HCM434E - Technical Data Sheet

HCM434E
SPECIFICATIONS & OPTIONS

STANDARDS TERMINALS & TERMINAL BOX


Marine generators may be certified to Lloyds, DnV, Standard generators are 3-phase reconnectable
Bureau Veritas, ABS, Germanischer-Lloyd or RINA. with 12 ends brought out to the terminals, which are
Other standards and certifications can be considered mounted on a cover at the non-drive end of the
on request. generator. A sheet steel terminal box contains the
AVR and provides ample space for the customers'
VOLTAGE REGULATORS wiring and gland arrangements. It has removable
panels for easy access.
MX341 AVR - STANDARD
This sophisticated Automatic Voltage Regulator (AVR) SHAFT & KEYS
is incorporated into the Stamford Permanent Magnet All generator rotors are dynamically balanced to
Generator (PMG) control system, and is standard on better than BS6861:Part 1 Grade 2.5 for minimum
marine generators of this type. vibration in operation. Two bearing generators are
The PMG provides power via the AVR to the main balanced with a half key.
exciter, giving a source of constant excitation power
independent of generator output. The main exciter INSULATION/IMPREGNATION
output is then fed to the main rotor, through a full wave The insulation system is class 'H'.
bridge, protected by a surge suppressor. The AVR has All wound components are impregnated with
in-built protection against sustained over-excitation, materials and processes designed specifically to
caused by internal or external faults. This de-excites provide the high build required for static windings
the machine after a minimum of 5 seconds. and the high mechanical strength required for
An engine relief load acceptance feature can enable rotating components.
full load to be applied to the generator in a single step.
If three-phase sensing is required with the PMG QUALITY ASSURANCE
system the MX321 AVR must be used. Generators are manufactured using production
We recommend three-phase sensing for applications procedures having a quality assurance level to BS
with greatly unbalanced or highly non-linear loads. EN ISO 9001.

MX321 AVR The stated voltage regulation may not be


The most sophisticated of all our AVRs combines all maintained in the presence of certain radio
the features of the MX341 with, additionally, three- transmitted signals. Any change in performance
phase rms sensing, for improved regulation and will fall within the limits of Criteria 'B' of EN 61000-6
performance. 2:2001. At no time will the steady-state voltage
Over voltage protection is built-in and short circuit regulation exceed 2%
current level adjustments is an optional facility.

WINDINGS & ELECTRICAL PERFORMANCE


All generator stators are wound to 2/3 pitch. This
eliminates triplen (3rd, 9th, 15th …) harmonics on the
voltage waveform and is found to be the optimum
design for trouble-free supply of non-linear loads. The
2/3 pitch design avoids excessive neutral currents
sometimes seen with higher winding pitches, when in NB Continuous development of our products
parallel with the mains. A fully connected damper entitles us to change specification details without
winding reduces oscillations during paralleling. This notice, therefore they must not be regarded as
winding, with the 2/3 pitch and carefully selected pole binding.
and tooth designs, ensures very low waveform
distortion. Front cover drawing typical of product range.

2
HCM434E
WINDING 311
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.
A.V.R. MX321 MX341
VOLTAGE REGULATION ± 0.5 % ± 1.0 % With 4% ENGINE GOVERNING
SUSTAINED SHORT CIRCUIT REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7)

INSULATION SYSTEM CLASS H


PROTECTION IP23
RATED POWER FACTOR 0.8
STATOR WINDING DOUBLE LAYER LAP
WINDING PITCH TWO THIRDS
WINDING LEADS 12
STATOR WDG. RESISTANCE 0.009 Ohms PER PHASE AT 22°C SERIES STAR CONNECTED
ROTOR WDG. RESISTANCE 1.19 Ohms at 22°C
EXCITER STATOR RESISTANCE 18 Ohms at 22°C
EXCITER ROTOR RESISTANCE 0.068 Ohms PER PHASE AT 22°C
R.F.I. SUPPRESSION BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others
WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%
MAXIMUM OVERSPEED 2250 Rev/Min
BEARING DRIVE END BALL. 6317 (ISO)
BEARING NON-DRIVE END BALL. 6314 (ISO)
1 BEARING 2 BEARING
WEIGHT COMP. GENERATOR 1024 kg 1030 kg
WEIGHT WOUND STATOR 470 kg 470 kg
WEIGHT WOUND ROTOR 400 kg 377 kg
2
WR² INERTIA 4.6331 kgm 4.4343 kgm2
SHIPPING WEIGHTS in a crate 1095 kg 1100 kg
PACKING CRATE SIZE 155 x 87 x 107(cm) 155 x 87 x 107(cm)
50 Hz 60 Hz
TELEPHONE INTERFERENCE THF<2% TIF<50
COOLING AIR 0.80 m³/sec 1700 cfm 0.99 m³/sec 2100 cfm
VOLTAGE SERIES STAR 380/220 400/231 415/240 440/254 416/240 440/254 460/266 480/277
VOLTAGE PARALLEL STAR 190/110 200/115 208/120 220/127 208/120 220/127 230/133 240/138
VOLTAGE SERIES DELTA 220/110 230/115 240/120 254/127 240/120 254/127 266/133 277/138
kVA BASE RATING FOR
295 295 295 295 340 350 365 370
REACTANCE VALUES
Xd DIR. AXIS SYNCHRONOUS 2.53 2.29 2.12 1.89 2.95 2.71 2.59 2.41
X'd DIR. AXIS TRANSIENT 0.17 0.15 0.14 0.13 0.18 0.16 0.16 0.15
X''d DIR. AXIS SUBTRANSIENT 0.12 0.11 0.10 0.09 0.13 0.12 0.11 0.10
Xq QUAD. AXIS REACTANCE 2.17 1.96 1.82 1.62 2.48 2.28 2.18 2.03
X''q QUAD. AXIS SUBTRANSIENT 0.30 0.27 0.25 0.22 0.35 0.32 0.31 0.28
XL LEAKAGE REACTANCE 0.06 0.05 0.05 0.04 0.07 0.06 0.06 0.06
X2 NEGATIVE SEQUENCE 0.20 0.18 0.17 0.15 0.24 0.22 0.21 0.19
X0 ZERO SEQUENCE 0.08 0.07 0.07 0.06 0.09 0.08 0.07 0.07
REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
T'd TRANSIENT TIME CONST. 0.08s
T''d SUB-TRANSTIME CONST. 0.019s
T'do O.C. FIELD TIME CONST. 1.7s
Ta ARMATURE TIME CONST. 0.018s
SHORT CIRCUIT RATIO 1/Xd

3
HCM434E
50 Winding 311
Hz THREE PHASE EFFICIENCY CURVES

4
HCM434E
60 Winding 311
Hz THREE PHASE EFFICIENCY CURVES

5
HCM434E
Winding 311

Locked Rotor Motor Starting Curve


50
Hz 346V 380V 400V 415V 440V
30

25

20
PER CENT TRANSIENT VOLTAGE DIP .

15

10

0
0 200 400 600 800 1000 1200
LOCKED ROTOR kVA

60
Hz 380V 416V 440V 460V 480V
30

25

20
PER CENT TRANSIENT VOLTAGE DIP .

15

10

0
0 200 400 600 800 1000 1200
LOCKED ROTOR kVA

6
HCM434E

Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed


Based on star (wye) connection.
50
Hz
10000

SYMMETRICAL

ASYMMETRICAL
CURRE NT (Am ps)

1000

100
0.001 0.01 0.1 1 10
TIME (secs)

Sustained Short Circuit = 1,500 Amps

60 10000
Hz
SYMMETRICAL

ASYMMETRICAL
CURRENT (Am ps)

1000

100
0.001 0.01 0.1 1 10
TIME (secs)

Sustained Short Circuit = 1,600 Amps


Note 1 Note 2
The following multiplication factors should be The following multiplication factor should be used to convert the
used to adjust the values from curve between values calculated in accordance with NOTE 1 to those applicable to
time 0.001 seconds and the minimum current the various types of short circuit :
point in respect of nominal operating voltage :
50Hz 60Hz 3-phase 2-phase L-L 1-phase L-N
Voltage Factor Voltage Factor Instantaneous x 1.00 x 0.87 x 1.30
380v X 1.00 416v X 1.00 Minimum x 1.00 x 1.80 x 3.20
400v X 1.05 440v X 1.06 Sustained x 1.00 x 1.50 x 2.50
415v X 1.10 460v X 1.10 Max. sustained duration 10 sec. 5 sec. 2 sec.
440v X 1.16 480v X 1.15 All other times are unchanged
Note 3
The sustained current value is constant irrespective
of voltage level Curves are drawn for Star (Wye) connected machines. For other
connection the following multipliers should be applied to current
values as shown :
Parallel Star = Curve current value X 2
Series Delta = Curve current value X 1.732

7
HCM434E
Winding 311 / 0.8 Power Factor

RATINGS
Class - Temp Rise Cont. E - 65/50°C Cont. B - 70/50°C Cont. F - 90/50°C Cont. H - 110/50°C

Series Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
50 Parallel Star (V) 190 200 208 220 190 200 208 220 190 200 208 220 190 200 208 220
Hz Series Delta (V) 220 230 240 254 220 230 240 254 220 230 240 254 220 230 240 254

kVA 230 230 230 230 240 240 240 240 275 275 275 275 295 295 295 295

kW 184 184 184 184 192 192 192 192 220 220 220 220 236 236 236 236

Efficiency (%) 94.5 94.5 94.6 94.5 94.4 94.5 94.5 94.5 94.2 94.3 94.4 94.4 93.9 94.1 94.2 94.3

kW Input 195 195 195 195 203 203 203 203 234 233 233 233 251 251 251 250

Series Star (V) 416 440 460 480 416 440 460 480 416 440 460 480 416 440 460 480
60
Parallel Star (V) 208 220 230 240 208 220 230 240 208 220 230 240 208 220 230 240
Hz
Series Delta (V) 240 254 266 277 240 254 266 277 240 254 266 277 240 254 266 277

kVA 265 275 285 290 275 285 295 305 315 325 340 345 340 350 365 370

kW 212 220 228 232 220 228 236 244 252 260 272 276 272 280 292 296

Efficiency (%) 94.4 94.5 94.5 94.6 94.4 94.5 94.5 94.5 94.2 94.3 94.3 94.4 94.0 94.1 94.2 94.2

kW Input 225 233 241 245 233 241 250 258 268 276 288 292 289 298 310 314

DIMENSIONS

Barnack Road • Stamford • Lincolnshire • PE9 2NB


Tel: 00 44 (0)1780 484000 • Fax: 00 44 (0)1780 484100

© 2006 TD_HCM434E.GB_10.06_04_GB