HCI634H - Technical Data Sheet

HCI634H
SPECIFICATIONS & OPTIONS

STANDARDS TERMINALS & TERMINAL BOX

Newage Stamford industrial generators meet the Standard generators feature a main stator with 6
requirements of BS EN 60034 and the relevant ends brought out to the terminals, which are
section of other international standards such as mounted on the frame at the non-drive end of the
BS5000, VDE 0530, NEMA MG1-32, IEC34, CSA generator. A sheet steel terminal box contains the
C22.2-100, AS1359. AVR and provides ample space for the customers'
Other standards and certifications can be considered wiring and gland arrangements. It has removable
on request. panels for easy access.

VOLTAGE REGULATORS SHAFT & KEYS

MX321 AVR - STANDARD All generator rotors are dynamically balanced to


better than BS6861:Part 1 Grade 2.5 for minimum
This sophisticated Automatic Voltage Regulator vibration in operation. Two bearing generators are
(AVR) is incorporated into the Stamford Permanent balanced with a half key.
Magnet Generator (PMG) system and is fitted as
standard to generators of this type.
The PMG provides power via the AVR to the main INSULATION/IMPREGNATION
exciter, giving a source of constant excitation power
independent of generator output. The main exciter The insulation system is class 'H'.
output is then fed to the main rotor, through a full All wound components are impregnated with
wave bridge, protected by a surge suppressor. The materials and processes designed specifically to
AVR has in-built protection against sustained over- provide the high build required for static windings
excitation, caused by internal or external faults. This and the high mechanical strength required for
de-excites the machine after a minimum of 5 rotating components.
seconds.
Over voltage protection is built-in and short circuit
current level adjustments is an optional facility. QUALITY ASSURANCE

Generators are manufactured using production


WINDINGS & ELECTRICAL PERFORMANCE procedures having a quality assurance level to BS
EN ISO 9001.
All generator stators are wound to 2/3 pitch. This
eliminates triplen (3rd, 9th, 15th …) harmonics on The stated voltage regulation may not be maintained
the voltage waveform and is found to be the optimum in the presence of certain radio transmitted signals.
design for trouble-free supply of non-linear loads. Any change in performance will fall within the limits
The 2/3 pitch design avoids excessive neutral of Criteria 'B' of EN 61000-6-2:2001. At no time will
currents sometimes seen with higher winding the steady-state voltage regulation exceed 2%.
pitches, when in parallel with the mains. A fully
connected damper winding reduces oscillations
during paralleling. This winding, with the 2/3 pitch
and carefully selected pole and tooth designs,
ensures very low waveform distortion.

NB Continuous development of our products


entitles us to change specification details without
notice, therefore they must not be regarded as
binding.

Front cover drawing typical of product range.

2
HCI634H
WINDING 312
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.
A.V.R. MX321
VOLTAGE REGULATION ± 0.5 % With 4% ENGINE GOVERNING

SUSTAINED SHORT CIRCUIT REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7)

INSULATION SYSTEM CLASS H

PROTECTION IP23

RATED POWER FACTOR 0.8

STATOR WINDING DOUBLE LAYER LAP

WINDING PITCH TWO THIRDS

WINDING LEADS 6

STATOR WDG. RESISTANCE 0.003 Ohms PER PHASE AT 22°C STAR CONNECTED

ROTOR WDG. RESISTANCE 1.88 Ohms at 22°C

EXCITER STATOR RESISTANCE 17 Ohms at 22°C

EXCITER ROTOR RESISTANCE 0.079 Ohms PER PHASE AT 22°C

R.F.I. SUPPRESSION BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others
WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%
MAXIMUM OVERSPEED 2250 Rev/Min
BEARING DRIVE END BALL. 6224 (ISO)

BEARING NON-DRIVE END BALL. 6317 (ISO)

1 BEARING 2 BEARING
WEIGHT COMP. GENERATOR 2117 kg 2145 kg

WEIGHT WOUND STATOR 1010 kg 1010 kg

WEIGHT WOUND ROTOR 866 kg 821 kg


2
WR² INERTIA 20.0438 kgm 19.4965 kgm2
SHIPPING WEIGHTS in a crate 2173kg 2180kg
PACKING CRATE SIZE 183 x 92 x 140(cm) 183 x 92 x 140(cm)
50 Hz 60 Hz

TELEPHONE INTERFERENCE THF<2% TIF<50

COOLING AIR 1.614 m³/sec 3420 cfm 1.961 m³/sec 4156 cfm
VOLTAGE STAR 380/220 400/231 415/240 440/254 416/240 440/254 460/266 480/277
VOLTAGE DELTA 220 230 240 254 240 254 266 277
kVA BASE RATING FOR
910 910 910 875 1025 1063 1075 1125
REACTANCE VALUES
Xd DIR. AXIS SYNCHRONOUS 2.99 2.70 2.51 2.15 3.37 3.13 2.89 2.78
X'd DIR. AXIS TRANSIENT 0.25 0.23 0.21 0.18 0.29 0.27 0.25 0.24
X''d DIR. AXIS SUBTRANSIENT 0.18 0.16 0.15 0.13 0.19 0.18 0.17 0.16
Xq QUAD. AXIS REACTANCE 1.77 1.60 1.49 1.27 2.00 1.86 1.72 1.65
X''q QUAD. AXIS SUBTRANSIENT 0.19 0.17 0.16 0.14 0.22 0.20 0.19 0.18
XL LEAKAGE REACTANCE 0.09 0.08 0.07 0.06 0.10 0.09 0.08 0.08
X2 NEGATIVE SEQUENCE 0.20 0.18 0.17 0.14 0.23 0.21 0.20 0.19
X0 ZERO SEQUENCE 0.03 0.02 0.02 0.02 0.03 0.03 0.02 0.02
REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
T'd TRANSIENT TIME CONST. 0.185
T''d SUB-TRANSTIME CONST. 0.025
T'do O.C. FIELD TIME CONST. 2.44
Ta ARMATURE TIME CONST. 0.04
SHORT CIRCUIT RATIO 1/Xd

3
HCI634H
50 Winding 312
Hz THREE PHASE EFFICIENCY CURVES

4
HCI634H
60 Winding 312
Hz THREE PHASE EFFICIENCY CURVES

5
HCI634H
Winding 312

Locked Rotor Motor Starting Curve


50
Hz 346V 380V 400V 415V 440V
30

25

20
PER CENT TRANSIENT VOLTAGE DIP .

15

10

0
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400
LOCKED ROTOR kVA

60
Hz 380V 416V 440V 460V 480V
30

25

20
PER CENT TRANSIENT VOLTAGE DIP .

15

10

0
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800
LOCKED ROTOR kVA

6
HCI634H

Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed


Based on star (wye) connection.
50 100000

Hz

SYMMETRICAL
CURRENT (Amps)

ASYMMETRICAL

10000

1000
0.001 0.01 0.1 1 10
TIME (secs)

Sustained Short Circuit = 3,300 Amps

60 100000

Hz

SYMMETRICAL
CURRENT (Amps)

ASYMMETRICAL

10000

1000
0.001 0.01 0.1 1 10
TIME (secs)

Sustained Short Circuit = 4,000 Amps


Note 1 Note 2
The following multiplication factors should be The following multiplication factor should be used to convert the
used to adjust the values from curve between values calculated in accordance with NOTE 1 to those applicable
time 0.001 seconds and the minimum current to the various types of short circuit :
point in respect of nominal operating voltage :
50Hz 60Hz 3-phase 2-phase L-L 1-phase L-N
Voltage Factor Voltage Factor Instantaneous x 1.00 x 0.87 x 1.30
380v X 1.00 416v x 1.00 Minimum x 1.00 x 1.80 x 3.20
400v X 1.07 440v x 1.06 Sustained x 1.00 x 1.50 x 2.50
415v X 1.12 460v x 1.12 Max. sustained duration 10 sec. 5 sec. 2 sec.
440v X 1.18 480v x 1.17 All other times are unchanged
The sustained current value is constant irrespective
of voltage level Note 3
Curves are drawn for Star (Wye) connected machines.
For Delta connection multiply the Curve current value by 1.732

7
HCI634H
Winding 312 0.8 Power Factor

RATINGS

Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C

50Hz Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440

Delta (V) 220 230 240 254 220 230 240 254 220 230 240 254 220 230 240 254

kVA 830 860 830 800 910 940 910 875 960 980 960 920 1000 1010 1000 960

kW 664 688 664 640 728 752 728 700 768 784 768 736 800 808 800 768

Efficiency (%) 95.2 95.3 95.4 95.6 94.9 95.0 95.2 95.4 94.7 94.8 95.1 95.3 94.5 94.7 94.9 95.2

kW Input 697 722 696 669 767 792 765 734 811 827 808 772 847 853 843 807

60Hz Star (V) 416 440 460 480 416 440 460 480 416 440 460 480 416 440 460 480

Delta (V) 240 254 266 277 240 254 266 277 240 254 266 277 240 254 266 277

kVA 913 963 1000 1025 1025 1063 1075 1125 1088 1125 1138 1188 1125 1163 1175 1219

kW 730 770 800 820 820 850 860 900 870 900 910 950 900 930 940 975

Efficiency (%) 95.2 95.3 95.3 95.4 94.9 95.1 95.2 95.2 94.8 94.9 95.0 95.1 94.6 94.8 94.9 95.0

kW Input 767 808 839 860 864 894 903 945 918 948 958 999 951 981 991 1027

DIMENSIONS

SAE 14 18 21 24
AN 25.4 15.87 0 0