32 - 630 AMP
Control Display
The DCR from AMETEK
Solidstate Controls is a
microprocessor-controlled,
thyristor-based system designed
for high-efficiency conversion
of incoming commercial AC
power to clean DC power. It is
used for charging batteries while
supplying power to continuous
DC loads such as inverters.
The rugged solid-state design
utilizes SCR phase control to With the DCR’s Digital Display, you have all the
provide regulated, current- vital system information right at your fingertips.
limited DC power. The DCR The user-friendly display menu provides the
can operate with or without link between operator, all monitoring controls
batteries and is intended for and alarms. Set points for control and alarm
use in UPS systems. The DCR parameters are customer configurable.
can also be used as a stand-
alone device for battery- The Display Features:
charging-only applications. • Adjustable Backlit Status Display
• Latest digital and power • Charger Condition LEDs
electronics technology - AC On
• Reliable industrial design; - Fault
MTBF >205,000 hours - High DC Voltage
• User definable control and - Low DC Voltage
alarm set-points - Charger Fail (Loss of AC Input)
• Simultaneous voltage and
current readings • Soft-touch Menu Scrolling Keypad
• CE safety and EMC • Float and Manual Equalize Controls
standards compliant with LEDs
• UL1012 (UL, cUL) Approved • Lamp Test and Alarm Silence Control
• Vacuum impregnated 1
Consult us for additional sizes
magnetics, 200˚C
• Efficiency up to 95%
General Specifications - Standard Features General Specifications - Optional Features
Design Features Optional Circuit Breakers (Option #)
SCR (Thyristor) based rectifier with double wound isolation transformer 65 kAIC Rated AC Input Breaker (82)
Electronic control, current limiting and voltage regulation DC Output Breaker (10 kAIC) (182)
Floating ground output DC Output Breaker (High kAIC) (183)
Event counter retains up to 64,000 events
Optional Alarms (Option #) (Optional Relay) Notes
Detailed data logging for the last 500 events
Long life LED indicators Charger Fan Fail (120) (120R) With relay
Protected from phase rotation Charger Overload (119) (119R) options (2), (57),
Charger Fuse Blown (67) (67R) (60) and (107)
Standard Protection Devices Pos/Neg to Ground (3) (3R)
AC Input Breaker (14 kAIC Minimum) Charger Output Circuit Breaker open (191) (191R)
DC Output Fuse Additional Options (Option #) Notes
Standard Metering Charger Output Diode (29) Blocking diode
DC Output Voltage Auto-equalize (130) After AC power failure > 5 minutes
DC Charger Current Alarm Relay Test (132) Facilitate testing of the alarms through LCD
screens
Standard Relays
Charger Ripple Filter (59) Extra filtering can be added to the charger
Fault (Common) for lower ripple requirements
Low DC Voltage
Percent Loading (115) Displays the percentage of output current
Standard Indications (Optional Relay) being used as compared to total output
current
AC ‘ON’ Green LED
“Float” Green LED Input Power Metering (111) Optional charger AC input metering for the
Fault (Common) Alarm Red LED LCD Display. (Volts, Amps, Frequency)
DC High Voltage Alarm Red LED Equalize Inhibit (155) External potential free dry contact closure
DC Low Voltage Alarm Red LED input will prevent the charger from going into
Loss of AC Input Alarm Red LED 192R equalize mode.
“Equalize” Amber LED 185R Dual Charger Current Limit Control (186) Optional external input
Control Modes Battery Temperature Compensation (108) DC battery float voltage is adjusted based on
room ambient temperature over a range of
6 Pulse Standard or 12 Pulse Optional
32°F and 104°F (0°C to +40°C)
Stand Alone or Parallel (Capacity and/or Redundancy)
Latching Alarms (28) Requires manual reset
Display Default Alarms (Optional Relay)
Additional Relays Additional relay contacts (maximum of 15
AC Input Available allowed)
Low DC Voltage
Charger Loss of Communications General Specifications - Performance
Charger Board Reset
Electrical Specifications
AC Power Supply Fail
AC Input Failure AC Input Available Voltages: 3-phase: 208, 380, 480, 600
High DC Shutdown (± 10%)
System Reset Frequency: 50 or 60 Hz (± 5%)
System Over Temperature DC Output Nominal voltages: 110, 120, 220, 240 VDC
DC Power Supply Fail (± 0.5% Float, ± 1.0% Equalize)
Charger Bridge Over Temperature 193R
Ripple (RMS) Unfiltered Units: < 2% with battery connected
Charger Failure 69R
Filtered: 0.1% with battery connected
High DC Voltage 5R
Mechanical Specifications
General Specifications - Optional Features Enclosure NEMA1 (IP20), 14 GA (2 mm) steel with
Option Packages (Option #) LCD Indicators hinged front access door and drip shield
Cable Entry Top or Bottom
Communications Package (187) MODBUS RTU
MODBUS over Ethernet Finish Standard Powder Coat ANSI 61, Light Gray
Ethernet Web-page Cooling Convection cooling up to 160 A Output
Capability Current, 200 A and larger has fans
MODBUS TCP-IP
Optional Mechanical Features (Option #)
Consult us for additional
Communications options Lifting Eye Bolts (105) Key-lockable Enclosure (159)
Pad Lockable Breakers (93) IP-21 Rated Cabinet w/optional
AC Input Monitoring Package (188) AC Input CB Open Drip Shield (65)
AC Input Failure
Low AC Input 20% Spare Alarm Terminals (96) DC Rated Alarm Contacts (72)
High AC Input Conformal Coating of PC Boards (127) Space Heater (88)
Battery Monitoring Package (227) Battery Test Fungus/moisture spay (70) Labeling in Other Languages (158)
Battery Time Remaining (133)
Battery I & V Metering Environmental
Battery Current Limit
Audible Noise 65-72 dB(A) at 3 feet (1 meter) at half
Battery Discharging
equipment height
Optional Relays (Option #) Notes Operating Temp 32°F to 104°F (-0°C to +40°C), To 55°C with
AC Input Failure (26R) derate
Low AC Input (68R) Available When Storage Temp -4°F to 158°F (-20°C to 70°C)
AC Input CB Open (101R) Package 188 is Selected Operating Humidity Up to 95% (Non-condensing)
High AC Input (124R)
Altitude 10,000 feet (3,048 meters) without derate
Battery Discharging (197R) Cabinet Type Dimensions Inches Millimeters
Available When FS11 HxWxD 48 x 24 x 24 1,220 x 610 x 610
Package 227 is Selected
FS2 HxWxD 79 x 32 x 36 2,007 x 813 x 915
1
The drip shield adds 5 in (127 mm) to the height
Current Limit: 100 = 100% Current Limit, 115 = 115% Current Limit