SPECIFICATIONS & OPTIONS
TERMINALS & TERMINAL BOX Standard generators feature a main stator with 6 ends brought out to the terminals, which are mounted on the frame at the non-drive end of the generator. A sheet steel terminal box contains the AVR and provides ample space for the customers' wiring and gland arrangements. It has removable panels for easy access.
STANDARDS Marine generators may be certified to Lloyds, DnV, Bureau Veritas, ABS, Germanischer-Lloyd or RINA. Other standards and certifications can be considered on request.
SHAFT & KEYS This sophisticated Automatic Voltage Regulator (AVR) is incorporated into the Stamford Permanent Magnet Generator (PMG) system and is fitted as standard to generators of this type. The PMG provides power via the AVR to the main exciter, giving a source of constant excitation power independent of generator output. The main exciter output is then fed to the main rotor, through a full wave bridge, protected by a surge suppressor. The AVR has in-built protection against sustained overexcitation, caused by internal or external faults. This de-excites the machine after a minimum of 5 seconds. Over voltage protection is built-in and short circuit current level adjustment is an optional facility. All generator rotors are dynamically balanced to better than BS6861:Part 1 Grade 2.5 for minimum vibration in operation. Two bearing generators are balanced with a half key.
INSULATION/IMPREGNATION The insulation system is class 'H'. All wound components are impregnated with materials and processes designed specifically to provide the high build required for static windings and the high mechanical strength required for rotating components.
WINDINGS & ELECTRICAL PERFORMANCE All generator stators are wound to 2/3 pitch. This eliminates triplen (3rd, 9th, 15th ) harmonics on the voltage waveform and is found to be the optimum design for trouble-free supply of non-linear loads. The 2/3 pitch design avoids excessive neutral currents sometimes seen with higher winding pitches, when in parallel with the mains. A fully connected damper winding reduces oscillations during paralleling. This winding, with the 2/3 pitch and carefully selected pole and tooth designs, ensures very low waveform distortion.
QUALITY ASSURANCE Generators are manufactured using production procedures having a quality assurance level to BS EN ISO 9001. The stated voltage regulation may not be maintained in the presence of certain radio transmitted signals. Any change in performance will fall within the limits of Criteria 'B' of EN 61000-6-2:2001. At no time will the steady-state voltage regulation exceed 2%.
NB Continuous development of our products entitles us to change specification details without notice, therefore they must not be regarded as binding. Front cover drawing typical of product range.
HCM634J
WINDING 312
CONTROL SYSTEM A.V.R. VOLTAGE REGULATION SUSTAINED SHORT CIRCUIT INSULATION SYSTEM PROTECTION RATED POWER FACTOR STATOR WINDING WINDING PITCH WINDING LEADS STATOR WDG. RESISTANCE ROTOR WDG. RESISTANCE EXCITER STATOR RESISTANCE EXCITER ROTOR RESISTANCE R.F.I. SUPPRESSION WAVEFORM DISTORTION MAXIMUM OVERSPEED BEARING DRIVE END BEARING NON-DRIVE END 1 BEARING WEIGHT COMP. GENERATOR WEIGHT WOUND STATOR WEIGHT WOUND ROTOR WR INERTIA SHIPPING WEIGHTS in a crate PACKING CRATE SIZE 2279 kg 1120 kg 962 kg 22.9287 kgm 2328 kg 183 x 92 x 140(cm) 50 Hz TELEPHONE INTERFERENCE COOLING AIR VOLTAGE STAR VOLTAGE DELTA 380/220 220 THF<2% 1.614 m/sec 3420 cfm 400/231 230 850 415/240 240 870 440/254 254 870 416/240 240 1031
2
REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7) CLASS H IP23 0.8 DOUBLE LAYER LAP TWO THIRDS 6 0.0022 Ohms PER PHASE AT 22C STAR CONNECTED 2.09 Ohms at 22C 17 Ohms at 22C 0.079 Ohms PER PHASE AT 22C BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0% 2250 Rev/Min BALL. 6224 (ISO) BALL. 6317 (ISO) 2 BEARING 2300 kg 1120 kg 916 kg 22.3814 kgm2 2329 kg 183 x 92 x 140(cm) 60 Hz TIF<50 1.961 m/sec 4156 cfm 440/254 254 1063 460/266 266 1113 480/277 277 1150
kVA BASE RATING FOR 830 REACTANCE VALUES Xd DIR. AXIS SYNCHRONOUS 2.51 X'd DIR. AXIS TRANSIENT 0.20 X''d DIR. AXIS SUBTRANSIENT 0.14 Xq QUAD. AXIS REACTANCE 1.48 X''q QUAD. AXIS SUBTRANSIENT 0.17 0.07 XL LEAKAGE REACTANCE 0.17 X2 NEGATIVE SEQUENCE 0.02 X0 ZERO SEQUENCE REACTANCES ARE SATURATED T'd TRANSIENT TIME CONST. T''d SUB-TRANSTIME CONST. T'do O.C. FIELD TIME CONST. Ta ARMATURE TIME CONST. SHORT CIRCUIT RATIO
2.32 2.21 1.97 3.13 2.88 2.76 2.62 0.19 0.17 0.16 0.25 0.23 0.22 0.21 0.13 0.12 0.10 0.17 0.16 0.15 0.14 1.37 1.31 1.16 1.84 1.69 1.62 1.54 0.16 0.16 0.14 0.22 0.20 0.20 0.19 0.07 0.07 0.06 0.09 0.09 0.08 0.08 0.16 0.16 0.14 0.22 0.20 0.20 0.19 0.02 0.02 0.02 0.03 0.03 0.03 0.03 VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED 0.185 s 0.025 s 3.03 s 0.046 s 1/Xd
50 Hz
HCM634J
Winding 312 THREE PHASE EFFICIENCY CURVES
60 Hz
HCM634J
Winding 312 THREE PHASE EFFICIENCY CURVES
HCM634J
Winding 312 Locked Rotor Motor Starting Curve
50
Hz
30
346V 380V 400V 415V 440V
25
20
15
10
0 0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800
LOCKED ROTOR kVA
60
Hz
30
380V 416V 440V 460V 480V
25
20
15
10
0 0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200
LOCKED ROTOR kVA
HCM634J
Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed Based on star (wye) connection.
50 Hz
100000
CURRENT (Amps)
SYMMETRICAL ASYMMETRICAL
10000
1000 0.001
0.01
10
60 Hz
100000
SYMMETRICAL ASYMMETRICAL
CURRENT (Amps)
10000
1000 0.001
0.01
0.1
TIME (secs)
10
Note 2 The following multiplication factor should be used to convert the values calculated in accordance with NOTE 1 to those applicable to the various types of short circuit :
3-phase 2-phase L-L 1-phase L-N x 1.30 x 3.20 x 2.50 2 sec.
60Hz
Voltage 416v 440v 460v 480v Factor X 1.00 X 1.06 X 1.12 X 1.17
Instantaneous x 1.00 x 0.87 Minimum x 1.00 x 1.80 Sustained x 1.00 x 1.50 Max. sustained duration 10 sec. 5 sec. All other times are unchanged Note 3
Curves are drawn for Star (Wye) connected machines. For Delta connection the following multiplier should be used: Delta = Curve current X 1.732
HCM634J
Winding 312 / 0.8 Power Factor RATINGS
Class - Temp Rise Cont. E - 65/50C 380 220 680 544 400 230 690 552 95.8 576 415 240 710 568 95.8 593 440 254 710 568 95.8 593 380 220 735 588 95.6 615 Cont. B - 70/50C 400 230 750 600 95.7 627 415 240 760 608 95.7 635 440 254 760 608 95.8 635 380 220 810 648 95.5 679 Cont. F - 90/50C 400 230 830 664 95.6 695 415 240 850 680 95.6 711 440 254 850 680 95.7 711 Cont. H - 110/50C 380 220 830 664 95.5 695 400 230 850 680 95.5 712 415 240 870 696 95.6 728 440 254 870 696 95.7 727
50
Hz
60
Hz
DIMENSIONS
Barnack Road Stamford Lincolnshire PE9 2NB Tel: 00 44 (0)1780 484000 Fax: 00 44 (0)1780 484100
2006