Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

UCM224D - Technical Data Sheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

UCM224D - Technical Data Sheet

UCM224D
SPECIFICATIONS & OPTIONS
TERMINALS & TERMINAL BOX Standard generators are 3-phase reconnectable with 12 ends brought out to the terminals, which are mounted on a cover at the non-drive end of the generator. A sheet steel terminal box contains the AVR and provides ample space for the customers' wiring and gland arrangements. It has removable panels for easy access. SHAFT & KEYS This sophisticated Automatic Voltage Regulator (AVR) is incorporated into the Stamford Permanent Magnet Generator (PMG) control system, and is standard on marine generators of this type. The PMG provides power via the AVR to the main exciter, giving a source of constant excitation power independent of generator output. The main exciter output is then fed to the main rotor, through a full wave bridge, protected by a surge suppressor. The AVR has in-built protection against sustained overexcitation, caused by internal or external faults. This de-excites the machine after a minimum of 5 seconds. An engine relief load acceptance feature can enable full load to be applied to the generator in a single step. If three-phase sensing is required with the PMG system the MX321 AVR must be used. We recommend three-phase sensing for applications with greatly unbalanced or highly non-linear loads. MX321 AVR The most sophisticated of all our AVRs combines all the features of the MX341 with, additionally, threephase rms sensing, for improved regulation and performance. Over voltage protection is built-in and short circuit current level adjustments is an optional facility. WINDINGS & ELECTRICAL PERFORMANCE All generator stators are wound to 2/3 pitch. This eliminates triplen (3rd, 9th, 15th ) harmonics on the voltage waveform and is found to be the optimum design for trouble-free supply of non-linear loads. The 2/3 pitch design avoids excessive neutral currents sometimes seen with higher winding pitches, when in parallel with the mains. A fully connected damper winding reduces oscillations during paralleling. This winding, with the 2/3 pitch and carefully selected pole and tooth designs, ensures very low waveform distortion. All generator rotors are dynamically balanced to better than BS6861:Part 1 Grade 2.5 for minimum vibration in operation. Two bearing generators are balanced with a half key. INSULATION/IMPREGNATION The insulation system is class 'H'. All wound components are impregnated with materials and processes designed specifically to provide the high build required for static windings and the high mechanical strength required for rotating components. QUALITY ASSURANCE Generators are manufactured using production procedures having a quality assurance level to BS EN ISO 9001. The stated voltage regulation may not be maintained in the presence of certain radio transmitted signals. Any change in performance will fall within the limits of Criteria 'B' of EN 61000-6-2:2001. At no time will the steady-state voltage regulation exceed 2%.

STANDARDS Marine generators may be certified to Lloyds, DnV, Bureau Veritas, ABS, Germanischer-Lloyd or RINA. Other standards and certifications can be considered on request. VOLTAGE REGULATORS MX341 AVR - STANDARD

NB Continuous development of our products entitles us to change specification details without notice, therefore they must not be regarded as binding. Front cover drawing typical of product range.

UCM224D
WINDING 311
CONTROL SYSTEM A.V.R. VOLTAGE REGULATION SUSTAINED SHORT CIRCUIT INSULATION SYSTEM PROTECTION RATED POWER FACTOR STATOR WINDING WINDING PITCH WINDING LEADS STATOR WDG. RESISTANCE ROTOR WDG. RESISTANCE EXCITER STATOR RESISTANCE EXCITER ROTOR RESISTANCE R.F.I. SUPPRESSION WAVEFORM DISTORTION MAXIMUM OVERSPEED BEARING DRIVE END BEARING NON-DRIVE END 1 BEARING WEIGHT COMP. GENERATOR WEIGHT WOUND STATOR WEIGHT WOUND ROTOR WR INERTIA SHIPPING WEIGHTS in a crate PACKING CRATE SIZE 285 kg 86 kg 86.28 kg 0.4216 kgm 307 kg 92 x 57 x 96(cm) 50 Hz TELEPHONE INTERFERENCE COOLING AIR VOLTAGE SERIES STAR VOLTAGE PARALLEL STAR VOLTAGE SERIES DELTA kVA BASE RATING FOR REACTANCE VALUES Xd DIR. AXIS SYNCHRONOUS X'd DIR. AXIS TRANSIENT X''d DIR. AXIS SUBTRANSIENT Xq QUAD. AXIS REACTANCE X''q QUAD. AXIS SUBTRANSIENT XL LEAKAGE REACTANCE X2 NEGATIVE SEQUENCE X0 ZERO SEQUENCE REACTANCES ARE SATURATED T'd TRANSIENT TIME CONST. T''d SUB-TRANSTIME CONST. T'do O.C. FIELD TIME CONST. Ta ARMATURE TIME CONST. SHORT CIRCUIT RATIO 380/220 190/110 220/110 44 2.05 0.16 0.11 0.94 0.12 0.06 0.11 0.07 THF<2% 0.216 m/sec 458 cfm 400/231 200/115 230/115 44 1.85 0.14 0.10 0.85 0.11 0.05 0.11 0.07 415/240 208/120 240/120 44 1.72 0.13 0.09 0.79 0.11 0.05 0.10 0.06 440/254 220/127 254/127 32.7 1.85 0.14 0.10 0.86 0.12 0.05 0.10 0.06 416/240 208/120 240/120 51 2.58 0.19 0.13 1.19 0.12 0.08 0.12 0.08
2

SEPARATELY EXCITED BY P.M.G. MX321 0.5 % MX341 1.0 % With 4% ENGINE GOVERNING

REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7) CLASS H IP23 0.8 DOUBLE LAYER CONCENTRIC TWO THIRDS 12 0.129 Ohms PER PHASE AT 22C SERIES STAR CONNECTED 0.64 Ohms at 22C 21 Ohms at 22C 0.071 Ohms PER PHASE AT 22C BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0% 2250 Rev/Min BALL. 6312-2RS (ISO) BALL. 6309-2RS (ISO) 2 BEARING 290 kg 86 kg 77.9 kg 0.4198 kgm 311 kg 92 x 57 x 96(cm) 60 Hz TIF<50 0.281 m/sec 595 cfm 440/254 220/127 254/127 53.1 2.40 0.17 0.12 1.10 0.11 0.07 0.11 0.07 460/266 230/133 266/133 54.3 2.25 0.17 0.11 1.03 0.10 0.07 0.10 0.07 480/277 240/138 277/138 56.3 2.14 0.16 0.10 0.99 0.10 0.06 0.10 0.06
2

VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED 0.027 s 0.006 s 0.7 s 0.0055 s 1/Xd

50 Hz

UCM224D
Winding 311 THREE PHASE EFFICIENCY CURVES

60 Hz

UCM224D
Winding 311 THREE PHASE EFFICIENCY CURVES

UCM224D
Winding 311 Locked Rotor Motor Starting Curve

50
Hz
30
346V 380V 400V 415V 440V

25

PER CENT TRANSIENT VOLTAGE DIP

20

15

10

0 0 20 40 60 80
LOCKED ROTOR kVA

100

120

140

160

60
Hz
30
380V 416V 440V 460V 480V

25
PER CENT TRANSIENT VOLTAGE DIP

20

15

10

0 0 20 40 60 80 100 120 140 160 180 200


LOCKED ROTOR kVA

UCM224D
Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed Based on star (wye) connection.

50 Hz
CURRENT (Amps)

10000

SYMMETRICAL ASYMMETRICAL

1000

100

10 0.001

0.01

0.1 TIME (secs)

10

Sustained Short Circuit = 230 Amps

60 Hz
CURRENT (Amps)

10000

SYMMETRICAL ASYMMETRICAL

1000

100

10 0.001

0.01

0.1 TIME (secs)

10

Sustained Short Circuit = 275 Amps


Note 1 The following multiplication factors should be used to adjust the values from curve between time 0.001 seconds and the minimum current point in respect of nominal operating voltage : 50Hz
Voltage 380v 400v 415v 440v Factor X 1.00 X 1.07 X 1.12 X 1.18

Note 2 The following multiplication factor should be used to convert the values calculated in accordance with NOTE 1 to those applicable to the various types of short circuit :
3-phase 2-phase L-L 1-phase L-N

60Hz
Voltage 416v 440v 460v 480v Factor X 1.00 X 1.06 X 1.12 X 1.17

The sustained current value is constant irrespective of voltage level

Instantaneous x 1.00 x 0.87 x 1.30 Minimum x 1.00 x 1.80 x 3.20 Sustained x 1.00 x 1.50 x 2.50 Max. sustained duration 10 sec. 5 sec. 2 sec. All other times are unchanged Note 3 Curves are drawn for Star (Wye) connected machines. For other connection the following multipliers should be applied to current values as shown : Parallel Star = Curve current value X 2 Series Delta = Curve current value X 1.732

UCM224D
Winding 311 / 0.8 Power Factor RATINGS
Class - Temp Rise Cont. E - 65/50C 380 190 220 400 200 230 33.5 26.8 89.5 29.9 415 208 240 33.5 26.8 89.6 29.9 440 220 254 25.0 20.0 89.7 28.5 380 190 220 37.5 30.0 89.0 33.7 Cont. B - 70/50C 400 200 230 37.5 30.0 89.2 33.6 415 208 240 37.5 30.0 89.4 33.6 440 220 254 27.3 21.8 89.6 31.3 380 190 220 40.0 32.0 88.7 36.1 Cont. F - 90/50C 400 200 230 40.0 32.0 89.0 36.0 415 208 240 40.0 32.0 89.2 35.9 440 220 254 29.7 23.8 89.5 34.0 Cont. H - 110/50C 380 190 220 44.0 35.2 88.4 39.8 400 200 230 44.0 35.2 88.7 39.7 415 208 240 44.0 35.2 88.9 39.6 440 220 254 32.7 26.2 89.3 37.4 Series Star (V) Parallel Star (V) Series Delta (V)

50
Hz

kVA 33.5 kW 26.8 Efficiency (%) 89.3 kW Input 30.0

60
Hz

Series Star (V) Parallel Star (V) Series Delta (V)

416 208 240

440 220 254 42.0 33.6 89.8 37.4

460 230 266 43.0 34.4 90.0 38.2

480 240 277 43.0 34.4 90.1 38.2

416 208 240 42.0 33.6 89.5 37.5

440 220 254 43.8 35.0 89.7 39.1

460 230 266 46.3 37.0 89.8 41.2

480 240 277 46.3 37.0 90.0 41.2

416 208 240 47.5 38.0 89.1 42.6

440 220 254 50.0 40.0 89.3 44.8

460 230 266 51.3 41.0 89.5 45.9

480 240 277 51.3 41.0 89.8 45.7

416 208 240 51.0 40.8 88.8 45.9

440 220 254 53.1 42.5 89.1 47.7

460 230 266 54.3 43.4 89.4 48.6

480 240 277 56.3 45.0 89.5 50.3

kVA 40.0 kW 32.0 Efficiency (%) 89.6 kW Input 35.7

DIMENSIONS

Barnack Road Stamford Lincolnshire PE9 2NB Tel: 00 44 (0)1780 484000 Fax: 00 44 (0)1780 484100

2006

TD_UCM224D.GB_10.06_05_GB

You might also like