DECS-150 Digital Excitation Control System

Overview
The DECS-150 Digital Excitation Control System is a high powered, low-cost,
and environmentally rugged solution for controlling the output of rotary
excited synchronous generators. The DECS-150 is perfect for machines that
are paralleled to other generators and/or the utility system. It is ideal for
distributed generation, cogeneration, and peak shaving applications.

Features Benefits
• Microprocessor based • Microprocessor-based design provides high functionality and
• 0.25% voltage regulation accuracy performance.

• 0.5% accuracy up to 40% Total Harmonic Distortion (THD) • Powerful 7-amp, PWM power stage provides high field forcing for
(harmonics associated with six-thyristor load) increased system response.

• 63 Vdc and 125 Vdc @ 10 Adc pulse-width-modulated (PWM) output • THD-tolerant design offers reliable operation with nonlinear loads.

• Capable of 10 Adc continuous field current output when system • Integrated generator and exciter protection ensure proper system
temperature is 55°C (131°F) or below operation.

• Load Sharing over Ethernet • Rugged, potted design for exceptional reliability in the harshest
environments.
• Auto tuning feature with two PID stability groups
• Auto tuning allows for easier commissioning, saving time and
• Var/PF control money.
• Exciter Diode Monitor (EDM) • External Autotracking provides redundancy and more reliable
• Overexcitation limiting system design.
• Underexcitation limiting • Grid code settings provide compatibility with grid code compliant
systems.
• Stator current limiting
• Voltage matching
• Manual mode (field current regulation)
• Paralleling input from 1-amp or 5-amp CT secondaries
• Nominal sensing inputs of 120, 240, 480, and 600 Vac
• Power input from 50/60 Hz shunt connection or permanent magnet
generator (PMG) operating at 50 to 500 Hz
• Integrated protection functions including Loss of Sensing and Transfer
to Manual
• LED annunciation of operating conditions
• Ethernet communications with Modbus® TCP
• Set up via PC using BESTCOMSPlus® software (included)
• Customizable logic in BESTlogic™Plus
• IP54 rating when rear-mounted USB option is selected
Figure 1 - DECS-150 Connection Diagram for a Typical Application

For additional information visit: www.basler.com SZT-5 (04-19)


DECS-150 Digital Excitation Control System

Specifications
AC Operating Power and DC Operating Power Generator Current Sensing Agency/Certification
All Styles Configuration: 1-phase or 3-phase with UL recognized (evaluated to UL 6200), CSA certified,
Full Load Continuous Current: 10 A at 55°C (131°F) separate input for cross- EAC certified, CE EMC, LVD, and RoHS compliant,
7 A at 70°C (158°F) current compensation maritime recognitions by BV, DNV•GL, and ABS
Power Input Configuration: 1-phase and 3-phase Nominal Current: 1 Aac or 5 Aac Environmental
Power Input Frequency: dc, 50 to 500 Hz Frequency: 50/60 Hz Operating Temperature
63 Vdc Burden with 1 Aac Sensing: <0.1 VA 10 A Continuous: –40°C to 55°C (–40°F to 131°F)
Nominal Input Voltage: 120 Vac, 125 Vdc Burden with 5 Aac Sensing: <0.3 VA 7 A Continuous: –40°C to 70°C (–40°F to 158°F)
Full Load Continuous Voltage: 63 Vdc Storage Temperature: –40°C to 85°C (–40°F to 185°F)
Inputs and Outputs
Minimum Field Resistance: 9Ω Humidity: MIL-STD-705B, Method 711-1C
Contact Inputs: 8 programmable
10-Second Forcing: 100 Vdc, 11 Adc Salt Fog: IEC 60068-2-11
Type: Dry contact
125 Vdc Shock: Withstands 30 G in 3
Interrogation Voltage: 12 Vdc
Nominal Input Voltage: 240 Vac, 250 Vdc perpendicular planes
Auxiliary Inputs: 1
Full Load Continuous Voltage: 125 Vdc Vibration: 5 G for 3 hours from 18 to 2,000 Hz
Current Input: 4 to 20 mAdc
Minimum Field Resistance: 18 Ω Transients: EN61000-4-4
Voltage Input: –10 to +10 Vdc
10-Second Forcing: 200 Vdc, 11 Adc Static Discharge: EN61000-4-2
Output Contacts: 2 programmable
Generator and Bus Voltage Sensing 1 watchdog Physical
Configuration: 1-phase or 1 breaker shunt trip Weight: 3.95 lb (1.79 kg)
3-phase–3-wire Rating: 7 A at 24 Vdc/240 Vac Dimensions (WxHxD): 6.41 x 11.88 x 3.23 inches
50 Hz Voltage Ranges: 100 Vac ±10% (163 x 302 x 82 mm)
Communication
200 Vac ±10%
USB: USB type B port (front
400 Vac ±10% or rear panel optional) For complete specifications, download the instruction
60 Hz Voltage Ranges: 120 Vac ±10% manual at www.basler.com.
Ethernet: RJ45 jack (rear panel)
240 Vac ±10% 10BASE-T/100BASE-TX
480 Vac ±10% (copper), Modbus® TCP
600 Vac ±10% CAN Bus: External Autotracking
Frequency: 50/60 Hz nominal Related Products
Burden: <1 VA per phase
BE1-11g Generator Protection System
Combines with the DECS-150 to offer a complete
generator control and protection system.
ES Series Protection Relays
Style Chart A wide range of cost-saving options to simplify
industrial application protection.
DECS-250 Digital Excitation Control System
Provides precise voltage, var and Power Factor
regulation, and exceptional system response, plus
generator and motor protection.
DGC-2020 Digital Genset Controller
An advanced genset control system with extensive
functionality and flexibility.
DGC-2020ES Digital Genset Controller
The total system solution for emergency and stand
alone generator set applications.
DGC-2020HD Digital Genset Controller
An advanced, but rugged genset control system
designed for paralleling and complex load sharing
schemes.

No. 59 Heshun Road Loufeng District (N), Accessories


Suzhou Industrial Park, 215122, Suzhou, P.R.China
ICRM-7, ICRM-15
Tel +86.512.8227.2888 • Fax +86.512.8227.2887
Protects PWM-type voltage regulators from high
e-mail: chinainfo@basler.com
inrush currents when powered by an independent
source.
12570 Route 143 • Highland, Illinois 62249-1074 USA 111 North Bridge Road #15-06 Peninsula Plaza
Tel +1 618.654.2341 • Fax +1 618.654.2351 Singapore 179098 MVC Manual Voltage Controllers
email: info@basler.com Tel +65 68.44.6445 • Fax +65 68.44.8902 Provides backup manual source for excitation in the
e-mail: singaporeinfo@basler.com event of AVR failure.

For additional information visit: www.basler.com SZT-5 (04-19)