0 152.9 148.0 167.4 120.2 184.0 91.4 146.8 145.0 160.3 117.1 176.1 88.5 139.6 139.6 152.3 113.6 167.3 85.4
85 163.9 163.9 174.0 145.2 191.2 117.0 159.3 159.3 167.9 142.5 184.3 114.5 153.7 153.7 160.8 139.4 176.5 111.6 147.4 147.4 152.9 135.9 167.7 108.5
90 172.3 172.3 175.4 168.0 191.4 139.5 167.5 167.5 169.6 165.3 184.5 136.8 161.7 161.7 162.9 162.3 176.7 133.7 155.2 155.2 155.4 155.4 168.0 130.4
5500 75 159.6 133.5 176.0 103.6 193.4 71.9 154.0 130.8 169.6 101.0 186.1 69.3 147.3 127.6 162.2 98.0 177.9 66.3 139.8 124.0 153.9 94.7 168.8 63.2
80 161.2 158.2 176.2 128.0 193.5 96.9 156.0 155.6 169.9 125.2 186.4 94.3 149.6 149.6 162.5 122.0 178.3 91.4 143.2 143.2 154.3 118.5 169.3 88.2
85 168.5 168.5 176.7 152.1 193.8 121.9 163.6 163.6 170.5 149.4 186.8 119.3 157.8 157.8 163.2 146.2 178.4 116.0 151.2 151.2 155.2 142.8 169.6 112.6
90 177.2 177.2 178.8 177.0 194.1 145.9 172.1 172.1 172.3 172.3 187.0 143.2 166.1 166.1 166.2 166.2 179.0 140.1 159.3 159.3 159.5 159.5 170.1 136.7
6000 75 161.7 138.8 178.2 106.8 195.5 72.8 156.0 136.0 171.6 104.2 188.1 70.2 149.3 132.8 164.1 101.2 179.7 67.2 141.7 129.2 155.6 97.9 170.4 64.0
80 163.6 163.6 178.4 132.8 195.7 99.7 158.8 158.8 172.0 130.0 188.4 97.1 152.9 152.9 164.4 126.8 180.1 94.2 146.3 146.3 156.1 123.2 171.0 91.0
85 172.6 172.6 179.1 158.8 196.0 126.5 167.5 167.5 172.7 156.1 188.6 123.4 161.4 161.4 165.4 152.9 180.4 120.3 154.6 154.6 157.3 149.4 171.4 116.9
90 181.5 181.5 181.7 181.7 196.3 152.1 176.2 176.2 176.4 176.4 189.1 149.3 169.9 169.9 170.1 170.1 180.9 146.2 162.9 162.9 163.1 163.1 171.9 142.8
Note: All temperatures are in degrees Fahrenheit. Airflow is in cfm.

Table PD-3 — Gross Cooling Capacities (kW) TWA155B Heat Pump with TWE155B Air Handler (SI)
AmbientTemperature (°C)
29.4 35.0 40.6 46.1
Enter.
Dry Entering Wet Bulb (°C)
Bulb 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
3
m /h (°C) Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.
7646 24 45.1 35.8 49.9 29.8 55.0 20.3 43.5 35.0 48.1 29.1 53.0 19.6 41.7 34.1 46.1 28.2 50.7 18.8 39.6 33.1 43.8 27.3 48.2 17.9
27 45.3 41.8 50.0 34.5 55.0 26.6 43.8 41.0 48.2 33.7 53.0 25.9 42.0 40.2 46.1 32.8 50.8 25.0 40.1 39.2 43.9 31.8 48.3 24.1
29 46.4 46.4 50.0 40.4 55.1 32.8 45.1 45.1 48.3 39.6 53.1 32.1 43.6 43.6 46.3 38.7 50.9 31.2 41.9 41.9 44.0 37.7 48.4 30.3
32 48.8 48.8 50.3 46.5 55.1 38.9 47.5 47.5 48.6 45.7 53.2 38.1 45.9 45.9 46.7 44.8 50.9 37.2 44.1 44.1 44.5 43.9 48.5 36.3
8495 24 46.0 37.5 50.8 29.3 55.9 20.7 44.4 36.7 49.0 28.6 53.8 19.9 42.5 35.8 46.9 27.7 51.5 19.1 40.3 34.7 44.5 26.8 48.9 18.2
27 46.3 44.1 50.8 36.0 55.9 27.5 44.8 43.3 49.0 35.2 53.9 26.8 43.0 42.4 46.9 34.3 51.6 25.9 40.9 40.9 44.6 33.3 49.0 25.0
29 48.0 48.0 50.9 42.5 56.0 34.3 46.6 46.6 49.2 41.7 54.0 33.5 45.0 45.0 47.1 40.8 51.7 32.7 43.2 43.2 44.8 39.8 49.1 31.8
32 50.5 50.5 51.3 49.2 56.0 40.8 49.0 49.0 49.6 48.4 54.0 40.0 47.4 47.4 47.7 47.5 51.7 39.2 45.4 45.4 45.5 45.5 49.2 38.2
9345 24 46.7 39.1 51.5 30.3 56.6 21.0 45.1 38.3 49.7 29.6 54.5 20.3 43.1 37.4 47.5 28.7 52.1 19.4 40.9 36.3 45.1 27.7 49.4 18.5
27 47.2 46.3 51.6 37.5 56.7 28.4 45.7 45.6 49.7 36.7 54.6 27.6 43.8 43.8 47.6 35.7 52.2 26.8 41.9 41.9 45.2 34.7 49.6 25.8
29 49.3 49.3 51.7 44.5 56.8 35.7 47.9 47.9 49.9 43.7 54.7 34.9 46.2 46.2 47.8 42.8 52.2 34.0 44.3 44.3 45.4 41.8 49.7 33.0
32 51.9 51.9 52.3 51.8 56.8 42.7 50.4 50.4 50.4 50.4 54.8 41.9 48.6 48.6 48.7 48.7 52.4 41.0 46.6 46.6 46.7 46.7 49.8 40.0
10194 24 47.4 40.6 52.2 31.3 57.2 21.3 45.7 39.8 50.3 30.5 55.1 20.5 43.7 38.9 48.0 29.6 52.6 19.7 41.5 37.8 45.6 28.7 49.9 18.8
27 47.9 47.9 52.2 38.9 57.3 29.2 46.5 46.5 50.4 38.1 55.2 28.4 44.8 44.8 48.2 37.1 52.7 27.6 42.8 42.8 45.7 36.1 50.1 26.6
29 50.5 50.5 52.4 46.5 57.4 37.0 49.0 49.0 50.6 45.7 55.2 36.1 47.3 47.3 48.4 44.8 52.8 35.2 45.3 45.3 46.0 43.7 50.2 34.2
32 53.2 53.2 53.2 53.2 57.5 44.5 51.6 51.6 51.6 51.6 55.4 43.7 49.8 49.8 49.8 49.8 53.0 42.8 47.7 47.7 47.8 47.8 50.3 41.8
Note: All temperatures are in degrees Celsius. Airflow is in liters per second.

14 SSP-PRC002-EN
Performance
Data (System)

Table PD-4 — Gross Cooling Capacities (MBh) TWA200B Heat Pump with TWE200B Air Handler (I-P)
AmbientTemperature (°F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (°F)
Bulb 61 67 73 61 67 73 61 67 73 61 67 73
CFM (°F) Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.
6000 75 203.1 161.9 223.6 134.6 245.6 90.5 195.3 158.0 215.0 131.1 236.2 87.2 187.1 153.8 206.1 127.5 226.3 83.8 178.5 149.6 196.9 123.8 216.2 80.4
80 204.0 189.2 223.9 154.6 245.5 118.7 196.4 185.3 215.4 150.9 236.2 115.1 188.5 181.3 206.5 147.1 226.5 111.5 180.4 177.1 197.1 142.8 216.4 107.8
85 209.2 209.2 224.1 181.3 245.8 146.0 202.6 202.6 215.6 177.5 236.5 142.5 195.6 195.6 206.8 173.4 226.8 138.8 188.4 188.4 197.6 169.3 216.8 135.1
90 219.3 219.3 225.1 208.3 246.0 173.3 212.6 212.6 216.9 204.5 236.8 169.7 205.4 205.4 208.4 200.6 226.9 165.4 198.1 198.1 199.8 196.6 217.0 161.4
6675 75 206.9 169.4 227.5 131.5 249.5 92.2 198.8 165.3 218.7 127.8 239.7 88.9 190.3 161.2 209.5 124.0 229.7 85.4 181.6 156.9 200.0 120.1 219.2 81.6
80 208.4 199.4 227.8 161.7 249.5 122.5 200.6 195.4 218.8 157.5 239.8 119.0 192.7 191.4 209.7 153.5 229.8 115.3 184.1 184.1 200.3 149.3 219.5 111.5
85 215.7 215.7 228.0 190.5 249.7 152.4 208.8 208.8 219.3 186.6 240.1 148.8 201.6 201.6 210.3 182.5 230.2 145.1 194.0 194.0 201.0 178.4 219.9 141.3
90 226.3 226.3 229.8 220.2 249.8 181.5 219.2 219.2 221.5 216.4 240.3 177.7 211.7 211.7 213.0 212.4 230.4 173.8 204.0 204.0 203.9 203.9 220.1 169.7
7350 75 210.0 176.5 230.7 135.8 252.6 93.8 201.8 172.4 221.7 132.1 242.7 90.2 193.1 168.2 212.3 128.3 232.3 86.5 184.3 163.9 202.6 124.4 221.6 82.8
80 212.3 209.2 230.9 167.8 252.7 126.2 203.5 203.5 221.9 163.9 242.8 122.6 196.3 196.3 212.6 159.8 232.6 118.9 188.6 188.6 202.9 155.6 222.0 115.1
85 221.4 221.4 231.4 199.3 253.0 158.4 214.2 214.2 222.6 195.4 243.2 154.8 206.7 206.7 213.4 191.3 233.0 151.1 198.9 198.9 204.0 187.2 222.4 147.3
90 232.3 232.3 234.1 231.7 253.1 189.6 225.0 225.0 224.8 224.8 243.4 185.8 217.2 217.2 217.1 217.1 233.2 181.8 209.2 209.2 209.1 209.1 222.7 177.7
8025 75 212.7 183.3 233.5 140.0 255.3 95.0 204.4 179.2 224.2 136.2 245.1 91.4 195.6 175.0 214.6 132.4 234.6 87.7 186.7 170.6 204.8 128.4 223.7 83.9
80 215.3 215.3 233.7 174.0 255.5 129.7 208.1 208.1 224.5 170.0 245.4 126.1 200.5 200.5 215.0 165.9 234.9 122.4 192.7 192.7 205.2 161.7 224.1 118.6
85 226.5 226.5 234.4 207.9 255.8 164.2 219.0 219.0 225.5 203.9 245.7 160.6 211.3 211.3 216.2 199.8 235.1 156.3 203.2 203.2 206.6 195.7 224.4 152.2
90 237.7 237.7 237.6 237.6 256.0 197.4 230.1 230.1 230.0 230.0 246.0 193.5 222.1 222.1 222.0 222.0 235.6 189.5 213.7 213.7 213.6 213.6 224.9 185.4
Note: All temperatures are in degrees Fahrenheit. Airflow is in cfm.

Table PD-4 — Gross Cooling Capacities (kW) TWA200B Heat Pump with TWE200B Air Handler (SI)
AmbientTemperature (°C)
29.4 35.0 40.6 46.1
Enter.
Dry Entering Wet Bulb (°C)
Bulb 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
3
m /h (°C) Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.
10194 24 59.5 47.4 65.5 39.4 71.9 26.5 57.2 46.3 63.0 38.4 69.2 25.5 54.8 45.0 60.3 37.3 66.3 24.5 52.3 43.8 57.6 36.2 63.3 23.5
27 59.7 55.4 65.6 45.3 71.9 34.7 57.5 54.3 63.1 44.2 69.2 33.7 55.2 53.1 60.5 43.1 66.3 32.6 52.8 51.9 57.7 41.8 63.4 31.6
29 61.2 61.2 65.6 53.1 72.0 42.8 59.3 59.3 63.1 52.0 69.2 41.7 57.3 57.3 60.5 50.8 66.4 40.6 55.2 55.2 57.9 49.6 63.5 39.5
32 64.2 64.2 65.9 61.0 72.0 50.7 62.2 62.2 63.5 59.9 69.3 49.7 60.2 60.2 61.0 58.7 66.4 48.4 58.0 58.0 58.5 57.6 63.5 47.3
11341 24 60.6 49.6 66.6 38.5 73.0 27.0 58.2 48.4 64.0 37.4 70.2 26.0 55.7 47.2 61.3 36.3 67.2 25.0 53.2 45.9 58.6 35.2 64.2 23.9
27 61.0 58.4 66.7 47.3 73.0 35.9 58.7 57.2 64.1 46.1 70.2 34.8 56.4 56.0 61.4 44.9 67.3 33.8 53.9 53.9 58.6 43.7 64.3 32.7
29 63.2 63.2 66.8 55.8 73.1 44.6 61.1 61.1 64.2 54.6 70.3 43.6 59.0 59.0 61.6 53.4 67.4 42.5 56.8 56.8 58.9 52.2 64.4 41.4
32 66.2 66.2 67.3 64.5 73.1 53.1 64.2 64.2 64.8 63.4 70.4 52.0 62.0 62.0 62.4 62.2 67.5 50.9 59.7 59.7 59.7 59.7 64.5 49.7
12488 24 61.5 51.7 67.6 39.8 74.0 27.5 59.1 50.5 64.9 38.7 71.1 26.4 56.5 49.2 62.2 37.6 68.0 25.3 54.0 48.0 59.3 36.4 64.9 24.2
27 62.2 61.2 67.6 49.1 74.0 36.9 59.6 59.6 65.0 48.0 71.1 35.9 57.5 57.5 62.2 46.8 68.1 34.8 55.2 55.2 59.4 45.6 65.0 33.7
29 64.8 64.8 67.8 58.4 74.1 46.4 62.7 62.7 65.2 57.2 71.2 45.3 60.5 60.5 62.5 56.0 68.2 44.2 58.2 58.2 59.7 54.8 65.1 43.1
32 68.0 68.0 68.5 67.8 74.1 55.5 65.9 65.9 65.8 65.8 71.3 54.4 63.6 63.6 63.6 63.6 68.3 53.2 61.3 61.3 61.2 61.2 65.2 52.0
13634 24 62.3 53.7 68.4 41.0 74.8 27.8 59.8 52.5 65.7 39.9 71.8 26.8 57.3 51.2 62.8 38.8 68.7 25.7 54.7 50.0 60.0 37.6 65.5 24.6
27 63.0 63.0 68.4 51.0 74.8 38.0 60.9 60.9 65.7 49.8 71.8 36.9 58.7 58.7 63.0 48.6 68.8 35.8 56.4 56.4 60.1 47.3 65.6 34.7
29 66.3 66.3 68.6 60.9 74.9 48.1 64.1 64.1 66.0 59.7 72.0 47.0 61.9 61.9 63.3 58.5 68.8 45.8 59.5 59.5 60.5 57.3 65.7 44.6
32 69.6 69.6 69.6 69.6 74.9 57.8 67.4 67.4 67.3 67.3 72.0 56.7 65.0 65.0 65.0 65.0 69.0 55.5 62.6 62.6 62.6 62.6 65.9 54.3
Note: All temperatures are in degrees Celsius. Airflow is in liters per second.

SSP-PRC002-EN 15
Performance
Data (TWA075A)

Table PD-5 — Gross Cooling Performance (MBh) TWA075A Heat Pump Only (I-P)
ODTemp Suction ReferenceTemperature °F
°F 30 35 40 45 50 55
Head press PSIG 166 171 177 183 189 196
65 Cap. Btuh/1000 72.2 79.8 87.7 95.9 104.3 112.8
OD Unit KW 4.91 5.01 5.13 5.25 5.39 5.52
Head press PSIG 192 198 204 210 217 223
75 Cap. Btuh/1000 70.3 77.5 85.0 92.7 100.5 108.5
OD Unit KW 5.42 5.54 5.66 5.80 5.94 6.08
Head press PSIG 220 227 233 240 247 254
85 Cap. Btuh/1000 67.5 74.4 81.5 88.8 96.2 103.7
OD Unit KW 6.01 6.15 6.28 6.42 6.57 6.72
Head press PSIG 251 258 265 272 279 286
95 Cap. Btuh/1000 64.1 70.7 77.4 84.2 91.2 98.3
OD Unit KW 6.71 6.84 6.98 7.12 7.27 7.42
Head press PSIG 284 291 298 306 313 321
105 Cap. Btuh/1000 60.2 66.3 72.6 79.1 85.7 92.5
OD Unit KW 7.48 7.61 7.75 7.89 8.04 8.19
Head press PSIG 320 327 334 342 350 358
115 Cap. Btuh/1000 55.9 61.6 67.5 73.5 79.8 86.2
OD Unit KW 8.32 8.45 8.59 8.72 8.87 9.02

Table PD-5 — Gross Cooling Performance (kW) TWA075A Heat Pump Only (SI)
ODTemp Suction ReferenceTemperature °C
°C -1.1 1.7 4.4 7.2 10 12.8
Head pressure (kPA) 1142 1180 1220 1262 1305 1350
18.3 Capacity (kW) 21.2 23.4 25.7 28.1 30.5 33.0
OD Unit Power (kW) 4.91 5.01 5.13 5.25 5.39 5.52
Head pressure (kPA) 1324 1364 1406 1449 1494 1541
23.9 Capacity (kW) 20.6 22.7 24.9 27.1 29.4 31.8
OD Unit Power (kW) 5.42 5.54 5.66 5.80 5.94 6.08
Head pressure (kPA) 1519 1563 1607 1653 1701 1749
29.4 Capacity (kW) 19.8 21.8 23.9 26.0 28.2 30.4
OD Unit Power (kW) 6.01 6.15 6.28 6.42 6.57 6.72
Head pressure (kPA) 1733 1778 1825 1873 1922 1973
35.0 Capacity (kW) 18.8 20.7 22.7 24.7 26.7 28.8
OD Unit Power (kW) 6.71 6.84 6.98 7.12 7.27 7.42
Head pressure (kPA) 1961 2009 2057 2107 2159 2212
40.6 Capacity (kW) 17.6 19.4 21.3 23.2 25.1 27.1
OD Unit Power (kW) 7.48 7.61 7.75 7.89 8.04 8.19
Head pressure (kPA) 2206 2255 2305 2357 2411 2467
46.1 Capacity (kW) 16.4 18.0 19.8 21.5 23.4 25.2
OD Unit Power (kW) 8.32 8.45 8.59 8.72 8.87 9.02

16 SSP-PRC002-EN
Performance
Data (TWA100A)

Table PD-6— Gross Cooling Performance (MBh) TWA100A Heat Pump Only (I-P)
ODTemp Suction ReferenceTemperature °F
°F 30 35 40 45 50 55
Head press PSIG 164 169 174 179 185 191
65 Cap. Btuh/1000 99.4 109.5 120.0 130.9 142.2 153.9
OD Unit KW 6.39 6.53 6.67 6.83 6.99 7.16
Head press PSIG 188 193 199 204 210 216
75 Cap. Btuh/1000 95.1 104.5 114.4 124.8 135.5 146.6
OD Unit KW 7.06 7.21 7.36 7.52 7.69 7.88
Head press PSIG 215 220 226 232 238 245
85 Cap. Btuh/1000 90.3 99.2 108.6 118.5 128.7 139.3
OD Unit KW 7.85 8.01 8.18 8.35 8.54 8.74
Head press PSIG 245 250 256 263 269 276
95 Cap. Btuh/1000 85.2 93.7 102.7 112.1 121.8 131.8
OD Unit KW 8.79 8.95 9.13 9.32 9.51 9.71
Head press PSIG 277 283 289 296 302 309
105 Cap. Btuh/1000 79.8 88.0 96.6 105.5 114.7 124.2
OD Unit KW 9.84 10.03 10.22 10.41 10.61 10.81
Head press PSIG 312 318 325 331 338 346
115 Cap. Btuh/1000 74.2 82.1 90.3 98.8 107.6 116.4
OD Unit KW 11.02 11.22 11.42 11.63 11.83 12.02

Table PD-6 — Gross Cooling Performance (kW) TWA100A Heat Pump Only (SI)
ODTemp Suction ReferenceTemperature °C
°C -1.1 1.7 4.4 7.2 10 12.8
Head pressure (kPA) 1129 1163 1199 1237 1276 1316
18.3 Capacity (kW) 29.1 32.1 35.1 38.3 41.6 45.1
OD Unit Power (kW) 6.39 6.53 6.67 6.83 6.99 7.16
Head pressure (kPA) 1299 1334 1370 1409 1449 1491
23.9 Capacity (kW) 27.8 30.6 33.5 36.5 39.7 42.9
OD Unit Power (kW) 7.06 7.21 7.36 7.52 7.69 7.88
Head pressure (kPA) 1483 1520 1559 1600 1643 1688
29.4 Capacity (kW) 26.4 29.1 31.8 34.7 37.7 40.8
OD Unit Power (kW) 7.85 8.01 8.18 8.35 8.54 8.74
Head pressure (kPA) 1688 1726 1767 1810 1855 1901
35.0 Capacity (kW) 25.0 27.4 30.1 32.8 35.7 38.6
OD Unit Power (kW) 8.79 8.95 9.13 9.32 9.51 9.71
Head pressure (kPA) 1910 1950 1993 2038 2085 2133
40.6 Capacity (kW) 23.4 25.8 28.3 30.9 33.6 36.4
OD Unit Power (kW) 9.84 10.03 10.22 10.41 10.61 10.81
Head pressure (kPA) 2149 2192 2238 2285 2333 2382
46.1 Capacity (kW) 21.7 24.0 26.4 28.9 31.5 34.1
OD Unit Power (kW) 11.02 11.22 11.42 11.63 11.83 12.02

SSP-PRC002-EN 17
Performance
Data (TWA155B)

Table PD-7 — Gross Cooling Performance (MBh) TWA155B Heat Pump Only (I-P)
ODTemp Suction ReferenceTemperature °F
°F 30 35 40 45 50 55
Head press PSIG 165 170 176 182 188 194
65 Cap. Btuh/1000 142.4 157.4 173.0 189.2 205.9 222.8
OD Unit KW 9.59 9.80 10.02 10.26 10.52 10.78
Head press PSIG 191 197 203 209 215 222
75 Cap. Btuh/1000 138.7 153.0 167.9 183.1 198.7 214.6
OD Unit KW 10.58 10.82 11.06 11.32 11.59 11.87
Head press PSIG 219 225 232 238 245 252
85 Cap. Btuh/1000 133.3 147.0 161.1 175.6 190.3 205.3
OD Unit KW 11.75 12.01 12.27 12.54 12.82 13.11
Head press PSIG 250 257 263 270 277 285
95 Cap. Btuh/1000 126.8 139.8 153.1 166.7 180.6 194.9
OD Unit KW 13.10 13.36 13.63 13.91 14.20 14.49
Head press PSIG 283 290 297 304 312 319
105 Cap. Btuh/1000 119.1 131.3 143.9 156.7 169.9 183.4
OD Unit KW 14.61 14.87 15.14 15.41 15.70 16.00
Head press PSIG 319 326 333 340 348 356
115 Cap. Btuh/1000 110.6 122.0 133.7 145.9 158.4 171.2
OD Unit KW 16.26 16.51 16.77 17.04 17.32 17.62

Table PD-7 — Gross Cooling Performance (kW) TWA155B Heat Pump Only (SI)
ODTemp Suction ReferenceTemperature °C
°C -1.1 1.7 4.4 7.2 10.0 12.8
Head pressure (kPA) 1136 1173 1213 1254 1297 1341
18.3 Capacity (kW) 41.7 46.1 50.7 55.4 60.3 65.2
OD Unit Power (kW) 9.59 9.80 10.02 10.26 10.52 10.78
Head pressure (kPA) 1317 1356 1398 1441 1485 1531
23.9 Capacity (kW) 40.6 44.8 49.1 53.6 58.2 62.8
OD Unit Power (kW) 10.58 10.82 11.06 11.32 11.59 11.87
Head pressure (kPA) 1512 1555 1599 1644 1691 1739
29.4 Capacity (kW) 39.0 43.0 47.2 51.4 55.7 60.1
OD Unit Power (kW) 11.75 12.01 12.27 12.54 12.82 13.11
Head pressure (kPA) 1725 1770 1816 1863 1912 1963
35.0 Capacity (kW) 37.1 40.9 44.8 48.8 52.9 57.1
OD Unit Power (kW) 13.10 13.36 13.63 13.91 14.20 14.49
Head pressure (kPA) 1953 2000 2048 2097 2149 2201
40.6 Capacity (kW) 34.9 38.5 42.1 45.9 49.8 53.7
OD Unit Power (kW) 14.61 14.87 15.14 15.41 15.70 16.00
Head pressure (kPA) 2197 2246 2295 2347 2400 2456
46.1 Capacity (kW) 32.4 35.7 39.2 42.7 46.4 50.1
OD Unit Power (kW) 16.26 16.51 16.77 17.04 17.32 17.62

18 SSP-PRC002-EN
Performance
Data (TWA200B)

Table PD-8 — Gross Cooling Performance (MBh) TWA200B Heat Pump Only (I-P)
ODTemp Suction ReferenceTemperature °F
°F 30 35 40 45 50 55
Head press PSIG 173 179 185 191 198 205
65 Cap. Btuh/1000 196.4 215.5 235.3 255.8 276.9 298.5
OD Unit KW 12.94 13.25 13.58 13.93 14.30 14.69
Head press PSIG 198 204 211 217 224 232
75 Cap. Btuh/1000 187.3 205.2 223.9 243.3 263.4 284.0
OD Unit KW 14.32 14.65 15.00 15.38 15.79 16.22
Head press PSIG 226 233 240 247 254 262
85 Cap. Btuh/1000 177.5 194.5 212.3 230.8 249.9 269.5
OD Unit KW 15.95 16.32 16.71 17.12 17.56 18.01
Head press PSIG 257 264 271 278 286 294
95 Cap. Btuh/1000 167.2 183.4 200.3 218.0 236.1 254.8
OD Unit KW 17.84 18.24 18.66 19.10 19.56 20.02
Head press PSIG 290 298 305 313 321 330
105 Cap. Btuh/1000 156.3 171.9 188.1 205.0 222.3 239.9
OD Unit KW 19.96 20.40 20.86 21.33 21.80 22.27
Head press PSIG 326 334 342 350 359 368
115 Cap. Btuh/1000 145.0 160.1 175.7 191.8 208.2 224.8
OD Unit KW 22.32 22.80 23.30 23.79 24.27 24.73

Table PD-8 — Gross Cooling Performance (kW) TWA200B Heat Pump Only (SI)
ODTemp Suction ReferenceTemperature °C
°C -1.1 1.7 4.4 7.2 10.0 12.8
Head pressure (kPA) 1193 1232 1274 1318 1363 1411
18.3 Capacity (kW) 57.5 63.1 68.9 74.9 81.1 87.4
OD Unit Power (kW) 12.94 13.25 13.58 13.93 14.30 14.69
Head pressure (kPA) 1368 1409 1453 1499 1547 1599
23.9 Capacity (kW) 54.8 60.1 65.5 71.2 77.1 83.2
OD Unit Power (kW) 14.32 14.65 15.00 15.38 15.79 16.22
Head pressure (kPA) 1561 1605 1652 1701 1752 1805
29.4 Capacity (kW) 52.0 56.9 62.2 67.6 73.2 78.9
OD Unit Power (kW) 15.95 16.32 16.71 17.12 17.56 18.01
Head pressure (kPA) 1773 1819 1869 1920 1974 2030
35.0 Capacity (kW) 48.9 53.7 58.7 63.8 69.1 74.6
OD Unit Power (kW) 17.84 18.24 18.66 19.10 19.56 20.02
Head pressure (kPA) 2001 2051 2104 2159 2215 2273
40.6 Capacity (kW) 45.8 50.3 55.1 60.0 65.1 70.2
OD Unit Power (kW) 19.96 20.40 20.86 21.33 21.80 22.27
Head pressure (kPA) 2248 2302 2358 2416 2475 2536
46.1 Capacity (kW) 42.5 46.9 51.5 56.2 61.0 65.8
OD Unit Power (kW) 22.32 22.80 23.30 23.79 24.27 24.73

SSP-PRC002-EN 19
Performance
Data (System)

Table PD-9 — Gross Heating Capacities (MBh)


TWA075A Heat Pump with TWE075A Air Handler At 2500 CFM (I-P)
Outdoor Heating Capacity (Btu/1000) At Total Power in Kilowatts At
Temperature Indicated Indoor Dry BulbTemperature Indicated Indoor Dry BulbTemperature
(°F) 60 70 75 80 60 70 75 80
-18 33.0 28.7 27.1 25.9 5.6 5.7 5.9 6.0
-13 34.1 30.4 29.0 27.9 5.5 5.7 5.9 6.1
-8 35.6 32.4 31.2 30.3 5.5 5.8 5.9 6.2
-3 37.5 34.8 33.9 33.2 5.5 5.8 6.0 6.3
2 40.0 37.7 37.0 36.4 5.5 5.9 6.1 6.4
7 42.8 41.1 40.5 40.1 5.6 6.0 6.2 6.5
12 46.2 44.9 44.4 44.2 5.6 6.1 6.3 6.6
17 50.0 49.1 48.7 48.5 5.7 6.2 6.5 6.8
22 54.4 53.6 53.4 53.2 5.8 6.3 6.6 7.0
27 59.2 58.6 58.4 58.2 5.9 6.4 6.8 7.1
32 64.5 63.9 63.7 63.5 6.0 6.6 6.9 7.3
37 69.9 69.4 69.1 68.8 6.1 6.7 7.1 7.5
42 75.7 75.1 74.7 74.3 6.2 6.9 7.2 7.6
47 81.8 81.1 80.6 80.1 6.4 7.0 7.4 7.8
52 88.3 87.4 86.8 86.2 6.5 7.2 7.6 8.0
57 95.1 93.9 93.2 92.4 6.7 7.4 7.7 8.1
62 102.0 100.6 99.8 98.9 6.8 7.5 7.9 8.3
67 109.0 107.4 106.5 105.5 7.0 7.7 8.1 8.5
72 116.3 114.5 113.4 112.3 7.2 7.9 8.2 8.6

Table PD-9 — Gross Heating Capacities (kW)


TWA075A Heat Pump with TWE075A Air Handler At 4247 m3/h (SI)
Outdoor Heating Capacity (kW) At Total Power in Kilowatts At
Temperature Indicated Indoor Dry BulbTemperature Indicated Indoor Dry BulbTemperature
(°C) 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7
-27.8 9.7 8.4 7.9 7.6 5.5 6.0 6.2 6.5
-25.0 10.0 8.9 8.5 8.2 5.6 6.1 6.3 6.6
-22.2 10.4 9.5 9.1 8.9 5.7 6.2 6.5 6.7
-19.4 11.0 10.2 9.9 9.7 5.8 6.3 6.6 6.9
-16.7 11.7 11.0 10.8 10.7 5.9 6.5 6.7 7.0
-13.9 12.5 12.0 11.9 11.7 6.0 6.6 6.9 7.2
-11.1 13.5 13.1 13.0 12.9 6.2 6.7 7.0 7.4
-8.3 14.7 14.4 14.3 14.2 6.3 6.9 7.2 7.5
-5.6 15.9 15.7 15.6 15.6 6.5 7.0 7.4 7.7
-2.8 17.3 17.2 17.1 17.0 6.6 7.2 7.5 7.9
0.0 18.9 18.7 18.7 18.6 6.8 7.4 7.7 8.1
2.8 20.5 20.3 20.2 20.1 6.9 7.6 7.9 8.3
5.6 22.2 22.0 21.9 21.8 7.1 7.8 8.1 8.5
8.3 24.0 23.7 23.6 23.4 7.3 8.0 8.4 8.8
11.1 25.9 25.6 25.4 25.2 7.5 8.2 8.6 9.0
13.9 27.8 27.5 27.3 27.1 7.7 8.4 8.8 9.2
16.7 29.9 29.5 29.2 29.0 7.9 8.7 9.1 9.5
19.4 31.9 31.5 31.2 30.9 8.1 8.9 9.3 9.8
22.2 34.1 33.5 33.2 32.9 8.4 9.2 9.6 10.0
Correction Factors - Other Airflows Airflow = 2500 cfm (4247 m3/h)
(Table Value x Correction Factor = Value at new airflow) Heating Capacity (High Temp.) = 81,000 (23.72)
Heating Capacity (Low Temp.) = 49,000 (14.35)
Airflow 2250 cfm 2750 cfm Compressor Power (High Temp) = 5.67 kW
3822 m3/h 4672 m3/h Compressor Power (Low Temp) = 4.80 kW
Heating Capacity x 0.99 x 1.01 Coeff. Of Perf. (High Temp) = 3.4
Compressor kW x 1.02 x 0.98 Coeff. Of Perf. (Low Temp) = 2.3
Outdoor Fan Power = 550 watts
Values at ARI Rating Conditions of: Indoor Fan Power = 800 watts
70F (21.1C) and 47/43F (8.3/6.1C)(High Temp.Cond.)
70F (21.1C) and 17/15F (-8.3/-9.4C)(Low Temp. Cond) Note:
1. Rated with 25 feet of 1-3/8" suction and 1/2" liquid line.

20 SSP-PRC002-EN
Performance
Data (System)

Table PD-10 — Gross Heating Capacities (MBh)


TWA100A Heat Pump with TWE100A Air Handler At 3325 CFM (I-P)
Outdoor Heating Capacity (Btu/1000) At Total Power in Kilowatts At
Temperature Indicated Indoor Dry BulbTemperature Indicated Indoor Dry BulbTemperature
(°F) 60 70 75 80 60 70 75 80
-18 20.4 37.3 41.2 43.6 5.7 7.3 7.9 8.5
-13 31.4 41.8 44.6 46.4 6.2 7.5 8.0 8.6
-8 39.0 46.3 48.4 49.7 6.5 7.6 8.1 8.6
-3 45.5 50.8 52.4 53.3 6.8 7.8 8.2 8.7
2 51.8 55.6 56.7 57.3 7.0 7.9 8.4 8.8
7 57.9 60.6 61.3 61.6 7.2 8.0 8.5 9.0
12 64.1 65.8 66.2 66.3 7.3 8.2 8.6 9.1
17 70.4 71.3 71.4 71.3 7.5 8.3 8.7 9.2
22 76.9 77.1 77.0 76.7 7.6 8.4 8.9 9.4
27 83.6 83.3 82.9 82.5 7.8 8.6 9.0 9.5
32 90.7 89.7 89.2 88.7 7.9 8.8 9.2 9.7
37 97.6 96.2 95.5 94.9 8.1 8.9 9.4 9.9
42 104.6 102.9 102.1 101.4 8.2 9.1 9.6 10.1
47 112.0 109.9 109.0 108.2 8.4 9.3 9.7 10.3
52 119.5 117.2 116.2 115.2 8.6 9.5 10.0 10.5
57 127.1 124.6 123.5 122.5 8.8 9.7 10.2 10.7
62 134.8 132.1 130.8 129.7 9.0 9.9 10.4 11.0
67 142.6 139.7 138.3 137.2 9.2 10.1 10.7 11.2
72 150.7 147.5 146.1 144.8 9.4 10.4 10.9 11.5

Table PD-10 — Gross Heating Capacities (kW)


TWA100A Heat Pump with TWE100A Air Handler At 5649 m3/h (SI)
Outdoor Heating Capacity (kW) At Total Power in Kilowatts At
Temperature Indicated Indoor Dry BulbTemperature Indicated Indoor Dry BulbTemperature
(°C) 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7
-27.8 6.0 10.9 12.1 12.8 5.5 6.0 6.2 6.5
-25.0 9.2 12.2 13.1 13.6 5.6 6.1 6.3 6.6
-22.2 11.4 13.5 14.2 14.6 5.7 6.2 6.5 6.7
-19.4 13.3 14.9 15.3 15.6 5.8 6.3 6.6 6.9
-16.7 15.2 16.3 16.6 16.8 5.9 6.5 6.7 7.0
-13.9 17.0 17.7 17.9 18.0 6.0 6.6 6.9 7.2
-11.1 18.8 19.3 19.4 19.4 6.2 6.7 7.0 7.4
-8.3 20.6 20.9 20.9 20.9 6.3 6.9 7.2 7.5
-5.6 22.5 22.6 22.5 22.5 6.5 7.0 7.4 7.7
-2.8 24.5 24.4 24.3 24.1 6.6 7.2 7.5 7.9
0.0 26.5 26.3 26.1 26.0 6.8 7.4 7.7 8.1
2.8 28.6 28.2 28.0 27.8 6.9 7.6 7.9 8.3
5.6 30.6 30.1 29.9 29.7 7.1 7.8 8.1 8.5
8.3 32.8 32.2 31.9 31.7 7.3 8.0 8.4 8.8
11.1 35.0 34.3 34.0 33.7 7.5 8.2 8.6 9.0
13.9 37.2 36.5 36.2 35.9 7.7 8.4 8.8 9.2
16.7 39.5 38.7 38.3 38.0 7.9 8.7 9.1 9.5
19.4 41.7 40.9 40.5 40.2 8.1 8.9 9.3 9.8
22.2 44.1 43.2 42.8 42.4 8.4 9.2 9.6 10.0
Correction Factors - Other Airflows Airflow = 3325 cfm (5649 m3/h)
(Table Value x Correction Factor = Value at new airflow) Heating Capacity (High Temp.) = 110,000 (32.21)
Heating Capacity (Low Temp.) = 71,000 (20.79)
Airflow 3000 cfm 3675 cfm Compressor Power (High Temp) = 7.59 kW
5097 m3/h 6243 m3/h Compressor Power (Low Temp) = 6.60 kW
Heating Capacity x 0.99 x 1.01 Coeff. Of Perf. (High Temp) = 3.4
Compressor kW x 1.02 x 0.98 Coeff. Of Perf. (Low Temp) = 2.4
Outdoor Fan Power = 615 watts
Values at ARI Rating Conditions of: Indoor Fan Power = 1,030 watts
70F (21.1C) and 47/43F (8.3/6.1C)(High Temp.Cond.)
70F (21.1C) and 17/15F (-8.3/-9.4C)(Low Temp. Cond) Note:
1. Rated with 25 feet of 1-3/8" suction and 1/2" liquid line.

SSP-PRC002-EN 21
Performance
Data (System)

Table PD-11 — Gross Heating Capacities (MBh)


TWA155B Heat Pump with TWE155B Air Handler At 5000 CFM (I-P)
Outdoor Heating Capacity (BTUH/1000) At Total Power in Kilowatts At
Temperature Indicated Indoor Dry BulbTemperature Indicated Indoor Dry BulbTemperature
(°F) 60 70 75 80 60 70 75 80
-18 68.8 60.9 58.1 55.9 11.9 12.3 12.5 12.8
-13 71.2 64.2 61.7 59.9 11.9 12.3 12.6 12.9
-8 74.3 68.2 66.2 64.7 11.9 12.4 12.7 13.2
-3 78.2 73.2 71.6 70.5 11.9 12.5 12.9 13.4
2 83.0 79.0 77.8 77.0 11.9 12.7 13.1 13.7
7 88.7 85.7 84.8 84.4 12.0 12.9 13.4 14.0
12 95.5 93.2 92.6 92.4 12.2 13.1 13.7 14.3
17 103.3 101.6 101.2 101.1 12.3 13.4 14.0 14.7
22 112.1 110.9 110.6 110.6 12.5 13.6 14.3 15.1
27 121.8 120.9 120.7 120.6 12.8 14.0 14.7 15.5
32 132.5 131.7 131.4 131.2 13.1 14.3 15.0 15.8
37 143.4 142.6 142.2 141.8 13.3 14.7 15.4 16.2
42 154.8 153.9 153.3 152.7 13.6 15.0 15.8 16.6
47 167.0 165.7 165.0 164.1 14.0 15.4 16.1 17.0
52 179.9 178.2 177.2 176.1 14.3 15.7 16.5 17.3
57 193.3 191.2 189.9 188.6 14.6 16.1 16.9 17.7
62 207.2 204.5 203.0 201.4 15.0 16.4 17.2 18.0
67 221.3 218.2 216.4 214.5 15.3 16.8 17.6 18.4
72 235.8 232.2 230.3 228.2 15.7 17.2 18.0 18.8

Table PD-11 — Gross Heating Capacities (kW)


TWA155B Heat Pump with TWE155B Air Handler At 8494 m3/h (SI)
Outdoor Heating Capacity (kW) At Total Power in Kilowatts At
Temperature Indicated Indoor Dry BulbTemperature Indicated Indoor Dry BulbTemperature
(°C) 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7
-27.8 20.1 17.8 17.0 16.4 5.5 6.0 6.2 6.5
-25.0 20.9 18.8 18.1 17.5 5.6 6.1 6.3 6.6
-22.2 21.8 20.0 19.4 19.0 5.7 6.2 6.5 6.7
-19.4 22.9 21.4 21.0 20.6 5.8 6.3 6.6 6.9
-16.7 24.3 23.1 22.8 22.6 5.9 6.5 6.7 7.0
-13.9 26.0 25.1 24.8 24.7 6.0 6.6 6.9 7.2
-11.1 28.0 27.3 27.1 27.0 6.2 6.7 7.0 7.4
-8.3 30.2 29.8 29.6 29.6 6.3 6.9 7.2 7.5
-5.6 32.8 32.5 32.4 32.4 6.5 7.0 7.4 7.7
-2.8 35.7 35.4 35.3 35.3 6.6 7.2 7.5 7.9
0.0 38.8 38.6 38.5 38.4 6.8 7.4 7.7 8.1
2.8 42.0 41.7 41.6 41.5 6.9 7.6 7.9 8.3
5.6 45.3 45.0 44.9 44.7 7.1 7.8 8.1 8.5
8.3 48.9 48.5 48.3 48.1 7.3 8.0 8.4 8.8
11.1 52.7 52.2 51.9 51.6 7.5 8.2 8.6 9.0
13.9 56.6 56.0 55.6 55.2 7.7 8.4 8.8 9.2
16.7 60.7 59.9 59.4 59.0 7.9 8.7 9.1 9.5
19.4 64.8 63.9 63.4 62.8 8.1 8.9 9.3 9.8
22.2 69.0 68.0 67.4 66.8 8.4 9.2 9.6 10.0
Correction Factors - Other Airflows“(Table Value Airflow = 5000 cfm (8495 m3/h)
Correction Factor = Value at new airflow) Heating Capacity (High Temp.) = 166,000 (48.60)
Airflow 4500 cfm 5500 cfm Heating Capacity (Low Temp.) = 101,000 (29.57)
7645 m3/h 9344 m3/h Compressor Power (High Temp) = 11.67 kW
Compressor Power (Low Temp) = 9.66 kW
Heating Capacity x 0.99 x 1.01 Coeff. Of Perf. (High Temp) = 3.2
Compressor kW x 1.02 x 0.98 Coeff. Of Perf. (Low Temp) = 2.2
Outdoor Fan Power = 1100 watts
Values at ARI Rating Conditions of: Indoor Fan Power = 2570 watts
70F (21.1C) and 47/43F (8.3/6.1C)(High Temp.Cond.)
70F (21.1C) and 17/15F (-8.3/-9.4C)(Low Temp. Cond) Note:
1.Rated with 25 feet of 1-3/8"" suction and 1/2"" liquid line."

22 SSP-PRC002-EN
Performance
Data (System)

Table PD-12 — Gross Heating Capacities (MBh)


TWA200B Heat Pump with TWE200B Air Handler At 6675 CFM (I-P)
Outdoor Heating Capacity (BTUH/1000) At Total Power in Kilowatts At
Temperature Indicated Indoor Dry BulbTemperature Indicated Indoor Dry BulbTemperature
(°F) 60 70 75 80 60 70 75 80
-18 42.4 79.1 84.7 87.4 11.5 15.4 16.6 17.6
-13 68.2 86.2 90.2 92.3 13.0 15.6 16.7 17.7
-8 81.5 93.8 96.7 98.0 13.6 15.9 16.9 17.9
-3 93.1 101.8 103.7 104.5 14.1 16.2 17.1 18.1
2 104.2 110.2 111.4 111.7 14.5 16.4 17.4 18.3
7 115.2 119.2 119.8 119.7 14.9 16.7 17.6 18.6
12 126.6 128.8 128.9 128.5 15.2 17.0 17.9 18.9
17 138.2 139.1 138.8 138.2 15.5 17.3 18.2 19.2
22 150.3 150.1 149.5 148.6 15.9 17.6 18.6 19.6
27 162.9 161.8 160.9 159.8 16.2 18.0 18.9 20.0
32 176.1 174.3 173.2 171.9 16.5 18.3 19.3 20.4
37 189.2 186.9 185.6 184.3 16.9 18.7 19.7 20.8
42 202.8 200.0 198.6 197.2 17.2 19.1 20.2 21.3
47 216.9 213.8 212.3 210.8 17.6 19.5 20.6 21.8
52 231.9 228.5 226.8 225.3 18.0 20.0 21.1 22.3
57 247.4 243.6 241.9 240.3 18.4 20.5 21.7 22.9
62 263.2 259.1 257.2 255.6 18.9 21.0 22.2 23.5
67 279.3 274.8 272.8 271.0 19.4 21.6 22.8 24.1
72 295.9 291.1 289.0 287.0 20.0 22.2 23.4 24.7

Table PD-12 — Gross Heating Capacities (kW)


TWA200B Heat Pump with TWE200B Air Handler At 11340 m3/h (SI)
Outdoor Heating Capacity (kW) At Total Power in Kilowatts At
Temperature Indicated Indoor Dry BulbTemperature Indicated Indoor Dry BulbTemperature
(°C) 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7
-27.8 12.4 23.2 24.8 25.6 5.5 6.0 6.2 6.5
-25.0 20.0 25.3 26.4 27.0 5.6 6.1 6.3 6.6
-22.2 23.9 27.5 28.3 28.7 5.7 6.2 6.5 6.7
-19.4 27.2 29.8 30.4 30.6 5.8 6.3 6.6 6.9
-16.7 30.5 32.3 32.6 32.7 5.9 6.5 6.7 7.0
-13.9 33.7 34.9 35.1 35.1 6.0 6.6 6.9 7.2
-11.1 37.1 37.7 37.8 37.6 6.2 6.7 7.0 7.4
-8.3 40.5 40.7 40.7 40.5 6.3 6.9 7.2 7.5
-5.6 44.0 43.9 43.8 43.5 6.5 7.0 7.4 7.7
-2.8 47.7 47.4 47.1 46.8 6.6 7.2 7.5 7.9
0.0 51.6 51.0 50.7 50.3 6.8 7.4 7.7 8.1
2.8 55.4 54.7 54.3 54.0 6.9 7.6 7.9 8.3
5.6 59.4 58.6 58.1 57.7 7.1 7.8 8.1 8.5
8.3 63.5 62.6 62.2 61.7 7.3 8.0 8.4 8.8
11.1 67.9 66.9 66.4 66.0 7.5 8.2 8.6 9.0
13.9 72.4 71.3 70.8 70.3 7.7 8.4 8.8 9.2
16.7 77.1 75.9 75.3 74.8 7.9 8.7 9.1 9.5
19.4 81.8 80.5 79.9 79.4 8.1 8.9 9.3 9.8
22.2 86.6 85.2 84.6 84.0 8.4 9.2 9.6 10.0
Correction Factors - Other Airflows Airflow = 6700 cfm (11383 m3/h)
(Table Value x Correction Factor = Value at new airflow) Heating Capacity (High Temp.) = 214,000 (62.66)
Heating Capacity (Low Temp.) = 139,000 (40.70)
Airflow 6000 cfm 7325 cfm Compressor Power (High Temp) = 15.83 kW
10194 m3/h 12445 m3/h Compressor Power (Low Temp) = 13.50 kW
Heating Capacity x 0.99 x 1.01 Coeff. Of Perf. (High Temp) = 3.2
Compressor kW x 1.02 x 0.98 Coeff. Of Perf. (Low Temp) = 2.3
Values at ARI Rating Conditions of: Outdoor Fan Power = 1,200 watts
70F (21.1C) and 47/43F (8.3/6.1C)(High Temp.Cond.) Indoor Fan Power = 2,300 watts
70F (21.1C) and 17/15F (-8.3/-9.4C)(Low Temp. Cond)
Note:
1. Rated with 25 feet of 1-3/8” suction and 1/2" liquid line."

SSP-PRC002-EN 23
Performance
Data (Air Handler)

Table PD-13 — Evaporator Fan Performance — TWE050A (I-P)


External Static Pressure (Inches of Water Column)
.10" .20" .30" .40" .50" .60" .70" .80" .90" 1.00" 1.10"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1400 — — — — 646 0.37 698 0.42 751 0.47 803 0.52 856 0.56 908 0.61 941 0.65 973 0.68 1006 0.71
1500 — — 607 0.36 661 0.40 713 0.45 764 0.50 816 0.54 867 0.59 919 0.64 952 0.67 984 0.71 — —
1600 — — 625 0.38 676 0.43 727 0.48 778 0.52 828 0.57 879 0.62 930 0.67 963 0.70 995 0.74 — —
1700 601 0.35 648 0.40 696 0.44 744 0.49 792 0.54 841 0.59 889 0.64 937 0.69 971 0.73 1005 0.77 — —
1800 625 0.36 671 0.41 716 0.46 762 0.51 807 0.56 853 0.61 898 0.66 944 0.71 979 0.76 — — — —
1900 642 0.40 687 0.45 731 0.50 776 0.55 820 0.60 865 0.66 909 0.71 951 0.75 987 0.80 — — — —
2000 659 0.44 703 0.49 745 0.54 790 0.60 833 0.65 877 0.70 920 0.75 957 0.80 994 0.84 — — — —
2100 674 0.48 722 0.54 770 0.60 817 0.65 857 0.70 897 0.75 936 0.80 973 0.85 1009 0.89 — — — —
0.75 HP Standard Motor and Standard Static Drive 1.0 HP Oversized Motor and High Static Drive
Notes:
1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters.
2. Tabulated brake horsepower is the motor shaft output required.
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.

Table PD-13— Evaporator Fan Performance — TWE050A (SI)


External Static Pressure (Pascal)
25 50 75 100 125 150 174 199 224 249 274
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
2379 — — — — 646 0.28 698 0.31 751 0.35 803 0.39 856 0.42 908 0.45 941 0.48 973 0.51 1006 0.53
2549 — — 607 0.27 661 0.30 713 0.34 764 0.37 816 0.40 867 0.44 919 0.48 952 0.50 984 0.53 — —
2718 — — 625 0.28 676 0.32 727 0.36 778 0.39 828 0.43 879 0.46 930 0.50 963 0.52 995 0.55 — —
2888 601 0.26 648 0.30 696 0.33 744 0.37 792 0.40 841 0.44 889 0.48 937 0.51 971 0.54 1005 0.57 — —
3058 625 0.27 671 0.31 716 0.34 762 0.38 807 0.42 853 0.45 898 0.49 944 0.53 979 0.57 — — — —
3228 642 0.30 687 0.34 731 0.37 776 0.41 820 0.45 865 0.49 909 0.53 951 0.56 987 0.60 — — — —
3398 659 0.33 703 0.37 745 0.40 790 0.45 833 0.48 877 0.52 920 0.56 957 0.60 994 0.63 — — — —
3568 674 0.36 722 0.40 770 0.45 817 0.48 857 0.52 897 0.56 936 0.60 973 0.63 1009 0.66 — — — —
0.56 kW Standard Motor and Standard Static Drive 0.75 kW Oversized Motor and High Static Drive
Notes:
1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters.
2. Tabulated brake horsepower is the motor shaft output required.
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.

Table PD-14 — Blower Speeds — TWE050A


Motor DriveTurns Open
Drive 6 5 4 3 2 1 0
Standard N/A 590 639 688 737 786 835
High Static N/A 713 772 832 891 951 1009

24 SSP-PRC002-EN
Performance
Data (Air Handler)

Table PD-15 — Evaporator Fan Performance TWE075A (I-P)


External Static Pressure (In. Of Water Column)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2000 — — 443 0.44 489 0.49 535 0.54 581 0.59 627 0.64 673 0.69 719 0.74 765 0.79 791 0.83 818 0.89
2125 — — 453 0.46 499 0.52 546 0.57 592 0.63 638 0.68 684 0.74 730 0.79 771 0.85 798 0.90 825 0.96
2250 — — 463 0.49 510 0.55 556 0.61 602 0.67 649 0.73 695 0.79 742 0.85 776 0.91 804 0.97 831 1.03
2375 — — 473 0.51 520 0.57 567 0.64 613 0.70 660 0.77 706 0.83 753 0.90 782 0.97 810 1.03 838 1.10
2500 445 0.47 489 0.54 533 0.60 578 0.67 622 0.73 667 0.80 711 0.86 756 0.93 784 0.99 813 1.07 842 1.14
2625 464 0.50 506 0.57 548 0.63 589 0.69 631 0.76 672 0.82 714 0.88 757 0.95 786 1.01 815 1.09 844 1.17
2750 484 0.53 523 0.59 562 0.66 601 0.72 640 0.78 678 0.84 717 0.91 758 0.97 787 1.03 817 1.12 847 1.21
2875 504 0.56 540 0.62 576 0.68 612 0.74 648 0.81 684 0.87 720 0.93 759 0.99 789 1.05 819 1.15 850 1.24
3000 524 0.59 557 0.65 590 0.71 624 0.77 657 0.83 690 0.89 723 0.95 760 1.01 790 1.07 821 1.17 853 1.27
1.0 HP Standard Motor 1.0 HP Standard Motor 1.5 HP Oversized Motor
and Low Static Drive and Drive and High Static Drive
Notes:
1. Performance based on a wet coil and 1 inch (25.4 mm) Table PD-15— Continued
throwaway filters.
2. Tabulated brake horsepower is the motor shaft output External Static Pressure (In. Of Water Column)
required.
1.20 1.30 1.40 1.50 1.60
3. Factory setting of motor sheave is 1.5 turns open.
Adjustments are made in 0.5 turn increments. CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2000 844 0.96 871 1.02 897 1.09 924 1.15 950 1.21
2125 852 1.03 879 1.09 906 1.16 933 1.22 — —
2250 859 1.10 886 1.17 914 1.23 942 1.30 — —
2375 866 1.17 894 1.24 922 1.30 950 1.37 — —
2500 870 1.21 899 1.29 928 1.36 — — — —
2625 874 1.25 903 1.33 932 1.42 — — — —
2750 877 1.29 907 1.38 937 1.47 — — — —
2875 880 1.33 911 1.43 942 1.52 — — — —
3000 884 1.37 915 1.48 946 1.58 — — — —
1.5 HP Oversized Motor
and High Static Drive

1.0 HP Standard Motor


and Drive

Table PD-15 — Evaporator Fan Performance TWE075A (SI)


External Static Pressure (Pascal)
25 50 75 100 125 150 174 199 224 249 274
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
3338 — — 443 0.33 489 0.37 535 0.4 581 0.44 627 0.48 673 0.51 719 0.55 765 0.59 791 0.62 818 0.66
3547 — — 453 0.34 499 0.39 546 0.43 592 0.47 638 0.51 684 0.55 730 0.59 771 0.63 798 0.67 825 0.72
3755 — — 463 0.37 510 0.41 556 0.45 602 0.5 649 0.54 695 0.59 742 0.63 776 0.68 804 0.72 831 0.77
3964 — — 473 0.38 520 0.43 567 0.48 613 0.52 660 0.57 706 0.62 753 0.67 782 0.72 810 0.77 838 0.82
4173 445 0.35 489 0.4 533 0.45 578 0.5 622 0.54 667 0.6 711 0.64 756 0.69 784 0.74 813 0.8 842 0.85
4381 464 0.37 506 0.43 548 0.47 589 0.51 631 0.57 672 0.61 714 0.66 757 0.71 786 0.75 815 0.81 844 0.87
4590 484 0.4 523 0.44 562 0.49 601 0.54 640 0.58 678 0.63 717 0.68 758 0.72 787 0.77 817 0.84 847 0.9
4798 504 0.42 540 0.46 576 0.51 612 0.55 648 0.6 684 0.65 720 0.69 759 0.74 789 0.78 819 0.86 850 0.92
5007 524 0.44 557 0.48 590 0.53 624 0.57 657 0.62 690 0.66 723 0.71 760 0.75 790 0.8 821 0.87 853 0.95
.75 kW Standard Motor .75 kW Standard Motor 1.12 kW Oversized Motor
and Low Static Drive and Drive and High Static Drive
Notes:
1. Performance based on a wet coil and 1 inch (25.4 mm) Table PD-15 — Continued
throwaway filters.
External Static Pressure (Pascal)
2. Tabulated brake horsepower is the motor shaft
output required. 299 324 349 374 398
3. Factory setting of motor sheave is 1.5 turns open.
Adjustments are made in 0.5 turn increments.
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW
3338 844 0.72 871 0.76 897 0.81 924 0.86 950 0.9
3547 852 0.77 879 0.81 906 0.87 933 0.91 — —
3755 859 0.82 886 0.87 914 0.92 942 0.97 — —
3964 866 0.87 894 0.92 922 0.97 950 1.02 — —
Table PD-16 — Blower Speeds — TWE075A 4173 870 0.9 899 0.96 928 1.01 — — — —
Motor DriveTurns Open 4381 874 0.93 903 0.99 932 1.06 — — — —
4590 877 0.96 907 1.03 937 1.1 — — — —
Drive 6 5 4 3 2 1 0
4798 880 0.99 911 1.07 942 1.13 — — — —
Standard N/A 600 650 700 750 800 850 5007 884 1.02 915 1.1 946 1.18 — — — —
Low Static N/A 428 464 499 535 571 606 1.12 kW Oversized Motor and High Static Drive
High Static N/A 700 750 800 850 900 950
.75 kW Standard Motor
and Drive
SSP-PRC002-EN 25
Performance
Data (Air Handler)

Table PD-17 — Evaporator Fan Performance TWE100A, TWE100B (I-P)


External Static Pressure (In. Of Water Column)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.20
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP Standard Motor and Low Static Drive
2600 460 0.32 493 0.39 527 0.47 565 0.55 603 0.63 641 0.71 679 0.79 717 0.87 744 0.94 772 1.01 826 1.16
2775 473 0.37 506 0.45 540 0.53 576 0.61 613 0.69 649 0.77 686 0.85 723 0.93 748 1.00 775 1.07 830 1.20
2950 487 0.43 519 0.50 552 0.58 587 0.67 623 0.75 658 0.83 693 0.91 728 0.99 751 1.06 779 1.12 833 1.25
3125 501 0.49 532 0.56 565 0.64 599 0.72 632 0.81 666 0.89 700 0.97 734 1.05 755 1.11 783 1.18 737 1.30
3300 520 0.58 548 0.65 581 0.73 613 0.81 644 0.89 677 0.98 710 1.06 740 1.13 759 1.19 787 1.25 841 1.37
3475 541 0.69 568 0.76 600 0.84 631 0.93 658 1.00 691 1.08 721 1.16 746 1.21 764 1.28 793 1.34 846 1.48
3650 562 0.82 588 0.88 618 0.97 648 1.05 671 1.11 703 1.19 732 1.27 753 1.31 772 1.38 801 1.45 853 1.59
3825 582 0.96 608 1.03 637 1.11 666 1.20 685 1.26 711 1.31 739 1.38 763 1.44 787 1.51 815 1.58 862 1.74
4000 602 1.11 628 1.17 656 1.26 683 1.35 698 1.40 720 1.43 747 1.50 773 1.58 801 1.64 829 1.71 872 1.89
1.5 HP Standard Motor and Drive 2.0 HP Oversized Motor
and High Static Drive
Notes:
1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters.
2. Tabulated brake horsepower is the motor shaft output required.
Table PD-17— Continued
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are External Static Pressure (In. Of Water Column)
made in 0.5 turn increments.
4. Low Static Drive must be field supplied. 1.40 1.60
CFM RPM BHP RPM BHP
2.0 HP Oversized Motor and High Static Drive
2600 881 1.30 936 1.45
2775 884 1.36 938 1.51
2960 886 1.41 939 1.57
3125 889 1.47 941 1.64
3300 892 1.54 945 1.73
3475 897 1.63 950 1.85
3650 902 1.73 955 1.99
3825 912 1.89 960 2.18
4000 922 2.04 965 2.30

Table PD-17— Evaporator Fan Performance TWE100A, TWE100B (SI)


External Static Pressure (Pascal)
25 50 75 100 125 150 174 199 224 249 299
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 kW Standard Motor and Low Static Drive
4417 460 0.24 493 0.29 527 0.35 565 0.41 603 0.47 641 0.53 679 0.59 717 0.65 744 0.7 772 0.75 826 0.87
4715 473 0.28 506 0.34 540 0.4 576 0.45 613 0.51 649 0.57 686 0.63 723 0.69 748 0.75 775 0.8 830 0.89
5012 487 0.32 519 0.37 552 0.43 587 0.5 623 0.56 658 0.62 693 0.68 728 0.74 751 0.79 779 0.84 833 0.93
5309 501 0.37 532 0.42 565 0.48 599 0.54 632 0.6 666 0.66 700 0.72 734 0.78 755 0.83 783 0.88 737 0.97
5607 520 0.43 548 0.48 581 0.54 613 0.6 644 0.66 677 0.73 710 0.79 740 0.84 759 0.89 787 0.93 841 1.02
5904 541 0.51 568 0.57 600 0.63 631 0.69 658 0.75 691 0.8 721 0.87 746 0.9 764 0.95 793 1 846 1.1
6201 562 0.61 588 0.66 618 0.72 648 0.78 671 0.83 703 0.89 732 0.95 753 0.98 772 1.03 801 1.08 853 1.19
6499 582 0.72 608 0.77 637 0.83 666 0.89 685 0.94 711 0.98 739 1.03 763 1.07 787 1.13 815 1.18 862 1.3
6796 602 0.83 628 0.87 656 0.94 683 1.01 698 1.04 720 1.07 747 1.12 773 1.18 801 1.22 829 1.28 872 1.41
1.12 kW Standard Motor and Drive 1.49 kW Oversized Motor
and High Static Drive
Notes:
1. Performance based on a wet coil and 1 inch (25.4 mm)
throwaway filters. Table PD-17— Continued
2. Tabulated brake horsepower is the motor shaft output required.
3. Factory setting of motor sheave is 3.0 turns open. Adjustments are External Static Pressure (Pascal)
made in 0.5 turn increments.
4. Low Static Drive must be field supplied. 349 398
m3/hr RPM kW RPM kW
1.49 kW Oversized Motor and High Static Drive
4417 881 0.97 936 1.08
Table PD - 18 — Blower Speeds — TWE100A, TWE100B 4715 884 1.01 938 1.13
5012 886 1.05 939 1.17
Motor SheaveTurns Open 5309 889 1.1 941 1.22
Drive 6 5 4 3 2 1 0 5607 892 1.15 945 1.29
Standard N/A 587 629 671 713 755 796 5904 897 1.22 950 1.38
Low Static N/A 453 485 518 550 583 615 6201 902 1.29 955 1.48
High Static N/A 606 641 677 713 748 784 6499 912 1.41 960 1.63
High Static II N/A 745 789 833 877 920 965 6796 922 1.52 965 1.72

26 SSP-PRC002-EN
Performance
Data (Air Handler)

Table PD-19 — Evaporator Fan Performance — TWE155B (I-P)


External Static Pressure (Inches of Water Column)
.10" .20" .30" .40" .50" .60" .70" .80" .90" 1.00" 1.20" 1.40"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3.0 HP Oversized Motor
2.0 HP Standard Motor and Drive and High Static Drive
4000 628 1.34 653 1.38 678 1.43 692 1.48 708 1.52 723 1.57 738 1.60 749 1.61 759 1.62 795 1.66 851 1.85 907 2.03
4250 633 1.37 658 1.41 683 1.46 697 1.51 713 1.55 728 1.60 743 1.62 751 1.63 770 1.64 806 1.71 862 1.90 918 2.11
4500 637 1.40 662 1.44 687 1.49 701 1.53 717 1.58 732 1.63 747 1.64 754 1.65 782 1.67 817 1.76 873 1.96 929 2.19
4750 641 1.42 666 1.50 691 1.53 705 1.61 721 1.63 736 1.65 751 1.66 765 1.67 793 1.72 828 1.81 884 2.01 940 2.27
5000 645 1.44 670 1.52 695 1.56 710 1.65 725 1.67 739 1.68 758 1.70 777 1.74 806 1.81 839 1.91 896 2.13 — —
5260 650 1.46 675 1.53 700 1.59 716 1.67 728 1.70 741 1.73 765 1.75 790 1.82 819 1.92 849 2.03 907 2.28 — —
5500 652 1.47 678 1.55 703 1.63 721 1.71 734 1.75 747 1.78 775 1.83 804 1.92 832 2.03 861 2.15 920 2.44 — —
5750 653 1.48 680 1.57 706 1.68 726 1.76 743 1.81 761 1.86 789 1.94 817 2.04 846 2.16 875 2.29 935 2.61 — —
6000 655 1.49 681 1.59 709 1.74 731 1.80 752 1.87 774 1.94 803 2.05 831 2.17 860 2.29 889 2.44 950 2.78 — —
Notes:
1. Performance based on a wet coil and 2 inch (51 mm) throwaway filters.
2. Tabulated brake horsepower is the motor shaft output required.
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.

Table PD-19 — Evaporator Fan Performance TWE155B (SI)


External Static Pressure (Pascal)
25 50 75 100 125 150 174 199 224 249 299 349
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
2.24 kW Oversized Motor
1.49 kW Standard Motor and Drive and High Static Drive
6796 628 1 653 1.03 678 1.07 692 1.1 708 1.13 723 1.17 738 1.19 749 1.2 759 1.21 795 1.24 851 1.38 907 1.51
7221 633 1.02 658 1.05 683 1.09 697 1.13 713 1.16 728 1.19 743 1.21 751 1.22 770 1.22 806 1.28 862 1.42 918 1.57
7646 637 1.04 662 1.07 687 1.11 701 1.14 717 1.18 732 1.22 747 1.23 754 1.23 782 1.25 817 1.31 873 1.46 929 1.63
8070 641 1.06 666 1.12 691 1.14 705 1.2 721 1.22 736 1.23 751 1.24 765 1.25 793 1.28 828 1.35 884 1.5 940 1.69
8495 645 1.07 670 1.13 695 1.16 710 1.23 725 1.25 739 1.25 758 1.27 777 1.3 806 1.35 839 1.42 896 1.59 — —
8937 650 1.09 675 1.14 700 1.19 716 1.25 728 1.27 741 1.29 765 1.3 790 1.36 819 1.43 849 1.51 907 1.7 — —
9345 652 1.1 678 1.16 703 1.22 721 1.28 734 1.3 747 1.33 775 1.36 804 1.43 832 1.51 861 1.6 920 1.82 — —
9769 653 1.1 680 1.17 706 1.25 726 1.31 743 1.3 761 1.39 789 1.45 817 1.52 846 1.61 875 1.71 935 1.95 — —
10194 655 1.11 681 1.19 709 1.3 731 1.34 752 1.35 774 1.45 803 1.53 831 1.62 860 1.71 889 1.82 950 2.07 — —
Notes:
1. Performance based on a wet coil and 2 inch (51 mm) throwaway filters.
2. Tabulated brake horsepower is the motor shaft output required.
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.

Table PD-20— Blower Speeds — TWE155B


Motor SheaveTurns Open
Drive 6 5 4 3 2 1 0
Standard 619 648 677 705 734 763 N/A
High Static 777 806 835 863 892 921 950

SSP-PRC002-EN 27
Performance
Data (Air Handler)

Table PD-21— Evaporator Fan Performance TWE200B (I-P)


External Static Pressure (In. Of Water Column)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.20 140
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5200 — — 461 0.74 503 0.91 545 1.07 587 1.03 619 1.17 685 1.40 723 1.59 750 1.74 777 1.89 851 2.19 898 2.39
5525 — — 479 0.88 521 1.04 563 1.21 605 1.21 640 1.35 701 1.58 739 1.77 766 1.92 793 2.07 859 2.37 906 2.60
5850 — — 497 1.01 539 1.18 581 1.34 623 1.39 661 1.53 717 1.76 755 1.95 782 2.10 809 2.25 868 2.55 915 2.81
6175 473 0.99 515 1.15 557 1.31 599 1.48 641 1.57 682 1.71 732 1.94 769 2.12 796 2.27 823 2.43 877 2.73 924 3.02
6500 492 1.12 534 1.28 576 1.45 618 1.61 660 1.75 702 1.90 748 2.12 784 2.30 811 2.45 838 2.60 886 2.91 933 3.22
6825 510 1.25 552 1.42 594 1.59 636 1.75 678 1.91 723 2.10 763 2.30 794 2.47 820 2.62 846 2.77 894 3.09 941 3.42
7150 528 1.38 570 1.56 612 1.73 654 1.90 697 2.07 744 2.30 779 2.49 804 2.64 830 2.78 855 2.94 903 3.26 950 3.62
7475 550 1.61 594 1.77 640 1.92 683 2.08 721 2.29 760 2.50 790 2.67 815 2.81 840 2.96 865 3.11 914 3.47 959 3.85
7800 572 1.83 618 1.97 668 2.10 712 2.27 746 2.52 776 2.69 802 2.84 826 2.99 851 3.13 876 3.27 926 3.67 969 4.08
3.0 HP Standard 3 HP Standard 3 HP Standard Motor 5 HP Oversized Motor
Motor and Low Motor and Low and Standard and High Static
Static Drive Static Drive System II Drive System Drive System
Notes:
1. Performance based on a wet coil and 2 inch (51 mm) throwaway filters. Table PD-21— Continued
2. Tabulated brake horsepower is the motor shaft output required.
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in External Static Pressure (In. Of Water Column)
0.5 turn increments.
4. Low static drive components referencing this note are field supplied. 1.60 1.80
CFM RPM BHP RPM BHP
5 HP Oversized Motor and High Static Drive System
5200 944 2.75 989 3.12
5525 952 2.96 997 3.33
5850 961 3.17 1006 3.54
5175 970 3.38 1015 3.75
8500 978 3.59 1023 3.96
8825 986 3.80 — —
7150 994 4.01 — —
7475 1003 4.25 — —
7800 1012 4.50 — —

Table PD-21— Evaporator Fan Performance TWE200B (SI)


External Static Pressure (Pascal)
25 50 75 100 125 150 174 199 224 249 299 349
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
8835 — — 461 0.55 503 0.68 545 0.8 587 0.77 619 0.87 685 1.04 723 1.19 750 1.3 777 1.41 851 1.63 898 1.78
9387 — — 479 0.66 521 0.78 563 0.9 605 0.9 640 1.01 701 1.18 739 1.32 766 1.43 793 1.54 859 1.77 906 1.94
9939 — — 497 0.75 539 0.88 581 1 623 1.04 661 1.14 717 1.31 755 1.45 782 1.57 809 1.68 868 1.9 915 2.1
10491 473 0.74 515 0.86 557 0.98 599 1.1 641 1.17 682 1.28 732 1.45 769 1.58 796 1.69 823 1.81 877 2.04 924 2.52
11044 492 0.84 534 0.95 576 1.08 618 1.2 660 1.3 702 1.42 748 1.58 784 1.72 811 1.83 838 1.94 886 2.17 933 2.4
11596 510 0.93 552 1.06 594 1.19 636 1.3 678 1.42 723 1.57 763 1.72 794 1.84 820 1.95 846 2.07 894 2.3 941 2.55
12148 528 1.03 570 1.16 612 1.29 654 1.42 697 1.54 744 1.72 779 1.86 804 1.97 830 2.07 855 2.19 903 2.43 950 2.7
12700 550 1.2 594 1.32 640 1.43 683 1.55 721 1.71 760 1.87 790 1.99 815 2.1 840 2.21 865 2.32 914 2.59 959 2.87
13252 572 1.36 618 1.47 668 1.57 712 1.69 746 1.88 776 2.01 802 2.12 826 2.23 851 2.33 876 2.44 926 2.74 969 3.04
2.24 kW Standard 2.24 kW Standard 2.24 kW Standard 3.73 kW Oversized Motor
Motor and Low Motor and Low Motor and Standard and High Static Drive System
Static Drive System Static Drive System II Drive System
Notes:
1. Performance based on a wet coil and 2 inch (51 mm) throwaway filters. Table PD-21— Continued
2. Tabulated brake horsepower is the motor shaft output required.
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in External Static Pressure (Pascal)
0.5 turn increments.
4. Low static drive components referencing this note are field supplied. 398 448
m3/hr RPM kW RPM kW
3.73 kW Oversized Motor
and High Static Drive System
8835 944 2.05 989 2.33
9387 952 2.21 997 2.48
Table PD-22 — Blower Speeds — TWE200B
9939 961 2.36 1006 2.64
Motor SheaveTurns Open 10491 970 2.52 1015 2.8
Drive 6 5 4 3 2 1 0 11044 978 2.68 1023 2.95
11596 986 2.83 — —
Standard 706 732 758 784 811 837 863
12148 994 2.99 — —
Low Static I 457 478 500 521 542 563 585
12700 1003 3.17 — —
Low Static II 574 595 617 638 659 680 702
13252 1012 3.36 — —
High Static N/A 821 862 903 945 986 1027

28 SSP-PRC002-EN
Performance
Data

Table PD-23— Discharge Plenum And Grille Assembly Throw Distance — Air Handler — ft (m)
Unit Louver Angle Deflection Position
Model No. CFM m3/h Straight 20 40 55
1400 2378 38 (11.6) 24 (7.3) 22 (6.7) 18 (5.5)
1600 2718 42 (12.8) 31 (9.4) 26 (7.9) 20 (6.1)
TWE050 1800 3058 46 (14.0) 37 (11.3) 29 (8.8) 22 (6.7)
2000 3398 48 (14.6) 43 (13.1) 33 (10.1) 24 (7.3)
2200 3737 51 (15.5) 50 (15.2) 36 (11.0) 25 (7.6)
2100 3568 49 (14.9) 38 (11.6) 31 (9.4) 27 (8.2)
2400 4077 52 (15.9) 43 (13.1) 35 (10.7) 29 (8.8)
2700 4587 55 (16.8) 48 (14.6) 38 (11.6) 31 (9.4)
TWE075 3000 5097 58 (17.7) 53 (16.2) 42 (12.8) 32 (9.8)
3200 5436 56 (17.1) 46 (14.0) 38 (11.6) 30 (9.1)
3600 6116 62 (18.9) 51 (15.5) 42 (12.8) 33 (10.1)
4000 6795 66 (20.1) 57 (17.4) 47 (14.3) 35 (10.7)
4400 7475 71 (21.6) 62 (18.9) 52 (15.9) 38 (11.6)
TWE100 4800 8154 76 (23.2) 67 (20.4) 56 (17.1) 42 (12.8)
4300 7305 42 (12.8) 32 (9.8) 29 (8.8) 21 (6.4)
4900 8324 47 (14.3) 38 (11.6) 32 (9.8) 25 (7.6)
5400 9174 52 (15.9) 44 (13.4) 37 (11.3) 29 (8.8)
TWE155 5600 9514 50 (15.2) 40 (12.2) 33 (10.1) 27 (8.2)
6000 10193 57 (17.4) 49 (14.9) 41 (12.5) 32 (9.8)
6400 10873 56 (17.1) 46 (14.0) 38 (11.6) 30 (9.1)
7200 12232 62 (18.9) 51 (15.5) 42 (12.8) 33 (10.1)
TWE200 8000 13591 66 (20.1) 57 (17.4) 47 (14.3) 35 (10.7)
Throw distance values are based on a terminal velocity of 75 FPM (0.38 m/s).
Throw distance values at other terminal velocities may be established by multiplying throw distances in table above by throw
factor:
Terminal Velocity Throw Factor
50 fpm (.25 m/s) x 1.50
100 fpm (.51 m/s) x .75
150 fpm (.76 m/s) x .50

Table PD-24— Static Pressure Drop Through Accessories (Inches Of Water Column)1 — Air Handler
Discharge Electric Heaters (kW)
Unit Return Grille Plenum and Grille2 5-10 15-20 25-30 35-50
Model No. CFM m3/h In. wc1 Pascal In. wc1 Pascal In. wc (Pascal)
1400 2380 .09 (22.4) .16 (39.8) .06 (15.0) .06 (15.0) .12 (29.9) —
TWE050A 1600 2718 .12 (29.9) .21 (52.3) 08 (19.9) .08 (19.9) .14 (34.9) —
2000 3398 .18 (44.8) .33 (82.2) .13 (32.4) .13 (32.4) .19 (47.3) —
2100 3568 .05 (12.5) .19 (47.3) .02 (5.0) .03 (7.5) .05 (12.5) .08 (19.9)
TWE075A 2400 4079 .08 (19.9) .27 (67.2) .03 (7.5) .06 (15.0) .08 (19.9) .12 (29.9)
3000 5098 .13 (32.4) .40 (99.6) .06 (15.0) .12 (29.9) .17 (42.4) .23 (57.3)
TWE100A 2800 4756 .04 (10.0) .34 (84.7) .03 (7.5) .04 (10.0) .14 (34.9) .20 (49.8)
TWE100B 3200 5436 .07 (17.4) .43 (107.1) .06 (15.0) .13 (32.4) .19 (47.3) .26 (64.8)
4300 7304 .07 (17.4) .18 (44.8) .02 (5.0) .02 (5.0) .04 (10.0) .05 (12.5)
TWE155B 4800 8154 .09 (22.4) .23 (57.3) .03 (7.5) .03 (7.5) .06 (15.0) .08 (19.9)
6000 10195 .15 (37.4) .34 (84.7) .06 (15.0) .06 (15.0) .12 (29.9) .17 (42.4)
5600 9515 .07 (17.4) .32 (79.7) .04 (10.0) .04 (10.0) .10 (25.0) .15 (37.4)
TWE200B 6400 10872 .11 (27.4) .43 (107.1) .06 (15.0) .06 (15.0) .13 (32.4) .19 (47.3)
8000 13594 .17 (42.3) .66 (164.3) .10 (25.0) .10 (25.0) .20 (49.8) .30 (74.7)
1. Return air filter ESP included in Fan PerformanceTable data.
2. At louver opening angle of 42°F (5.5°C). For ESP at other angle openings, see accessory Installer’s Guide.

SSP-PRC002-EN 29
Performance
Data

Table PD-25 — Auxiliary Electric Heat Capacity — Air Handler


No. Stage 1 Stage 2 Total
Unit Total of kW Btu kW kW Btu kW Btu kW
Model No. kW Stages Input Output Output Input Output Output Output Output
TWE050, 075,100 3.47 1 3.47 11,851 3.47 — — — 11,851 3.47
6.92 1 9.92 23,606 6.92 — — — 23,606 6.92
10.39 1 10.39 35,457 10.39 — — — 35,457 10.39
17.31 2 10.39 35,457 10.39 6.92 23,606 6.92 59,063 17.31
TWE075, 100A, 100 24.22 2 13.83 47,213 13.83 10.39 35,457 10.39 82,670 24.22
TWE155, 200 6.94 1 6.94 23,701 6.94 — — — 23,701 6.94
13.83 1 13.83 47,213 13.83 — — — 47,213 13.83
20.78 2 13.83 47,213 13.83 6.94 23,701 6.94 70,915 20.78
34,62 2 20.78 70,915 20.78 13.84 47,213 13.89 118,128 34.61
*Heaters are rated at 400v. For other than rated voltage,

( ) ( RatedVoltage
Voltage )
2 2
Capacity = Voltage x Rated Capacity and kW = x Rated kW.
Rated Voltage

30 SSP-PRC002-EN
Electrical
Data

Table ED-1— Electrical Characteristics — Motors — Air Handler


Standard Fan Motor Oversized Fan Motor
Unit Amps Amps
Model No. Volts Phase FLA LRA Phase FLA LRA
TWE050 380/415 3 1.4 8.2 3 1.8 21.6
TWE075 380/415 3 3.2 19.7 3 4.0 25.5
TWE100 380/415 3 3.6 25.5 3 5.3 37.5
TWE155 380/415 3 4.6 37.5 3 6.9 39.2
TWE200 380/415 3 7.6 39.2 3 9.0 65.1

Table ED-2 — Unit Wiring — Air Handler


Minimum Maximum Fuse
Unit Unit Operating Circuit Size or Maximum
Model No. Voltage Range Ampacity Circuit Breaker
TWE050 380/415 2 15
TWE075 380/415 4 15
TWE100 380/415 5 15
TWE155 380/415 6 15
TWE200 380/415 10 15

Table ED-3— Electrical Characteristics — Motors — 50 Cycle — Heat Pumps


Compressor Motor Condenser Fan Motor
Amps Amps
Unit RLA LRA FLA LRA
Model No. No. Volts Phase (Ea.) (Ea.) No. Volts Phase (Ea.) (Ea.)
TWA075AD 1 380/415 3 8.8 90.0 1 380/415 1 1.6 3.7
TWA100AD 1 380/415 3 15.6 124.0 1 380/415 1 2.7 7.0
TWA155BD 2 380/415 3 11.2 94.8 2 380/415 1 1.6 3.7
TWA200BD 2 380/415 3 14.9 118.0 2 380/415 1 2.7 7.0

Table ED-4 — Unit Wiring — Heat Pumps


Minimum Maximum Fuse
Unit Unit Operating Circuit Size or Maximum
Model No. Voltage Range Ampacity Circuit Breaker
TWA075 380/415 12.6 50
TWA100 380/415 22 .2 35
TWA155 380/415 28.4 35
TWA200 380/415 40.5 50

SSP-PRC002-EN 31
Electrical
Data

Table ED-5— Unit Wiring With Electric Heat (Single Point Connection) — Air Handlers
Heater Heater To Use Control Minimum Maximum
Model No. kW Rating1 with Unit Stages Circuit Ampacity 2 Fuse Breaker Size 2
BAYHTRL405A 3.47 1 9 15
BAYHTRL410A 6.92 TWE050AD 1 17 20
BAYHTRL415A 10.39 1 24 25
BAYHTRL425A 17.31 2 39 40
BAYHTRL405A 3.47 1 11 15
BAYHTRL410A 6.92 1 18 20
BAYHTRL415A 10.39 TWE075AD 1 26 30
BAYHTRL425A 17.31 2 41 45
BAYHTRL435A 24.22 2 56 60
BAYHTRL405A 3.47 1 12 15
BAYHTRL410A 6.92 1 19 25
BAYHTRL415A 10.39 TWE100AD, TWE100BD 1 27 30
BAYHTRL425A 20.78 2 42 45
BAYHTRL435A 24.22 2 57 60
BAYHTRM410A 6.94 1 21 30
BAYHTRM420A 13.83 TWE155BD 1 36 40
BAYHTRM430A 20.78 2 51 60
BAYHTRM450A 34.62 2 81 90
BAYHTRM410A 6.94 1 25 40
BAYHTRM420A 13.83 TWE200BD 1 40 50
BAYHTRM430A 20.78 2 55 60
BAYHTRM450A 34.62 2 85 90
1. kW ratings are at 400v for 3 phase, 400v air handlers

( ) ( )
2 2
For other than rated voltage, ampacity = Voltage Voltage
x Rated Capacity and kW = Rated kW.
Rated Voltage Rated Voltage
2. Any power supply and circuits must be wired and protected in accordance with local codes.
3. Field wire must be rated at least 75°C.
4. Field wire must be rated at least 90°C.

32 SSP-PRC002-EN
Jobsite
Connections

Wiring shown with dashed lines is to be


furnished and installed by the customer.
All customer- supplied wiring must be
copper only and must conform to NEC
and local electrical codes. Codes may
require line of sight between disconnect
switch and unit.
NOTE:
1. When electric heater accessory is used
single point power entry or dual point
power entry is field optional. Single point
power entry option is through electric
heater only.
TWA050/TWE050
Field Wiring:
A — 3 power wires. Line voltage.
B — 3 power wires. Line voltage.
C — Heat pump thermostat: 6 wires,
24 volts.
— Electric heat: add 2 additional
wires, 24 volts.
D — 2 wires, 24 volts.
— Outdoor thermostat: add 1
additional wire per ODT, 24 volts.
— Electric heat: add 1 additional
wire, 24 volts.
(2) TWA050/TWE100B
Field Wiring:
A — 3 power wires. Line voltage.
B — 3 power wires. Line voltage. TWA075A/TWE075A; D — 9 wires, 24 volts.
C — Heat pump thermostat: 7 wires, TWA100A/TWE100A — Electric heat: add 4 additional
24 volts Electric Heat: add 2 Field Wiring: wires, 24 volts.
additional wires, 24 volts. A — 3 power wires, line voltage. — Outdoor thermostat: add 3
D — 5 wires, 24 volts to outdoor B — 3 power wires, line voltage. additional wires, 24 volts.
section ‘’A’’ 2 wires, 24 volts to C — Heat pump thermostat: 6 wires, TWA155B/TWE155B;
outdoor section ‘’B’’ 2 wires, 24 24 volts. TWA200B/TWE200B
volts between outdoor sections — Electric heat: add 2 additional Field Wiring:
‘’A’’ ‘’B’’ wires, 24 volts. A — 3 power wires, line voltage.
— Electric heat: add 1 additional D — 6 wires, 24 volts. B — 3 power wires, line voltage.
wire, 24 volts. — Outdoor thermostat: add 1 C — Heat pump thermostat: 7 wires,
— Outdoor thermostat: add 1 additional wire, 24 volts. 24 volts.
additional wire, 24 volt. — Electric heat: add 1 additional — Electric heat: add 2 additional
wire, 24 volts. wires, 24 volts.
(2) TWA075A/TWE155B; D — 7 wires, 24 volts.
(2) TWA100A/TWE200B — Electric heat: add 4 additional
Field Wiring: wires, 24 volts.
A — 3 power wires, line voltage. — Outdoor thermostat: add 1
B — 3 power wires, line voltage. additional wire, 24 volts.
C — Heat pump thermostat: 7 wires,
24 volts.
— Electric heat: add 2 additional
wires, 24 volts.

SSP-PRC002-EN 33
Typical
Wiring (Heat Pump)

Heat Pump — Single Compressor

Typical unit wiring diagram. For specific


wiring, see individual Service Facts.

34 SSP-PRC002-EN
Typical
Wiring (Heat Pump)

SSP-PRC002-EN 35
Typical
Wiring (Heat Pump)

Heat Pump — Dual Compressors

Typical unit wiring diagram. For specific


wiring, see individual Service Facts.

36 SSP-PRC002-EN
Typical
Wiring (Heat Pump)

SSP-PRC002-EN 37
Typical
Wiring (Air Handler)

Air Handler
Typical unit wiring diagram. For specific
wiring, see individual Service Facts.

38 SSP-PRC002-EN
Dimensional
Data (Heat Pump)

Figure DD-1 — TWA075 Heat Pump

All dimensions are in inches and millimeters.

Note 1
MINIMUM CLEARANCE FOR PROPER
OPERATION IS 36 INCHES (914 MM)
FROM WALLS, SHRUBBERY, PRIVACY
FENCES, ETC. MINIMUM CLEARANCE
BETWEEN ADJACENT UNITS IS 72
INCHES (1828 MM)

SSP-PRC002-EN 39
Dimensional
Data (Heat Pump)

Figure DD-2 — 10 Ton TWA100A Heat Pump

All dimensions are in inches and millimeters.

Note 1
MINIMUM CLEARANCE FOR PROPER
OPERATION IS 36 INCHES (914 MM)
FROM WALLS, SHRUBBERY, PRIVACY
FENCES, ETC. MINIMUM CLEARANCE
BETWEEN ADJACENT UNITS IS 72
INCHES (1828 MM)

40 SSP-PRC002-EN
Dimensional
Data (Heat Pump)

Figure DD-3 — TWA155B Heat Pump

All dimensions are in inches and millimeters.

Note 1
MINIMUM CLEARANCE FOR PROPER
OPERATION IS 36 INCHES (914 MM)
FROM WALLS, SHRUBBERY, PRIVACY
FENCES, ETC. MINIMUM CLEARANCE
BETWEEN ADJACENT UNITS IS 72
INCHES (1828 MM)

SSP-PRC002-EN 41
Dimensional
Data (Heat Pump)

Figure DD-4 — TWA200B Heat Pump

All dimensions are in inches and millimeters.

Note 1
MINIMUM CLEARANCE FOR PROPER
OPERATION IS 36 INCHES (914 MM)
FROM WALLS, SHRUBBERY, PRIVACY
FENCES, ETC. MINIMUM CLEARANCE
BETWEEN ADJACENT UNITS IS 72
INCHES (1828 MM)

42 SSP-PRC002-EN
Dimensional
Data (Air Handler)

Figure DD-5 — TWE050A Air Handlers


All dimensions are in inches and millimeters.

Notes:
1. Length, Width, and Height Dimensions do not include 1/2”
(12.7mm) access panel depth.
2. Removable drain pan and attached drain connection may be
installed on either end of unit in either the vertical or horizontal
configuration. Plastic drain pan access plate on the end of unit
opposite drain connection must be removed to slide drain pan out
for cleaning. Access plate must be reinstalled after sliding drain
pan back into unit.
3. If periodic drain pan cleaning is required, allow room for partial
removal of pan on drain connection end of unit.

SSP-PRC002-EN 43
Dimensional
Data (Air Handler)

Figure DD-6 — TWE075A Air Handler


All dimensions are in inches and millimeters.

Notes:
1. Length, Width, and Height Dimensions do not include 1/2”
(12.7mm) access panel depth.
2. Removable drain pan and attached drain connection may be
installed on either end of unit in either the vertical or horizontal
configuration. Plastic drain pan access plate on the end of unit
opposite drain connection must be removed to slide drain pan out
for cleaning. Access plate must be reinstalled after sliding drain
pan back into unit.
3. If periodic drain pan cleaning is required, allow room for partial
removal of pan on drain connection end of unit.

44 SSP-PRC002-EN
Dimensional
Data (Air Handler)

Figure DD-7— TWE100A Air Handler


All dimensions are in inches and millimeters.

Notes:
1. Length, Width, and Height Dimensions do not include 1/2”
(12.7mm) access panel depth.
2. Removable drain pan and attached drain connection may be
installed on either end of unit in either the vertical or horizontal
configuration. Plastic drain pan access plate on the end of unit
opposite drain connection must be removed to slide drain pan out
for cleaning. Access plate must be reinstalled after sliding drain
pan back into unit.
3. If periodic drain pan cleaning is required, allow room for partial
removal of pan on drain connection end of unit.

SSP-PRC002-EN 45
Dimensional
Data (Air Handler)

Figure DD-8— TWE100B Air Handler


All dimensions are in inches and millimeters.

Notes:
1. Length, Width, and Height Dimensions do not include 1/2”
(12.7mm) access panel depth.
2. Removable drain pan and attached drain connection may be
installed on either end of unit in either the vertical or horizontal
configuration. Plastic drain pan access plate on the end of unit
opposite drain connection must be removed to slide drain pan out
for cleaning. Access plate must be reinstalled after sliding drain
pan back into unit.
3. If periodic drain pan cleaning is required, allow room for partial
removal of pan on drain connection end of unit.

46 SSP-PRC002-EN
Dimensional
(Air Handlers)
Data

Figure DD-9— TWE050A, 075A, 100A and TWE100B Air Handler

All dimensions are in inches and millimeters.

Table DD-1 — Air Handler Dimensions — in. (mm)


Model No. AA AB AC AD AE AF AJ AK AL
TWE050A 35 5/8 12 1/16 1 5/8 32 1/4 2 15/16 32 1/4 7 13/16 12 3/8 34 9/16
(905) (306.4) (41.3) (819.2) (74.6) (819.2) (198.4) (314.3) (878)
TWE075A 45 1/8 16 1 11/16 41 15/16 6 5/8 41 3/4 7 16 36 7/8
(1146.2) (406.4) (42.9) (1065.2) (168.3) (1060.5) (177.8) (406.4) (936.6)
TWE100A 61 1/8 16 1 11/16 57 15/16 6 5/8 57 13/16 7 16 36 7/8
(1552.6) (406.4) (42.9) (1471.6) (168.3) (1468.4) (177.8) (406.4) (936.6)
TWE100B 61 1/8 16 1 11/16 57 15/16 6 5/8 57 13/16 7 16 36 7/8
(1552.6) (406.4) (42.9) (1471.6) (168.3) (1468.4) (177.8) (406.4) (936.6)

SSP-PRC002-EN 47
Dimensional
Data (Air Handler)

Figure DD-10— TWE155B Air Handler


All dimensions are in inches and millimeters.

Notes:
1. Length, Width, and Height Dimensions do not include 1/2”
(12.7mm) access panel depth.
2. Removable drain pan and attached drain connection may be
installed on either end of unit in either the vertical or horizontal
configuration. Plastic drain pan access plate on the end of unit
opposite drain connection must be removed to slide drain pan out
for cleaning. Access plate must be reinstalled after sliding drain
pan back into unit.
3. If periodic drain pan cleaning is required, allow room for partial
removal of pan on drain connection end of unit.

48 SSP-PRC002-EN
Dimensional
Data (Air Handlers)

Figure DD-11 — TWE200B Air Handler

All dimensions are in inches and millimeters.

Notes:
1. Length, Width, and Height Dimensions do not include 1/2”
(12.7mm) access panel depth.
2. Removable drain pan and attached drain connection may be
installed on either end of unit in either the vertical or horizontal
configuration. Plastic drain pan access plate on the end of unit
opposite drain connection must be removed to slide drain pan out
for cleaning. Access plate must be reinstalled after sliding drain
pan back into unit.
3. If periodic drain pan cleaning is required, allow room for partial
removal of pan on drain connection end of unit.

SSP-PRC002-EN 49
Dimensional
Data (Air Handlers)

Figure DD-12— TWE155B and 200B Air Handlers

All dimensions are in inches and millimeters.

Table DD-2 — Air Handler Dimensions — in. (mm)


Model No. A B C D E F G H J
TWE155B 77 1/4 (1962.2) 1 3/16 (30.2) 48 (1219.2) 11 7/16 (290.5) 18 (457.2) 3 3/8 (85.7) 35 1/16 (890.6) 73 7/8 (1876.4) 3 3/4 (95.3)
TWE200B 89 1/4 (2267) 1 11/16 (42.9) 50 13/16 (1290.6) 11 1/2 (292.1) 20 1/8 (511.2) 3 1/16 (77.8) 39 1/8 (993.8) 82 7/8 (2105) 4 9/16 (115.9)

Table DD-2— Air Handler Dimensions — in. (mm) (Continued)


Model No. K L M N P Q R S T
TWE155B 35 1/16 (890.6) 2 13/16 (71.4) 18 (457.2) 3 9/16 (90.5) 2 7/8 (73) 35 1/16 (890.6) 3 3/4 (95.3) 35 1/16 (890.6) 73 3/8 (1863.7)
TWE200B 39 1/8 (993.8) 4 7/8 (123.8) 20 (508) 3 (76.2) 4 13/16 (122.2) 39 1/8 (993.8) 4 9/16 (115.9) 39 1/8 (993.8) 82 7/8 (2105)

50 SSP-PRC002-EN
Dimensional
Data (Accessories)

Figure DD-13— Electric Heater for TWE050, 075, 100 Air Handlers

All dimensions are in inches and millimeters.

Figure DD-14 — Electric Heater for TWE155 and 200 Air Handlers

SSP-PRC002-EN 51
Mechanical
Specifications

Heat Pumps Refrigeration System — Dual


Compressor
shall be 24-volt control circuit which
includes fusing and control transformer.
General Units shall provide external location for
TWA155B,TWA200B units shall have
Unit shall be assembled on heavy gauge mounting a fused disconnect device.
two separate and independent
steel mounting/lifting rails and shall be Time delay timers to prevent
weather proofed. Unit shall include a refrigeration circuits. Each refrigeration
circuit shall have an integral subcooling compressors in dual compressor units
hermetic scroll or reciprocating from simultaneous start-up and anti-
circuit. A refrigeration filter drier shall be
compressor(s), plate fin condenser coil, recycle timers are available as optional
fans and motors, controls, and holding provided as standard. Unit shall have
both a liquid line and suction gas line accessories.
charge of nitrogen. Operating Range
service valve with gauge ports. Defrost Controls
shall be between 115° F (46°C) and 50°F
(10°C) in cooling as standard from Unit shall have twoTrane direct drive, Electronic timed initiated, temperature
hermetic scroll compressors with terminated defrost system with choice
factory. Unit shall be UL 1995 listed and
centrifugal oil pump and provide positive of 50, 70, or 90 minute cycle shall be
rated in accordance with ARI Standard
340/360. lubrication to all moving parts. Motor included.Timed override limits defrost
shall be suction gas-cooled and shall cycle to 10 minutes.
Casing
Unit casing shall be constructed of zinc have a voltage utilization range of plus or Low Ambient Operation
minus 10 percent of nameplate voltage. Standard units shall start and operate to
coated, heavy gauge, galvanized steel.
Crankcase heater, and current-sensitive approximately 50°F (10°C) when
Exterior surfaces shall be cleaned,
phosphatized, and finished with a motor overloads shall be included for matched withTrane air handlers and
maximum protection. Scroll type coils. Optional head pressure control
weather-resistant baked enamel finish.
compressor shall provide inherently low accessory permits operation to 0°F
Unit’s surface shall be tested 500 hours
in salt spray test. Unit shall have vibration and noise by having no suction (-17.8°C).
removable end panels which allow and discharge valves. External high and ACCESSORIES
low pressure cutout devices shall be Low Ambient Head Pressure Control —
access to all major components and
controls. provided. Evaporator defrost control This accessory shall modulate the RPM
provided in indoor blower coil shall of unit outdoor fan motor in response
Refrigeration System — Single prevent compressor slugging by
Compressor to outdoor ambient temperatures and
temporarily interrupting compressor liquid line temperature. Accessory
TWA075A,TWA100A units shall have a operation when low evaporator coil provides unit cooling operation to
single refrigeration circuit. Each temperatures are encountered. outdoor temperatures of 0°F (-17.8°C).
refrigeration circuit has an integral Condenser Coil Vibration Isolation Packages —This
subcooling circuit. A refrigeration filter Coils shall be internally finned or smooth
drier, expansion valve, and check valves accessory shall reduce transmission of
bore, 3/8" (10mm) copper tubes noise and vibration to building
shall be provided as standard.The unit mechanically bonded to a configured structures, equipment, and adjacent
shall have both a liquid line and suction aluminum plate fin as standard. Coil
gas line service valve with gauge port. spaces. Packages shall be available in
shall be factory pressure and leak tested either neoprene-in-shear or spring-flex
Unit shall have one direct drive,Trane to 420 psig (2,930 kPa) air pressure. types.
hermetic scroll compressor with Metal grilles with PVC coating for coil
centrifugal oil pump providing positive protection is optional. Time Delay Relay —This accessory
shall prevent compressors in dual
lubrication to moving parts. Motor shall Condenser Fan And Motor(s)
be suction gas-cooled and shall have a compressor unit from coming on line
Direct-drive, statically and dynamically simultaneously.Timer shall be 24-volt,
voltage utilization range of plus or minus balanced, 26 or 28 inch (660 or 711 mm) 60 cycle, with four minute timing
10 percent of nameplate voltage. propeller fan(s) with aluminum blades
Crankcase heater, discharge line period.
and electro-coated steel hubs shall be
thermostat, and current-sensitive motor used in draw-through vertical discharge Anti-Short-Cycle Timer —This
overloads shall be included for position. Either permanently lubricated accessory shall prevent rapid on-off
maximum protection. Scroll type totally enclosed or open construction compressor cycling in light load
compressor shall provide inherently low type motors shall be provided and shall conditions by not allowing compressor
vibration and noise by having no suction have built-in current and thermal to operate for 5-7 minutes upon
and discharge valves. External high and overload protection. Motor(s) shall have shutdown.This accessory shall consist
low pressure cutout devices shall be either ball or sleeve bearing type. of a 24-volt, 60 cycle, solid state timing
provided. Evaporator defrost control device with either 5 or 7 minute fixed-
provided in indoor blower coil unit shall Controls off timing period.
prevent compressor slugging by Heat pump units shall be completely
factory wired with necessary controls
temporarily interrupting compressor
operation when low evaporator coil and contactor pressure lugs or terminal
temperatures are encountered. block for power wiring. Control wiring
52 SSP-PRC002-EN
Mechanical
Specifications

Condenser Coil Guard — Metal grille shall be factory pressure and leak tested three phase. Each 400 volt heater shall
with PVC coating shall be provided to at 375 psig (2586 kPa). Coil is arranged have automatic line break high limit
alleviate coil damage. for draw-through airflow and shall controls.
Black Epoxy Coated Condenser Coil — provide a double sloped condensate Discharge Plenums and Grilles —
This factory installed option is designed drain pan constructed of PVC plastic.The Accessory discharge plenums shall be
to provide corrosion protection of air drain pan shall be removable for available for vertical, free discharge
cooled condenser coils for seacoast cleaning.The condensate drain pan can applications. Plenums shall be
application. The black epoxy coil be installed in any of four positions constructed of heavy-gauge, zinc coated,
protection is a factory applied thermoset allowing for vertical or horizontal galvanized steel finished with baked
vinyl coating, bonded to normal application and providing external enamel to match the air handler unit.
aluminum fin stock. The uniform connections on either side of the unit. Grilles shall be satin finished aluminum
thickness of the bonded vinyl layer Evaporator Fan and have four-way adjustable louvers.
exhibits excellent corrosion protection in Double inlet, double width, forward Return Air Grilles — Accessory return air
salt spray tests performed in accordance curved, centrifugal-type fan(s) with grille shall be provided for vertical front,
with ASTM B177. adjustable belt drive shall be standard. free return applications. Grilles shall be
Thermal overload protection shall be installed in place of the front lower side
Air Handlers standard on motor. Fan and motor
bearings shall be permanently
panel. Grille shall be satin finished
General aluminum with non-adjustable louvers.
lubricated. Oversized motors shall be
Air handler units shall be completely available as an option for high static Mounting Subbase —The accessory
factory assembled including coil, application. All indoor fan motors meet shall be available for vertical floor mount
condensate drain pan, fan motor(s), the U.S. Energy Policy Act of 1992 configurations. Subbase shall be
filters, and controls in an insulated (EPACT). constructed of heavy gauge, zinc coated,
casing that can be applied in either galvanized steel with baked enamel
vertical or horizontal configuration. Unit Controls finish to match air handler unit. Subbase
shall be rated and tested in accordance Magnetic evaporator fan contactor, low is required in the vertical air flow
with ARI standard 340/360. Unit shall be voltage terminal strip, check valve(s), and application for condensate drain
UL listed and labeled in accordance with single point power entry shall be trapping and when isolators are
UL 1995 for indoor blower coil units. included. All necessary controls shall be required.
factory-installed and wired. Evaporator
Casing defrost control shall be included to Vibration Isolators —This accessory
Unit casing shall be constructed of zinc prevent compressor slugging by shall reduce transmission of noise and
coated, heavy gauge, galvanized steel. temporarily interrupting compressor vibration to building structures,
Exterior surfaces shall be cleaned, operation when low evaporator coil equipment, and adjacent spaces.
phosphatized, and finished with a temperatures are encountered. Packages shall be available in either
weather-resistant baked enamel finish. neoprene-in shear or spring-flex types in
Casing shall be completely insulated Filters floor or suspended mountings.
with cleanable, foil faced, fire-retardant, One inch, throw-away filters shall be
standard onTWE050A,TWE075A, Oversized Motors — Field installed
permanent, odorless, glass fiber oversized motors shall be available for
material. All insulation edges shall be TWE100A and TWE120B model air
handlers. Filters shall be accessible from high static pressure applications.
either captured or sealed. Knockouts
shall be provided for unit electrical the side coil access panel. Filter rack can CONTROL OPTIONS
power and refrigerant piping be field converted to two inch capability.
Two inch, throw-away filters shall be Standard Indoor Thermostats —Two
connections. Captive screws shall be stage heating and cooling operation or
standard on all access panels. standard onTWE155B andTWE200B
models. one stage heating and cooling
Refrigeration System thermostats shall be available in either
TheTWE050A,TWE075A,TWE100A units ACCESSORIES manual or automatic changeover.
shall have a single refrigeration circuit Electric Heaters — UL and CSA Programmable Electronic Night Setback
and theTWE100B,TWE155B,TWE200B approved electric heat modules shall be Thermostat —The option shall provide
units shall have dual refrigeration available for installation directly on fan heating setback and cooling setup with 7-
circuits. Each refrigeration circuit is discharge. Electric heaters shall be day programming capability.
controlled by a factory installed thermal available in a wide range of capacities
expansion valve. Outdoor Thermostat —This option
with one or two stage control, single-
point electric power connection, and shall provide staging control of
Evaporator Coil electric heaters based on a set
Configured aluminum fin surface shall terminal strip connections. Electric
outdoor temperature.
be mechanically bonded to 3/8" (10 mm) heater elements shall be constructed of
internally enhanced copper tubing and heavy-duty nickel chromium elements
internally wye connected on 400 volt,

SSP-PRC002-EN 53
Literature Order Number SSP-PRC002-EN
File Number PL-UN-SSP-PRC002-EN-1103
Trane
An American Standard Company Supersedes SS-PRC002-EN 1003
www.trane.com Stocking Location November Publication Electronic Only
For more information contact your Since Trane has a policy of continuous product and product data improvement, it reserves the right to
local office or e-mail us at change design and specifications without notice.
comfort@trane.com

You might also like