HCM434E - Technical Data Sheet

HCM434E
SPECIFICATIONS & OPTIONS
TERMINALS & TERMINAL BOX Standard generators are 3-phase reconnectable with 12 ends brought out to the terminals, which are mounted on a cover at the non-drive end of the generator. A sheet steel terminal box contains the AVR and provides ample space for the customers' wiring and gland arrangements. It has removable panels for easy access. SHAFT & KEYS All generator rotors are dynamically balanced to better than BS6861:Part 1 Grade 2.5 for minimum vibration in operation. Two bearing generators are balanced with a half key. INSULATION/IMPREGNATION The insulation system is class 'H'. All wound components are impregnated with materials and processes designed specifically to provide the high build required for static windings and the high mechanical strength required for rotating components. QUALITY ASSURANCE Generators are manufactured using production procedures having a quality assurance level to BS EN ISO 9001. The stated voltage regulation may not be maintained in the presence of certain radio transmitted signals. Any change in performance will fall within the limits of Criteria 'B' of EN 61000-6 2:2001. At no time will the steady-state voltage regulation exceed 2%

STANDARDS Marine generators may be certified to Lloyds, DnV, Bureau Veritas, ABS, Germanischer-Lloyd or RINA. Other standards and certifications can be considered on request. VOLTAGE REGULATORS MX341 AVR - STANDARD This sophisticated Automatic Voltage Regulator (AVR) is incorporated into the Stamford Permanent Magnet Generator (PMG) control system, and is standard on marine generators of this type. The PMG provides power via the AVR to the main exciter, giving a source of constant excitation power independent of generator output. The main exciter output is then fed to the main rotor, through a full wave bridge, protected by a surge suppressor. The AVR has in-built protection against sustained over-excitation, caused by internal or external faults. This de-excites the machine after a minimum of 5 seconds. An engine relief load acceptance feature can enable full load to be applied to the generator in a single step. If three-phase sensing is required with the PMG system the MX321 AVR must be used. We recommend three-phase sensing for applications with greatly unbalanced or highly non-linear loads. MX321 AVR The most sophisticated of all our AVRs combines all the features of the MX341 with, additionally, threephase rms sensing, for improved regulation and performance. Over voltage protection is built-in and short circuit current level adjustments is an optional facility. WINDINGS & ELECTRICAL PERFORMANCE All generator stators are wound to 2/3 pitch. This eliminates triplen (3rd, 9th, 15th ) harmonics on the voltage waveform and is found to be the optimum design for trouble-free supply of non-linear loads. The 2/3 pitch design avoids excessive neutral currents sometimes seen with higher winding pitches, when in parallel with the mains. A fully connected damper winding reduces oscillations during paralleling. This winding, with the 2/3 pitch and carefully selected pole and tooth designs, ensures very low waveform distortion.

NB Continuous development of our products entitles us to change specification details without notice, therefore they must not be regarded as binding. Front cover drawing typical of product range.

HCM434E
WINDING 311
CONTROL SYSTEM A.V.R. VOLTAGE REGULATION SUSTAINED SHORT CIRCUIT INSULATION SYSTEM PROTECTION RATED POWER FACTOR STATOR WINDING WINDING PITCH WINDING LEADS STATOR WDG. RESISTANCE ROTOR WDG. RESISTANCE EXCITER STATOR RESISTANCE EXCITER ROTOR RESISTANCE R.F.I. SUPPRESSION WAVEFORM DISTORTION MAXIMUM OVERSPEED BEARING DRIVE END BEARING NON-DRIVE END 1 BEARING WEIGHT COMP. GENERATOR WEIGHT WOUND STATOR WEIGHT WOUND ROTOR WR INERTIA SHIPPING WEIGHTS in a crate PACKING CRATE SIZE 1024 kg 470 kg 400 kg 4.6331 kgm 1095 kg 155 x 87 x 107(cm) 50 Hz TELEPHONE INTERFERENCE COOLING AIR VOLTAGE SERIES STAR VOLTAGE PARALLEL STAR VOLTAGE SERIES DELTA 380/220 190/110 220/110 THF<2% 0.80 m/sec 1700 cfm 400/231 200/115 230/115 295 415/240 208/120 240/120 295 440/254 220/127 254/127 295 416/240 208/120 240/120 340
2

SEPARATELY EXCITED BY P.M.G. MX321 0.5 % MX341 1.0 % With 4% ENGINE GOVERNING

REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7) CLASS H IP23 0.8 DOUBLE LAYER LAP TWO THIRDS 12 0.009 Ohms PER PHASE AT 22C SERIES STAR CONNECTED 1.19 Ohms at 22C 18 Ohms at 22C 0.068 Ohms PER PHASE AT 22C BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0% 2250 Rev/Min BALL. 6317 (ISO) BALL. 6314 (ISO) 2 BEARING 1030 kg 470 kg 377 kg 4.4343 kgm2 1100 kg 155 x 87 x 107(cm) 60 Hz TIF<50 0.99 m/sec 2100 cfm 440/254 220/127 254/127 350 460/266 230/133 266/133 365 480/277 240/138 277/138 370

kVA BASE RATING FOR 295 REACTANCE VALUES Xd DIR. AXIS SYNCHRONOUS 2.53 X'd DIR. AXIS TRANSIENT 0.17 X''d DIR. AXIS SUBTRANSIENT 0.12 Xq QUAD. AXIS REACTANCE 2.17 X''q QUAD. AXIS SUBTRANSIENT 0.30 0.06 XL LEAKAGE REACTANCE 0.20 X2 NEGATIVE SEQUENCE 0.08 X0 ZERO SEQUENCE REACTANCES ARE SATURATED T'd TRANSIENT TIME CONST. T''d SUB-TRANSTIME CONST. T'do O.C. FIELD TIME CONST. Ta ARMATURE TIME CONST. SHORT CIRCUIT RATIO

2.29 2.12 1.89 2.95 2.71 2.59 2.41 0.15 0.14 0.13 0.18 0.16 0.16 0.15 0.11 0.10 0.09 0.13 0.12 0.11 0.10 1.96 1.82 1.62 2.48 2.28 2.18 2.03 0.27 0.25 0.22 0.35 0.32 0.31 0.28 0.05 0.05 0.04 0.07 0.06 0.06 0.06 0.18 0.17 0.15 0.24 0.22 0.21 0.19 0.07 0.07 0.06 0.09 0.08 0.07 0.07 VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED 0.08s 0.019s 1.7s 0.018s 1/Xd

50 Hz

HCM434E
Winding 311 THREE PHASE EFFICIENCY CURVES

60 Hz

HCM434E
Winding 311 THREE PHASE EFFICIENCY CURVES

HCM434E
Winding 311 Locked Rotor Motor Starting Curve

50
Hz
30
346V 380V 400V 415V 440V

25

PER CENT TRANSIENT VOLTAGE DIP .

20

15

10

0 0 200 400 600


LOCKED ROTOR kVA

800

1000

1200

60
Hz
30
380V 416V 440V 460V 480V

25

PER CENT TRANSIENT VOLTAGE DIP .

20

15

10

0 0 200 400 600


LOCKED ROTOR kVA

800

1000

1200

HCM434E
Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed Based on star (wye) connection.

50 Hz

10000

SYMMETRICAL ASYMMETRICAL

CURRE NT (Am ps)

1000

100 0.001

0.01

TIME (secs)

0.1

10

Sustained Short Circuit = 1,500 Amps

60 Hz

10000

SYMMETRICAL ASYMMETRICAL

CURRENT (Am ps)

1000

100 0.001

0.01

TIME (secs)

0.1

10

Sustained Short Circuit = 1,600 Amps


Note 1 The following multiplication factors should be used to adjust the values from curve between time 0.001 seconds and the minimum current point in respect of nominal operating voltage : 50Hz
Voltage 380v 400v 415v 440v Factor X 1.00 X 1.05 X 1.10 X 1.16

Note 2 The following multiplication factor should be used to convert the values calculated in accordance with NOTE 1 to those applicable to the various types of short circuit :
3-phase 2-phase L-L 1-phase L-N

60Hz
Voltage 416v 440v 460v 480v Factor X 1.00 X 1.06 X 1.10 X 1.15

The sustained current value is constant irrespective of voltage level

Instantaneous x 1.00 x 0.87 x 1.30 Minimum x 1.00 x 1.80 x 3.20 Sustained x 1.00 x 1.50 x 2.50 Max. sustained duration 10 sec. 5 sec. 2 sec. All other times are unchanged Note 3 Curves are drawn for Star (Wye) connected machines. For other connection the following multipliers should be applied to current values as shown : Parallel Star = Curve current value X 2 Series Delta = Curve current value X 1.732

HCM434E
Winding 311 / 0.8 Power Factor RATINGS
Class - Temp Rise Cont. E - 65/50C 380 190 220 230 184 400 200 230 230 184 94.5 195 415 208 240 230 184 94.6 195 440 220 254 230 184 94.5 195 380 190 220 240 192 94.4 203 Cont. B - 70/50C 400 200 230 240 192 94.5 203 415 208 240 240 192 94.5 203 440 220 254 240 192 94.5 203 380 190 220 275 220 94.2 234 Cont. F - 90/50C 400 200 230 275 220 94.3 233 415 208 240 275 220 94.4 233 440 220 254 275 220 94.4 233 Cont. H - 110/50C 380 190 220 295 236 93.9 251 400 200 230 295 236 94.1 251 415 208 240 295 236 94.2 251 440 220 254 295 236 94.3 250 Series Star (V) Parallel Star (V) Series Delta (V) kVA kW

50
Hz

Efficiency (%) 94.5 kW Input 195

60
Hz

Series Star (V) Parallel Star (V) Series Delta (V) kVA kW

416 208 240 265 212

440 220 254 275 220 94.5 233

460 230 266 285 228 94.5 241

480 240 277 290 232 94.6 245

416 208 240 275 220 94.4 233

440 220 254 285 228 94.5 241

460 230 266 295 236 94.5 250

480 240 277 305 244 94.5 258

416 208 240 315 252 94.2 268

440 220 254 325 260 94.3 276

460 230 266 340 272 94.3 288

480 240 277 345 276 94.4 292

416 208 240 340 272 94.0 289

440 220 254 350 280 94.1 298

460 230 266 365 292 94.2 310

480 240 277 370 296 94.2 314

Efficiency (%) 94.4 kW Input 225

DIMENSIONS

Barnack Road Stamford Lincolnshire PE9 2NB Tel: 00 44 (0)1780 484000 Fax: 00 44 (0)1780 484100

2006

TD_HCM434E.GB_10.06_04_GB